You are on page 1of 2

A.

GENERAL CHARACTERISTICS
B. TECHNICAL SPECIFICATION
Design standars
Transformer type
Service Condition
Type of oil
Cooling
Number of phase
Frequency
: IEC 76
: Hermetically Sealed Totally Oil Filled
: Indoor
Primary Voltage
Capacity
No load losses at nominal voltage
On load losses at principal tapping
Impedance voltage
Noise
C. INSULATION CLASS OF THE WINDINGS
: Mineral Oil Class 1 acc. to IEC 296
: ONAN
: 3
: 50
:
:
: 925
:
: 4
: 56
TECHNICAL SPECIFICATIONS
Original
Date
Est.
Chk
App.
Client / Project:
No
Page
:
:
Primary Secondary
Applied test voltage (kV)
Impulse test voltage (kV)
PRIVATE
Phase
Hz
400
Watts
6100 Watts
%
125
50
0
3
1 / 2
Secondary Voltage
20
: 0.4
Vector Group : Dyn5
Temperature Rise : 60
Temperature Insulation Class :
Off load current at nominal voltage : 1.9 %
A
Efficiency ( % ) Voltage Regulation
3/4 load 4/4 load 1/4 load 2/4 load in % in Volt
Pf 0.8 97.85
98.27
98.22
98.57
98.49
98.79
98.39
98.71
386
394
3.46
1.59 Pf 1.0
Highest system voltage (kV) 24 1.1
: 65
- Oil
- Winding
kVA


kV
kV






oC
oC




E. APPROXIMATE WEIGHTS AND DIMENSION
Total length 1,530 :
Total width 840 :
Total height 1,440 :
Weight of oil 280 :
Weight of core and winding 680 :
Total weight 1,175 :
mm
mm
mm
kg
kg
kg
Approximate Drawing No. :
D. EFFICIENCY AND VOLTAGE REGULATION
Light Grey RAL 7032 : Painting Colour
The above dimensions and masses are approximate and provided to give a general description of our proposed
:
:
:
Revision
Off Circuit Tapping value : +/-2.5%;+/-5%
dB
transformer.
Jakarta - Indonesia
Joint venture between AREVA TD - P
16-Feb-05
BUD
D 0697
TECHNICAL SPECIFICATIONS
Original
Date
Est.
Chk
App.
Client / Project:
No
Page
:
:
PRIVATE
2 / 2
Revision
I. LIST OF TEST
Routine Test :
- Measurement of the resistance value and checking of polarities
- Measurement of the ratio on all taps
- No load test for measurement of the no load loss and no load current
- Short circuit test for determination of the on load loss and impedance
- Applied voltage test
- Induced voltage test
:
:
:
:
:
:
Type test :
- Temperature rise test
- Full wave impuls test ( 1.2 / 50 us )
:
:
F. ACCESSORIES
- Name Plate and Rating Plate
- HV Plug in Bushings and LV Porcelain Bushings
- Off Circuit Tap Changer
- Oil Filling Plug
- Oil Draining Valve
- Lifting Lugs
- Grounding Terminal
- Bidirectional Rollers
- Pressure Relief Device Without Contact
- Protection Relay RIS
Tests other than the above mentioned list needs further confirmation
G. DEVIATIONS / EXCEPTIONS
- None
Yes No
- None
H. NOTES

Jakarta - Indonesia
Joint venture between AREVA TD - PL
16-Feb-05
BUD
D 0697