Professional Documents
Culture Documents
a
n
g
e
N
.
8
h
o
l
e
s
a
n
g
e
A
A
A
A
A A
A A
Pos.(1)
Pos.(2) Pos.(3) Pos.(4)
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 11
13. Actuator power supply
The Bif gas-over-oil actuator is engineered and manufactured to work with a pressure supply
varying from 7 bar to 105 bar (from 100 psi to 1500 psi). Bif can also provide actuators working at
pressure supply values outside the above range.
The advantage of the Bif gas-over-oil actuator is that it functions with the gas owing in the
pipeline without requiring another power source supply.
Each actuator is also provided with a connection port to be fed by a separate supply line from a
gas storage unit or by bottled gas.
The Bif gas-over-oil actuator is supplied with a lter to avoid the entrance of particles which
might prevent the proper working of the pneumatic components. In case of wet gas, Bif can
supply a lter-condensate separator-dehydrator unit.
14. Final testing
It is very important to point out that Bif
tests 100% of the actuators. In order to do
so, Bif testing department is equipped with
sophisticated test rigs which allow to check
the correct working of the actuator with all
the foreseen control modes.
The testing department is also equipped with
electronic devices which allow to measure
various actuators parameters like the output
torques, the values of which are written on
the test certicate attached to each actuator.
The tests are carried out in accordance with
Bif internal specications and they can be
integrated with additional tests in accordance
with customer requirements.
These tests can be witnessed by third party
authorities or by the customer, in accordance
with contractual terms.
Figure 18
Figure 19
*3.3C-75 3000 22 64 31 40 38
*0.3C-100 3000 41 115 57 73 69
*0.9C-100 9000 47 132 65 85 80
*0.9C-135 9000 87 243 120 154 146
*1.5C-135 15000 108 304 150 212 169
*1.5C-175 15000 184 512 255 356 287
*3C-135 30000 176 493 244 346 285
*3C-175 30000 298 829 412 582 482
*6C-175 60000 348 970 482 679 565
*6C-200 60000 451 1320 624 887 732
*6C2-200 60000 947 2419 1311 1695 1536
14C-235 120000 700 1912 969 1360 1115
14C-280 120000 996 2715 1379 1931 1588
14C2-235 120000 1448 3700 2005 2631 2309
14C2-280 120000 2059 5261 2851 3741 3282
18C-235 180000 805 2197 1114 1564 1283
18C-280 180000 1146 3122 1586 2220 1827
18C2-235 180000 1666 4255 2306 3025 2656
18C2-280 180000 2368 6050 3278 4300 4152
32C-235 300000 955 2616 1323 1812 1529
32C-280 300000 1360 3707 1883 2573 2177
32C2-235 300000 1978 5052 2738 3506 3165
32C2-280 300000 2812 7183 3892 4984 4499
50C-235 400000 1073 2934 1486 2013 1699
50C-280 400000 1528 4165 2116 2858 2419
50C-300 400000 1739 4782 2407 3281 2751
50C2-235 400000 2198 5614 3042 3895 3517
50C2-280 400000 3124 7981 4325 5538 4999
50C2-300 400000 3568 9121 4943 6329 5713
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 12
Notes
1. * standard models
2. Max. allowable pressure 100 bar
(staticpressure applicable to fully stroked
actuator against the travel stops)
3. For Symmetric yoke, please change C
withS
GPO actuators performance table
Canted yoke Symmetric yoke
Actuator Max. operating Output torque Output torque Output torque Output torque Output torque
model torque (Nm) at 45 (Nm/bar) at 0 (Nm/bar) at 90 (Nm/bar) at 0 (Nm/bar) at 90 (Nm/bar)
Figure 20 - Typical GPO conguration
0.3C*-75 0.7 1.6 4.3 38 8
0.3C*-100 1.2 2.7 4.3 65 7.6
0.9C*-100 1.4 3.2 7.5 76 13.5
0.9C*-135 2.4 5.2 7.5 130 13
1.5C*-135 3 6 7.5 162 12.5
1.5C*-175 5 9 12 270 20
3C*-135 5 9 19 270 33
3C*-175 8 14 19 432 33
6C*-175 10 17 24 392 40
6C*-200 12 20 24 470 40
6C*2-200 24 40 49 470 80
14C*-235 18 30 35 706 60
14C*-280 26 42 50 1020 85
14C*2-235 36 59 75 706 120
14C*2-280 51 84 96 1020 170
18C*-235 21 34 40 824 70
18C*-280 30 48 60 1176 100
18C*2-235 41 68 82 824 135
18C*2-280 59 97 123 1176 190
32C*-235 25 40 50 980 80
32C*-280 35 57 75 1372 115
32C*2-235 48 80 96 980 160
32C*2-280 68 113 130 1372 220
50C*-235 27 44 60 1060 90
50C*-280 39 3 82 1530 130
50C*-300 45 72 96 1765 150
50C*2-235 52 85 96 1060 170
50C*2-280 76 125 140 1530 250
50C*2-300 88 144 171 1765 290
Gas-over-Oil actuators, series GPO
actuators technical data
Pentair reserves the right to change the contents without notice page 13
Figure 21 - GPO bi-cylinder actuator complete with line break device
Note
For Symmetric yoke, please change C with S
GPO actuators technical data
Actuator Oil Gas Tank Hand pump Oil
model displacement consumption capacity operations content
(lt.) (lt.) (lt.) per stroke (lt.)
Figure 22 - GPO 6S-200 complete with
torque limiting device
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 14
Note
The operating diagram is drawn with control
valves not actuated
Local control
Item Name
1 Double-acting gas-over-oil actuator
2 Hydraulic manual override
A Hand pump
B Adjustable relief valve
C Hand-operated directional control valve
3 Unidirectional ow regulator (adjustable setting)
4 Gas-hydraulic tank
5 Hydraulic lter
6 Stop valve
7 Gas lter/Condensate separator
8 Dust excluder with check valve
9 Control valves enclosure with vent valve
10 Double 3/2 n.c. hand-operated/spring-return valve
PC 3/2 n.c. hand-operated/ spring pilot valve (to close)
PO 3/2 n.c. hand-operated/spring pilot valve (to open)
DC 3/2 n.c. pneumatic pilot/spring-return valve (to close)
DO 3/2 n.c. pneumatic pilot/spring-return valve (to open)
11 Electric microswitches
Local control
Press lever of valve 10-PO to open or 10-PC to
close with power supply
Manual operation
Select by the valve 2C the opening or closing
operation and actuate the hand pump 2A
Pneumatic connection
Hydraulic connection
11
1
Electric connection
to microswitches
C
3-O
4-O 4-C
9
10
8
7
6
Gas exhaust
Auxiliary gas supply
connection
Figure 23 - Local control
Gas supply
connection
Close
Open
5
2
A
B
5
3-C
E.M.
PC PO
DC DO
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 15
Note
The operating diagram is drawn with control
valves not actuated
Local and remote control
Item Name
1 Double-acting gas-over-oil actuator
2 Hydraulic manual override
A Hand pump
B Adjustable relief valve
C Hand-operated directional control valve
3 Unidirectional ow regulator (adjustable setting)
4 Gas-hydraulic tank
5 Hydraulic lter
6 Stop valve
7 Gas lter/Condensate separator
8 Dust excluder with check valve
9 Control valves enclosure with vent valve
10 Double 3/2 n.c. solenoid valve with manual override
PC 3/2 n.c. pilot solenoid valve, manual override (to close)
PO 3/2 n.c. pilot solenoid valve, manual override (to open)
DC 3/2 n.c. pneumatic pilot/spring-return valve (to close)
DO 3/2 n.c. pneumatic pilot/spring-return valve (to open)
11 Electric microswitches
12 Terminals enclosure
Figure 24 - Local and remote control
Pneumatic connection
Hydraulic connection
Electric connection
Electric remote control
Energize solenoid valve 10-PC to close or
10-PO to open the actuator, during the entire
valve stroke.
Solenoid valves must be de-energized at the
end of the actuator operation.
Local control
Press lever of valves 10-PO to open and 10-PC
to close with power supply
Manual operation
Select by the valve 2C the opening or closing
operation and actuate the hand pump 2A
10
9
4-C 4-O
5 5
3-C
3-O
2
Gas
exhaust
6
7
8
12
Open
Close
Electric connection
to solenoid valves
and microswitches
DC DO
PO PC
1
11
E.M.
Auxiliary gas supply
connection
Gas supply
connection
C
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 16
Electric remote control
Energize solenoid valve 10-PC to close or
10-PO to open the actuator, during the entire
valve stroke
Solenoid valves must be de-energized at the
end of the actuator operation
Local control
Press lever on valves 10-PO to open or 10-PC
to close with power supply
Manual operation
Select by the valve 2C the opening or closing
operation and actuate the hand pump 2A
Torque limiting device
When the actuator output torque exceeds the
set value, the torque limiting switch 13 stops
the gas ow to the relevant gas-hydraulic tank
4, and the enclosed gas is exhausted
Local and remote control, torque limiting device
Item Name
1 Double-acting gas-over-oil actuator
2 Hydraulic manual override
A Hand pump
B Adjustable relief valve
C Hand-operated directional control valve
3 Unidirectional ow regulator (adjustable setting)
4 Gas-hydraulic tank
5 Hydraulic lter
6 Stop valve
7 Gas lter/Condensate separator
8 Dust excluder with check valve
9 Control valves enclosure with vent valve
10 Double 3/2 n.c. solenoid valve with manual override
PC 3/2 n.c. pilot solenoid valve, manual override (to close)
PO 3/2 n.c. pilot solenoid valve, manual override (to open)
DC 3/2 n.c. pneumatic pilot/spring-return valve (to close)
DO 3/2 n.c. pneumatic pilot/spring-return valve (to open)
11 Electric microswitches
12 Terminals enclosure
13 Torque limit switch Note
The operating diagram is drawn with control
valves not actuated
Pneumatic connection
Hydraulic connection
Electric connection
Close
Open
8
6
7
DC DO
Figure 25 - Local and remote control, torque limiting device
Gas supply
connection
Electric connection to
solenoid valves and
microswitches
Gas
exhaust
Auxiliary gas supply
connection
12
11
1
9
10
T.E.
PO
PC
E.M.
C
3-C
3-O
5
2
5
13-O 13-C
4-C 4-O
A
B
15*
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 17
Local and remote control, emergency low pressure shut down
Item Name
1 Double-acting gas-over-oil actuator
2 Hydraulic manual override
A Hand pump
B Adjustable relief valve
C Hand-operated directional control valve
3 Unidirectional ow regulator (adjustable setting)
4 Gas-hydraulic tank
5 Hydraulic lter
6 Stop valve
7 Gas lter/Condensate separator
8 Dust excluder with check valve
9 Control valves enclosure with vent valve
10 Double 3/2 n.c. solenoid valve with manual override
PC 3/2 n.c. pilot solenoid valve, manual override (to close)
PO 3/2 n.c. pilot solenoid valve, manual override (to open)
DC 3/2 n.c. pneumatic pilot/spring-return valve (to close)
DO 3/2 n.c. pneumatic pilot/spring-return valve (to open)
11 Electric microswitches
12 Terminals enclosure
13 Mechanical lter
14 Check valve
15 Gas storage tank
16 Needle valve
17 Pressure gauge
18 Relief valve
19 Manual drain valve
20 N.o. pneumatic pressure switch (adjustable setting)
21 3/2 n.o. cam-actuated/spring-return valve
22 3/2 n.o. pneumatic pilot/hand-return valve
23 Higher pressure shuttle valve
Electric remote control
Energize solenoid 10-PC to close or 10-PO
to open the actuator during the entire valve
stroke. Solenoid valves must be de-energized
at the end of the actuator operation.
Local operation
Press lever of valves 10-PO to open or 10-PC
to close with power supply
Manual operation
Select by the valve 2C the opening or closing
operation and actuate the hand pump 2A
Emergency shutdown operation
The pressure to be controlled is connected to
the pressure switch (20) pilot.
When the pressure decreases below the set
point of the pressure switch (20), a pressure
signal pilots the valve (22) to inhibit opening
operation and power valve (10-PO) causes the
actuator closing.
The pilot pressure must be re-established and
the opening operation inhibition valve must
be manually reset before the actuator can be
reopened
Note
The operating diagram is drawn for solenoid
valves coils not energized, low pressure in the
ESD device pilot line, and no pressure in the
gas supply line and into the storage tank
Open
Close
9
4-C 4-O
2
5
A
B
5
3-O
3-C
1
11
8
Figure 26 - Local and remote control, emergency low pressure shut down
C
E.M.
T.E.
12
7
Gas
exhaust
Auxiliary gas supply
connection
Electric connection to
solenoid valves and
microswitches
Esd device pilot
connection
* = Optional
6B
21
22
20
10
23
PO
DC
DO
PC
18*
19*
17*
16*
14*
13*
6A
Gas supply
connection Pneumatic connection
Hydraulic connection
Electric connection
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 18
Pneumatic connection
Hydraulic connection
Electric connection
Electric remote control
Energize solenoid 21 to open, de-energize to
close the actuator: in case of electric supply
failure the actuator moves automatically in
closing
At the end of actuator strokes the valves 24
are actuated and cause the exhaust of the gas
utilized for the operation
Local control
Move the valve 20 to local operation
Press lever on valves 10-PO to open or 10-PC
to close with power supply
Manual operation
Move the valve 20 to local operation
Select by the valve 2C the opening or closing
operation and actuate the hand pump 2A
24-C
DC DO
Figure 27 - Local and remote control, electric fail safe
1
11
12
8
20
22
21
5
2
5
3-C 3-O
24-O
9
10
23 23
T.E.
18*
17A*
16A*
* = Optional
15*
19*
14*
E.M.
16B
17B
Gas exhaust
Electric connection
to solenoid valve and
microswitches
Auxiliary gas supply
connection
Gas supply
connection 6
7
PO PC
4-O 4-C
C
Close
Open
Local and remote control, electric fail safe
Item Name
1 Double-acting gas-over-oil actuator
2 Hydraulic manual override
A Hand pump
B Adjustable relief valve
C Hand-operated directional control valve
3 Unidirectional ow regulator (adjustable setting)
4 Gas-hydraulic tank
5 Hydraulic lter
6 Stop valve
7 Gas lter/Condensate separator
8 Dust excluder with check valve
9 Control valves enclosure with vent valve
10 Double 3/2 n.c. hand-operated/spring-return valve
PC 3/2 n.c. hand-operated/ spring pilot valve (to close)
PO 3/2 n.c. hand-operated/spring pilot valve (to open)
DC 3/2 n.c. pneumatic pilot/spring-return valve (to close)
DO 3/2 n.c. pneumatic pilot/spring-return valve (to open)
11 Electric microswitches
12 Terminals enclosure
13 Mechanical lter
14 Check valve
15 Gas storage tank
16 Needle valve
17 Pressure gauge
18 Relief valve
19 Manual drain valve
20 3/2 hand-operated valve
21 3/2 n.o. solenoid/spring-return pilot valve
22 3/2 n.o. pneumatic pilot/spring-return valve
23 Higher pressure shuttle valve
24 3/2 n.o. cam-actuated/spring-return valve
Note
The operating diagram is drawn for solenoid
valve coil not energized, no pressure in the
gas supply line and into the storage tank,
valve in intermediate position
13*
Local and remote control, line break device
Item Name
1 Double-acting gas-over-oil actuator
2 Hydraulic manual override
A Hand pump
B Adjustable relief valve
C Hand-operated directional control valve
3 Unidirectional ow regulator (adjustable setting)
4 Gas-hydraulic tank
5 Hydraulic lter
6 Stop valve
7 Gas lter/Condensate separator
8 Dust excluder with check valve
9 Control valves enclosure with vent valve
10 Double 3/2 n.c. solenoid valve with manual override
PC 3/2 n.c. pilot solenoid valve, manual override (to close)
PO 3/2 n.c. pilot solenoid valve, manual override (to open)
DC 3/2 n.c. pneumatic pilot/spring-return valve (to close)
DO 3/2 n.c. pneumatic pilot/spring-return valve (to open)
11 Electric microswitches
12 Terminals enclosure
13 Mechanical lter
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 19
A
16*
15*
19*
14*
C
B
L.B. Device
test ports
L.B.
23
DO DC
E
F
Figure 28 - Local and remote control, line break device
Pneumatic connection
Hydraulic connection
Electric connection
Electric remote control
Energize solenoid valve 10-PC to close or
10-PO to open the actuator, during the entire
valve stroke
Solenoid valves must be de-energized at the
end of the actuator operation
Local control
Press lever on valves 10-PO to open or 10-PC
to close with power supply
21
22
* = Optional
A
B
C
10 8
9
7A
T.E.
6C
B
5
5
2
1
3-O
4-C 4-O
7B
12
PC
PO
Gas
exhaust
17*
18*
13A*
6A*
13B*
6B*
24
Line break
device
connection
Auxiliary
gas supply
connection
3-C
A
11
E.M.
Gas supply connection
(upstream the valve)
Gas supply connection
(downstream the valve)
Electric connection to solenoid
valves and microswitches
Close
Open
Note
The operating diagram is drawn with control
valves not actuated
Manual operation
Select by the valve 2C the opening or closing
operation and actuate the hand pump 2A
Line break operation
A rate of pressure drop in the pipeline causes
a differential pressure across the diaphragm
valve 22. When the differential pressure is
higher than the preset value, the diaphragm
valve 22 trips and pilots the valve 20 to inhibit
open operation and the power valve 10C
causes the actuator to close.
After the line break intervention, the inhibition
valve (20) must be manually reset before the
actuator can be reopened.
The line break pilot has to be connected to
the pipeline (downstream the valve) and the
pressure intake has to be separate from the
gas supply pressure intake
14 Higher pressure shuttle valve (double check valve)
15 Gas storage tank
16 Needle valve
17 Pressure gauge
18 Relief valve
19 Manual drain valve
20 3/2 n.o. pneumatic pilot/hand-return valve
21 Shuttle valve device
A Check valve
B Low pressure vent valve
C Stop valve for pressure gauge
D Pressure gauge
E 2/2 hand-operated valve
F Higher pressure shuttle valve
22 2/2 n.c. diaphragm pilot valve (adjustable)
23 Check valve with orice for line break device
A Check valve with orice
B Stop valve
24 Reference tank for line break device
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 20
15. Sizing of gas-over-oil actuators
Normally the power gas for GPO actuator feeding is taken directly from the gasline. This means
that the pressure of the gasline is the same used by the actuator. Being the pipeline pressure
normally not constant, a minimum and a maximum value of the pipeline pressure is dened by the
technical specications.
With the minimum pressure the actuator must move the valve with the minimum P. With the
maximum pressure the actuator must move the valve with maximum P.
Usually the most critical situation for the actuator is the running torque of the valve when the
minimum pipeline pressure is available.
Only when the gas supply is taken from an independent source (separate pipeline, emergency
tank, separate control system) the actuator with the minimum supply pressure must be able to
move the valve with the maximum P.
Particular attention must be paid to the opening of vent valves and by-pass valves, generally of
small size. In this case the gas speed and the P across the valve generate a signicant dynamic
torque to close the valve not only near to the closing position, but along the valve stroke. The
valve makers must carefully evaluate this situation and provide the correct torque values for the
real operating condition of the valve.
The rule of thumb for this application is to consider the actuator supply at minimum pressure
(i.e.25 barg) to move the valve with the max P (i.e. 100 barg).
16. Gas-over-oil actuators HYGLA for Linear Valves
For the motorization of linear valves, as through-conduit gate valves frequently used in the gas
pipelines, Bif can also propose the proper gas-over-oil actuators of the HYGLA series.
HYGLA actuators utilize the same high-pressure controls used for quarter-turn actuators GPO.
Proper pedestals with anges and adjustable stem joint to meet the valve top mounting design are
normally supplied.
In order to keep the valve in position, the control systems usually include the hydraulic locking
device with double piloted check valves with thermal relief function or mechanical lock piloted by
the power gas.
Figure 29
0.3*-75 947 615 862 515 268 186 427 147 72 790 200 319 222 532 292 221 189 345 70 155 332 300 102 SCN 6200 125
0.3*-100 969 615 862 515 268 186 427 147 72 790 200 319 222 554 292 221 189 345 70 155 332 300 102 SCN 6200 140
0.9*-100 1043 681 829 551 304 222 463 147 12 817 243 342 245 593 315 244 250 393 80 185 367 377 142 SCN 6200 170
0.9*-135 1110 681 829 551 304 222 463 147 12 817 243 342 245 660 315 244 250 393 80 185 367 377 142 SCN 6200 190
1.5*-135 1152 742 829 552 305 223 464 147 11 818 284 362 293 702 335 264 270 413 100 185 367 377 142 SCN 6200 210
1.5*-175 1213 742 1157 552 305 223 464 147 11 1146 284 362 293 763 335 264 270 413 100 185 367 377 142 SCN 6200 250
3*-135 1555 917 1313 565 318 234 476 147 20 1293 371 443 391 1032 416 345 319 493 160 235 438 337 168 SCN 6200 390
3*-175 1623 917 1313 565 318 234 476 147 20 1293 371 443 391 1100 416 345 319 493 160 235 438 337 168 SCN 6200 410
Gas-over-Oil actuators, series GPO
overall dimensions
Pentair reserves the right to change the contents without notice page 21
Notes
X = 1/2 NPT gas supply connection
Y = 1/4 NPT emergency gas supply
connection
W = 1 NPT electric connection
Z = 25 mm lifting holes diameter
Weights are referred to base construction
(without adaptor)
* = C For canted yoke
SForsymmetricyoke
a
y
A
l m
u t
X
p
q
r
B
n
o
Exhaust
z
z
e
d
f
g
C
w
h i
Lifting points
c
b
Figure 30 - TN 1037-1
Dimensions in mm
Actuator A B C a b c d e f g h i l m n o p q r s t u Coupling Weight
model dwg (Kg)
6*-175 1785 1160 1120 602 355 271 512 202 77 1043 480 279 430 1154 241 170 398 680 185 455 478 90 219 SCN 6200 515
6*-200 1855 1160 1120 602 355 271 512 202 77 1043 480 279 430 1224 241 170 398 680 185 455 478 90 219 SCN 6200 550
14*-235 2098 1223 1475 715 468 384 618 202 59 1416 543 392 496 1252 354 283 381 660 200 630 501 0 219 SCN 6201 950
14*-280 2098 1223 1865 715 468 384 618 202 59 1806 543 392 496 1252 354 283 381 660 200 630 501 0 219 SCN 6201 1320
18*-235 2255 1230 1525 729 482 398 682 202 37 1488 550 456 564 1355 418 347 384 870 230 630 726 0 219 SCN 6201 1190
18*-280 2255 1230 1400 729 482 398 682 202 37 1363 550 456 564 1355 418 347 441 870 230 630 726 0 273 SCN 6201 1430
32*-235 2446 1548 1865 750 503 419 703 202 80 1785 660 430 610 1556 392 321 543 920 270 630 890 0 219 SCN 6201 1580
32*-280 2446 1548 1850 750 503 419 703 202 80 1770 660 430 610 1556 392 321 570 920 270 630 890 0 273 SCN 6201 1820
50*-235 2610 1825 1540 780 533 449 733 202 92 1448 685 355 698 1700 317 246 551 1140 300 860 900 42 273 SCN 6201-1 1800
50*-280 2610 1825 1400 780 533 449 733 202 92 1308 685 355 698 1700 317 246 592 1140 300 860 900 42 355 SCN 6201-1 2120
50*-300 2610 1825 1500 780 533 449 733 202 92 1408 685 355 698 1700 317 246 592 1140 300 860 900 42 355 SCN 6201-1 2290
s
Gas-over-Oil actuators, series GPO
overall dimensions
Pentair reserves the right to change the contents without notice page 22
a
y
A
l m
t
X
p
q
r
B
n
o
Exhaust
e
d
f
g
C
w
h i
Lifting points
Lifting points
c
b
u
Figure 31 - TN 1037-2
Notes
X = 1/2 NPT gas supply connection
Y = 1/4 NPT emergency gas supply
connection
W = 1 NPT electric connection
Z = 25 mm lifting holes diameter
Weights are referred to base construction
(without adaptor)
* = C For canted yoke
SForsymmetricyoke
Dimensions in mm
Actuator A B C a b c d e f g h i l m n o p q r s t u Coupling Weight
model dwg (Kg)
6*-2-200 2396 1160 1290 602 355 271 512 202 77 1213 480 279 1172 1224 241 170 425 680 185 455 478 90 273 SCN 6200 700
14*2-235 2445 1223 1842 715 468 384 618 202 59 1783 543 392 1193 1252 354 283 410 660 200 630 501 0 273 SCN 6201 1400
14*2-280 2445 1223 1400 715 468 384 618 202 59 1341 543 392 1193 1252 354 283 452 660 200 630 501 0 356 SCN 6201 1620
18*2-235 2642 1230 1225 729 482 398 682 202 37 1188 550 456 1287 1355 418 347 452 870 230 630 726 0 356 SCN 6201 1550
18*2-280 2642 1230 1737 729 482 398 682 202 37 1700 550 456 1287 1355 418 347 452 870 230 630 726 0 356 SCN 6201 1800
32*2-235 3032 1548 1400 750 503 419 703 202 80 1320 660 430 1476 1556 392 321 570 920 270 630 890 0 356 SCN 6201 1950
32*2-280 3032 1548 1824 750 503 419 703 202 80 1744 660 430 1476 1556 392 321 570 920 270 630 890 0 356 SCN 6201 2220
50*2-235 3315 1825 1400 780 533 449 733 202 92 1308 685 355 1615 1700 317 246 542 1140 300 860 900 42 356 SCN 6201-1 2220
50*2-280 3315 1825 1400 780 533 449 733 202 92 1308 685 355 1615 1700 317 246 592 1140 300 860 900 42 457 SCN 6201-1 2480
50*2-300 3315 1825 1542 780 533 449 733 202 92 1450 685 355 1615 1700 317 246 592 1140 300 860 900 42 457 SCN 6201-1 2700
Gas-over-Oil actuators, series GPO
overall dimensions
Pentair reserves the right to change the contents without notice page 23
Notes
X = 1/2 NPT gas supply connection
Y = 1/4 NPT emergency gas supply
connection
W = 1 NPT electric connection
Z = 25 mm lifting holes diameter
Weights are referred to base construction
(without adaptor)
* = C For canted yoke
SForsymmetricyoke
a
y
A
l m
t
X
p
q
r
B
n
o
Exhaust
e
d
f
g
C
w
h
i
Lifting points
Lifting points
c
b
u
s
Figure 32 - TN 1037-3
Dimensions in mm
Actuator A B C a b c d e f g h i l m n o p q r s t u Coupling Weight
model dwg (Kg)
0.3 240 93 165 M20 4 5 17 127 70 12 75.6
0.9 310 112 254 M16 8 5 19 150 86 14 93.6
1.5 360 144 298 M20 8 6 19 190 112 18 119
3 430 195 356 M30 8 9 23 200 157 25 167.8
6 520 250 406 M36 8 14 29 260 200 28 212.8
Gas-over-Oil actuators, series GPO
coupling dimensions
Pentair reserves the right to change the contents without notice page 24
d4
h
2
W
45
D
1
0
Drive sleeve
Flow line
Top view of the scotch yoke mechanism
(actuator shown in closed position)
N. Threaded holes
N
.
8
h
o
l
e
s
a
n
g
e
N
.
4
h
o
l
e
s
a
n
g
e
H
m
a
x
d1 max
P.C.D., number and size according to
ISO 5211 (but the holes are on centerline
instead of stradole the centerline)
d5
+0.4
+0.1
Figure 33 - SCN 6200
d2
+0.1
0
d3
0.2
h
1
+
0
.
5
0
k +
0
.
4
0
Note
P.C.D., number and size according to ISO 5211
(but the holes are on centerline instead of
straddle the centerline)
Dimensions in mm
Actuator d1 d2 d3 d4 N h1 h2 H max d5 W K
model
14 580 250 483 M36 12 10 29 340 175 45 195.8
18 680 290 603 M36 16 12 32 350 200 45 220.8
32 780 290 603 M36 16 12 32 400 220 50 242.8
Gas-over-Oil actuators, series GPO
coupling dimensions
Pentair reserves the right to change the contents without notice page 25
Note
P.C.D., number and size according
to ISO 5211
Figure 34 - SCN 6201
d4
h
2
Drive sleeve
H
m
a
x
d1 max
d2
+0.1
0
d3
0.2
h
1
+
0
.
5
0
N. Threaded holes
N
.
1
2
h
o
l
e
s
a
n
g
e
N
.
1
6
h
o
l
e
s
a
n
g
e
W D10
Flow line
Top view of the scotch yoke mechanism
(actuator shown in closed position)
d5
+0.2
+0.1
k
+
0
.
4
0
Dimensions in mm
Actuator d1 d2 d3 d4 N h1 h2 H max d5 W K
model
50 800 315 698 M36 24 10 32 430 240 56 264.8
60 840 315 698 M36 24 10 32 430 240 56 264.8
Gas-over-Oil actuators, series GPO
coupling dimensions
Pentair reserves the right to change the contents without notice page 26
Top view of the scotch yoke mechanism
(actuator shown in closed position)
Drive sleeve
Flow line
Flange sizing according to ISO
N. Threaded holes
Figure 35 - SCN 6201-1
H
m
a
x
h
1
+
0
.
5
0
d4
h
2
W D10
d1 max
d2
+0.1
0
d3
0.2
d5
+0.2
+0.1
k
+
0
.
4
0
Notes
- Insert bush supplied by Bif with
unmachined bore
Blind insert on request
For maximum stem acceptance see table
on page 28
- Fixing bolts and nuts supplied by Bif only
on request
- Different values of insert protrusion K on
request
Dimensions in mm
Actuator d1 d2 d3 d4 N h1 h2 H max d5 W K
model
0.3 240 93 165 M20 4 5 17 23 70 20 106
0.9 310 112 254 M16 8 5 19 41 86 20 130
1.5 360 144 298 M20 8 6 19 53 112 22 157
3 430 195 356 M30 8 9 23 73 157 32 162
6 520 250 406 M36 8 14 29 109 200 35 214
2
+0.1
0
h
1
+
0
.
5
0
Gas-over-Oil actuators, series GPO
coupling dimensions
Pentair reserves the right to change the contents without notice page 27
Notes
- Insert bush supplied by Bif with
unmachined bore
Blind insert on request
For maximum stem acceptance see table
on page 28
- Fixing bolts and nuts supplied by Bif only
on request
- Different values of insert protrusion K on
request
h
2
Drive sleeve
Snap ring
Housing
Insert bush (1)
Flow line
N
.
8
h
o
l
e
s
a
n
g
e
N
.
4
h
o
l
e
s
a
n
g
e
H
K
(
3
)
I
E
d3
0.2
d1 max
d4(2)
Adaptor ange
N. Threaded holes
Figure 36 - SCN 6202
Dimensions in mm
Actuator d1 d2 d3 d4 N h1 h2 H max d5 W K
model
W
S max
0.3 2500 52 (14) 55 46 64 120
0.9 7000 66 (16) 70 55 77 140
1.5 12000 85 (18) 90 73 103 180
3 25000 120 (32) 130 104 147 190
6 50000 150 (36) 170 133 188 250
M8 20
M10 40
M12 70
M14 110
M16 160
M20 320
M22 420
M24 550
M27 800
M30 1100
M33 1400
M36 1700
Gas-over-Oil actuators, series GPO
Pentair reserves the right to change the contents without notice page 28
Notes
* S max: maximum external diameter in case
of rounded edge
** Without adaptor ange
- Key according to UNI6604 or DIN6885 sh.1
or BS4235 part 1, or ISO773, or equivalent
- The listed max acceptance values are
applicable for stems with keyway parallel
or perpendicular to the ow line and for
square stems with diagonal in parallel to
the ow line
1
2
Coupling bolts tightening torque
Thread size Recommended tightening torque (Nm)
Table TN 1005 - stem acceptance for insert bush (dim in mm)
Actuator Max. Max. stem Max. stem Square stem
2
Max. stem
model operating diameter diameter with protrusion **
torque (Nm) with square key rectangular
(key dimension)
1
key
1
() W S*