SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

ADVANCE AND EVER ADVANCING


TECHNICAL & SERVICE MANUAL
<indoor unit> Service ref.
Models
PEHD-1.6EKA2.UK
PEHD-1.6EKHA2.UK
PEHD-2EKA2.UK
PEHD-2EKHA2.UK
PEHD-2.5EKA2.UK
PEHD-2.5EKHA2.UK
The Slim Line.
From Mitsubishi Electric
TM
1. FEATURES 1
2. PART NAMES AND FUNCTIONS 2
3. SPECIFICATIONS 5
4. DATA 8
5. REFRIGERANT SYSTEM DIAGRAM 13
6. OUTLINES AND DIMENSIONS 14
7. WIRING DIAGRAM 15
8. DISASSEMBLY INSTRUCTIONS 16
9. PARTS LIST 19
10. OPTIONAL PARTS 23
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
This manual does not cover the
following outdoor units. When
servicing them, please refer to
the service manual No.OC150A
and this manual as a set.
PUH-1.6VKA3.UK
PUH-2VKA2.UK
PUH-2.5VKA2.UK

2000
1
1. NEXT GENERATION AIR-CONDITIONING VENTILATION INTERLOCKING SYSTEM "Mr.SLIM" +
"LOSSNAY"
Proper ventilation is important to improve the quality of indoor environments. It eliminates unclean air, which is not only
unpleasant, but unhealthy. This "Mr.SLIM" + "LOSSNAY" ventilation interlocking system achieves high air quality with mini-
mum energy consumption.
LOSSNAY's unique total heat exchanger reduces heating and cooling expenses by about 25 percent annually(in compari-
son with our existing models). In addition, its mechanism of simultaneous forced air supply and exhaust enables it to deliv-
er high quality air.
Together, "Mr.SLIM" + "LOSSNAY" system makes next-generation air conditioning possible. This system is both people
and environment friendly.
2. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILING
The totally hidden indoor unit that lies above the ceiling surface enables you to utilize full floor space while allowing for
flexible interior design. This new feature is recommended for stores and offices where the user's own imagination is
allowed to be incorporated.
3. MOST SUITABLE FOR SIMULTANEOUS TWO ROOM AIR CONDITIONING
Using air ducts for cooling/heating airflow that matches the structure and purpose of the room enables you to provide two
air outlets for simultaneous cooling/heating of two rooms.
4. HIGH EXTERNAL STATIC PRESSURE
The exceptional external static pressure of 70Pa allows long ducts to be used more extensively to achieve convenient
location of indoor units.(The factory setting is 30Pa.)
5. DRAIN WATER LIFT-UP MECHANISM(OPTION KIT)
This allows more versatility when selecting drain piping layouts.
FEATURES 1
lndoor unit
Remote controller
Models Cooling capacity / Heating capacity (240V)
Btu/h(with heater) W(with heater)
PEHD-1.6EK(H)A2
PEHD-2EK(H)A2
PEHD-2.5EK(H)A2
15,000/15,700(19,100)
19,100/21,500(24,900)
23,200/24,600(29,700)
4,400/4,600(5,600)
5,600/6,300(7,300)
6,800/7,200(8,700)
air outlet air outlet
Air outlet duct Air intake duct
air intake
2
6. ADVANCED MICROPROCESSOR
(1) Easy to use microprocessor
1) Ultra-thin remote controller
The streamlined, square controller is designed to blend well with any interior. Also, the sophisticated micro-proces-
sor allows you to easily carry out a wide range of operations.
2) Attractive liquid crystal display (LCD)
The unit's operation mode, set temperature, room temperature, timer setting, and fan speed are displayed on the
remote controller's easy-to-read Liquid Crystal Display (LCD)
3) Convenient 24-hour ON-OFF timer
The timer switches Mr.SLIM on and off automatically at the time you set. Once the timer is set, the remaining time
is shown on the LCD.
4) Self-diagnostic feature indicates faults instantly
If a problem occurs, the unit will stop operating and the set temperature indicator will change to a self-diagnostic
indicator, which shows the location of the trouble.
If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The location of the
most recent problem that was stored in the memory is displayed on the LCD. This is extremely useful for mainte-
nance purposes.
5) Useful memory feature for storing instructions
The previous set value is memorized so that constant temperature control can be achieved. For example, if a power
failure occurs, the temperature will not have to be re adjusted afterwards.
(2) Non-polar two-wire remote controller cable
The slim, non-polar, two-wire remote controller cable makes installation simple and trouble free. Also, the remote con-
troller wire can be extended up to 500m.
(3) Automatic cooling/heating changeover operation
An automatic cooling and heating changeover operation system allows you to easily control comfortable year-round air
conditioning.
Once the desired temperature is set, unit operation switches automatically between cooling and heating, in accordance
with the room temperature. In addition, the use of an outdoor unit fan speed controller allows cooling even when out-
door temperatures are as low as - 5C.
7. INNOVATIVE MICROPROCESSOR CONTROL SYSTEM
The most significant feature of PEHD-EK series is the advanced microprocessor control. The development of this system is
due to the recent world-wide trend in the air conditioning of larger buildings. They are moving away from centralized duct
systems to using individual split type units instead. There are a number of reasons for this change. First of all, the duct's
costly and troublesome installation is eliminated. Second, the overall air conditioning balance is excellent in split type units.
Lastly, the operation costs are low due to the flexible control of each unit. This system was developed exclusively by
Mitsubishi Electric because of high demand. The microprocessor control makes individual control, group control, control
using two remote controllers, and remote on/off and individual control possible without troublesome equipment modifica-
tions.
PART NAMES AND FUNCTIONS 2
G Indoor Unit
Air intake
(sucks the air from inside the room into the unit)
Air outlet
or
3
This switches between continu-
ous operation and the timer
operation.
Press this button to switch the
cool, electronic dry (dehumidify)
automatic and heat modes.
This sets the room tempera-
ture. The temperature setting
can be performed in 1C
units.
Setting range :
Cool 19C to 30C
Heat 17C to 28C
The model name of the
remote controller is indicated.
This switches the horizontal
fan motion ON and OFF.
(This button does not operate
in this model.)
Only press this button to per-
form an inspection check or
test operation. Do not use it
for normal operation.
This resets the filter service
indication display.
(This button dose not operate
in this model.)
This adjusts the vertical angle
of the ventilation.
(This button dose not operate
in this model.)
This switches between the
operation and stop modes
each time it is pressed. The
lamp on this button lights dur-
ing operation.
This sets / switches the current
time, start time and stop time.
This sets the ventilation fan
speed.
button
button
TEMP button
button CHECK-TEST RUN button
FILTER button
button
ON/OFF button
button button
G Remote controller
G Operation buttons
G Once the operation of the unit is set, subsequent operations
can be performed only by pressing the ON/OFF button
repeatedly.
4
This indicates when the unit
is controlled by optinal fea-
tures such as central control
type remote controller.
The current time, start time
and stop time can be dis-
played in tencecond intervals
by pressing the time switch
button. The start time or stop
time is always displayed during
the timer operation.
The selected fan speed is dis-
played.
This indicates when the con-
tinuous operation and time
operation modes are set.
It also displays the time for
the timer operation at the
same time as when it is set.
This indicates the operation
mode.
This indicates when the stand
by mode is set from the time
the sleep operation starts
until the heating air discharges.
This indicates when the de-
frost operation is performed.
This indicates when a malfun-
ction has occurred in the unit
which should be checked.
This displays the selected set-
ting temperature.
The temperature of the suc-
tion air is displayed during
operation. The display range is
8C to 39C. The display flashes
8C when the actual tempera-
ture is less then 8C and
flashes 39C when the actual
temperature is greater then
39C.
This lamp lights during opera-
tion, goes off when the unit
stops and flashes when a mal-
function occurs.
This display lights in the
check mode or when a test
operation is perfomed.
This lamp lights when electric-
ity is supplied to the unit.
Caution
Only the display lights whe the unit is stopped and power is supplied to the unit.
When power is turned ON for the first time, the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON - OFF button,
button and TEMP button do not operate.
"NOT AVAILABLE" is displayed when the button and button are pressed. This indicates that this room
unit is not equipped with the fan direction adjustment function and the louver function.
CENTRALLY
CONTROLLED display
display
OPERATION MODE display
STANDBY display
DEFROST display
CHECK display
Display
display
display
display
Operation lamp
CHECK MODE
TEST RUN
C display
C display
CLOCK
ON OFF
G Display
3 SPECIFICATION
5
Item
Function
Capacity
Total input
I
N
D
O
O
R
U
N
I
T
Model name
Power supply
Starting current
Running current
Input
External finish
Heat exchanger
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Booster heater
Operation control & Thermostat
Noise level(Low-High)
Cond.drain conn.O.D.
Dimensions
Weight
dB(A)
mm,(in)
mm,(in)
mm,(in)
mm,(in)
W
D
H
kg,(lbs)
Model name
Power supply
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output kW
Protection devices
Stater type
Heat exchanger
Fan(drive) x No.
Fan motor output kW
Airflow CMM,(CFM)
Defrost method
Noise level dB(A)
Dimensions
W
D
H
mm,(in)
mm,(in)
mm,(in)
kg,(lbs) Weight
Refrigerant
kg,(lbs) Charge
Pipe size O.D.
Connection method
Between the indoor
& outdoor unit
Liquid mm,(in)
Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
R
E
F
R
I
G
E
R
A
N
T
P
I
P
I
N
G
O
U
T
D
O
O
R
U
N
I
T
kW
A
A
Btu/h
W
kW
kW
A
A
kW
kW
CMM,(CFM)
Pa(mmAq)
Model
4
4
6 6
6
6
6
6
6
6
6
6
6
5
1
2
3
1. External static pressure at 70Pa
2. Ex-works at 30Pa
3. External static pressure at 30Pa
4. Rating conditions <JIS B 8615, 8616>
(INDOOR) Cooling: 27CDB, 19CWB Heating: 20CDB
(OUTDOOR) Cooling: 35CDB Heating: 7CDB, 6CWB
5. Noise level: Sound pressure level
PEHD-1.6EK(H)A2.UK
Cooling
15,000
4,400
1.57
PEHD-1.6EK(H)A2.UK
~/N,50Hz, 220-240V
0.13
0.55
0.92
0.13 (1.13)
0.55 (4.71)
0.92 (5.08)
~/N, 220-240V ,50Hz
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.043
11-14 (388-494)
30(3)/70(7) at Hi-notch
1.0
Remote control & Built-in
34-38
32 (1-1/4)
935 (36-13/16)
700 (27-9/16)
295 (11-5/8)
33 (73) [35 (77)]
PUH-1.6VKA3
1.44
6.74
33
1.41
6.60
33
Munsell 5Y7/1
Capillary tube
Hermetic
RH247VFCT
1.2
Line start
Plate fin coil
Propeller (direct)x1
0.065
45 (1590)
Reverse cycle
49
870 (34-1/4)
295+24 (11-5/8 add 1)
650 (25-5/8)
53 (117)
R-22
2.2 (4.8)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max.40m
Max.40m
Heating
15,700 (19,100)
4,600 (5,600)
1.54 (2.54)
Inner thermostat,HP switch
6
Item
Function
Capacity
Total input
I
N
D
O
O
R
U
N
I
T
Model name
Power supply
Starting current
Running current
Input
External finish
Heat exchanger
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Booster heater
Operation control & Thermostat
Noise level(Low-High)
Cond.drain conn.O.D.
Dimensions
Weight
dB(A)
mm,(in)
mm,(in)
mm,(in)
mm,(in)
W
D
H
kg,(lbs)
Model name
Power supply
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output kW
Protection devices
Stater type
Heat exchanger
Fan(drive) x No.
Fan motor output kW
Airflow CMM,(CFM)
Defrost method
Noise level dB(A)
Dimensions
W
D
H
mm,(in)
mm,(in)
mm,(in)
kg,(lbs) Weight
Refrigerant
kg,(lbs) Charge
Pipe size O.D.
Connection method
Between the indoor
& outdoor unit
Liquid mm,(in)
Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
R
E
F
R
I
G
E
R
A
N
T
P
I
P
I
N
G
O
U
T
D
O
O
R
U
N
I
T
kW
A
A
Btu/h
W
kW
kW
A
A
kW
kW
CMM,(CFM)
Pa(mmAq)
Model
4
4
6 6
6
6
6
6
6
6
6
6
6
5
1
2
3
1. External static pressure at 70Pa
2. Ex-works at 30Pa
3. External static pressure at 30Pa
4. Rating conditions <JIS B 8615, 8616>
(INDOOR) Cooling: 27CDB, 19CWB Heating: 20CDB
(OUTDOOR) Cooling: 35CDB Heating: 7CDB, 6CWB
5. Noise level: Sound pressure level
PEHD-2EK(H)A2.UK
Cooling
19,100
5,600
2.35
PEHD-2EK(H)A2.UK
~/N, 50Hz, 220-240V
0.15
0.63
1.1
0.15 (1.15)
0.63 (4.79)
1.1 (5.26)
~/N, 220-240V, 50Hz
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.076
13.5-17 (476-600)
30(3) / 70(7) at Hi-notch
1.0
Remote control & Built-in
36-40
32 (1-1/4)
935 (36-13/16)
700 (27-9/16)
295 (11-5/8)
33 (73) [35(77)]
PUH-2VKA2
2.20
9.86
45
2.22
9.95
45
Munsell 5Y7/1
Capillary tube
Hermetic
NH38VMDT
1.7
Line start
Plate fin coil
Propeller (direct) x1
0.065
45 (1590)
Reverse cycle
49
870 (34-1/4)
295+24 (11-5/8 and 1)
650 (25-5/8)
64 (141)
R-22
2.2 (4.8)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max.40m
Max.40m
Heating
21,500 (24,900)
6,300 (7,300)
2.37 (3.37)
Inner thermostat, HP switch
7
Item
Function
Capacity
Total input
I
N
D
O
O
R
U
N
I
T
Model name
Power supply
Starting current
Running current
Input
External finish
Heat exchanger
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Booster heater
Operation control & Thermostat
Noise level(Low-High)
Cond.drain conn.O.D.
Dimensions
Weight
dB(A)
mm,(in)
mm,(in)
mm,(in)
mm,(in)
W
D
H
kg,(lbs)
Model name
Power supply
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output kW
Protection devices
Stater type
Heat exchanger
Fan(drive) x No.
Fan motor output kW
Airflow CMM,(CFM)
Defrost method
Noise level dB(A)
Dimensions
W
D
H
mm,(in)
mm,(in)
mm,(in)
kg,(lbs) Weight
Refrigerant
kg,(lbs) Charge
Pipe size O.D.
Connection method
Between the indoor
& outdoor unit
Liquid mm,(in)
Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
R
E
F
R
I
G
E
R
A
N
T
P
I
P
I
N
G
O
U
T
D
O
O
R
U
N
I
T
kW
A
A
Btu/h
W
kW
kW
A
A
kW
kW
CMM,(CFM)
Pa(mmAq)
Model
4
4
5
1
2
3
1. External static pressure at 70Pa
2. Ex-works at 30Pa
3. External static pressure at 30Pa
4. Rating conditions < JIS B 8615, 8616>
(INDOOR) Cooling: 27CDB, 19CWB Heating: 20CDB
(OUTDOOR) Cooling: 35CDB Heating: 7CDB, 6CWB
5. Noise level: Sound pressure level
PEHD-2.5EK(H)A2.UK
Cooling
23,200
6,800
2.63
Heating
PEHD-2.5EK(H)A2.UK
~/N, 50Hz, 220-240V
0.17
0.72
1.6
0.17 (1.67)
0.72 (6.96)
1.6 (7.84)
~/N, 220-240V, 50Hz
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.116
17-21 (600-740)
30(3) /70(7) at Hi-notch
1.5
Remote control & Built-in
37-41
32 (1-1/4)
1,175 (46-1/8)
700 (27-9/16)
295 (11-5/8)
42(93) [44(97)]
PUH-2.5VKA2
2.46
10.68
52
2.23
9.78
52
Munsell 5Y7/1
Capillary tube
Hermetic
NH41VMDT
2
Line start
Plate fin coil
Propeller(direct)x1
0.085
50
Reverse cycle
52
870 (34-1/4)
295+24 (11-5/8 add 1)
650 (25-5/8)
68 (150)
R-22
2.8 (6.2)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max.50m
Max.50m
24,600 (29,700)
7,200 (8,700)
2.40 (3.90)
Internal thermostat, HP switch
6
6
6
6
6
6
6
6
6
6
6
4 DATA
8
Service Ref.
Indoor
intake air
WBC
20 25 30 35 40 45
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
1. PERFORMANCE DATA
1) COOLING CAPACITY
Note C A: Capacity(W)
P.C.: Power consumption(kW)
Service Ref.
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Cooling capacity correction factors
Service Ref. -10 -5 0 5 10 15
2) HEATING CAPACITY
Indoor
intake air
WBC
Outdoor intake air DBC
Outdoor intake air DBC
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
Note C A : Capacity(W)
P.C.: Power consumption(kW)
Service Ref.
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Heating capacity correction factors
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
4,479 1.35
1.38
1.40
1.43
2.16
2.21
2.24
2.28
2.51
2.56
2.60
2.65
4,356
4,642
4,937
5,249
5,544
5,909
6,283
6,681
6,732
7,175
7,630
8,112
1.41
1.44
1.46
1.49
2.26
2.30
2.34
2.39
2.62
2.67
2.71
2.77
4,180
4,453
4,743
5,047
5,320
5,667
6,037
6,423
6,460
6,882
7,330
7,800
1.51
1.55
1.58
1.61
2.41
2.47
2.52
2.58
2.80
2.87
2.93
2.99
3,991
4,259
4,541
4,840
5,079
5,421
5,779
6,160
6,168
6,582
7,018
7,480
1.61
1.65
1.69
1.73
2.58
2.64
2.70
2.77
2.99
3.07
3.14
3.21
3,793
4,057
4,334
4,629
4,827
5,163
5,516
5,891
5,862
6,270
6,698
7,154
1.71
1.76
1.80
1.85
2.74
2.81
2.88
2.96
3.18
3.26
3.35
3.44
3,590
3,850
4,123
4,409
4,570
4,901
5,247
5,611
5,549
5,951
6,372
6,814
1.36
1.46
1.57
1.67
2.18
2.34
2.50
2.68
2.53
2.71
2.91
3.11
16
4,765 18
5,056 20
5,350 22
5,701 16
6,065 18
6,434 20
6,810 22
6,922 16
7,364 18
7,813 20
8,269 22
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
1.00 0.993
0.992
0.989
0.984
0.983
0.980
0.978
0.978
0.970
0.969
0.966
0.960
0.961
0.959
0.950
0.956
0.950
0.940
0.948
0.945
0.930
-
-
0.920
-
-
0.910
1.00
1.00
3,192
3,054
2,940
4,372
4,183
4,026
4,996
4,780
4,601
1.14
2.22
1.30
1.80
1.93
2.06
1.87
2.01
2.14
3,643
3,500
3,358
4,990
4,794
4,599
5,703
5,479
5,256
1.25
1.34
1.43
1.97
2.13
2.27
2.05
2.21
2.36
4,136
3,979
3,822
5,664
5,450
5,235
6,473
6,229
5,983
1.37
1.47
1.58
2.17
2.33
2.50
2.25
2.42
2.59
4,669
4,494
4,328
6,395
6,155
5,928
7,309
7,035
6,775
1.49
1.61
1.72
2.37
2.55
2.73
2.46
2.65
2.84
5,240
5,042
4,876
7,176
6,905
6,678
8,201
7,892
7,632
1.63
1.76
1.88
2.58
2.78
2.98
2.68
2.89
3.09
5,846
5,626
5,460
8,007
7,705
7,478
9,151
8,805
8,547
2.11
2.03
1.97
3.34
3.21
3.12
3.47
3.34
3.24
15
20
25
15
20
25
15
20
25
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 - -
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 - -
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
9
2. PERFORMANCE CURVE
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
Cooling
1.4
1.2
1
0.8
0.6
1.4
1.2
1
0.8
0.6

0.4
1.4
1.2
1
0.8
0.6
1.4
1.2
1
0.8
0.6

0.4
22
20
18
16
22
20
18
16
INDOOR WB (C)
INDOOR WB (C)
INDOOR DB (C)
INDOOR DB (C)
C
A
P
A
C
I
T
Y
(
R
A
T
I
O
)
C
A
P
A
C
I
T
Y
(
R
A
T
I
O
)
T
O
T
A
L

I
N
P
U
T
(
R
A
T
I
O
)
T
O
T
A
L

I
N
P
U
T
(
R
A
T
I
O
)
OUTDOOR DB (C) OUTDOOR WB (C)
-12 -10 -5 0 5 10 15
-5 5 15 25 35 46
Heating
15
20
25
25
20
15
Fan Performance <30Pa>
E
x
t
e
r
n
a
l

s
t
a
t
i
c

p
r
e
s
s
u
r
e

(
P
a
)
(
1
P
a





0
.
1
m
m
A
g
)
Air Flow (CMM)
8 6 10 12 14 16
6 8 10 12 14 16
20
40
60
80
100
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
C
o
r
r
e
c
t
i
o
n

f
a
c
t
o
r
Fan Performance <70Pa>
E
x
t
e
r
n
a
l

s
t
a
t
i
c

p
r
e
s
s
u
r
e

(
P
a
)
(
1
P
a





0
.
1
m
m
A
g
)
Air Flow (CMM)
10 12 6 8 14 16 18
6 8 10 12 14 16
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
C
o
r
r
e
c
t
i
o
n

f
a
c
t
o
r
10
3. FAN PERFORMANCE AND CORRECTED AIR FLOW
PEHD-1.6EK(H)A2.UK
Fan Performance <30Pa>
E
x
t
e
r
n
a
l

s
t
a
t
i
c

p
r
e
s
s
u
r
e

(
P
a
)
(
1
P
a





0
.
1
m
m
A
g
)
Air Flow (CMM)
6 8 10 12 14 16 18 20
8 10 12 14 16 18 20 22
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
C
o
r
r
e
c
t
i
o
n

f
a
c
t
o
r
Fan Performance <70Pa>
E
x
t
e
r
n
a
l

s
t
a
t
i
c

p
r
e
s
s
u
r
e

(
P
a
)
(
1
P
a





0
.
1
m
m
A
g
)
Air Flow (CMM)
8 10 12 14 16 18 20 22
8 10 12 14 16 18 20 22
20
40
60
80
100
120
140
160
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
C
o
r
r
e
c
t
i
o
n

f
a
c
t
o
r
PEHD-2EK(H)A2.UK
11
PEHD-2.5EK(H)A2.UK
Fan Performance <30Pa>
E
x
t
e
r
n
a
l

s
t
a
t
i
c

p
r
e
s
s
u
r
e

(
P
a
)
(
1
P
a





0
.
1
m
m
A
g
)
Air Flow (CMM)
8 10 12 14 16 18 20 22 24
12 14 16 18 20 22 24 26
20
40
60
80
100
120
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
C
o
r
r
e
c
t
i
o
n

f
a
c
t
o
r
Fan Performance <70Pa>
E
x
t
e
r
n
a
l

s
t
a
t
i
c

p
r
e
s
s
u
r
e

(
P
a
)
(
1
P
a





0
.
1
m
m
A
g
)
Air Flow (CMM)
10 12 14 16 18 20 22 24 26
12 14 16 18 20 22 24 26
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
C
o
r
r
e
c
t
i
o
n

f
a
c
t
o
r
12
Models
Indoor
Outdoor
Mode
Capacity(W)
Total input(kW)
Input(kW)
Current(A)
Starting current(A)
Input(kW)
Current(A)
Starting current(A)
I
n
d
o
o
r
O
u
t
d
o
o
r
Indoor 220V 50Hz 1phase
Outdoor 220V 50Hz 1phase
Models
Indoor
Outdoor
Mode
Capacity(W)
Total input(kW)
Input(kW)
Current(A)
Starting current(A)
Input(kW)
Current(A)
Starting current(A)
I
n
d
o
o
r
O
u
t
d
o
o
r
Indoor 230V 50Hz 1phase
Outdoor 230V 50Hz 1phase
Models
Indoor
Outdoor
Mode
Capacity(W)
Total input(kW)
Input(kW)
Current(A)
Starting current(A)
Input(kW)
Current(A)
Starting current(A)
I
n
d
o
o
r
O
u
t
d
o
o
r
Indoor240V 50Hz 1phase
Outdoor 240V 50Hz 1phase
PEHD-2EK(H)A
2
.UK PEHD-1.6EK(H)A
2
.UK PEHD-2.5EK(H)A
2
.UK
PUH-2VKA PUH-2.5VKA
PEHD-2.5EK(H)A
2
.UK
PUH-2.5VKA
PUH-1.6VKA
Cool
6,600
2.56
0.15
0.69
1.53
2.41
11.18
48
Heat
7,100
(8,350)
2.31
(3.56)
0.15
(1.40)
0.69
(6.36)
1.53
(7.16)
2.16
10.02
48
Cool
6,700
2.60
0.16
0.70
1.56
2.44
10.94
50
Heat
7,150
(8,550)
2.36
(3.76)
0.16
(1.56)
0.70
(6.78)
1.56
(7.64)
2.20
9.86
50
Cool
4,300
1.48
0.12
0.55
0.92
1.36
6.79
30
Heat
4,500
(5,350)
1.44
(2.29)
0.12
(0.97)
0.55
(4.41)
0.92
(4.76)
1.32
6.59
30
Cool
5,500
2.25
0.13
0.60
1.05
2.12
9.83
41
Heat
6,100
(6,950)
2.27
(3.12)
0.13
(0.98)
0.60
(4.45)
1.05
(4.89)
2.14
9.93
41
PEHD-2EK(H)A
2
.UK PEHD-1.6EK(H)A
2
.UK
PUH-2VKA PUH-1.6VKA
Cool
4,350
1.53
0.13
0.55
0.92
1.40
6.76
32
Heat
4,550
(5,450)
1.49
(2.39)
0.13
(1.03)
0.55
(4.48)
0.92
(4.83)
1.36
6.57
32
Cool
5,550
2.30
0.14
0.61
1.07
2.16
9.78
43
Heat
6,200
(7,100)
2.32
(3.22)
0.14
(1.04)
0.61
(4.52)
1.07
(4.96)
2.18
9.87
43
PEHD-2.5EK(H)A
2
.UK
PUH-2.5VKA
Cool
6,800
2.63
0.17
0.72
1.60
2.46
10.68
52
Heat
7,200
(8,700)
2.40
(3.90)
0.17
(1.67)
0.72
(6.96)
1.60
(7.84)
2.23
9.78
52
PEHD-2EK(H)A
2
.UK PEHD-1.6EK(H)A
2
.UK
PUH-2VKA PUH-1.6VKA
Cool
4,400
1.57
0.13
0.55
0.92
1.44
6.74
33
Heat
4,600
(5,600)
1.54
(2.54)
0.13
(1.13)
0.55
(4.71)
0.92
(5.08)
1.41
6.60
33
Cool
5,600
2.35
0.15
0.63
1.10
2.20
9.86
45
Heat
6,300
(7,300)
2.37
(3.37)
0.15
(1.15)
0.63
(4.79)
1.10
(5.26)
2.22
9.95
45
4. ELECTRICAL DATA
Indoor unit
Indoor
heat
exchanger
Strainer
Restrictor
valve
Thermistor
TH2
Distributor
with strainer
Capillary
tube
PEHD-1.6(OD3.2xID1.6xL630)
PEHD-2(OD3.2xID1.8xL300)
PEHD-2.5(OD3.2xID1.8xL430)
Refrigerant flow in cooling R.V.coil
Refrigerant flow in heating Heating : ON
Cooling : OFF
Unit : mm
13
5. STANDARD OPERATION DATA
Models
Mode
T
o
t
a
l
E
l
e
c
t
r
i
c
a
l
c
i
r
c
u
i
t
R
e
f
r
i
g
e
r
a
n
t
c
i
r
c
u
i
t
I
n
d
o
o
r
s
i
d
e
O
u
t
d
o
o
r
s
i
d
e
SHF
BF
Capacity
Input
Indoor unit model
Phase . Hz
Volts
Amperes
Outdoor unit-model
Phase,Hz
Volts
Amperes
W
kW
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref.Pipe length
Intake air temperature
Intake air temperature
Discharge air temperature
MPa
MPa
C
C
C
m
DBC
WBC
DBC
DBC
WBC
Cooling Heating
6,800 7,200
2.63 2.40
PEHD-2.5EK(H)A
1, 50
240
0.72 0.72
PUH-2.5VKA
1, 50
240
PEHD-2.5EK(H)A2.UK
Cooling Heating
5,600 6,300
2.35 2.37
PEHD-2EK(H)A
1, 50
240
0.63 0.63
PUH-2VKA
1, 50
240
PEHD-2EK(H)A2.UK
Cooling Heating
4,400 4,600
1.57 1.54
PEHD-1.6EK(H)A
1, 50
240
0.55 0.55
PUH-1.6VKA
1, 50
240
6.74
1.76
0.54
76.6
47.1
8
5
27.0
19.0
15.4
35.0
24.0
0.74
0.21
6.6
1.51
0.41
66.8
-
0.2
5
20.0
15.0
35.1
7.0
6.0
-
-
9.86
1.93
0.47
87.3
51.2
4.8
5
27.0
19.0
14.5
35.0
24.0
0.76
0.19
9.95
2.15
0.37
101.4
-
-2.1
5
20.0
15.0
40.4
7.0
6.0
-
-
10.68
2.05
0.52
85
53.7
7.4
5
27.0
19.0
14.7
35.0
24.0
0.76
0.19
9.78
1.65
0.37
73.8
-
-2.4
5
20.0
15.0
39.1
7.0
6.0
-
-
PEHD-1.6EK(H)A2.UK
REFRIGERANT SYSTEM DIAGRAM 5
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
1
0
1
0
3
0
15 256
176 40
A
81 C B 81
29
227 61
81
A
E 13 13
163
2
8
2
8
5
4
5
8
0
2
7
7
2
1
30 640 30
2
4
3
5
10
1
7
9
1
0
9
10
3
.
5
3
.
5
2
5
6
2
8
8
4
0
1
7
6
Set
10-3 (1.6, 2HP)
12-3 (2.5HP)
10-3 (1.6, 2HP)
12-3 (2.5HP)
450
4
5
0
A
C B 81
1
0
C
30 D
In case of bottom inlet
In case of rear inlet
10-3 (1.6, 2HP)
12-3 (2.5HP)
(1422)
Lifting bolt hole
8
8
Air inlet
3
5
5
5
6
1
0
81 B
3
6
5
~
4
6
5
1
5
9
1
8
44 75
7
6
7
5
6
5
4
3
2
1 Refrigerant piping flare connection (liquid 9.52 copper tube):HP
Refrigerant piping flare connection (gas 15.88 copper tube):LP
Drain R1(External thread)
Electrical parts box
Electric HeaterOnly PEHD-EKHA Type
Drain Pump (Option)
Drain Pipe (Option)Use VP25(O.D.32 PVC TUBE)
Filter
Keep duct-work length 850mm or more.
Be sure to apply the air filter (field supply) near the air inlet grille.
Service space:500 or more
1
9
7
81
50~150
55
Access door
Air outlet Air inlet
4
3
1 2
PE(H)D-1.6,2
PE(H)D-2.5
Model
1012
772 305
280 290
830
1070
804
1044
-
A B C D E
6 OUTLINES & DIMENSIONS
14
1. INDOOR UNIT
PEHD-1.6EK(H)A2.UK
PEHD-2EK(H)A2.UK
PEHD-2.5EK(H)A2.UK
2. REMOTE CONTROLLER
Unit:mm (inch)
Rear side wiring arangement opening
46
8
3
.
5
130
18
1
2
0
7 WIRING DIAGRAM
15
6 5
5 4 6 3 1 2
2 1 3
4 3 1 2 5 6 7 8 9 0
9 10 4 3 1 2 8 7 5 6 4 3 1 2 4 3 1 2 4 3 1 2 4 3 2 1
2
1
3
2
1
4 3 2 1 3 2 1
#
#
*
*
*
*
*
*Only models PEHD-1.6,2,2.5EK(H)A
#Option parts
SYMBOL
TB4
TB5, TB6
TH1
TH2
X1(I.B)
X4(I.B)
X5(I.B)
X6(I.B)
ZNR
26H
88H1
88H2
CN50
DP
DS
SYMBOL
SW1(R.B)
SW3(R.B)
SW4(R.B)
SW5(R.B)
SW6(R.B)
SW7(R.B)
SW8(R.B)
SW9(R.B)
SW10(R.B)
SW14(R.B)
SW15(R.B)
SW17(R.B)
T
TB2
MF
SYMBOL EXPLANATION
SYMBOL
C
CN1<R.B>
CN2<R.B>
CN2L<R.B>
CN51<R.B>
F<I.B>
FS1,FS2
H
I.B
LCD
R.B
SW1(I.B)
SW2(I.B)
SW3(I.B)
SW5(I.B)
SW6(I.B)
fig:*1
220V
230V
220
230
240
NOTES
1.Since the indoor transfomer(T) is connected with 240V power. if 220,230V
power is used. Change the wiring connection showihg fig: *1
When power supply is
B
L
K
O
R
N
PE
G
R
Y
G
R
Y
B
L
U
B
L
K
B
L
K
GRN/YLW
PRP
BLU
RED
ORN
BRN
PRP
YLW
R
E
D
R
E
D
B
L
U
B
L
U
YLW YLW
YLW
G
R
N
/
Y
L
W
B
L
U
B
L
K
P
N
K
R
E
D
Y
L
W
W
H
T
W
H
T
O
R
N
R
E
D
W
H
T
Y
L
W
A
C
1
0
.
8
V
A
C
1
4
.
5
V
B
R
N
R
E
D
B
R
N
R
E
D
TRANSMISSION WIRES
DC 12V
TO OUTDOOR UNIT
CONNECTING WIRES
DC 12V(polar)
CN24
HEATER
CN51
CENTRALLY
CONTROL
B
R
N
B
R
N
G
R
N
/
Y
L
W
2 1
CN50
DRAIN
2
4 3 2 1
4 1 3 5
DS
LCD
CN2
OFF
ON
CN1 SW17
SW15 SW14
SW5
SW10
SW9
SW7
SW4
SW8
SW6
SW3
CN2L
LOSSNAY
ON
OFF
SW1
R.B
SW3 SW5
I.B
CN21
PIPE
CN20
INTAKE
1 1 2 2
TH2 TH1
SW6 SW2 SW1
MODELS:PEHD-1.6,2,2.5EK(H)A2 WIRING DIAGRAM
2. Since the outdoor side electric wiring may change be sure
to check the outdoor unit electric wiring for servicing.
3. Indoor and outdoor connecting wires are made with palarities
make wiring matching terminal.
4. Symbols used in circuit diagram above are, :Terminal block,
:connector, :PC board insertion tab.
5. Emergency operation
If a trouble occurs with either the remote controller or
the indoor microcomputer and no other trouble exists,emer-
gency operation for cooling or heating can be performed by
changing the setting of dip switch(SW3<I.B>)on the indoor
controller board (emergency dry operation is not possible).

[Check items]
(1) Make sure that no other trouble exists with the outdoor unit.
Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists with the outdoor unit, the trouble
location will be displayed on the remote controller and
the trouble position will be shown on the outdoor contro-
ller board LED.See electric circuit diagram of the outdoor
unit for details.)
(2) Make sure that there is no trouble with the indoor fan.
Emergency operation will be a continuous run with the power
ON/OFF(ON/OFFwith the remote controller is not possible).
[Emergency operation procedure]
(1) Set the dip switch(SW3<I.B>)on the indoor controller board
to 1 2 3 on and 4 off for cooling, and 2 3 4 on and
1 off for heating.
(2) Turn on the outdoor unit side circuit breaker.
(3) During emergency operation indoor fan runs at High speed.
(4) Thermostat will not function. Cold air blows out for defro-
sting during heating thus do not operate de frosting for
a long time.
(5) Emergency cooling should be limited to 10 hours maximum(the
indoor unit heat exchanger may freeze).
X3 X2 X1 X6X5X4
R S
M0 M1 M2 M3
ZNR
F
T
CN4T
TRANS
External static
pressure 70Pa pressure 30Pa
External static
RED
WHITE
4 1 6 3 5 2
DP
2
BREAKER
TO DUCT
TB5
FS1
1
2
TB6
TB4
CN30
OUTDOOR
CN40
REMOCON
POWER
CN22
TO REMOCON
5
5
3
3
4
3
7
7
8
8
TB2
N
L POWER SUPPLY
~ (1phase)
220~240V 50Hz
88H1
88H2 FS2
H
26H
88H2
88H1
C
5 3 6 1 4
MF
NAME
Capacitor(fan motor)
Connector(program timer)
Connector(remote switch)
Connector(lossnay)
Connector(centrally control)
Fuse<6.3A>
Thermal fuse(10A)
Electric heater
Indoor controller board
Liquid crystal display
Remote controller board
Switch(mode selector)
Switch(address selector)
Switch(emergency operation)
Switch(model selector)
Switch(model selector)
NAME
Switch(ON/OFF)
Switch(cooling/drying operation mode)
Switch(automatic operation mode)
Switch(heatihg operation mode)
Switch(lowers set temperature)
Switch(raises set temperature)
Switch(timer time)
Switch(timer.continuous and ON/OFF)
Switch(fan speed high/low selector)
Switch(test run)
Switch(inspection)
Switch(address selector)
Transformer
Terminal block(power)
Fan motor(with inner thermostat)
NAME
Terminal block (indoor/outdoor connecting line)
Terminal block (remote controller transmission line)
Thermistor (room temperature sensor 0C/15k.25C/5.4k)
Thermistor (pipe temperature sensor 0C/15k.25C/5.4k)
Auxiliary relay (drain pump)
Auxiliary relay (fan motor)
Auxiliary relay (fan motor)
Auxiliary relay (fan motor)
Varistor
Thermal switch(over heat prevention)
Contactor(electric heater)
Contactor(electric heater)
Drain sensor connector
Drain pump
Drain sensor
YELLOW
ORANGE
RED
8 DISASSEMBLY INSTRUCTIONS
16
Figure1.
Disconnect the fan motor connecter
(and the booster heater connector)
Drain pan
catches (Hidden)
Drain pan
catches (Hidden)
Filter
Bottom plate
Drain pan
Heat exchanger
Bottom plate
assembly
1
2
A
1. Removing the fan motor
1. Removing the 9 screws that fix the bottom plate A, and
remove it.
2. Removing the drain pan as follows:
(1) Remove the screw that fixes the drain pan.
(2) Slide the drain pan in the direction 1, Figure1 and
unhook the drain pan catch near the drain pipe.
(3) Slide the drain pan in the direction 2, Figure1 and
unhook the 2 catches on the other side of the drain
pipe.
3. Remove the 8 screws that fix the bottom plate assembly,
and remove it.
4. Disconnect the fan motor connector from the controller
box.
(For the models with booster heater, disconnect the
booster heater connector as well.)
5. Remove the fan plate as follow:
Figure2.
(1)Remove the 4 screws1
(2)Slide down the fan plate to remove.
6. Remove the sirocco fan setting screw and the
motor fixture setting screw to remove the motor
fixture.
Remove the other motor fixture as well, and then
remove the fan motor.
1
1
Fan base
Screw holes
Booster heater
17
Figure3.
Booster heater
Fan base
Sirocco fan
Sirocco fan
Housing assembly
Housing
assembly
Piece
Piece
Leg
Bush
Bush
Motor
2. Removing the booster heater
1. Remove the bottom plate, drain pan, and bottom plate
assembly. (Refer 1-1~3.)
2. Disconnect the booster heater connector from the
controller box.
3. Remove the 2 lower screws on the both sides of the
booster heater.
4. Loosen the 2 upper screws on the both sides of the
booster heater.
5. Removing the booster heater.
Figure4.
18
Pump cover
assembly
Drain socket
Drain pan cover
Drain pump
assembly
Drain hose
Rubber plug
Drain pan
1
2
3. Removing the drain water lift-up pump
1. Remove the drain pan. (Refer 1- 2.)
2. Disconnect the drain pump connector and drain sensor connector from the
controller box.
3. Remove the two screws of the pump cover assembly.
4. Remove the drain hose from drain socket.
5. Remove the three screws of the drain pump assembly.
6. Remove the earth screw and four nuts of the drain pump assembly.
7. Remove the drain pump from drain pump assembly.
9 PARTS LIST
19
PEHD-1.6EKA2.UK, PEHD-1.6EKHA2.UK
PEHD-2EKA2.UK, PEHD-2EKHA2.UK
PEHD-2.5EKA2.UK, PEHD-2.5EKHA2.UK
EXTERNAL PARTS
10, 11
1.2
8, 9
3, 4
5, 6, 7
No.
1
2
3
4
5
6
7
8
9
10
11
Part No. Part Name Drawing No.
Qty/set
Spec.
1 1
1 1 1 1
PEHD-
2.5EKHA2
PEHD-
2.5EKA2
PEHD-
2EKHA2
PEHD-
2EKA2
PEHD-
1.6EKHA2
PEHD-
1.6EKA2
W638918G02 Bottom plate 2 assy
W638940G02 Bottom plate 2 assy
W638917Z03 Bottom plate 1
W638939Z03 Bottom plate 1
W268511G03 H.EX.General assy
W268511G02 H.EX.General assy
W268511G01 H.EX.General assy
W638920G01 Drain pan assy
W638942G01 Drain pan assy
W638181G02 Filter
W638181G01 Filter
S70 091 669
S70 081 669
S70 011 669
S70 031 669
S70 019 480
S70 018 480
S70 017 480
S70 021 529
S70 011 529
S70 031 500
S70 021 500
1 1
1 1 1 1
1 1
1 1 1 1
1 1
1 1 1 1
1 1
1 1
1 1
20
PEHD-1.6EKA2.UK, PEHD-1.6EKHA2.UK
PEHD-2EKA2.UK, PEHD-2EKHA2.UK
PEHD-2.5EKA2.UK, PEHD-2.5EKHA2.UK
BLOWER PARTS
5, 6
7, 8
1
1
4
4
9, 10, 11
12
7, 8
5, 6
2, 3
13, 14
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Part No. Part Name Drawing No.
Qt'y/set
W353715H01 2 2 2 2
2 2 2 2
2 2
2 2
1 1
1 1
1 1
1
2 2
2 2
2 2
2 2
1 1
1 1
1 1
1 1
1
1
1 1
1 1
W122296G01
W638949G03
W241060H03
P714774X01 <MF>
<MF>
<MF>
Attachment
W638905G02 Fan base ass'y
W638932G02 Fan base ass'y
Sirocco fan
2 2 W122297G01 Sirocco fan
Housing ass'y
2 2 W638949G04 Housing ass'y
Motor
Motor support
P714316X02 Motor
P714315X02 Motor
P493640X02 Heater ass'y 4
P493639X02 Heater ass'y 3
W818836H01 Bush
S70 652 131
S70 061 677
S70 051 677
S70 A88 114
S70 A89 114
S70 989 110
S70 985 110
S70 Y56 221
S70 652 130
S70 Y58 220
S70 Y57 220
S70 Y03 300
S70 Y07 300
S70 922 105
PEHD-
2.5EKHA2
PEHD-
2.5EKA2
PEHD-
2EKHA2
PEHD-
2EKA2
PEHD-
1.6EKHA2
PEHD-
1.6EKA2
21
PEHD-1.6EKA2.UK, PEHD-1.6EKHA2.UK
PEHD-2EKA2.UK, PEHD-2EKHA2.UK
PEHD-2.5EKA2.UK, PEHD-2.5EKHA2.UK
CONTROL BOX PARTS
6
7
4
10
5
8
2
1
9
3
No.
1
2
3
4
5
6
7
8
9
10
Part No. Part Name Drawing No.
P436109X01
P436110X01
BA73S950H02
RG00C006G02
W855468G06
BG71V163H03
BG71V164H08
P419114X01
P419115X01
P421221X01
Qty/set
Spec.
< TB4 >
< TB2 >
< TB5 >
< I.B>
< T>
< RT1 >
< RT2 >
LY1F< 88H1,2 >
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
2 2 2
Terminalbed
Terminalbed
Terminalbed
Controller
Transformer work DWG.
Thermistor S
Thermistor H
Ferrite core
Ferrite core
Start relay
S70 978 717
S70 979 717
S70 435 717
S70 030 310
S70 020 799
S70 030 202
S70 040 202
S70 010 292
S70 020 292
S70 274 215
PEHD-
2.5EKHA2
PEHD-
2.5EKA2
PEHD-
2EKHA2
PEHD-
2EKA2
PEHD-
1.6EKHA2
PEHD-
1.6EKA2
22
PEHD-1.6EKA2.UK, PEHD-1.6EKHA2.UK
PEHD-2EKA2.UK, PEHD-2EKHA2.UK
PEHD-2.5EKA2.UK, PEHD-2.5EKHA2.UK
ELECTRICAL PARTS
No.
1
2
Part No. Part Name Drawing No.
KA00D026G34
BB78K214G05
Qt'y/set
Spec.
Remote controller
Remote controller cable
1 1 1 1 1 1
1 1 1 1 1 1
K controller
10m
PEHD-
2.5EKHA2
PEHD-
2.5EKA2
PEHD-
2EKHA2
PEHD-
2EKA2
PEHD-
1.6EKHA2
PEHD-
1.6EKA2
2
1
O
N
/O
F
F
F
IL
T
E
R
C
H
E
C
K
T
E
S
T
R
U
N
T
IM
E
R
S
E
T
REMOTE CONTROLLER
PAR-JH050KA
T
E
M
P.
ON
OFF
CLOCK
23
PEHD-1.6EKA2.UK, PEHD-1.6EKHA2.UK
PEHD-2EKA2.UK, PEHD-2EKHA2.UK
PEHD-2.5EKA2.UK, PEHD-2.5EKHA2.UK
DRAIN WATER LIFT-UP PUMP PARTS (OPTIONAL PARTS)
3
4
1.2
5
No.
1
2
3
4
5
Part No. Part Name Drawing No.
BG56J144G13
DB26F111H03
BB00P145G17
DE00H343G21
P312040X01
Qty/set
Spec.
1 1 1 1 1 1
4 4 4 4 4 4
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
Drain pump-94
Cushion
Drain socket assy
Drain sensor assy
Rubber plug
S70 11K 355
S70 010 533
S70 K01 523
S70 W28 266
S70 E69 558
PEHD-
2.5EKHA2
PEHD-
2.5EKA2
PEHD-
2EKHA2
PEHD-
2EKA2
PEHD-
1.6EKHA2
PEHD-
1.6EKA2
24
10 OPTIONAL PARTS
1. REFRIGERANT PIPES
28C
26C
8:00
Normai
operation
8:00
Normai
operation
23:00
Setback
operation
2. TIMER
2-1 Program timer specifications
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minute units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation(PAC-SK65PT)
Set back operation is useful for reducing running costs.
e.g.AT a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26 C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the right, the set temperature rises 2
degrees automatically during the setback operation. When the set-
back operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E
5m 7m 10m 15m Pipe length
Pipe size OD
Connection method
Liquid:/9.52 Gas:/15.88
Indoor unit:Flared Outdoor unit:Flared
Note 1.How to connect refrigerant pipes.
Factory supplied optional piping contains refrigerant at above atmospheric pressure. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and
outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m, an additional charge of refrigerant is needed.
Note 2.The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange(for wall hole), connecting cables.
Part No.
Model Name
PAC-SC32PTA
Program timer
Part name
Part No.
Program timer
PAC-SC32PTA
Exterior dimensions(mm) 5-4/32X4-23/32X23/32(130X120X18mm)
Installation Wall mount
Type of clock Quartz
Clock accuracy 50second/month at 25 C
Display-Time Liquid crystal display
Liquid crystal display
Liquid crystal display
Program cycle
-Timer setting unit
-Week
24 hours
Timer setting unit 30 minutes
No. of set points 48/day
Power rating 5V DC 5%(Supplied by Remote Controller)
25
2-3 HOW to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below.
NOTE: While the program timer is connected to the remote controller,
the 24 hour ON/OFF timer on the remote controller will not
operate.
How to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below.
NOTE: While the program timer is connected to the remote controller,
the 24 hour ON/OFF timer on the remote controller will not
operate.
2-4 Names and functions
<PAC-SC32PTA>
To Indoor unit 2.wire cable
Remote
controller
Program
timer
Connector CN 1 Connector CN 1
6-wire cable
2.wire cable
Connector CN 1 Connector CN 1
5-wire cable
To Indoor unit
Used for selection of it. The day
operation pattern set by PATTERN
SETTING is to be applied in weekly
day unit setting.
When SET is displayed, clock
adjustment, change of weekly day, daily
and weekly timer setting can be
performed. When MONITOR i s
di spl ayed, al l swi tches except
SET/MONITOR SW are invalidat-ed.
This is normal status.
Used for week day setting.
Using this switch, select "MONITOR"
or "SET" Mode.
"MONITOR" : Indicates the current
timer setting. All
switches expect MODE
SELECTOR SW are
invalidated then. This
is the normal status.
"SET" : Set to "SET" mode for clock
adjustment, charge or week
day, daily and weekly timer
setting.
During MONITOR status,
current time is displayed.
During Daily timer setting,
time desired for timer set-
ting is displayed.
Indicates the setting
set back range.
24 hours is divided indo 48 blocks
and each block represents 30
minutes. The block display consists
of patterns.
Used for set back setting.
Set back can be done in the range
of 1, 2, 4, 6, and 8C.
Used to specify the setting pattern.
Used for timer in 30 minute units.
Used for setting timer in day or
week unit.
Pushing SW moves the week day
light display in order of
SMTW
enabling the week day.
Used for adjustment of the current time.
Push SW to advance the time. Each time the but-
ton is pushed the time advances by 1 minute, push-
ing continuously advances by 1 minute at 0.5 sec-
ond interval, and when the lower digit of minutes
becomes 0, indication advances in 10 minute units.
SW is used for reversing the time. Each time the
button is pushed the time reverses by 1 min-ute,
pushing continuously reverses the time by 1 minute
at 0.5 second interval, and when the lower digit
of minute becomes 0 indication reverses in 10
minute units.
WEEKLY TIMER SETTING DISPLAY CURRENT TIME DISPLAY
SET/ MONITOR DISPLAY
WEEK DAY SETTING SW
MODE SELECTOR SW CLOCK ADJUSTMENT SW WEEKLY TIMER SW
DAILY TIMER SW
ON/ SET BACK/ OFF SW
SET BACK SETTING SW
DAILY TIMER SETTING DISPLAY SET BACK DISPLAY
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described
on page 27.
Part No. PAC-SA89TA-E
1
2
3
ORN
BRN
RED
26
117
1
1
7
12
113
1
1
3
56.5
23.5 11
8
"ENGAGED" indicator
When this indicator is lit, transmisson is in
progress and all swiches are inoperative.
switch
This change-over switch governs the opera-
tion of the accessory remote controller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
remote controller are valid. (Priority
given to the last instruction received.)
"CENTRAL"
ON / OFF switching by the accessory
remote controller is invalidate. Operation is
controlled by the centralized remote con-
troller only.
Inital setting is "DUAL"
LCD Matrix display
This display indicates the operational sta-
tus of all connected units either by steady
lighting or by flashing.
switch
Operation ON / OFF switch.
buttons These
buttons are used to designate the
attached unit (s). (They designate the unit
to be centrally controlled.)
When group "00" is designated ; collec-
tive ON/OFF instruction is sent to all
units.
When group "01" - "16" is designated ;
ON/OFF instruction is sent only to
the designated units.
switch
This change-over switch is for the pro-
gram timer.
Use "ACTIVE" when a program timer is
connected.
Use "BYPASS" when a program timer is
not connected.
Independent "DUAL / CENTRAL" and "ACTIVE / BYPASS" setting of all the groups is prossible. When the power supply to
the centralized remote controller is cut due to power failure, all settings will return to the original "DUAL" and "BYPASS".
DUAL / CENTRAL
POWER ON/ OFF
BACK AHEAD
ACTIVE/ BYPASS
Part No. PAC-SA88HA-E
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication(operation/check.)
1
2
3
4
5
BRN
RED
ORN
YLW
GRN
non-polarity
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units.When using the PAC-805RC, the program timer adapter(PAC-
825AD) is also needed.
5-1 Dimensions
Part No. PAC-805RC
5-2 Functions
Unit:mm
27
5-3 Connection method
(1) Connection in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix in-place with a tie-wrap. Connect a single
phase 200V AC(220, 230, 240V)to AN .
As E is the GND terminal,be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a 1.6
(AWG14)or above two-wire cable for the transmission line.
CAUTION: Never connect the power supply cord to the transmission terminal-block.
TERMINAL-BLOCK
FOR TRANSMISSION
TERMINAL-BLOCK
OF POWER SUPPLY
Fuse(5A) TRANSFORMER
Tie-wrap
Tie-wrap
Transmission
POWER
SUPPLY
Wiring has to be changed when
a 200,230 or 240V power is used.
TO adaptor's
terminal-block
TO adaptor's
terminal-block
Non-polar
two-wire cable
Power supply board box
Centralized
remote controller
Power supply
board
Dip swirch
SW17
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram
3. Be sure to set the maximum address number with the dipswitch
SW17 on the centralized remote controller.
28
Fig. 1
TERMINAL-BLOCK
FOR
TRANSMISSION Dip switch
SW 1
Transmission cord
TRANSFORMER
Fuse(5A)
TERMINAL-BLOCK
FOR POWER
SUPPLY
POWER SUPPLY CORD
Terminal block for
transmission to
program timer or
centralized remote
controller
Wiring has to be changed when 200V power supply is used.
POWER
SUPPLY
Fig. 2
6. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer(PAC-SK65PT)or a centralised remote controller(PAC-805RC)is used.
Part No. PAC-825AD
6-1 Parts included
1ADAPTER x1 23-core cable x1 23-core cable x1
24-core cable x1 25-core cable x1
Length:2m(6' 7") Length:2m(6' 7")
Length:2m(6' 7" ) Length:2m(6' 7")
6-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out
the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix in-place with a tie-wrap.
Connect a single phase 200V AC(220, 230, 240V) to AN.
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap(when a central-
ized remote controller is being used).
CAUTION: Never connect the power supply cord to the transmission terminal-block.
(2) When the centralised remote controller is used, set the address number with the dipswitch SW1 of the program
timer adapter.
29
(3)Connections from adapter
6-3 Dimensions (Unit:mm)
Fig. 3
To program timer or
centralized remote
controller
Adaptor
200-240V AC
CN30 CN50
CN51
5-core cable 3-core cable
Remote controller Indoor unit
Maximum length of each cable is 10m.
Fig. 4
40 80 40 27
4 Fixing screw holes
5.5 9
5
2
0
0
2
2
2
2
35
8
6
7
0
2
3
0
1
5
1
5
18
1
5
27
35
65
3 holes
h
o
le
7. OPTIONAL REMOTE CONTROLLER
This is for the control using two remote controllers.
Rear side wiring arangement opening.
46
8
3
.
5
130
18
1
2
0
Part No. PAC-JH050KA
Applied model PEHD-1.6/2/2.5EK(H)A2.UK
8. DRAIN WATER LIFT-UP MECHANISM
This allows more versatility when selecting drain piping layouts.
Part No. PAC-SK002DM-F
PEHD-1.6EK(H)A
2
.UK, PEHD-2EK(H)A
2
.UK, PEHD-2.5EK(H)A
2
.UK Applied model
HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
MEE00K027
Issued in Nov. 2000
Printed in Japan
New publication, effective Nov. 2000