You are on page 1of 18

Release 3.

0, (042904)
Page 1

METRON, INC.
Packaged Pumping Systems for Raw & Irrigation Water
Horizontal Centrifugal Pump, Variable Speed Drive
Prefabricated Pumping System Specifications

HES-IRR-4.0
Metron PPS Raw & Irrigation Water Definition For Horizontal Pump Stations

Project Name: Date:

Project Location: Customer:



Prefabricated Booster Pumping Station


Part 1 - General

1.00 General. To provide single source responsibility for the manufacture, warranty, service and operation of a prefabricated,
skid-mounted, fully automatic variable speed pumping system (systems) for Raw or irrigation water. The pumping system shall
automatically maintain a constant discharge pressure regardless of varying flow demands within the design point of the pumping
system. The pumping system shall conform to the following Specifications in all respects. This Specification covers the
minimum requirements; however, it should not be construed as all inclusive. It is the manufacturers responsibility to include all
necessary appurtenances to provide for a complete, fully automatic and reliable pumping system. The manufacturer shall supply
a complete set of general arrangement drawings, electrical power schematics, and control schematics in the Installation, Operation
& Maintenance Manual.

1.10 Manufacturer. The pumping system shall be of the type manufactured by Metron, Inc. Denver, Colorado, U.S.A., (303)
592-1903, or equal, approved by the purchaser prior to the bid opening. The pumping system shall be of the model number and
capacities as shown in the attached Technical Data Sheet. For consideration of a proposed equal system, the contractor shall
furnish the following data to the architect / engineer at least 10 days prior to the date of the bid opening:

A complete Specification of the pumping system proposed as an equal.
A Statement of Full Conformance to the following Specifications signed by an officer of the manufacturer.
A General Arrangement Drawing showing the overall dimensions, piping, and components.
A complete Submittal, with Data Sheets, for all major equipment: pumps, motors, variable frequency drive (VFD),
programmable logic controller (PLC), valves, and motor starters.
An Electrical Schematic showing power wiring, and controls.
Manufacturers Industrial Electrical Control Panel UL 508A File Number.
Manufacturers Packaged Pumping Systems UL QCZJ File Number.
Manufacturers Buildings built to meet NEC UL QRNZ File Number.
A list with references of 20 projects that are similar in scope within 250 mile radius of project site.
List of 5 factory trained service technicians, and 2 VFD factory trained service centers, within 100 mile radius of project site.
A copy of manufacturers Certificate of Insurance showing as a minimum, a general liability coverage of
$1,000,000, and an excess liability coverage of $10,000,000.

If, in the opinion of the purchaser, the data submitted shows the pumping system to be equal to the system specified, the bidding
contractors shall be notified not less than seven (7) days prior to the bid opening date.

Part 2 - Mechanical

Release 3.0, (042904)
Page 2
2.10 Scope. The packaged pumping system shall be skid-mounted, with centrifugal horizontal pumps, variable frequency
drive (VFD), fully automated, and built by a single manufacturer. All equipment, including but not limited to, pumps, motors,
piping, filters, valves, instrumentation and controls shall be mounted on a common structural steel base to form a complete, self-
contained, automated pumping system. The pumping system shall be a Metron Model ______________________ , as shown on
the Technical Data Sheet, or approved equal.

(Specific project overview.)

The pumping system shall be efficiently designed to minimize space, and to allow access to all critical components. Critical
components shall include the control panel, filter elements (if provided) for maintenance, auxiliary controls and electrical
components.

2.15 Pumping System Base (Skid). The pumping system skid shall be designed, fabricated and assembled to provide proper
structural support for all attached equipment. The skid shall provide sufficient rigidity to withstand the stresses of reasonable and
competent transportation to site, off loading, installation, and operation. Main structural members shall be constructed of six (6)
inch minimum, medium weight channel iron, or I-beam steel. Provisions shall be made in the system base for off-loading and
handling the pumping system at the site of installation. All skid joints shall be continuously welded, 100% seam welded, to main
structural members. Skip welding is not acceptable.

2.20 Piping. All piping shall be constructed from ASTM A53 schedule 40 pipe, or heavier as required to maintain a 3 to 1
pressure safety factor (including 1/16 corrosion allowance). All piping shall be hydrostatically tested to 150% of maximum
system design. All welds shall be completed by a certified welder per ASME Code Section IX or AWS Code Section 9.10.


2.30 Paint. All structural steel and piping shall be grit blasted per SSPC-6 to a near white metal finish, and evenly coated
with a dry thickness of (4-6) mils of a fast drying multi-purpose epoxy. Exterior surfaces shall be coated with a gloss aliphatic
polyurethane topcoat with a dry thickness of (3-4) mils and hunter green in color.

The control panel shall be made from cold-rolled steel and have a two (2) mil polyester powder coated, baked-on finish applied
after a phosphoric acid wash and phosphate coat, in accordance with UL Requirements.

2.35 Hardware. All nuts, bolts and washers used in the assembly of the pumping system shall be grade 5 zinc coated steel to
retard corrosion.

2.40 Main Horizontal Pump(s). The main Raw or irrigation water pumps shall be of the end suction horizontal type with
flow and head defined in the attached Technical Data Sheet. The end suction horizontal pumps should be manufactured
according to the Standards of the Hydraulic Institute and to ANSI Specifications No. B58.1. The pumping system manufacturer
shall have a network of service centers with available spare parts and factory trained service technicians to handle service, repair
and warranty.

Pump suction and discharge connections shall be either flanged or threaded. The flanges (or threaded connection) shall have a
working pressure of not less 150 PSIG, and incorporate a 125# ANSI flat faced flanges.

The pump impeller(s) shall be bronze. The pump shaft shall be AISI 416 SS turned and ground. The main pump(s) shall be as
manufactured by Armstrong, Cornell, Bell & Gossett or pre-approved equal.

2.45 Motors. Motor(s) for Raw or irrigation water pump(s) shall be of the squirrel cage induction type. Add more motor
description.
The design pump brake horsepower shall not exceed 98% of the motor horsepower exclusive of the service factor. All motors
shall be non-overloading throughout the entire designed impeller diameter operating curve, including pump run out, exclusive of
the service factor. The motor shall be rated for continuous duty and be designed to carry the maximum pump and will have L10
bearing life to provide an average life of five (5) years of service..

2.50 Pump Check Valves. Pump check valves shall be mounted downstream of the pump discharge and sized per the
Technical Data Sheet. They shall be of the silent operating type that begin to close as forward velocity diminishes, and be fully
closed at zero velocity preventing flow reversal. The check valve bodies shall be ASTM A126 Grade B cast iron, or better, and
shall be free from blowholes, sand holes, and other impurities. The check valve design shall be center guided, spring loaded
Release 3.0, (042904)
Page 3
poppet guided at opposite ends, and having a short linear stroke that generates a flow area equal to the pipe diameter. The
internals shall be machined bronze disc seat, and stem guide. The seat shall be bronze to provide resilient sealing. The valves
shall be sized to permit full pump capacity to discharge through them without exceeding a pressure drop of 2.0 PSIG. The pump
check valve(s) shall be a Valmatic Series 1400.

2.55 Pump Isolation Valves: The pump suction and discharge isolation valves shall be lever operated, butterfly valves with
grooved ends to provide for expansion, and vibration dampening. Lug style pump discharge isolation valves are not acceptable.
They shall be sized as shown in the Technical Data Sheet. The valve body shall be constructed of ductile iron with a
polyphenylene sulfide coating. The valve disc shall be rubber coated ductile iron. The valve shall be rated at 300 PSIG.

2.60 Air Release Valve. An properly sized air release valve shall be installed on each pump discharge head or at the highest
point on the pipe manifold. The air release shall allow for the release of air, generated by the starting of the pump, to atmosphere.
The discharge of the air release valve shall be vented back to the wet well through a polypropylene tube into the wet well

2.65 Pressure Relief Valve (PRV). A pilot operated modulating pressure relief valve shall be included, and sized per the
Technical Data Sheet. The PRV shall be set, and will relieve when the inlet pressure exceeds the spring setting on the pilot. The
PRV shall be field adjustable, quick opening, and slow closing, to minimize surging. The discharge of the PRV shall be piped
back to the suction piping. The PRV body shall be cast iron with 125 pound inlet, and outlet flanges, and shall be rated for 200
PSIG. A wye strainer shall be installed on the inlet side of the PRV body to provide clean water to its relief pilot. PRVs larger
than 2 shall have a wafer style butterfly valve installed on the inlet and discharge side of the PRV. PRVs 2 and smaller shall
have a brass ball valve installed on the inlet and discharge side of the PRV. The Pressure Relive Valve shall be a Cal-Val 50-01.

2.70 Pressure Gauge. A pressure gauge shall read pressure from the suction and discharge pipe. All gauges shall be silicon
filled to reduce effects due to vibration and incorporate isolation ball valves for maintenance. Accuracy of the pressure gauge
shall be within two (2)%. The gauge diameter shall be 2-1/2 minimum. The pressure gauge range shall be 0 200 PSIG. They
shall have a stainless steel back, and bronze internal parts. The Pressure Gauge(s) shall be an Ashcroft 63W3005HL.

2.75 Station Isolation Valves. The station isolation valve shall be installed on the suction manifold of the system and the
discharge meter run of the pumping system to completely isolate the pumping system from the Raw or irrigation water system.
This station isolation valve shall be lug style, butterfly type. It shall be one piece ASTM A126 Grade B cast iron. Its stem shall
be 416 stainless steel. Its disc shall be nickel plated ductile iron. Its stem bushings shall be Acetyl to prevent stem seizure to
body during prolonged periods of non-use. Its seat shall be EPDM, one piece construction, and shall also form the flange sealing
gaskets. Valves six (6) inch, and smaller shall have a 10-position locking handle. Valves eight (8) inch, and larger shall have
gear operator with hand wheel. All valves shall be rated at 200 PSIG bubble shut off. The Station Isolation Valve(s) shall be a
Keystone 222.

Part 3 - Electrical

3.00 Scope. To provide complete instrumentation and controls to automatically start, stop and modulate pump speed to
smoothly, efficiently and reliably deliver variable flow rates at a constant discharge pressure. To provide alarms, and safety
features needed to protect the equipment, personnel, and Raw or irrigation water piping system.

3.10 Control Enclosure. Controls shall be housed in a UL508 listed NEMA 12 enclosure with integral door latches. The
control enclosure shall be constructed of 12 gauge steel, and the back plate assembly shall be constructed of 12 gauge steel. The
enclosure shall be painted as specified in the paint Specifications listed under Mechanical Section 2.30 Paint. All indicating
lights, reset buttons, speed potentiometer, selector switches and the operator interface device shall be mounted on enclosure door
and also rated NEMA 12. All internal components shall be mounted and secured to the removable back plate assembly. Pilot
devices shall run from secondary, control voltage (24 VDC or 120 VAC). A closed type cooling system shall be included to
maintain a temperature below 100 degrees F in the enclosure based on a water temperature of 75
o
F and reject heat from the VFD.
Open type cooling systems allowing outside ambient air to enter the panel is not acceptable. No water line connections
shall be permitted inside of the control enclosure. The minimum ambient temperature where the panel is installed shall not drop
below 40 degrees F.

3.15 Lightning and Surge Arrestor. All electrical equipment shall be protected by a UL approved category C surge
arrestor to suppress voltage surges on incoming power. The surge arrestor should be intended for use on three-phase, 600 VAC
systems and designed to discharge the following amperages: 1.5kA @ 1700 V; 3 kA @ 2100 v; 5 kA @ 2510 V; 10 kA @
3800V. The Lightning and Surge Arrestor shall be a Delta LA603.
Release 3.0, (042904)
Page 4

3.20 Main Disconnect. A non-fusible main disconnect shall be provided to completely isolate controls, and motor starting
equipment from incoming power. The main disconnect shall have a interlocked, through-the-door, operator, and shall be sized as
shown in the Technical Data Sheet. The Main disconnect shall be as manufactured by Cutler Hammer.

3.25 Control Power. Power for the controls shall be provided by a control power transformer (CPT), which will provide 120
volt, single phase power for the pumping system control operation. The CPT shall not be used for any other external load. It
shall be protected on the primary side by current limiting fuses of adequate size and voltage rating. All controls will be protected
by time delay circuit breakers or fuses of adequate size.

3.27 Phase Monitor. A phase monitor shall be included to provide protection of all three-phase equipment against phase
loss, under voltage, and phase reversal; when fault is sensed the monitor output relay opens to turn the equipment off and/or cause
an alarm; automatic reset; LED indicator light.

3.30 Motor Starting Equipment. Unless specified otherwise, all motor starters for the pumping station shall be mounted on
a back pan in a single NEMA enclosure as specified in Section 3.10. Each main Raw or irrigation water motor shall have dual
contactors that are both electronically and mechanically interlocked to allow the VFD to operate on any of the main motors called
out in the technical data sheets. Motor starters shall meet I.E.C. Standards, be UL Listed, and shall be rated for a minimum of
1,250,000 operations. Motor overload relays shall be I.E.C. rated class 10 ambient compensated. Fuses shall supply short circuit
protection to each motor, and shall be rated for a minimum 200,000 amp interrupting capacity. Motor starters and overload relays
shall be UL Listed. The Motor Starting Equipment shall be as manufactured by Square D.

Option? 3.32 VFD Bypass Starter. The VFD shall have a bypass, across-the-line, starter to allow for continued manual
system operation while maintenance is performed on the VFD. The VFD Bypass Starter shall be as manufactured by Square D.

3.35 Variable Frequency Drive. The variable frequency drive (VFD) shall be digital, pulse width modulation (PWM) with
IGBT transistors. Any VFD error messages shall be displayed on a 4x20 character LCD readout in English and any one of eight
(8) other languages. The following fault protection circuits shall be included: Overcurrent (200%), Overvoltage (130%),
Undervoltage 65%, Over temperature (70 DEG. C), Ground fault, and Motor overload. The VFD shall have automatic extended
power loss ride through circuit that will utilize the inertia of the pump to keep the drive powered. Minimum power loss ride-
through shall be one cycle based on full load and no inertia. The VFD shall be configured for a 3kHz carrier frequency to reduce
motor noise. The following operating information shall be displayed on the VFDs LCD: kWh, elapsed time, output frequency
(Hz), motor speed (RPM), motor current (amps), and voltage. The VFD shall be an ABB ACS 550 Adjustable Speed Drive.

3.40 Pressure Transducer. The pressure transducer shall provide pressure signals for the control logic. The accuracy shall
be 1.0 of full scale, and constructed of 316L SS wetted parts. It shall be rated for the discharge pressure as shown on the
Technical Data Sheet, and shall provide gauge pressure output. The Pressure Transducer shall be a Dwyer Series 628.

3.45 Flowmeter (Sensor). The pumping system shall have a flowmeter (sensor) installed in a meter run of straight pipe,
with a minimum of ten (10) pipe diameters upstream, and five (5) pipe diameters downstream of the flowmeter (sensor) for
properly indicating the flow rate and total flow. The flow sensor shall be an insertion type with a non-magnetic, spinning impeller
(paddle wheel) as the only moving part. The sensor sleeve will be brass (or 316 stainless steel) with the sensor housing bei ng
PPS. The impeller shall be glass filled nylon. The shaft material shall be tungsten carbide. The sensor shall be supplied with a 2
NPT adapter for installation into any commercially available weld-on fitting or pipe saddle. The adapter shall have two ethylene-
propylene O-Rings. The sensor will have all electronics epoxy-sealed with a 2-conductor, shielded cable extending out through a
conduit connection on the top of the sensor. Insertion of the sensor into any pipe size shall be 1 from the inside wall to the
end of the sensor housing. The sensor shall operate in line pressures up to 400 psi and liquid temperatures up to 220 degrees
Fahrenheit, and operate in flows from 1-30 feet per second in pipe diameters from 3 to 40 with linearity of +/- 1% and
repeatability of +/- 1%. This flow sensor shall be a Data Industrial Model 220.

3.50 Controls. All control logic shall be handled by an industrial grade programmable logic controller (PLC) with a 4x20
character backlit LCD providing data entry and display. PLC shall provide demand controlled variable frequency drive transfer
pump start, shutdown and safety features through its pressure sensing, flow sensing and voltage sensing devices. PLC shall have
LED indicators for input, output, and diagnostic read outs showing PC Run, CPU Fault, and two communications ports. An LED
visual status light is provided for each I/O to indicate on/off status. PLC shall be provided with a built in EEPROM, and capacitor
for memory backup. A separate set point controller is not acceptable. The PLC shall have a built in clock calendar

Release 3.0, (042904)
Page 5
Control software shall be parameter driven, fully documented, and allow user to easily change all operator parameters.

Standard control features, and equipment that need to be included as a minimum are as follows:

A. Alarms and shutdowns:

Low discharge pressure
High flow demand
High discharge pressure
Low wet well level
Phase Loss (attempts restart)*
Low voltage (attempts restart)*
Phase reversal (attempts restart)*
Individual motor overload/phase loss (indicates which individual motor was shut down)
VFD fault (shutdown VFD pump only and attempts restart)*

*Three unsuccessful restarts in a 15 minute period will give hard shutdown as configured from the factory. Number of
restarts during a period and the length of period can be re-configured in the field.

All alarms will be indicated by a red general alarm light. Specific alarm conditions along with will be displayed in
English on the operator interface display (OID).

B. Panel face switches and lights:

Individual pump run lights
Individual pump on/off switches
System Hand/Off/Automatic switch
Mode Select switch allows manual bypass mode of operation which can be used if VFD should fail (inside panel on
back pan)
On/Off controls in OID to automatically alternate VFD (hours/sequential/off)
Reset Acknowledges pumping station alarms/ Silence Horn/ Lamp Test
Speed potentiometer in system manual mode allows user to adjust VFD pump speed
Low discharge pressure override disables low discharge pressure alarm (through OID)

C. System HOA works with PLC bypass switch and allows user to manually operate pump should PLC fail.

D. Four distinct set point pressure (normal, lockouts 1 & 2 and high elevation). The lockout feature gives the user the
flexibility to lower the set point pressure automatically at days and times, and locking out the operation of one or more
of main pumps if local power authority imposes penalties for operating these pumps during such times. It also allows
user to set maximum RPM for the VFD pump during these lockout times so that user can limit amperage draw during
penalty periods. The high elevation set point can be tied into a computerized Raw or irrigation water system, or directly
linked to high elevation satellites. When high elevation satellites are operating, control software will automatically and
gradually elevate the pressure to the new desired set point. When finished, the high set point will be lowered back to
normal. The high elevation set point will only be used if called out on the Technical Data Sheet.

E. LineFill Software will be included to automatically, and gradually increase the speed of the pump motor to maintain the
desired operating pressure for the Raw or irrigation water system (i.e., 1.5% every 4 seconds). This feature operates
whenever pressure drops below linefill set point pressure. The linefill set point is fully adjustable by the operator. This
control feature is based on an increase in pressure over a pre-defined time period. The acceleration control on the VFD
is NOT an acceptable means of adjusting pressure ramp up speed.

F. Software will be included for optionally maintaining a lower Raw or irrigation water system pressure when not
irrigating. Reduced pressure valves will be shown in the Technical Data Sheet. Controls will cycle the pressure
maintenance pump at these reduced pressures during non-operation times, and pressure will gradually increase to design
pressure when the operation periods begin.

Release 3.0, (042904)
Page 6
G. Neither flow meter nor VFD output frequency shall be used for shutting down last VFD driven pump. Controls and
software shall incorporate a method to eliminate excessive cycling of VFD pump at very low flow conditions, yet not run
the pump excessively at no-flow conditions.

H. Automatic alternation of VFD driven pumps. This shall be accomplished by incorporating dual mechanically and
electrically interlocked contactors allowing alternation of the VFD pumps.

I. User shall be able to field select either of two modes of VFD operation. Auto switch VFD option allows VFD to
sequentially start each pump. The manual mode of operation starts the first main pump on the VFD and the remaining
pumps start across the line as required.

J. An integral real time clock calendar shall allow the PLC to internally provide all date, and time functions.

K. Two separately adjustable proportional integral & derivity PID control loops shall provide for both low flow and high
flow pressure stability.

L. A shutoff algorithm, for fixed speed pumps, shall minimize pump cycling while also remaining responsive to sudden
flow reductions. Minimum run timers alone for minimizing fixed speed pump cycling are not acceptable. Discharging
pressure through the relief valve during pump transitions is not an acceptable method of maintaining constant pressure.

M. Manual operation of the VFD driven pump shall be done with a door mounted speed potentiometer to manually adjust
the speed of the pump motor.

N. A system manual, or automatic mode switch shall be provided. This mode switch, when in the manual mode, will allow
all pump motors and the VFD to be operational should the PLC fail. When the system mode switch is in automatic, the
controller will start, and stop all pumps automatically.

O. All panel lights shall be tested by pressing the reset button for three (3) seconds.

P. A rate of pressure change algorithm shall rapidly determine if there is a Raw or irrigation water demand and immediately
cycle on the VFD pump, instead of waiting for the pressure to drop to a predetermined start pressure.

Q. All pumping system shutdowns shall be controlled to sequentially turn pumps off at user selectable intervals to reduce
water hammer within the Raw or irrigation water system.

3.55 Operator Interface Device (OID). The pumping system shall include a NEMA 4, 4 lines by 20 character backlit liquid
crystal display (LCD) keypad mounted on the control panel door. This device will allow the operator to view, and selectively
modify system setpoints in the PLC. It shall store its messages in a non-volatile memory. The OID shall incorporate password
protection for protecting data integrity. The OID will allow for display, and modification of timers, set points, and lockout times.
The device shall communicate with the PLC through the programming port, and shall include a serial printer port allowing a
printer to be attached for real time station status logging.

In addition to normal data entry keys, the OID shall include a minimum of the following screens:

A. Event Log. Displays the last 254 sequential pumping system events with the date, and time of occurrence. Events
shall include but not be limited to: all alarms, starting of individual pumps, stopping of individual pumps, and changing
of selector switches.

B. Alarm Log. Shows the last nine (9) alarms recorded in memory, and are displayed with related detailed information
about the alarm, time of occurrence, date, pumps operating at time of alarm, and how to correct the alarm.

C. Pump Log #1. Operator can scroll through the historical pumping system flows, and pressures for up to the last seven
(7) days. Sampling time periods can be changed by the operator (from 10 seconds to 60 minutes). Averages are taken
over the sample period, and the average recorded with date, and time stamp.

Release 3.0, (042904)
Page 7
D. Pump Log #2. Pumping system flow and pressure are shown every second for the previous 60 seconds, and every
minute for the previous 30 minutes. If a shutdown occurs, the flow, and pressure tables are locked in so that the operator
may view how the pumping system was performing immediately before the shutdown occurred.

E. Status Screen. Will display the current operating status. When the pumping system is running, the display will show
the setpoint pressure, actual system pressure, flow, VFD pump frequency, and current date and time.

F. Daily Log Will display the following: individual pump run times, total flow, and total flow since last reset.

G. Configuration Menu Used to scroll up, and down through the data and menu options.

The OID shall be an information system only, and not required for pumping system operation. No switches, reset buttons, general
alarm lights, run lights, or speed potentiometers are to be included within this unit. The pumping system will be fully functional
in the event the OID should fail.

3.60 Codes. The control panel with controls shall be built in accordance to N.E.C. and UL standards. All equipment and
wiring shall be mounted within the enclosure, and labeled for proper identification. All user-required adjustments shall be made
from the front of the control enclosure. A wiring schematic complete with legend, terminals, components, and wiring
identification shall be provided. The main disconnect shall be interlocked with door.

3.65 Operation. During non operation times, the pressure maintenance pump (PMP) will cycle on and off as required to
maintain pressure. The cycling pressures can be user selected, and can be set substantially below normal system pressure, if
desired. If the PMP cannot maintain the desired pressure, than the VFD will start the first main pump, and will gradually ramp
the pressure up to the system pressure. The pump speed will be modulated to hold a constant discharge pressure regardless of
flow. As the flow rate increases, and the VFD pump can no longer maintain pressure while at maximum speed, the next main
pump will be started, and the VFD driven pump will accordingly reduce its speed, and modulate. An algorithm shall be included
for accurately reducing the VFD pump speed as the next sequential pump is started so that no pressure surges are generated
during the transition (even with across the line starting). If the user prefers to switch the VFD from pump to pump for starting the
pumps sequentially, he can select this option with the OID. As the flow continues to increase, pumps will sequentially be started
until all pumps are operating. As the flow begins to decrease, pumps will be turned off sequentially until only a single VFD
driven pump is operating. When a no flow condition occurs, the VFD pump shall be turned off. When there is a pressure set
point change all other related set point variables change relative to the new pressure set point.



Part 4 - Installation

4.10 General. The purchaser shall be responsible for providing all material, equipment, and labor necessary to install all
items associated with the pumping system. The manufacturer will assist with the installation by providing supervision of
installation, start up, training, and technical support. The purchaser must obtain from the manufacturer an Installation, Start-up
and Training Commencement certificate to validate the warranty. The manufacturer will provide Installation, Operation, and
Maintenance Manuals.

4.15 Installation. Offloading is the responsibility of the purchaser. Supervision of installation will be provided by the
manufacturer of the pumping system. Installation shall be done after the wet well is completed, and the level floor of the pump
house has been poured, and properly cured. The pumping system will be installed over the wet well, and leveled as necessary, as
per the Site Preparation Drawing. The pumps will be installed and connected to the piping of the pumping system, and the
packaged pumping system will be complete, and ready for the electrical hookup, and connecting all piping. The pumping system
will be anchored to the floor of the pump house. The purchaser shall notify the manufacturer of the pumping system two (2)
weeks prior to the scheduled installation date so that installation can be coordinated. Supervision of installation will be limited to
one (1) eight (8) hour day, unless otherwise specified.

4.20 Start Up. When electrical inspection of the purchasers service entrance equipment has been completed, and approved,
the pumping system manufacturer shall be contacted for start up by the purchaser. Truck access shall be provided to the site of
the pumping system by the purchaser. A minimum two (2) week notice shall be given to manufacturer prior to the scheduled start
up date. During start up, the pumping system shall be given a running test of normal start, and stop, and full demand. During this
test, each pump shall demonstrate its ability to operate without undue vibration, or overheating, and shall demonstrate its general
Release 3.0, (042904)
Page 8
fitness for service. Any defects shall be corrected, and adjustments made at the expense of the pumping system manufacturer.
Test shall be repeated until satisfactory results are obtained. Start up assistance will be provided, but will be limited to one (1)
eight (8) hour day, unless otherwise specified.

After the startup has been complete, but before leaving the job site, a training session will be given. The training session will be
given to the owner or the owners representative to familiarize them with the pumping system operation, maintenance and
adjustments. This training session will be limited to one (1) eight (8) hour day, unless otherwise specified.

4.25 Warranty. The manufacturer warrants that the water pumping system or component will be free of defects in
workmanship for one year from date of authorized start-up but not later than eighteen months from date of manufacturers
invoice.

Provided that all installation and operation responsibilities have been properly performed, manufacturer will provide a
replacement part or component during the warranty life. Repairs done at manufactures expense must be pre-authorized. The
start-up certificate must be on file with manufacturer to activate warranty. Upon request, manufacturer will provide advice for
trouble shooting of a defect during the warranty period.

Manufacturer uses only high quality material. As with any mechanical or electrical device, some preventative maintenance
efforts are required to enhance service life. The customer is encouraged to establish a methodical maintenance service program to
avoid premature failure. Manufacturer supports a wide network of technical service agents and recommends they be utilized for
service. Because of varied conditions beyond the control of manufacturer, this warranty does not cover damage under the
following condition or environment unless otherwise specified in writing:

1. Default of any agreement with manufacturer.
2. Misuse, abuse, or failure to conduct routine maintenance.
3. Handling any liquid other than clean, neutral Raw or irrigation water.
4. Exposure to electrolysis erosion, or abrasion.
5. Presence of destructive gaseous or chemical solutions.
6. Over voltage or unprotected low voltage.
7. Unprotected electrical phase loss or phase reversal.

The foregoing constitutes manufacturers sole warranty and has not nor does it make any additional warranty, whether express or
implied, with respect to the pumping system or component. Manufacturer makes no warranty, whether express or implied, with
respect to fitness for a particular purpose or merchantability of the pumping system or component. Manufacturer shall not be
liable to purchaser or any other person for any liability, loss, or damage caused or alleged to be caused, directly or indirectly, by
the pumping system. In no event shall manufacturer be responsible for incidental, consequential, or act of God damages nor shall
manufacturers liability for damages to purchaser or any other person ever exceed the original factory purchase price.

Part 5 - Options

If there are any discrepancies between the Options Sections, and the main Specifications, these Options Sections take precedence.

5.10 Autoflush Wye Strainer. The pump station manufacturer shall provide an automatic flushing wye strainer mounted and
wired on skid. The wye strainer basket shall be fabricated from 24 gauge stainless steel with 1/8 perforation. The body of the
strainer shall be cast iron with flanged connections. Pressure drop through the strainer shall be not more than 1.75 PSI at full
station capacity with a clean filter. The strainer shall be automatically flushed after a specific pump station run duration period.
This timer is adjustable through the operator interface device (OID) as called out for in these specifications. An H.O.A. selector
switch shall control a normally closed ball valve for flushing. The PLC shall initiate the flushing cycle by opening the valve for
15 seconds. The flushing duration shall be an adjustable timer through the computer interface device. The ball valves actuator
shall be slow acting, taking at least 15 seconds each way, to protect the system and pipe from destructive surges and water
hammer. A 2 ball valve shall be supplied to isolate the electrically actuated ball valve from the raw or irrigation water system.
The wye strainer size shall be specified in the technical data sheet. The Autoflush Wye Strainer shall be a Watts 77F-D.

5.15 Automatic Backwash Screen Filter System. The manufacturer shall provide an automatic self-cleaning filter system
mounted, and wired on the pumping system. The filter system shall remove suspended solids down to 230 microns (60 mesh).
Screen options offered are 40, and 80 mesh. The pressure drop through a clean filter system at the maximum rated flow shall not
exceed five (5) PSIG. The filter system Model number, and style shall be a type specified in the Technical Data Sheet.
Release 3.0, (042904)
Page 9

The filter vessels shall be fabricated of carbon steel, and lined with fusion bonded epoxy. Each filter vessel shall feature a safety
seal fusion epoxy lined lid, which is removable for cartridge inspection, and servicing. Each filter vessels shall be rated for a
maximum working pressure of 150 PSIG. The minimum operating pressure shall be 40 PSIG.

The filter system shall be provided with fusion epoxy lined carbon steel inlet, and outlet piping. The piping shall be connected
with grooved type couplings, or with flanged connections.

Each filter vessel shall be provided with an automatic backwash valve. The valves shall be of cast iron construction with fusion
epoxy lining on all wetted surfaces. The valve shall incorporate the use of a replaceable polyurethane valve seal, and replaceable
brass valve guide assembly. The valve shaft shall be double o ring protected from dirt, and contamination. The valve shall be
water powered by a diaphragm operated actuator assembly. The valve shall feature a self lubricating grease cavity with external
grease fitting for lubrication.

The filter cartridge element shall be sized so as not to exceed 70 GPM per square foot during the normal operating mode. The
filter cartridge shall be of a rigid Type 304 stainless steel design. The cartridge shall be constructed of continuously wound
stainless steel trapezoidal wire welded to rigid reinforcement members. Burst strength shall be a minimum of 400 PSIG. The
cartridge is intended to be a permanent part of the system, and should not normally require replacement. Cleaning of the cartridge
shall be accomplished by reversing the flow of the filter, and back washing out accumulated contaminants. The cartridge shal l be
protected on its ends with a U-channel seal for protection from sharp metal edges. A molded rubber gasket shall be fitted to each
cartridge end for sealing of the cartridge assembly. Automatic backwashing of the cartridge shall be accomplished through the
use of the automatic backwash controls. There shall be a flanged access port at the filter to permit immediate access to the
internal components.

The filter system shall include an automatic control system to monitor filter performance, and to automatically initiate
backwashing when required. Backwashing shall be automatically initiated via differential pressure, or time. The controller will
allow for user adjustable frequency of flush settings from 15 minutes up to a maximum of 24 hours from the OID. The differential
pressure setting (to initiate backwash) shall be from an external differential pressure switch. The backwash may also be initiated
through a cycle timer setting that shall be configurable through the pumping system OID. The controller will initiate a backwash
based upon elapsed time, or pressure differential, whichever event occurs first. Flush duration and the delay between filter
vessels flushing may be set by the user through the OID. A pressure differential switch with a range up to 15 PSIG shall be
provided. The pumping system control panel utilizing its PLC based design shall provide operating control of the individual filter
unit during the backwash mode of operation.

Upon sensing the preset differential pressure that develops in the filter system, the differential pressure switch shall activate a
signal to the control panel to begin the backwash. The backwash cycle shall require a minimum flow rate of 40 GPM (at the
minimum inlet pressure), and the filter system shall continue to provide filtered water to service during the entire backwash cycle.

The filter system flush line shall be piped back to the supply reservoir by others.

The filter system is designed to provide filtered backwash. The filter system will continue to process water during backwash, and
shall not require an outside water source for the backwash function. The filter system shall be configured with at least two filters
vessels per system to permit backwashing with filtered water while providing sufficient filter capacity to meet maximum flow
conditions, as specified in the Technical Data Sheet.

The filter vessels, piping and valving shall be lined with Type 134 Scotchkoat. All metal surfaces shall be sandblasted to a white
metal condition prior to epoxy application. Metal surfaces shall be preheated to 450 F prior to electrostatic application of the
powder coating. After coating application parts shall be cured at 400 F for a minimum of 20 minutes. Application shall provide
an even holiday free lining of the thermoset epoxy coating 8 - 10 mils thick. The coating material is nontoxic and is approved for
portable water application. The Automatic Backwash Screen Filter System shall be a Yardney Maxiflush.

5.20 Wet Well Controls for Transfer Pump, or Valve. The wet well level shall be continuously monitored by a liquid level
sensor. When low level is sustained for a period of time, a dry contact relay output closure signal shall be directed to start
reservoir pump, or open filling valve. This signal shall be maintained until reservoir is filled to the upper sensor. Upon loss of
signal, relay shall drop out, and pump shall stop, or valve shall close. Additionally, if the systems flow rate is exceeding a flow
rate that has been predefined through the OID, the same dry relay output closure signal shall be directed to start reservoir pump,
or open filling valve.
Release 3.0, (042904)
Page 10

5.25 Motor Space Heater. The pumping system manufacturer shall provide on each pump motor a 120 volt, single phase
space heater of ample size to prevent condensation within the motor. The space heater shall be de-energized when the motor is
running.

5.30 Remote Monitoring and Control. Remote computer compatible monitoring software shall be available and or provided
that allows the user to remotely view all specified items in Section 3.55Operator Interface Device. This software shall be
graphics oriented with point and click control. The user shall be able to view and / or change any and all station operating
parameters normally available through the Operator Interface Device, (i.e., set point pressure, lockout times, alarm set points, etc.)
and also be able to acknowledge and reset fault conditions. Complete historical reporting capabilities shall be included. All
required PLC interface modules, modems, telephone line surge protectors and or radios and related hardware required (other than
the computer hardware and any direct burial cable or telephone lines) shall be supplied and installed by pumping system
manufacturer.

A. Manufacturer shall provide the software and related hardware, except as noted, to monitor and control the pump station
from a remote location. Monitoring program shall require, by the customer, a desktop computer with a suitable monitor capable
of running Windows 2000, Windows 2000 Pro, XP or XP Pro operating system. This computer should have at a minimum
1.6GHz processor, 256MB of memory, a 30GB Hard drive, at least 2 serial data ports, 2 USB ports, a parallel port and either of
the following; an internal or external 56K Baud data modem.

B. Monitoring software shall provide the following capabilities:

I. Graphical and or text display of real-time pumping system status that will include:
a) Systems actual pressure, as well as set point pressure
b) System flow rate and maximum flow values
c) Status of system panel switch settings (System HOA switch, Pump On/Off selector switches, etc.)
d) Pumps current run status including total run hours for each pump
e) VFD driven pump assignment and speed
f) Status of any remote transfer or well pump
g) System fault(s) and or alarm status, to include pump faults and alarms, pressure alarms, flow alarms and
transducer faults along with date and time of occurrence.
h) Ability to adjust set points typically available through the pump station Operator Interface Device.
i) Adjust alarm settings and timers.
j) Adjust Motor Lockout scheduling
k) Ability to read, display, hard copy, and archive logged information including:
i) Total pump hours
ii) Total and daily flow
iii) Historical data logging of discharge pressure, well or tank level and flow values that are
recorded in either of two ways:
1) Recorded at user defined internals
2) Fault suspended recordings of 10-second intervals.
Note: Graphical display of data will include user selectable ranges of 1 to 24 hours per screen and the ability to display historical
data contained on the computers hard drive.
l) Remote RESET of alarms.

III. Monitoring software shall be configurable and capable of at least two of the methods listed below:
a) Direct connection via buried cable - two conductor (minimum) shielded twisted pair 20 16 AWG, cable.
Should meet at a minimum the specifications for Belden 9842 EIA RS-485 data communications cable and be
rated or suitable for direct burial applications. Communications speeds of 2400 to 19200 baud up to 10,000 ft
should be supported.
b) Modem - communicate via phone at speeds of 1200 to 56000 baud.
c) Radio Licensed VHF through UHF and unlicensed 900MHz to 5.2GHz Spread Spectrum.
Note: Antennas, feed line, poly-phasers, ground kits, mast and installation to be provided by the PS manufacture.
d) Direct connection via Ethernet CAT5 direct burial cable.
e) PLC or controller should be able to support Modbus RTU slave protocol

IV. Password security shall be provided to guard against unauthorized system changes
Release 3.0, (042904)
Page 11

V. Software should be either developed in-house or other suitable industry standard SCADA/HMI software
package and be fully documented and serviceable.

5.35 Remote Station Dialer. The pumping system shall have an automatic dialer programmed to call up a preset phone
number to indicate an alarm condition.

5.40 Fixed Inlet Screen. A reservoir inlet screen shall be provided at the inlet of the horizontal inlet flume leading to the wet
well. The entire screen is to be in the vertical plane with the total inlet screened area called out in the Technical Data Sheet. The
screen shall be fabricated from 14 gauge carbon steel sheet metal, and angle iron with , #13 flattened expanded carbon steel
metal mesh screen bolted to three vertical sides. The fixed inlet screen shall be powder coated to inhibit rust. The screen outlet
connection shall be compatible with the horizontal inlet flume, and fastened with three set screws. The inlet screen shall be
installed by others, with the bottom of the fixed inlet screen a minimum of 24 inches off the bottom of the reservoir.

5.45 Self-Cleaning Inlet Screen. A reservoir self-cleaning inlet screen shall be installed at the inlet of the horizontal inlet
flume leading to the wet well. It shall be supplied pressurized water from the pumping system through a one and one half (1 )
inch line. A solenoid valve shall be installed on the feed line to allow for cleaning of the screen during pumping operation. A
strainer shall be installed in the feed line if the water is not filtered. The self-cleaning inlet screen shall have 10-mesh and be
made from stainless steel covering a heavy steel epoxy coated or galvanized body. There shall be rotating bars, utilizing a heavy
bearing mechanism, with jets for cleaning the screen when the pump system is operating. The inlet screen shall be installed by
others, with the bottom of the inlet screen a minimum of 24 inches off the bottom of the reservoir. The flat faced flanged
connection shall be as defined in the technical data sheets.

5.50 Space Heater. A heavy duty, industrial rated, space heater shall be provided with a kW rating as indicated in the
Technical Data Sheet to maintain a pump house temperature above 40 degrees F. The heater shall be provided with a circuit
breaker, thermostat, and thermal safety overload shutdown. The heater shall be prewired and securely mounted on the pumping
system skid.

5.55 External Station Lighting Package. The pumping system shall have a lighting package to illuminate the control panel,
pumps and motors using two 100 watt industrial lamps. The lights will be controlled by an on / off switch mounted external to
the pumping system electrical control panel.

5.60 Z-pipe(s) A prefabricated section of schedule 40 steel pipe shall be provided to connect the discharge pipe of the
pumping system to the Raw or irrigation water piping, below ground. A flange shall be used to connect the Z-pipe to the lug-style
butterfly valve on the meter run of the discharge pipe of the pumping system. The connection, by the purchaser, to the Raw or
irrigation water pipe shall be flanged, grooved, or as specified by the purchaser. A one and one half (1 ) inch threadolet with
brass threaded ball valve shall be installed at the top of the Z-pipe to provide for winterization. The Z-pipe shall be painted to
match the pumping system. The z-pipe shall be installed by others in accordance with a properly designed thrust block.

5.70 Fabricated Steel Pump House with Shingled, Peaked Roof and Plywood Exterior. A building approximately __
wide x __ long x __ tall to the underside of the eaves. The building is constructed of interlocking, bolt-together, formed 16-
gauge sheet metal panels for the sidewalls and roof. Sidewall panels are 16 wide and roof panels are 16 wide. Sidewall panels
are bolted to the pump station skid using a formed steel z-base that forms a drip-lip to resist the penetration of moisture into the
building. Roof is peaked with a 4-to-12 slope and the center ridge runs the long dimension of the building. Building sidewalls
and roof are not insulated. Included are a ___ KVA mini-power center, quantity of ___ ___ watt interior fluorescent light
fixtures, ___ HP ventilation fan providing ___ SCFM @ ___ static pressure, gravity-operated louvers, ___ kW electric unit
heater for use during irrigation months (_________) with thermostat, and two (2) convenience outlets. Insulation is available as
an option (please contact Metron for information). All building wiring is routed in heavy wall, schedule 40 PVC conduit and
distributed to electrical devices. Entry to the building is through two sets of double doors located on one of the long sides of the
building and on one of the building ends. Building exterior has a AC plywood skin to which others will apply the appropriate
siding. The roof has felt paper and green colored shingles attached to it.




Part 6 Additional Items

Release 3.0, (042904)
Page 12
6.0 Amiad SAF-4500 Automatic Backwash Screen Filter System. An Amiad SAF-4500 Self-Cleaning Automatic Filter
stainless steel weavewire screen; automatic back washing based on differential pressure and/or time adjustable through the
Operator Interface Device (OID) on the front door of the control panel; check valve on the discharge side protects the filter
element from reverse flow; flush-line piping is by others. The filter connection size and filter element rating are as defined in the
Technical data sheet. The filter shall be an Amiad SAF-4500 (SAF4500) with a 300-micron screen. Filtration shall include a
check valve downstream to prevent back-flushing and damaging the screen. Note: There should be some form of pressure relief in
the raw or irrigation system downstream of the pump station. The pressure relief valve on the pump station is isolated from the
raw or irrigation system by this check valve. (AFLTR)

6.15 Filter By-Pass. Raw or irrigation portion of the pumping station to operate while the filter is being serviced or replaced;
includes three (3) isolation butterfly valves. This stations filter by-pass valves shall be lug style, butterfly type. The valves shall
be one piece ASTM A126 Grade B cast iron. The valves stems shall be 416 stainless steel. The valves discs shall be nickel
plated ductile iron. The valves stems bushings shall be Acetyl to prevent stem seizure to body during prolonged periods of non-
use. The valves seats shall be EPDM, one piece construction, and shall also form the flange sealing gaskets. Valves six (6) inch,
and smaller shall have a 10-position locking handle. Valves eight (8) inch, and larger shall have gear operator with hand wheel.
All valves shall be rated at 200 PSIG bubble shut off. The Station Isolation Valve(s) shall be a Keystone 222. (FLTRBP)

6.20 Auxiliary Power Supply Transformer / Mini Power Center. The pumping system manufacturer shall provide an
auxiliary power supply mounted on the skid, when requested by the purchaser. It shall be capable of delivering 120/ 220 volt,
single phase power, with KVA and breaker ratings as called out in the Technical Data Sheet. This transformer shall be capable of
powering: internal and external pump house lights; pump house ventilation fan; space heater (to maintain minimum 40 degree F.
pump house temperature); and other auxiliary power, as required and outlined on the technical data sheet. The Auxiliary Power
Supply Transformer shall be sized as outlined in the Technical Data Sheet. (MPC)

6.25 Soft-Start Motor Starter. A soft start shall be provided to gradually ramp up and down the speed, via soft start
programming, of the pump motor to eliminate/reduce shock forces to the pump mounting base and skid piping. The Soft Starter
size is as defined in the Technical Data Sheet. (SFTSTRT)

6.30 __ KW Space Heater. A heavy duty, industrial rated, space heater shall be provided with a 5 kW rating as indicated in
the Technical Data Sheet to maintain a pump house temperature above 40 degrees F. The heater shall be provided with a circuit
breaker, thermostat, and thermal safety overload shutdown. The heater shall be pre-wired and securely mounted on the pumping
system skid. (__HTR)

6.35 NEMA4 Electrical Enclosure with Air Conditioner. The control cabinet shall be NEMA 4 rate with through the door
disconnect switch and air conditioner for cabinet cooling. The air conditioner shall provide adequate cooling for the electrical
equipment within the control housing and for the environment the panel is located in so that all components are within their
respective manufacturers temperature requirements. (N4AC)

6.40 Automatic Alternation. This feature balances the run time on each of the main pumps based on a user selectable setting
through the OID to alternate based on hours logged or sequenced from last pump started. (AA)

6.45 Condensation Protection. There shall be a continuously operating heater in the electrical enclosure to prevent
condensation build-up. (CONP)

6.50 VFD By-Pass Switch. There shall be an across the line (ATL) by bypass wired in parallel to the main VFD that will be used as the primary starting
method in lieu of the VFD if the hand switch is switched to VFD Bypass. The hand switch shall be located inside the control panel. (BP)

6.55 Discharge Pressure Switch. A pressure switch rated at 200% of the operating pressure and in a NEMA4 enclosure
with a SPDT output shall be located in the downstream piping and sense if the system over pressures, which will lead to a shut
down of the system. (DPS)

6.60 Air Release Valve. A properly sized air release valve shall be installed on where identified on the drawing or at the
highest point on the pipe manifold. The air release shall allow for the release of air, generated by the starting of the pump, to
atmosphere. The discharge of the air release valve shall be vented back to the wet well through a polypropylene tube into the
wet well. The valve shall have a cast iron body, and cover, with stainless steel internal trim, and a viton orifice button to prevent
malfunctions due to corrosion. The air release valve shall be a Valmatic 15A. (AIRLS)

Release 3.0, (042904)
Page 13
6.65 2-Point Level Control Switch for the Wet Well. Two flexible probes shall extend into the wet well of a vertical pump
system for the purpose of sensing if there is water present and safe for the pumps to operate without running dry. One probe shall
serve as a reference and the other shall serve to indicate a level of water and they shall work on the conductivity. If no water is
present the pump system will shut down. (2LCP)

6.70 Dehumidifier. A dehumidifier shall be located on the skid in order to keep the humidity and moisture to a minimum.
with a capacity of 25 pints per 24-hours; refrigerant type; compressor; condensate piped to the wet well; 120-volt AC operation
by dial controlled adjustable humidistat; U.L. listed rubber cord; mounted to the vault skid. (DEHUMID)

6.75 Remote Panel. The systems control panel shall be located remotely from the systems skid and all wiring shall be done
by a licensed electrician as supplied by the contractor. (RMTPNL)

6.80 Pressure Transducer. The pressure transducer shall provide pressure signals for the control logic. It shall be a solid-
state bonded strain type with an accuracy of +/- 0.13% of full scale, and constructed of 17-4 PH stainless steel. It shall be rated
for the discharge pressure as shown on the Technical Data Sheet, and shall provide gauge pressure output, rather than absolute
pressure. The Pressure Transducer shall be a Setra Model 256. (PT13)

6.85 Pump Isolation Valves: The pump discharge isolation valves shall be lever operated, butterfly valves with grooved ends
to provide for expansion, and vibration dampening. Lug style pump discharge isolation valves are not acceptable. They shall be
sized as shown in the Technical Data Sheet. The valve body shall be constructed of ductile iron with a polyphenylene sulfide
coating. The valve disc shall be rubber coated ductile iron. The valve shall be rated at 300 PSIG. The Pump Isolation Valve(s)
shall be a Victaulic Series 300. (300BF)

6.90 Pressure Gauge. A pressure gauge shall read pressure from the discharge meter run. All gauges shall be silicon filled
to reduce effects due to vibration and incorporate isolation ball valves for maintenance. Accuracy of the pressure gauge shall be
within two (2) %. The gauge diameter shall be 4-1/2 minimum. The pressure gauge range shall be 0 200 PSIG. They shall
have a stainless steel back, and bronze internal parts. The Pressure Gauge(s) shall be manufactured by ASHCROFT.






2LCP/4LCP 2 or 4-Point Level Control Switch for the Wet Well
300BF
300 lbs Butterfly Isolation Valves
AA Automatic Alternation of Main Pumps
AFLTR Automatic Backwash Screen Filter System
AIRLS
Air Release Valve
APST
Auxiliary Power Supply Transformer
ATL
Across-the-Line Starters for pumps
BFV
Keystone Butterfly Valve for suction and discharge of pumps, flowmeter and
flowmeter bypass.
BLDG
Modular Style Building
BP
Variable Frequency Drive By Pass Switch
CLAVAL
60A-73B Cla-Val Pump Control Valve for each pump
CONP
Condensation Protection
CP
Control Panel
DBLDR
Double Door with window for building
DEHUMID
Dehumidifier
DPS/SPS
Discharge/Suction Pressure Switch
SPT/DPT
Suction and Discharge Pressure Transducers
EPC
Elastomer Pipe Connector for the suction of each pump with cables
Release 3.0, (042904)
Page 14
EXLTS
External Lighting Package for Enclosure
FCA
Flanged Coupling Adapter for the discharge of each pump
FIS
Fixed Inlet Screen
FLDRN
Floor Drain
FLTRBP
Filter Bypass
FRP
FRP Inner walls for Pump Station Building
GV
M&H Gate Valve for Flowmeter Isolation
HDC
High Discharge Shut-Off
HVAC
HVAC Unit including heater and air conditioner for building
HTR
__ kW Electric Space Heater
R__ INSUL
R___ Insulation for Pump Station Building
LSC
Low Suction Shut-Off
LTS
Fluorescent Light Fixtures For Building
MATS
Safety Floor Matting in front of control panels
MSH
Motor Space Heaters
MTEST
Manufacture Motor Test
__ kVA MPC
Mini Power Center ( 5, 7.5, 10, 15, 20 kVA)
N1
NEMA Rating
N__AC NEMA Rating with upgraded Air Conditioner
FBEPOX
Pipe Clad Red 1500, AWWA Approved Fusion-Bonded Epoxy Coating for
pipe interior
OI
An optical isolator will be an integral part of the flow meter component
enabling a separate signal to be available for other functions such as
fertigation.
PAIRLS
Individual Pump Air Release Valves
PPP
Pipe Penetration Plate for station suction and discharge connections
PNLTS
Control Panel Light Package
PRV
Pressure Relief Valve
PT13
Pressure Transducer with +/- 0.13 % Accuracy
PTEST
Manufacturer Pump Test
PVC
Schedule 40 PVC Conduit
RECP
(2) Convenience Receptacles
RM
Remote Monitoring Package
RMTPNL
Remote Mounted Control Panel
RSD
Remote Station Dialer
SCIS
Self Cleaning Inlet Screen
SFTSTRT
Motor Soft Starts
SLPRF
Sloped Roof for Enclosure
SHTR
Space Heater for Enclosure
ST
Sample Tap
STR
Strainer for Flowmeter
TANK
Hydro-pneumatic Tank or Storage Tank
TELMNT
Space to Mount Telemetry Panel
TESTPORT
Meter Test Port
TFM
Invensys Model #W100DR Turbine Flow Meter
Release 3.0, (042904)
Page 15
TIP
Telemetry Interface Panel
TNMC66
Tnemec Series 66 Hi-Build Epoxyline Coating for exterior of piping and floor
TVSS
Transient Voltage Surge Suppressor
UL
Underwriter's Laboratory Listing
WWLC
Wet Well Level Control
YSTR
Auto Flush Wye Strainer
ZPIPE
Z- Pipes for Suction and Discharge

Release 3.0, (042904)
Page 16
Technical Data Sheet
Metron, Inc.
Packaged Pumping Systems Division

End Suction Horizontal Pump, Variable Speed Drive
Prefabricated Pumping System

Project Name: Date:

Project Location: Customer:


Automatic Pumping System Model No. _______________________________________________________________________
System Design Point, flow and pressure at discharge of pumping system: _____________ @ _________ PSIG.
(accounting for losses through any strainer, or filter system)
Depth of wet well (from surface of pump house floor to surface of wet well floor): ______________ feet.
Maximum fluid lift in wet well _______________ feet.
Number of equally sized main pumps _____________

Motor Spec Motor (hp)
Inverter rated
BHP required at full run-out after
derating for altitude

Motor rpm 3600 1800 1800 1800
Motor service factor 1.15 1.15 1.15 1.15
Motor efficiency
Motor power factor
Motor type Submersible ODP ODP ODP
Motor disconnect volts 600 600 600 600
Motor Starter rating, amps
Motor fuse amps
Motor fuse AIC rating 200,000 200,000 200,000 200,000
Motor O.L. rating, amps
Motor cfm requirements
Pump Spec Pump ()
Maximum flow @ PSIG
Normal flow @ PSIG
Minimum flow @ PSIG
Pump efficiency at Design Point
Pump shutoff head
Pump check valve size (inches)
Pump check rating, PSIG
Pump check psi drop at capacity
Pump isolation valve size (in)

Motor Starting Code G, Class F Insulation
Minimum water coverage as measured from eye of bottom of VTP impeller: 24
Service Entrance: Circuit 1, __________ amps, __________ Fault Amps, __________ KVA, 3-phase, 460 volts, 60 hertz,
Circuit 2, __________ amps, __________ Fault Amps, __________ KVA, 3-phase, 460 volts, 60 hertz.

Motor and Pump Data: PMP Pump 1 Pump 2 Pumps 3
Release 3.0, (042904)
Page 17
Main Disconnect: Circuit 1, 600 Volts, ____ amps,
Circuit 2, 600 Volts, ____ amps.

Starting Equipment - UL Listed as Industrial Control Assembly:
Controls U.L. Listed as Industrial Control Assembly.
VFD Controls U.L. Listed as Industrial Control Assembly:
Operating Temp: 0
o
to 40
o
C (32
o
- 104
o
F)
Humidity: 5-95% Non-condensing
Minimum Efficiency (full load, base speed) 98%
Input Voltage: 3-phase, ____ Volts
Input Frequency: [ ] 50 Hz, or [ ] 60 Hz
Output Voltage: 3-phase, 0 - 480 Volts AC
Frequency Rating: 100% continuous drive rating,

Phase Failure, and low voltage shutoff at 90% of set voltage, for 4 seconds.

Low discharge pressure shutdown at ______ PSIG after all pumps are running for 60 seconds continuously.

High discharge pressure shutdown at ______ PSIG after all pumps are running for 60 seconds continuously.

Low water level safety shutdown, if water level drops to within two feet of highest pump suction.


Pressure Relief Valve
Size (inches)
Pressure Rating (PSIG)
Isolation Valve Size (inches)

Flowmeter/sensor: [ ] Pipe size ________ [ ] Pipe size ________

System Isolation Valve(s): Zone 1 ____ inch, lug style, butterfly valve Pressure rating: _______ PSIG
Zone 2 ____ inch, lug style, butterfly valve Pressure rating: _______ PSIG

Auxiliary Power Supply capacity: ______ KVA, including a minimum of the following-

Circuit Amps
1 Internal and external pump house lighting and receptacles
2 Heater
3 Ventilation fan and/or air conditioner
4 Lake Aeration and/or ozone equipment
5 Raw or irrigation Controls
6 Spare 1
7 Spare 2
8

Station Heater: _______ kW, Circuit 2 only

Z-pipe(s) #1: Inlet connection __________ inch, 150# RF ANSI
Outlet connection __________ inch, [ ] pipe/slip connection [ ] 150# RF ANSI
Reducer for inlet/outlet size transition in [ ] upper [ ] lower horizontal pipe run
Horizontal length (inlet face connect to outlet face connection) ___________________ Ft
Above ground horizontal, straight pipe run length ____________________ Ft
Below ground horizontal, straight pipe run length ____________________ Ft
[ ] 45% [ ] _______ diagonal slope from horizontal
Vertical length (centerline to centerline) _______________________ Ft
[ ] 1.5 threadolet with plug winterization connection on above ground, horizontal pipe
Release 3.0, (042904)
Page 18
[ ] Grooved coupling on above ground horizontal pipe to help with installation

#2: Inlet connection __________ inch, 150# RF ANSI
Outlet connection __________ inch, [ ] pipe/slip connection [ ] 150# RF ANSI
Reducer for inlet/outlet size transition in [ ] upper [ ] lower horizontal pipe run
Horizontal length (inlet face connect to outlet face connection) ___________________ Ft
Above ground horizontal, straight pipe run length ____________________ Ft
Below ground horizontal, straight pipe run length ____________________ Ft
[ ] 45% [ ] _______ diagonal slope from horizontal
Vertical length (centerline to centerline) _______________________ Ft
[ ] 1.5 threadolet with plug winterization connection on above ground, horizontal pipe
[ ] Grooved coupling on above ground horizontal pipe to help with installation

You might also like