You are on page 1of 25

Instalaciones elctricas 2

January 1, 2014

| Universidad de el salvador

1


Instalaciones elctricas 2


Profesor:
Ing. Jorge Alberto Zetino Chicas.


Tarea 2:
ESTUDIO DE CORTOCIRCUITO Y COORDINACIN
DE PROTECCIONES.







INTEGRANTES

Coto Portillo, Jonathan Alonzo CP09066
Lpez Orantes, Nstor Amlcar LO09013
Prez Henrquez, Kevin Rolando PH09009

2014
Toshiba
1/1/2014
Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

2
Diagrama unifilar completo.

Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

3
Calculo de reactancias en p.u
POTENCIA BASE = 3000 KVA
RED
Voltaje distribuidora = 23 KV
Corriente de corto circuito de la red distribuidora = 15 KA

X
RED
= 0.005 P.U

LINEA 1


Conductor seleccionado AWG # 2
Tabla 4 -7(ver anexo)
R= 0.202


X=0.0457


D=100 mts

(100)(3.28)=0.01499



TRANSFORMADOR 1

Potencia=300 KVA
Tabla 1.2 impedance data for three phase transformers (ver anexo)

Z=5.75%
X =0.0575

= 0.0575 P.U



Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

4
MOTOR DE INDUCCION 1

Potencia= 750 KVA
Velocidad= 1200rpm
V= 4.16 KV



Numero de polos= 6 polos
Motor de 6 polos utilizando la tabla 8d (ver anexo) se selecciona las reactancias tpicas en
P.U para maquinas elctricas rotatorias.
X=0.25
X=0.15

= 1 P.U

MOTOR DE INDUCCION 2

1 HP 1 KW
Potencia= 500HP
Velocidad= 1200rpm
V= 4.16 KV



Numero de polos= 6 polos
Motor de 6 polos utilizando la tabla 8d (ver anexo) se selecciona las reactancias tpicas en
P.U para maquinas elctricas rotatorias.
X=0.25
X=0.15

= 1.5 P.U




Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

5

MOTOR DE SINCRONO
Potencia= 1000 KVA
Velocidad= 1800rpm
V= 4.16 KV



Numero de polos= 4 polos
Motor de 4 polos utilizando la tabla 8d (ver anexo) se selecciona las reactancias tpicas en
P.U para maquinas elctricas rotatorias.
X=0.15
X=0.23

= 0.45 P.U

LINEA 2


Conductor seleccionado AWG # 2
Tabla 4 -7(ver anexo)
R= 0.202


X=0.0457


D=20 mts

(20)(3.28)=0.003



TRANSFORMADOR 2
Potencia=500 KVA
Tabla 1.2 impedance data for three phase transformers (ver anexo)
Z=1.3%

X =0.013

= 0.078P.U


Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

6
12 MOTORES DE INDUCCION TROQUELADORAS

Potencia= 7.5 KVA
CLASE= B
V= 480 KV

Tomando en cuenta que las doce maquinas troqueladoras tiene la misma reactancia.

DE TABLA 430-7(b).- Letras de cdigo para rotor bloqueado (VER ANEXO)
FACTOR=3.54


X=0.282

= 113 P.U

MOTORES DE INDUCCION 3

Potencia= 75 KVA
CLASE= A
V= 480 KV
DE TABLA 430-7(b).- Letras de cdigo para rotor bloqueado (VER ANEXO)
FACTOR=3.14


X=0.32

= 12.8 P.U

LINEA 3



Conductor seleccionado AWG # 1/0





Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

7
Tabla 4 -7(ver anexo)
R= 0.202


X=0.0457


D=20 mts

(20)(3.28)=0.003



TRANSFORMADOR 3

Potencia=75 KVA
Tabla 1.2 impedance data for three phase transformers (ver anexo )

Z=1.6%

X =0.016

= 0.64 P.U

GRUPO DE MOTORES
Motores de 600 volts o menores. en el sistema de 600 volts o menos, los motores mas
grandes ( es decir, motores del orden de cientos hp), son solo unos cuantos y representan
una pequea porcin de la carga total conectada. Estos motores grandes se pueden
representar en forma individual, o bien, se pueden agrupar con los motores pequeos
para representar los grupos completos como un motor equivalente en el diagrama de
impedancias. Los motores muy pequeos, por lo general se dejan fuera de los clculos, ya
que en estudios de cortocircuito es difcil predecir que tanto puedan contribuir y si es
seguro que agreguen complejidad al estudio. Una solucin alternativa es agrupar todos los
motores pequeos y representan una reactancia equivalente de ellos.
En sistemas industriales que operan con tensiones de 600, 440 o 480v trifsico, se supone
que los motores operan agrupados en el secundario del transformador y estn conectados
justamente en el bus secundario y tienen una reactancia del 25% a una base en KVA igual
al 100% de la capacidad del transformador.
Lo mencionado anterior mente obtenido del libro Proteccin de instalaciones elctricas
industriales y comerciales Escrito por Enrquez Harper.
Se obtiene la reactancia por unidad del grupo de motores alimentado por un
transformador trifsico de 75 KVA.

Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

8

)

LINEA 4



Conductor seleccionado AWG # 1/0
Tabla 4 -7(ver anexo)
R= 0.202


X=0.0457


D=20 mts

(20)(3.28)=0.003



TRANSFORMADOR 4

Potencia=75 KVA
Tabla 1.2 impedance data for three phase transformers (ver anexo )

Z=1.6%

X =0.016

= 0.64 P.U







Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

9
GENERADOR
POTENCIA= 75 KVA
VOLTAJE= 208/120

DE TABLA 5
X=0.09

X
p.u
(

)





























Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

10








l i n e a 1 8 5 u
T 1 5 7 . 5 m X r e d 5 m
M 1 1
M 2 1 . 5
M 3 4 5 0 m
i n e a 2 5 2 0 uT 2 7 8 m
T r o q u e l a d o r a 1 1 3
M 4 1 2 . 8
l i n e a 3 3 6 m
T 3 6 4 0 m
M 7 1 0
L i n e a 4 3 6 m
T 4 4 5 0 m
G e n e r 4 5 0 m
t r o q 1 1 3
T r o q 1 1 3
t r o q 1 1 3
T r o q 1 1 3
T r o q 1 1 3
T r o q 1 1 3
T r o q 1 1 3
T r o q 1 1 3
T r o q 1 1 3
T r o q 1 1 3
DIAGRAMA DE REACTANCIAS SUBTRANSITORIAS
23 KV
4.16 KV
BARRA 1
BARRA 2
480 V
240 V
208 V
BARRA 3
BARRA 4
Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

11

CALCULOS DE CORRIENTES DE FALLA.
Falla en barra de 4.16kV

X
barra1pu
=



X
1
=

+ 0.07852

X
barra1pu
= 0.05259226317

KVA
cckTbarra1
=



KVA
ccktbarra1
= 57.03422 MVA

I
cckTbarra1
=



I
cckTbarra1
= 7.915558 KA
Falla en barra de 480V
X
2
=



X
barra2pu
=



X
barra2pu
= 0.1240928594

KVA
cckTbarra2
=



KVA
ccktbarra2
= 24.175444 MVA

I
cckTbarra2
=



I
cckTbarra2
= 29.07854 KA
Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

12
Falla en barra de 240V

X
3
=



X
31
=



X
barra3pu
=



X
barra3pu
= 0.7420717332

KVA
cckTbarra3
=



KVA
ccktbarra3
= 4.0289 MVA

I
cckTbarra3
=



I
cckTbarra3
= 9.725311 KA
Falla en barra de 208V
X
4
=



X
41
=



X
barra4pu
=



X
barra3pu
= 0.8587683155

KVA
cckTbarra4
=



KVA
ccktbarra4
= 3.493375 MVA


Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

13
I
cckTbarra4
=



I
cckTbarra4
= 9.69664 KA
Falla M1.
X
M1pu
=



X
M1pu
= 0.0555117518

KVA
cckTM1
=



KVA
cckTM1
= 54.0426 MVA

I
cckTM1
=



I
cckTM1
= 7.5 KA
Falla M2.
X
M2pu
=



X
M2pu
= 0.05450301781

KVA
cckTM2
=



KVA
cckTM2
= 55.0428 MVA

I
cckTM2
=



I
cckTM2
= 7.639 KA
Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

14


Falla M3.
X
M3pu
=




X
M3pu
= 0.05271366


KVA
cckTM3
=



KVA
cckTM3
= 56.91 MVA

I
cckTM3
=



I
cckTM3
= 7.8985 KA

Falla A.

X
MApu
=



X
MApu
= 0.0545094733

KVA
cckTMA
=



KVA
cckTMA
= 55.036 MVA

I
cckTMA
=



I
cckTMA
= 7.638 KA

Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

15
Falla B.

X
MBpu
=



X
MBpu
= 0.13251

KVA
cckTMB
=



KVA
cckTMB
= 22.64 MVA

I
cckTMB
=



I
cckTMB
= 27.23 KA


Falla D.

X
1
=



X
MDpu
=



X
MDpu
= 0.1252816

KVA
cckTMD
=



KVA
cckTMD
= 23.946 MVA

I
cckTMD
=



I
cckTMD
= 28.8 KA



Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

16
Falla E.

X
1
=



X
MEpu
=



X
MEpu
= 0.125317

KVA
cckTME
=



KVA
cckTME
= 23.94 MVA

I
cckTME
=



I
cckTME
= 28.79 KA


Falla G.

X
MEpu
=



X
MEpu
= 0.329388

KVA
cckTME
=



KVA
cckTME
= 9.1 MVA

I
cckTME
=



I
cckTME
= 1.26 KA



Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

17
Simulacion en sofware etap.


Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

18
COORDINACION
La coordinacin de sobre corriente es una aplicacin sistemtica de dispositivos de proteccin que
actan por corriente en el sistema elctrico, que en respuesta a una falla o sobrecarga, sacar de
servicio slo una mnima cantidad de equipo. El objetivo principal ser proteger al personal de los
efectos de estas fallas, minimizar el dao al equipo elctrico y reducir los costos por salidas de
servicio de la carga asociada. El estudio de coordinacin de protecciones de sobre corriente
consiste en un estudio organizado tiempo corriente de todos los dispositivos en serie desde la
carga hasta la fuente. Este estudio es una comparacin del tiempo que toma cada uno de los
dispositivos individuales para operar cuando ciertos niveles de corriente normal o anormal pasa a
travs de los dispositivos de proteccin.
El objetivo de un estudio de coordinacin de protecciones de sobre corriente es determinar las
caractersticas, valores nominales y ajustes de los dispositivos de proteccin que aseguren que la
mnima carga no fallada se interrumpa cuando los dispositivos de proteccin aslen una falla o una
sobrecarga en cualquier parte del sistema elctrico. Los interruptores slo deben operar cuando
exista una falla y no deben operar cuando se presenten corrientes Inrush, arranques de motores,
transitorios. Adicionalmente, los dispositivos de proteccin se deben coordinar para interrumpir a
pocos clientes o cargas como sea posible. Las caractersticas que se deben considerar durante el
diseo y coordinacin de las protecciones que definen un diseo eficiente del esquema de
protecciones de cada sistema elctrico son: Confiabilidad, rapidez, economa, simplicidad y
selectividad.
Ahora analizaremos el circuito dividindolo en 6 ramales para poder analizar las curvas de los
dispositivos de proteccin.












Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

19
Simulacion de coordinacin de protecciones

Ramal 1






Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

20
Ramal 2







Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

21
Ramal 3

c





Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

22
Ramal 4







Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

23
Conclusiones

La corriente de falla ms elevada ocurre en la barra #2, debido a que adems de la red, los
motores contribuyen a esta falla. Pero el factor ms determinante para la elevada corriente en
este punto es la baja tensin a la que se encuentra la barra, 480V.

Los retardos que se le aplican a los dispositivos de proteccin sirven para establecer la apertura
oportuna y necesaria para sacar de funcionamiento nicamente el equipo o los equipos que estn
siendo afectados por la falla y dejar en operacin toda la dems carga que no tiene que ver con la
falla en cuestin.
Cuando un transformador se energiza se produce en el bobinado una corriente elevada (IN-RUSH)
que luego se estabiliza hasta el valor nominal. La magnitud de esta corriente depende de las
caractersticas de cada transformador. Esta consideracin se debe tomar en cuenta a la hora de
dimensionar la proteccin de los transformadores para permitirles iniciar su funcionamiento
adecuadamente. La curva de disparo de las protecciones debe quedar entre el punto de IN-RUSH y
la curva de dao del transformador.
La cordicaciones de protecciones es un estudio importante en construccion y analisis de una
subestacion ya que con protecciones descordinadas hubiera problemas de protecciones ya sea de
desconecciones inecesaria o que una proteccion no actue en el instante que ocurre la falla.

Para este tipo de analisis se necesita un sofware que facilite los calculos asi se comprobueba el
buen analisis que se necesita para seleccionar las protecciones.








Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

24
anexos









Instalaciones elctricas 2
January 1, 2014

| Universidad de el salvador

25

You might also like