Eaton 9135 6kVA UPS Technical Specification


CONSTRUCTION
Model PW9135G6000-XL3UEU PW9135N6000-EBM3U
Rating 6kVA/4.2kW Extended Battery Module
Technology VFI-SS-113, on-line double conversion with power factor correction,
convection cooled static bypass switch
UPS Dimensions: WxDxH (mm)
Rack Configuration:
444.5 x 741 x 130.6 (3U) 444.5 x 650 x 130.6 (3U)
UPS Dimensions: WxDxH (mm)
Tower Configuration:
130.6 x 741 x 444.5 130.6 x 650 x 444.5
Weight (kg) 57kg 70.5
ENVIRONMENTAL & SAFETY
Ambient storage temperature -20C to +40C with batteries and -25C to +55C without batteries
Ambient service temperature Power electronics part: +0 to +40C
Battery part: +5 to 25C without reducing battery life
Maximum service altitude 1000m above sea level.
Relative humidity 5 to 95%, no condensation allowed
Degree of protection IP20 (EN60529)
Acoustic Noise 46 dBA Normal mode, typical load and Battery mode
Surge Suppression ANSI C62.41 Category B, IEC 6100045
Safety Conformance UL 1778;
CSA C22.2, No. 107.1;
EN 6204011, IEC 609501, IEC 5009111
Electromagnetic Compatibility
(Class A)
EN 620402 C1, AS 620402 C1, FCC Part 15
Agency Markings TUV(GS), CE, cUL, CTick
POWER CONNECTIONS
Input Hardwired (up to 6mm
2
)
Output Hardwired (up to 6mm
2
) with (8) 10A, IEC 320C13; (2) 16A, IEC 320C19
USER INTERFACE
Display LCD with blue backlight, 4x LEDs for notice and alarm
Standard Communication Ports 1 x USB (HID), 1x RS232 (DB9), 1 x Relay Port (DB9), 1 x Remote Power
Off Port, 1 x Mini-Slot Port (Empty)
Relay Port Voltage Free Contacts On Mains, On Automatic Bypass, On Battery, Battery Low, Load Protected
Output Relay Specifications 48VDC Max, 2A Max, 62.5VA, 30W. Example: for 48 Vdc, Imax = 625 mA
Optional Mini Slot cards; Web/SNMP, Relay, ModBus/JBus
ELECTRICAL CHARACTERISTICS - INPUT
Rated input voltage and voltage
tolerance

Rectifier: 230Vac nominal (200, 208, 220, 240, 250V Selectable)
Tolerance: 156-280V (-32% to +22%) at 100% load,
120-280V (-48% to +22%) at 70% load
Bypass tolerance: 196 253V (-15%, +10% of nominal)
Operating Frequency / Tolerance 50 or 60Hz; Tolerance 40-70Hz (+0.2Hz)
Input current distortion <7% THDi (Linear load condition at rated input current)
Input power factor >0.95pf
Inrush Current < 100% of rated current
UPS Input Current 26A at 230V and full load
Recommended Input Circuit
Protection
32A D Curve MCB




Page 2 of 2

Eaton 9135 6kVA UPS Technical Specification
ELECTRICAL OUTPUT CHARACTERISTICS NORMAL MODE
Rated apparent/active power 6kVA/4.2kW
Transfernormal to stored energy No break
Rated output voltage 230V Single Phase (default), 200, 208, 220, 240, 250Vac (selectable)
Output voltage variation 2%
Crest factor 3:1
Rated output frequency 50Hz (default) or 60Hz
Output frequency regulation 4%
Total output voltage distortion < 3% (Across a linear load); <5% (Across a reference non-linear load)
Number of output phases 1 Phase
Frequency Slew Rate 1Hz/s (default), or 0.5 Hz/s
ELECTRICAL OUTPUT CHARACTERISTICS STORED ENERGY
Rated apparent/active power 6kVA/4.2kW
Waveform Sine Wave
Rated output voltage 230V Single Phase (default), 200, 208, 220, 240, 250Vac (selectable)
Output voltage variation 2%
Crest factor 3:1
Rated output frequency 50Hz (default) or 60Hz
Output frequency regulation 4%
Total output voltage distortion < 3% (Across a linear load); <5% (Across a reference non-linear load)
Load power factor range 0.7 lagging- 0.8 leading without derating
Number of output phases 1 Phase
EFFICIENCY (Input/Output)
Efficiency at 100% load (On Line
Mode/High Efficiency Mode)
91% / 97%
Heat dissipation 415W / 1416BTU/h
BATTERY
Battery Management Weekly automatic battery test (selectable daily, weekly or monthly)
Battery Nominal Voltage 180V (90 Cells)
Battery Re-charge time Six (6) hours to recover 90 percent of nominal backup
time after 100 percent load discharge
UPS Battery Configuration (15) 12V, 5.5 Ah internal batteries, Valve Regulated Lead Acid, AGM
EBM Configuration (2 strings of 15) 12V, 5.5 Ah internal batteries
Battery Replacement Hot-swappable internal and external batteries
Battery Run Times Internal
Batts
+ 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs
Minutes @ Full load 4 17 33 50 67
NOTE: Battery times are approximate and vary depending on age, temperature, load configuration and battery charge.
BYPASS CHARACTERISTICS
Type of bypass Automatic Bypass
Transfer No break