You are on page 1of 2

UQGS.

S726
Heat-automatic Fire Detectors
Page Bottom
Heat-automatic Fire Detectors
See General Information for Heat-automatic Fire Detectors
SIEMENS INDUSTRY INC S726
8 FERNWOOD RD
FLORHAM PARK, NJ 07932 USA
Spacing (Ft)
Model
No. Type
Compatibility
Restrictions
Contact
Arrangement
Temp
Range (F)
Smooth
Ceiling
to Wall or
Partition
DT-11, FPT-11, FPTF-11
FT None - 135 50 25
DT-135C, DT-135CS, DTC-135, DTC-135P
RC None - 135 50 25
DT-135P, DT-135CL, DT135CPF, DT-135CPS
RC D2 - 135 50 25
DT-135WP, DT-195WP (virtrically mounted)
RC None - 135, 194 50 25
DT-160CPS RC D2 - 160 25 12.5
DT-190CPS RC D2 - 190 50 25
DT-200C, DT200CS, DT-200
RC None - 200 25 12.5
DT-200CL, DT200CPF, DT-200CPS, DT-200P
RC D2 - 200 25 12.5
DT-225CP RC D2 - 225 25 12.5
DT-2R190, DTR-190, DTR-190P
FT/ROR None - 190 50 25
DT-3P, DTZ-3, ID-60T RC None - 135, 160, 200, 220 50 25
DT-5F175 FT None - 155 30 15
DTF-136, DTF-136P FT None - 136 15 7.5
DTF-190, DTF-190P FT None - 190 15 7.5
DTR-136, DTR-136P FT/ROR None - 136 50 25
FDT421, HI921 FT/ROR D2, D7 - 135-174 50 25
HFPT-11 FT/ROR None - 135 50 25
HI121 FT D2, D7 - 135 50 -
135 - -
ILT-1 FT None - 135 50 25
D2 - For connection to Listed control units with which compatibility was determined by test or a review of circuit parameters. Interconnection and
UQGS.S726 - Heat-automatic Fire Detectors http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpag...
1 de 2 30/06/2011 16:18
compatible models indicated on installation wiring diagram for detector (base) and/or control unit.
D7 - The detector head is used with a separable base where the base determines function and connection.
FT - Fixed temperature
RC - Rate compensation
FT/ROR - Fixed temperature/rate of rise combination
Trademark and/or Tradename: "SIEMENS"
Last Updated on 2011-06-28
Questions? Print this page Notice of Disclaimer Page Top
Copyright 2011 Underwriters Laboratories Inc.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data
(or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright
2011 Underwriters Laboratories Inc."
UQGS.S726 - Heat-automatic Fire Detectors http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpag...