You are on page 1of 2

Crompton Greaves Limited

Switchgear Division : Power Systems


A-3, MIDC, Ambad, Nasik 422 010, Maharashtra, India
T: +91 253 238 2271 F: +91 253 2381247




Doc No.: EIT/TC/002/R0



Registered Office:
CG House, 6
th
Floor Dr. Annie Besant Road, Worli, Mumbai 400 030, India
T: +91 22 2423 7777 F: +91 22 2423 7733 W: www.cgglobal.com


1/2

ROUTINE TEST CERTIFICATE
CAPACITOR VOLTAGE TRANSFORMER

Customer
Northern Electricity Development & Investment Joint
Stock Company No.2
Type CVE: 145 / 650 / 50
S.O.No. SX:3598-1B/10
Unit Serial No. XS107199

Transformation Ratio
115kV/3 / 110V/3 / 110V/3/ 110V/3.
Rated/Highest System Voltage 115 / 123 kV
Rated Frequency 50 Hz.
Rating
Secondary Winding 1a -1n 2a -2n 3a -3n
Rated Output 100 100 100
Accuracy Class 3P 0.2 0.2
Simultaneous output / Accuracy Class 100 V A / 0.2
Equivalent Capacitance of Coupling
Capacitor
6400 pF (+10%, -5%)
1 Verification of Terminal Markings OK
2
Measurement of Capacitance and Tangent Delta of Coupling Capacitor at Power Frequency.

Voltage (kV) Capacitance (pF) Tan Delta
Before HV
10 6400.87
0.00140
66 6402.57
0.00142
After HV
10 6402.37
0.00139
66 6403.87 0.00142
Measurement of Capacitance and Tangent Delta of Capacitor Voltage Transformer at 4kV
With g disconnected from tank 6152.00 0.0028
With g & N disconnected from tank 6346.00 0.0016
3
Partial Discharge at 1.2 Um / 3 85 kV 2 pC
Partial Discharge at Um 123 kV 3 pC
4
One minute Power Frequency AC Voltage Withstand Test
I. On Capacitor Divider Unit. 230 kV OK
II. On NHF terminal of Capacitor Divider Unit 4 kV OK
III. On Secondary Windings and On Neutral Lead of Intermediate
Voltage Transformer of EMU.
3 kV OK
5 Induced High Voltage Test on Electromagnetic Unit at 150 Hz. for 40 sec 49.37 kV OK
6 Dimensional Checks OK
7 Sealing Test at 1.1 kg / cm
2
pressure and at 70
0
C for 8 hours OK
8 Ferro-resonance check at three times at 0.8 U
PR
& at three times 1.5 U
PR
OK
Crompton Greaves Limited
Switchgear Division : Power Systems
A-3, MIDC, Ambad, Nasik 422 010, Maharashtra, India
T: +91 253 238 2271 F: +91 253 2381247




Doc No.: EIT/TC/002/R0



Registered Office:
CG House, 6
th
Floor Dr. Annie Besant Road, Worli, Mumbai 400 030, India
T: +91 22 2423 7777 F: +91 22 2423 7733 W: www.cgglobal.com


2/2



Unit Serial No. : XS107199




9
Determination of Errors
Winding
under Test
Rated Secondary
Voltage (Volts)
Applied
Voltage (%)
Burden 0.8
pf Lag (VA)
Ratio Error
(%)
Phase
Error (min)
1a-1n 110V/ 3 150 100 -0.26 -4
110V/ 3 150 25 +0.03 -3

110V/ 3 5 100 -0.24 -1

110V/ 3 5 25 +0.04 -0
2a-2n 110V/ 3 100 100 -0.09 -0

110V/ 3 100 25 +0.09 -1
3a-3n
110V/ 3 100 100 -0.10 +1

110V/ 3 100 25 +0.09 -0

This is to certify that the above Capacitor Voltage Transformer has been tested for routine tests in
accordance with the relevant clauses of IEC 60044-5 (2004), in so far as they are applicable and has
passed the test successfully.



Tested By:

Manager, QA
S1 Division,
Crompton Greaves Ltd.
Nashik.


Date of Test: 11/03/2011