= reinforcement location factor = 1.3 for top bars
e
= coating factor = 1.0 for uncoated bars
s
= reinforcement size factor = 1.0 for No.25 bars
= lightweight aggregate factor = 1.0
c
b
= spacing or cover dimension
(governs)
- 70 -
Beam Design
(c
b
+ K
tr
)/d
b
= (53 + 0)/25 = 2.12 < 2.5
l
d
= 0.92 < 1.5 m
Retain cutoff length of 1.5 m
36
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 71 -
Beam Design
ACI 12.10.5
Flexural reinforcement terminated in a tension zone:
Point of inflection is 4.6 m from face of support >
1.5 m
Check ACI 12.10.5.1:
If V
u
(cutoff point) 2V
n
/3, tension reinforcement
can be terminated there
- 72 -
Beam Design
V
n
= (V
c
+ V
s
) = (V
c
+ A
v
f
yt
d/s )
= 0.75 [288 + (157420487.5)/(1000x250)]
= 312 kN
2V
n
/3 = 208 kN
V
u
@ 1.5 m from face of support = 225.6 (60.1 1.5)
= 135 kN < 208 kN
Therefore, 3-No.25 bars can be terminated at 1.5 m
from face of support
37
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 73 -
Beam Design
Structural integrity reinforcement (ACI 7.13.2.5)
Other than perimeter beams, when closed stirrups
are not provided
At least one-quarter of positive reinforcement
required at midspan, but not less than two bars,
shall be continuous or spliced with Class B
tension splices over the supports
- 74 -
Beam Design
38
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 75 -
Column Design
7900 7900 7900 7900 7900 7900 7900
6
7
0
0
6
7
0
0
6
7
0
0
Column C4
Unit: mm
Column dimension: 650 mm 650 mm
- 76 -
Column Design
Table: Summary of Design Axial force, Bending Moments, and Shear
Forces for Column C4 Supporting the Second Floor
Load Case Axial
Forces (kN)
Bending
Moment (kN-m)
Shear Force (kN)
Dead (D) 5701 0 0
Live (L) 1100 0 0
Wind
(W)
Case 1 0 35 21
Case 2 0 26 15
Case 3 9 26 15
Case 4 6 21 12
39
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 77 -
Column Design
Table: Summary of Design Axial force, Bending Moments, and Shear
Forces for Column C4 Supporting the Second Floor
Load Case Axial
Forces (kN)
Bending
Moment (kN-m)
Shear Force (kN)
1.4D 7981 0 0
1.2D + 1.6L 8601 0 0
1.2D + 1.6L + 0.8W
(Wind Case 1)
8601 28 17
1.2D + 0.5L + 1.6W
(Wind Case 1)
7391 56 34
0.9D - 1.6W
(Wind Case 1)
5131 -56 -34
- 78 -
Column Design
Design for axial force and bending
650 650 mm column with 12 - No.28 bars
g
= 1.75 % > 1.0 % O.K.
< 8.0 % O.K.
40
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 79 -
Column Design
- 80 -
Column Design
Shear design
where N
u
= 5131 kN is the smallest axial force
corresponding to the largest shear force on the
section and d = 650 40 10 28/2 = 586 mm
ACI Eq. (11-4)
41
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 81 -
Column Design
V
u
(= 34 kN) < V
c
/2 = (0.75765)/2 = 287 kN
Transverse reinforcement requirements must satisfy
ACI 7.10.5, with No.10 ties, the vertical spacing of
the ties must not exceed the least of the following:
16(longitudinal bar diameter) = 1628 = 448 mm (governs)
48(tie bar diameter) = 4810 = 480 mm
Least column dimension = 650 mm
- 82 -
Column Design
Use No.10 ties @ 400 mm with the first tie located
vertically not more than 400/2 = 200 mm above the
top of the slab and not more than 75 mm below the
lowest horizontal reinforcement in the beams (ACI
7.10.5.4 and 7.10.5.5)
42
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 83 -
Column Design
Splice length of longitudinal reinforcement
ACI 12.17.2.1
From the P-M interaction diagram, it can be seen that
the column reinforcement is in compression for all
load combinations. As a result, lap splice length is
determined in accordance with ACI 12.16.1.
- 84 -
Column Design
Splice length of longitudinal reinforcement
ACI 12.16.1
For f
y
= 420 MPa and f
c
= 40 MPa,
l
dc
= 0.071f
y
d
b
= 0.071x420x28 = 835 mm
43
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 85 -
Column Design
Splice length of longitudinal reinforcement
ACI 12.17.2.4
In both directions of the cross-section:
0.0015hs = 0.0015x650x400 = 390 mm
2
Area of ties provided in both direction:
A
v
= 3-legged No.10 = 3x79 = 237 mm
2
< 0.0015hs
Thus, lap splice length cannot be reduced by a factor
of 0.83.
- 86 -
Column Design
Provide 850 mm splice length
44
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 87 -
Column Design
- 88 -
Shear Wall Design
7900 7900 7900 7900 7900 7900 7900
6
7
0
0
6
7
0
0
6
7
0
0
Shear Wall
Unit: mm
45
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 89 -
Shear Wall Design
Table: Summary of Design Axial forces, Bending Moments, and Shear
Forces at the Base of the Shear Wall on Line 7
Load Case Axial
Force (kN)
Bending
Moment (kN-m)
Shear Force
(kN)
Dead (D) 15,885 0 0
Live (L) 2539 0 0
Wind
(W)
Case 1 0 13,376 897
Case 2 0 14,211 955
Case 3 45 10,034 673
Case 4 34 11,021 741
- 90 -
Shear Wall Design
Table: Summary of Design Axial forces, Bending Moments, and Shear
Forces at the Base of the Shearwall on Line 7
Load Case Axial
Forces (kN)
Bending
Moment (kN-m)
Shear Force
(kN)
1.4D 22,239 0 0
1.2D + 1.6L 23,124 0 0
1.2D + 1.6L + 0.8W
(Wind Case 2)
23,124 11,369 764
1.2D + 0.5L + 1.6W
(Wind Case 2)
20,332 22,738 1528
0.9D - 1.6W
(Wind Case 2)
14,297 -22,738 -1528
46
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 91 -
Shear Wall Design
Shear design
The shear strength of the concrete is determined in
accordance with ACI 11.9.5 for walls subjected to
axial compression:
V
c
= 0.17(40)
0.5
3005880/1000 = 1897 kN
where, d = 0.8l
w
= 0.8x7350 = 5880 mm
- 92 -
Shear Wall Design
V
c
= 0.75x1897 = 1423 kN < V
u
= 1528 kN
Horizontal shear reinforcement shall be provided in
accordance with ACI 11.9.9.
Because the wall is more than 250 mm thick, two
layers of reinforcement is necessary in accordance
with ACI 14.3.4.
47
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 93 -
Shear Wall Design
According to ACI 11.9.9.3, spacing of horizontal
reinforcement shall not exceed
l
w
/5 = 7350/5 = 1470 mm,
3h = 3 300 = 900 mm, or
450 mm. (governs)
- 94 -
Shear Wall Design
According to ACI 11.9.9.2, ratio of horizontal shear
reinforcement shall not be less than 0.0025.
With 2 layers of No.14 bars, spacing required:
s = (2 154) / (300 0.0025) = 411 mm
Provide 2-No. 14 horizontal bars @ 400 mm
(
t
= 0.00257).
48
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 95 -
Shear Wall Design
By ACI 11.9.3, shear strength V
n
at any horizontal
section must be less than or equal to
0.83(40)
0.5
30058801/1000 = 9260 kN
V
n
= V
c
+ V
s
= 1897 + (2 1544205880)/(4001000)
= 3799 kN < 9260 kN O.K.
- 96 -
Shear Wall Design
The ratio of vertical shear reinforcement area to gross
concrete area of horizontal section shall not be less
than 0.0025 nor the value obtained by Eq. (11-30)
(ACI 11.9.9.4):
l
= 0.0025 + 0.5(2.5-h
w
/l
w
)(
t
0.0025)
= 0.0025 + 0.5 (2.5-45.6/7.35)(0.00257-0.0025)
= 0.00237
49
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 97 -
Shear Wall Design
According to ACI 11.9.9.5, spacing of vertical
reinforcement shall not exceed
l
w
/5 = 7450/5 = 1490 mm
3h = 3 300 = 900 mm or
450 mm
Provide 2-No. 14 vertical bars @ 400 mm
(
l
= 0.00257)
- 98 -
Shear Wall Design
The provided vertical and horizontal reinforcement
satisfy the requirements of ACI 14.3.2 and 14.3.3 for
minimum ratio of vertical and horizontal
reinforcement to gross concrete area, respectively,
and ACI 14.3.5 for maximum bar spacing.
50
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 99 -
Shear Wall Design
In accordance with ACI 14.4, the shear wall is
designed for combined flexure and axial load as a
compression member following the provisions of
ACI 10.2, 10.3, 10.10, 10.11, 10.14, 14.2, and 14.3.
- 100 -
Shear Wall Design
The wall is reinforced with 12-No. 28 bars in the 650
650 mm columns at both ends of the wall and 2-
No.14 vertical bars @ 400 mm in the web.
51
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 101 -
Shear Wall Design
- 102 -
Shear Wall Design
Development length of horizontal reinforcement
where,
t
= reinforcement location factor = 1.0
e
= coating factor = 1.0 for uncoated bars
s
= reinforcement size factor = 0.8 for No.14 bar
= lightweight aggregate factor = 1.0
52
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 103 -
Shear Wall Design
c
b
= spacing or cover dimension
(c
b
+ K
tr
)/d
b
= (27 + 0)/14 = 1.93 < 2.5
(governs)
- 104 -
Shear Wall Design
Required l
d
(= 347 mm) can be accommodated within
the 650 mm dimension of columns, so that hooks
are not needed at the ends of the bars.
53
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 105 -
Shear Wall Design
- 106 -
Question and Answer Session
If you are encountering technical difficulties, please call 00 1 847 991 2700
54
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
- 107 -
Thank You!!
For more information
www.skghoshassociates.com
Chicago Main Office
334 East Colfax Street, Unit E
Palatine, IL 60067
Phone: (847) 991-2700
Fax: (847) 991-2702
Email: skghoshinc@gmail.com
Southern California Office
43 Vantis Drive
Aliso Viejo, CA 92656
Phone: (949) 249-3739
Fax: (949) 249-3989
Email: susandowty@gmail.com