MiCOM P740

>

Our products

Numerical Busbar Protection

>

Customer benefits
This architecture can
accommodate the most
complex substation layouts
and different CT classes
and manufacturers.
The use of fibre optics for
communication between
Peripheral Units and the
Central Unit gives the
following advantages:
- High communication
speed
- Eliminates insulation
problems
Fast fault clearance
(Typical tripping time 15 ms).

>> The consequences of a fault


on the busbars of a power
transmission or distribution
network substation may be very
serious. Poor quality of supply to
consumers and damage to the
electrical equipment are very
real threats.

ALSTOM has developed a new


and fully numerical busbar
protection. The primary
objectives are to provide total
protection stability under normal
operating conditions and for all
external faults, whilst reacting
quickly to internal faults. This
protection scheme is the
MiCOM P740.
The MiCOM P740 provides
high-speed protection (<1 cycle)
which meets the requirements of
the most demanding
specifications for extra high
voltage transmission networks.
The MiCOM P740 differential
busbar protection protects
configurations up to 8 zones
and 32 feeders. Its architecture
may be centralised in one
cubicle, or distributed around the
substation.

>

>

Key features
> Distributed architecture (up to 1.000 m
of optical fibre) or in a centralised cubicle.
> Topological configuration can
accommodate up to 8 zones.
> Advanced topological analysis using
operational research algorithms
(registered patent).
> Trip supervision by "check zone"
element for security.
> Low CT requirements allow the core
to be shared with existing protection.
> Innovative algorithms for CT
saturation detection
(registered patent).
The minimum permitted saturation
time is 2 ms for stability.
> Bias characteristics to maintain
stability during transient CT responses
in presence of a significant DC
component.
> Security against accidental open
circuit of CTs by the use of delta
algorithms.
> Phase segregation with a separate
element for sensitive earth fault
detection (high impedance earthed
networks).
> Automatic control of the sensitive
earth fault element by phase elements.
> User-friendly interface for operation
and commissioning staff including
two levels of maintenance.

T&D
Energy Automation & Information

BB1

BB3

BB2

BB4
Transfer
Bus
Figure 1

2 P742
or
P743
P742

P743

Peripheral Units

Optical Fibre

P741

Double Busbar
with transfer bus

Central
Unit

Main protection functions

P742

P743

Peripheral Units

> Universal topological


processing algorithms

> Architecture
The architecture of the numerical
differential busbar protection is built
around a P741 Central Unit (CU) which
gathers and processes all the analogue
measurements from the P742 and P743
Peripheral Units (PU) via direct fibre
optic connections.
It is possible to protect:
8 zones.
32 Peripheral Units per Central Unit.
> Protection
> Central Unit (P741)
Busbar bias differential protection.
Check Zone protection

The MiCOM P740 uses new universal


algorithms based on operational
research which create, in real time,
architectures of up to 8 zones.
> Stabilisation against
CT saturation
One of the most important objectives of
a differential busbar protection is to
ensure stability when CTs become
saturated, particularly under external
fault conditions.
In order to avoid this risk of
maloperation, the MiCOM P740 uses
innovative ultra high-speed algorithms
based on signal consistence variation
model (registered patent).

Breaker Fail protection


(general 3 poles trip).

> Bias characteristic


The operation of the MiCOM P740 is
based on an algorithm with a
characteristic (see figure 2) in which the
differential current is compared with a
bias value.
The purpose of this characteristic is to
ensure the stability of the protection
when there is an external fault, differing
CT tolerances and errors which
otherwise would lead to spurious
detection of an in-zone fault.
> Global supervision by
check zone element
One of the most frequent causes of the
maloperation of busbar protection
schemes is an error in actual plant
status. This leads to the production of a
differential current.

Models available
> Peripheral Units (P742/3)
Dead zone protection (short zone
between CTs and circuit-breakers).
Non directional Overcurrent
protection.
- Phase fault (2 stages).
- Earth fault (2 stages).
Breaker Fail protection
(single or three pole retrip).
Busbar protection

The operation of the MiCOM P740 is


based on the numerical application of
Kirchoff's Law for the selective detection
and ultra high-speed isolation of a
faulty section of a busbar.

Features
Central
Unit
Peripheral
Unit

8 Opto Universal Inputs, 8 Output relays


(MiCOM 16 case, 80 TE)
16 Opto Universal Inputs, 8 Output relays
(MiCOM 8 case, 40 TE)

P741 P742 P743

24 Opto Universal Inputs, 21 Output relays


(MiCOM 12 case, 60 TE)
Phase segregated current
differential busbar protection

87BB/N
87CZ

Sensitive earth fault busbar protection


Check zone element (Supervision)

50/51/P

Phase Overcurrent protection

50/51/N

Earth Overcurrent protection

CTS

Current transformers supervision

50BF

Breaker fail protection


Local single or

Peripheral
Unit
87BB/P

three pole re-trip

General three pole


back-trip

Fibre Optic signalling channels

However, if all currents of the whole


substation are taken into account, their
sum will remain null if a fault is not
present, irrespective of the error in plant
status/position.
Consequently, the tripping order for a
zone element is conditional on the
operation of a check zone element.
The main advantage of this element is
the total insensitivity to defective
auxiliary contacts.
> Dead zone or Blind spot
The current transformers surrounding the
busbars define the limits of the main
zones. When the circuit breaker is
opened a dead zone or blind spot is
automatically created between the CB
and the associated CT.
> Continuous supervision of the
current circuits by
measurement of the
differential current value
Under normal operating conditions the
differential current will be negligible. An
anomaly is detected by a threshold,
ID>1, which can be set to alarm from
1% of the primary basis current (Ibp).
> Differential current setting
When switching operations are carried
out in the substation, incorrect topology
replicas may occur. In this case, a
differential current appears.
The differential elements of the MiCOM
P740 are allowed to operate only if the
differential current reaches a threshold
ID>2 which is set above the highest load
current.
> Stabilisation of the protection
in the event of CT saturation
for external fault
One main quality of the MiCOM P740
is its ability to detect CT saturation in
less than 2 ms.
The signal processing algorithms
implemented in the MiCOM P740
combine a simulation of the flux built up
in the core of the CTs with a recursive
consistence variation control
(registered patent).
> Additional ultra high speed
external fault blocking
The ultra high-speed saturation detection
is carried out in each PU and can
generate a control signal from the
moment of the first sample (0.4 ms).

i diff (t)

Tripping
Area

Figure 2
Bias
characteristic

i1

i2
i3

ias

eb

in

Differential current : idiff node (t) =

i1

Restraining current :

i bias (t) = i 1

i2

90

i bias (t)

i2

i diff (t) = idiff node (t)


+

pe

-k

to

Restrain
area

rce

ID > 2
Is
ID > 1

Operating current :

g
nta

0
=2

+ i3 + ....... + i n
=
+

i
i3

+ ....... +

in

> Dual characteristics

Additional protection

The MiCOM P740 offers phasesegregated protection and a separate


element for earth fault detection.

The following back-up protection


functions are implemented locally in the
Peripheral Units (P742/P743).

> Multiple tripping criteria

> Phase and Earth Fault


overcurrent protection either
Definite Time (DT) or IDMT
(IEC/UK, IEEE/US curves)

The MiCOM P740 maintains the highest


level of stability, under all conditions
including:
> A hardware failure
> Incoherence of signals applied from
external plant or generated by the
power system.
> Any tripping order must therefore be
made conditional on the simultaneous
occurrence of 5 or 6 criteria:
> Magnitude criteria; confirmation of
two simultaneous thresholds per zone:
Exceeding the bias slope
characteristic (k)
Exceeding differential operating
current threshold (ID>2).
> Exceeding the supervision threshold
(ID>1).
> Signal quality criteria:
No CT saturation detected
Current variation detected on at
least two Peripheral Units
No discrepancy detected.
> Time or angular criterion.
The measurement elements on 2
samples taken at 1200 Hz.
A first sample for the initial
measurement and a second sample
for trip confirmation.
> Check zone supervision.
The zone element(s) are only
permitted to trip if the order is
confirmed by the check zone element.
> Local criteria (optional)
The Peripheral Units can be set to
only authorise tripping if there is
confirmation by local overcurrent
criteria.

Two independent stages are available


for phase and earth:
> First stage (I>1 or IN>1) can be
programmed as Definite Time (DT)
delay or dependant on one of nine
inverse time (IDMT) curves
(IEC/UK and IEEE/US).
> Second stage (I>2 or IN>2) can only
be programmed as definite time.
> External Breaker Failure
protection from the busbar
protection system
The usual 50 BF relay is totally
independent of the others and the
control connection with the busbar
protection system is hardwired. Receipt
of an external 50BF information results
in tripping of all the adjacent circuit
breakers, via the topological recognition
system knowing which breaker is
connected to which zone.
> Internal breaker failure
protection in the busbar
protection system
Some operators prefer an integrated
solution, which requires all Peripheral
Units to receive a duplication of the trip
commands generated in their associated
bay.
In general the Breaker Failure protection
must be executed on a per phase basis
which involves the possibility of
receiving tripping orders on a per pole
basis.

Figure 3
Programmable Scheme Logic

Matching CT Transformer ratios


> Balancing protection
The MiCOM P740 can correct mismatch
between current transformer ratios over
a very wide range up to 40. Its
associated user interface provides a
range between 1 A and 30,000 A
primary.
> Common base ratio
Since the current transformer ratings in
a substation may be of mixed ratios, the
MiCOM P740 enables a common base
current to be defined, irrespective of the
feeder section concerned. The settings
on the CU are all adjusted to this
common current, known as the primary
basis current (Ibp).

> Differential protection (87 BB) and


Circuit Breaker Failure protection
(50 BF) in monitoring mode. The
additional local protection functions
(51, 51N, etc...) remain operational.
> Peripheral Units - PU
(P742 and P743)
A selective two-level command may be
applied selectively for each PU.
> Maintenance of bay(s) for human
intervention. In this state,
all I/O are deactivated.
The busbar protection is still in
service, but the CB of the feeder in
service can not be tripped.
> Intervention on the equipment for
maintenance and testing.

Control
Isolation and downgraded
operating mode
For ease of operation or maintenance of
the busbar protection system, the
Central Unit and the Peripheral Units
can receive specific commands designed
to allow system testing or other
intervention without any danger of
unwanted tripping.
> Central Unit - CU (P741)

A central command to isolate the


busbars at two levels can be applied
selectively zone by zone.
> Differential protection (87 BB) in
monitoring mode (measurements
active and tripping deactivated).
The Breaker Failure protection
remains operational.

> Circuit breaker control


The circuit breaker control is available
from the front panel user interface, or
the optically isolated inputs.
> Programmable scheme logic
Powerful Programmable Scheme Logic
(PSL) allows the user to customise the
protection and control functions. It is
also used to program the functionality of
the optically isolated inputs, relay
outputs and LED indications.
The PSL uses up to 256 logic gates and
8 timers and is configured using the
graphical MiCOM S1 PC based
software as illustrated in Figure 3.

> Independent protection


settings groups
The settings are divided into two
categories: protection settings and
control and configuration settings. Four
settings groups are provided for the
protection settings to allow different
operating conditions and adaptive
relaying.

Measurement and recording


facilities
The P740 series relays are capable of
measuring and storing the values
associated with a fault. All the events,
faults records and disturbance records
are time tagged to 1 ms using an
internal real time clock. An IRIG-B port
is also provided for accurate time
synchronisation.
A lithium battery provides a back up for
the real time clock and all records in the
event of supply failure.
> Measurements
The measurements provided, which may
be viewed in primary or secondary
values, can be accessed via the back lit
liquid crystal display. They are also
accessible via the communication ports.
> Instantaneous measurements
> Central unit (P741)
Differential current
Idiff/phase/zone
Bias Current
Ibias/phase/zone
Check zone
Idiff/phase
> Peripheral units (P742 & P743)
Phase currents
IA IB IC
Neutral current
IN
Frequency
f

Post fault analysis

Local communications port

> Event recorder

All the relays are equipped with a local


communications port on the front face.
The PUs are also accessible from one
central point via the protection
communication channel, i.e. via the
P741 Central Unit.

Up to 250 time tagged event records


are stored in battery backed memory,
and can be extracted via the
communication port or be viewed on the
front panel display.
> Fault recorder
Records of the last 5 faults are stored in
the battery-backed memory.
Each fault record includes:
Indication of the faulted phase
Indication of the faulted zone (CU)
Protection element operated
Active setting group
Fault duration
Currents and frequency (PU)
Faulty zone differential and
bias current (CU)
> Disturbance Recorder
The internal disturbance recorder stores
on non-volatile memory:
8 analogue channels
ibias/idiff (CU)
iA, iB, iC, iN (PU)
32 digital channels
1 time channel
Data is sampled 12 times a cycle
20 (PU) & 8 (CU) disturbance records
Max. duration of each record for
PU: 10.5 s & CU: 600 ms
All channels and trigger sources user
configured (PU)

The local communication port is


designed to be used with MiCOM S1. It
deals with the local functions and allows
the user to program bay settings and to
configure the PSL. Extraction and
viewing of events, disturbance recording
and the fault records is also possible.

The hardware variation between the


MiCOM P740 series relay models are:

Supervision & diagnostics


Continuous self monitoring
Continuous local supervision of
current transformers by zerosequence current control
Continuous central supervision of
current circuits by measurement of the
differential current
(circuitry fault detection)
Trip circuit supervision
(using specific PSL)
Power-up diagnostics
Test facilities

Diagnostics

P741

P743

Opto
-inputs (1)

Relay
Outputs (2)

6 N/O

6 N/O 15 N/O

2 C/O

2 C/O 6 C/O

16

24

(1) Universal voltage range opto-inputs


(2) N/O: Normally Open
C/O: Change Over

The opto inputs are independent, and


may be energised from any substation
battery voltage, or from the 48V-field
voltage.

User interface
6

These records may be examined using


MiCOM S1 or COMTRADE viewer.

Continous self-checking gives a high


degree of reliability. The results of the
self-test functions are saved in the
battery-backed memory.
The test features available on the user
interface provide the status of the input
quantities, the digital inputs, the relay
outputs and selected internal logic.
A local monitor port providing digital
outputs, selected from a prescribed list
of signals, including the status of
protection elements may be used in
conjunction with test equipment.

Plant status

Hardware description

(1)

Checks and monitoring of the plant


status can be made, and an alarm
raised for any discrepancy conditions
between the open and closed auxiliary
contacts of the isolators and circuit
breakers.

All models within the MiCOM P740


series relays include:
A back-lit liquid crystal display
12 LEDs
Optional IRIG-B port (CU),
RS232 Port,
Fibre optic connection from
the CU to the PUs,
Download/monitor port,
Battery (supervised),
N/O and C/O watchdog contacts
Supervised +48 V field voltage
Dual rated CT inputs 1A/5A

(2)
(3)
(4)

Disturbance records can be extracted


from the relay via the remote
communications and saved in the
COMTRADE format.

P742

5
7

The front panel user interface comprises:

(5)
(6)
(7)

(8)

A 2 x 16 characters backlit
LCD display
Four fixed LEDs
Eight user programmable LEDs
Menu navigation and data
entry keys
READ and CLEAR keys
to view alarms
An upper cover identifying
the product name.
A lower cover concealing the front
RS232 port & parallel port download/monitoring port and
battery compartment.
Facility for fitting a security
lead seal

116.55

23.25

142.45
A B

159.00
AB

10.30

B A

177.0
(4U)

BA

129.50
155.40
305.50
303.50

Sealing
strip

12 off holes Dia. 3.4


BA

168.00

AB

483 (19" rack)


A = Clearance holes
B = Mounting holes

>

All dimensions in mm

Secondary cover (when fitted)


240.00
Incl. wiring

Front view

157.5 max

177.00

309.60

30.00

Side view

Figure 4

The user interface and menu text are


available in English, French, German
and Spanish as standard. Labels
supplied with the device allow to
customise the LEDs descriptions.
A user selectable default display
provides measurement information,
time/date, protection functions and
plant reference information. The ability
to customise the menu text and alarm
text is also supported.

> Password Protection


Password protection may be
independently applied to the front user
interface, to the front communications
port and to the rear communication
port. Two levels of password protection
are available providing access to the
controls and settings respectively.

Software support
WindowsTM 98/ME/2000/NT compatible.
MiCOM S1 software which comprises:

Case size MiCOM P741 (80TE)

Technical data

> Optical fibre connection

> Nominal Operating time


Typic 15 ms to energisation of CB trip
coil (including relay contact closure).

Settings editor
Programmable Scheme Logic editor
Menu text editor
Display of fault diagnostics and
measurements
Disturbance recorder viewer

> Front communication port


> Inputs
AC Current (In)
1 A / 5 A Dual rated
Frequency 50/60 Hz 5Hz
Auxiliary Voltage (Vx)
Nominal

Operating range (V)

(V) DC

CC

24 - 48
48 - 110
110 - 250

19 - 65
37 - 150
87 - 300

Multi core Cable 15 m maxi.


Connector RS232 DTE
9 pins D-type Female
Protocol Courier
Isolation ELV for local access

CA

24 - 110
80 - 265

> Outputs
Field Voltage 48 Vdc
(current limit: 112 mA)
> Optocoupled digital inputs
Maximum voltage input
(any setting): 300V dc

> IRIG-B Port


Carrier signal
Amplitude modulated
Connection
BNC
50 coaxial cable
> Download/monitor port
This is a 25 pin D-type female connector
located on the front user interface and is
specially designed for test purposes and
software download.

> P741
With 8 comms. boards
37 to 41 W
With 5 comms. boards
25 to 29 W

850nm, ST connectors
Multi-mode fibre 62.5/125
Data rate: 2.5 Mbits
Maximum lenght: 1000 m

> Ratings

> Burdens

> P742: 16 to 23 W
> P743: 22 to 32 W

> Internal Battery


Battery type:

AA, 3.6V

8 off holes Dia. 3.4

155.40
A B

159.00
AB

Sealing strip

177.0
(4U)

168.00

116.55

23.25

BA

AB

142.45
A B

BA

159.00

BA

181.30
202.00

10.35

B A

BA

483 (19" rack)


A = Clearance holes
B = Mounting holes

303.50

Note: If mounting plate


is required use flush
mounting cut out dimensions

177.0
(4U)

129.50
155.40
305.50

10.30

Flush mounting panel


Panel cut-out detail

A = Clearance holes
B = Mounting holes
200.00

AB

483 (19"rack)

Sealing
strip

12 off holes Dia. 3.4


168.00

23.30

>

All dimensions in mm

All dimensions in mm
Secondary cover (when fitted)
240.00
Incl. wiring

Front view

Secondary cover (when fitted)


240.00
Incl. wiring

Front view

157.5 max

177.00
157.5 max

177.00

309.60
206.00

Figure 5

Case size MiCOM P742 (40TE)

> Case

Side view

30.00

Side view

30.00

Figure 6

Case size MiCOM P743 (60TE)

Information required with order

The MiCOM relays are housed in a


specially designed case providing a
high density of functionality within the
product, a customisable user interface,
and additional functions/information
concealed by upper an lower covers.
Physical protection of the front panel
user interface and prevention of casual
access is provided by an optional
transparent front cover, which can be
fitted or omitted according to choice
since the front panel has been designed
to IP52 protection against dust and
water.
The case is suitable for either rack or
panel mounting as shown in figures
4,5 and 6.
> P741

MiCOM 80TE

> P742

MiCOM 40TE

> P743

MiCOM 60TE

> Weight
P741
(with 8 comms. boards):
7.6 kg
P741
(with 1 comms. board):
6.2 kg
P742
7.5 kg
P743
9.2 kg

MiCOM P 7 4

Central Unit (CU)


1

P741: Central Unit,


8 opto inputs, 8 outputs,
Size 16" case (80 TE)

Vx aux rating
24 - 48V dc
48 - 125V dc
110 - 250V dc

1
2
3

(30 - 100V ac)


(100 - 240V ac)

Communication boards
1
2
3
4
5
6
7
8

communication
communication
communication
communication
communication
communication
communication
communication

board
boards
boards
boards
boards
boards
boards
boards

(up to
(up to
(up to
(up to
(up to
(up to
(up to
(up to

1
2

4 peripheral units)
8 peripheral units)
12 peripheral units)
16 peripheral units)
20 peripheral units)
24 peripheral units)
28 peripheral units)
32 peripheral units)

4
5
6
7
8

Hardware options
Standard version
IRIG-B input

1
2

MiCOM P 7 4

Peripheral Units (PU)


P742: Peripheral Unit,
16 opto inputs, 8 outputs,
Size 8" case (40 TE)

P743: Peripheral Unit,


24 opto inputs, 21 outputs,
Size 12" case (60 TE)

Vx aux rating
24 - 48V dc
48 - 125V dc
110 - 250V dc

(30 - 100V ac)


(100 - 240V ac)

1
2
3

In rating
Without analogue inputs
1 & 5 A - 110 V

0
1

P2

Busbar protection
Peripheral Unit
P742

P1
S2

S1
C
B
PHASE ROTATION

MiCOM P742 (PART)


E11
E13

EIA485/KBUS

MiCOM P742 (PART)


5A

IA

C12
B2

NOTE 2.

B3
B4

C13

1A

C14

5A

C15

IB

C16

B5

B6
B7

1A

C17

5A

C18

IC

A1
B8

B9

A2
1A

A3
A4
A5
A6

B10

IN

A7

5A

A8
A9

B11

B12

A10

1A

A11
A12
A13

OPTO 1

OPTO 2

OPTO 3

OPTO 4

+
+

OPTO 5

A14

C1

A15

C2

A16

C3

+
+
+

E18

D1
D3

OPTO 8

TEST/
DOWNLOAD

+
+
+
+
+
+
+
+

D5
TRIP C

D6
D7

SK2

RELAY 4

D8

10

D9
RELAY 5

D10

16

D11

DOWNLOAD
COMMAND

17

DO-D7

2-9

D14

TO-T7

11,12,15,13,
20,21,23,24

D15

RELAY 6

D12
D13

NOT
CONNECTED

RELAY 7

D16
D17

19,18,22,25

0V

OPTO 9

TRIP B

D4

EXTERNAL
RESET

OPTO 7

TRIP A

D2

DATA
ACKNOWLEDGE

COMMON
CONNECTION
-

A18

C5

E17

DATA READY

OPTO 6

RELAY 8

D18

14

OPTO 10

OPTO 11

OPTO 12

OPTO 13

SERIAL
PORT

TX

1
2

RX

SK1

4
5

0V

6
CTS

PAPER
RTS

8
9

OPTO 14

TX1

OPTO 15

OPTO 16

A17

C4

E16
SCN
C11

WATCHDOG
CONTACT

E14

PORT

B1

WATCHDOG
CONTACT

E12

COMMON
CONNECTION

FIBRE OPTIC
COMMUNICATION
CURR DIFF

RX1

TX2

RX2

E1
E2

C6
C7

E7

C8

E8

C9

E9

C10

E10

AC OR DC
AUX SUPPLY

Vx

+
+
-

48V DC FIELD
VOLTAGE OUT

CASE
EARTH

NOTES
1.
(a)

C.T. SHORTING LINKS

(b)

PIN TERMINAL (P.C.B. TYPE)

50 OHM BNC CONNECTOR


9-WAY & 25-WAY FEMALE D-TYPE SOCKET ANSI31_7

2.

C.T. CONNECTIONS ARE SHOWN 1A


CONNECTED AND ARE TYPICAL ONLY.

3.

THIS RELAY SHOULD BE ASSIGNED TO


ANY TRIP TO ENSURE CORRECT
OPERATION OF THE PROTECTIVE RELAY.

4.

OPTO INPUTS 1 & 2 MUST BE USED FOR


SETTING GROUP CHANGES IF THIS OPTION
IS SELECTED IN THE RELAY MENU.

POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Figure 7

System overview of the P742 relay

South East Asia


Tel.: +65 67 49 07 77 - Fax: +65 68 41 95 55
Pacific
Tel.: +65 67 49 07 77 - Fax: +65 68 46 17 95
China
Tel.: +86 10 64 10 62 88 - Fax: +86 10 64 10 62 64

ALSTOM Track Record -

India
Tel.: +91 11 26 44 99 07 - Fax: +91 11 26 44 94 47

>> Low impedance biased differential


busbar protection (MBCZ)
launched in 1988.
Over 6.522 units delivered.

Busbar protection

North America
Tel.: +1 (484) 766-8100 - Fax: +1 (484) 766-8150
Central America
Tel.: +52 55 11 01 07 00 - Fax: +52 55 26 24 04 93

>> Over 211 medium impedance


biased differential busbar
protection (DIFB) delivered since
launching in 1992.

South America
Tel.: +55 11 30 69 08 01 - Fax: +55 11 30 69 07 93
France
Tel.: +33 1 40 89 66 00 - Fax: +33 1 40 89 67 19

>> Medium impedance biased


differential busbar protection with
linear current combination
(DIFB CL). Over 73 cubicles
delivered since 1996.

British Isles
Tel.: +44 (0) 1785 27 41 08 - Fax: +44 (0) 1785 27 45 74
Northern Europe
Tel.: +49 69 66 32 11 51 - Fax: +49 69 66 32 21 54
Central Europe & Western Asia
Tel.: +48 22 850 96 00 - Fax: +48 22 654 55 90
Near & Middle East
Tel.: +971 6 556 3971 - Fax: +971 6 556 5133
Mediterranean, North & West Africa
Tel.: +33 1 41 49 20 00 - Fax: +33 1 41 49 24 23
Southern & Eastern Africa
Tel.: +27 11 82 05 111 - Fax: +27 11 82 05 220

Our policy is one of continuous development. Accordingly the design of our products may change at any time.
Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advise.

www.tde.alstom.com

T&D/BPROB/MiCOMP740/us/EAI/11.03/FR/4882- - ALSTOM - 2003. ALSTOM, the ALSTOM logo and their frameworks are trademarks and service trademarks applications of ALSTOM.
MiCOM is a registered trademark of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. 389191982 RCS PARIS - 11.03.006/Db - SONOVISION-ITEP