Rectifiers

for stationary battery systems


Range ADC II
GLR ADC_2_Eng_28_09_00.qxd 10.02.2002 14:26 Uhr Seite 2
AC-input

Input voltage: 230V 15 %, 47 - 63 Hz

Power factor: > 0,98 at nom. load

Efficiency: 82 - 90 % depending on
the output voltage

mains input fuse

soft start
DC-output

4 possible output voltages

constant power characteristic with current limiting

output voltage accuracy < 0,5 %

ripple < 0,05 % eff

phosmetric noise voltage 1 bzw 2 mV acc.to CCITT

short-circuit-proof

parallel switchable

blockable equalizing

automatic charging possible

output relay for "power failure"

output relay for "common alarm"


General
his rectier range is suitable for boost and oat-charging
of stationary installations. The low power ranges, are also
suitable for charging starter-batteries for diesel motors or gas
turbines.
Because the ADC has a very low output ripple current, it is ideal-
ly suited to be used with sealed batteries. The ADC can also be
connected to loads without batteries because of its excellent
dynamic performance.
These units can be supplied as a wall-mounted version (see pic-
ture 3) or as module (see picture 2) in a 19" plug-in version (see
picture 1).
Integrated function
he ADC is equipped with an active lter for sinusoidal
current consumption on the mains input. Using this tech-
nology a power factor of nearly 1 can be reached. This means
that only actual power is taken from the supply to feed the ADC.
The output is accurate, with constant power characteristic and
equipped with 3 different voltage levels as well as a current
limiting.
For optimizing the battery service life of sealed batteries tempe-
rature compensated charging voltage regulation is possible.
The unit is cooled with a fan which is temperature controlled
and superviced by a max. temperature guard.
T T
Monitoring functions

mains fault

rectier fault

monitoring of the adjusted constant voltage

fuse alarm

over temperature alarm


battery temperature monitoring with compensation charging
(temperature sensor necessary)
Standard display CL 20 (see picture 4)
The display unit is microprossesor controlled and supplied via
DC-DC-converter from the output voltage during mains failure
from the battery.

push button for ON/OFF with LED indication

push button for boost with LED indication

push button for reset

LCD display with push button and LEDs for indication of out-
put voltage and current also the adjusted limits

LED "operation"

LED "Failure"

LED "voltage deviation"


Picture 2: Module Picture 1: 19-plug in
TECHNICAL DATA
ADC II
GLR ADC_2_Eng_28_09_00.qxd 10.02.2002 14:26 Uhr Seite 3
Monitor unit CL 30 (see picture 5)

The monitor unit CL 30 provides the following indications, in


addition to those of the CL 20.
- charge level high
(varibale adjustment from 110-130% of nominal voltage)
- charge level low
(varibale adjustment from 90-110 % of nominal voltage)
- battery circuit failure
(daily automatic detection of a fault within the battery
circuit and a button for manual test)
- battery test
(variable adjustment for time and low voltage limit)
- Earth fault monitoring +/-
(adjustable from 0,1 up to 1 MOhm)
All monitoring functions can be individually delayed, and are lin-
ked to the common alarm relay and indicated via LED.
CL 40 option
This provides all the monitoring functions of the CL 30 via indi-
vidual volt free relay. The relay card is connected via an I
2
C-bus.
Relevant standards

EN 60950

EN 50081-1

EN-50082-2
Ambient conditions and mechanical details

ambient temperature max 40 C

Installation height max. 1000 m ab. sea level

Rel.humidity: < 95%

Acustic noise < 40 dB in 1 m distance


with fan oper. < 55 dB
in 1 m distance

Protection IP 20

Dimensions see type table

Paint nish
- Module: Galvanised
- Cabinet: RAL 7032
- 19 plug in: front panel RAL 7032
Picture 4: Standard display CL 20
Picture 3: Wall mounted cabinet
Picture 5: Monitor unit CL 30 and CL 40
Standard-displays
TECHNICAL DATA
ADC II
GLR ADC_2_Eng_28_09_00.qxd 10.02.2002 14:27 Uhr Seite 4
7
8
4
1
3
5
.
0
0




0
2
/
2
0
0
2




p
a
u
s

D
e
s
i
g
n

&

M
e
d
i
e
n
,
B
o
c
h
o
l
t




S
u
b
j
e
c
t

t
o

a
l
t
e
r
a
t
i
o
n
s
.
P
r
i
n
t
e
d

o
n

c
h
l
o
r
i
n
e

f
r
e
e

p
a
p
e
r
.
Type Input voltage Input current Output voltage Output current Dimensions Weight
( V ) ( A ) ( V ) ( A ) H x W x D kg
E 230 G 12/ 20 BWru - ADC/M 230 0,9 12 20 190 x 250 x 170 5
E 230 G 24/ 12 BWru - ADC/M 230 1,6 24 12 190 x 250 x 170 5
E 230 G 24/ 20 BWru - ADC/M 230 3,2 24 20 190 x 250 x 170 6
E 230 G 48/ 6 BWru - ADC/M 230 1,6 48 6 190 x 250 x 170 5
E 230 G 48/ 12 BWru - ADC/M 230 3,2 48 12 190 x 250 x 170 6
E 230 G 60/ 4,8 BWru - ADC/M 230 1,6 60 4,8 190 x 250 x 170 5
E 230 G 60/ 9,5 BWru - ADC/M 230 3,2 60 9,5 190 x 250 x 170 6
E 230 G 110/ 5 BWru - ADC/M 230 3,2 110 5 190 x 250 x 170 6
MODULE VERSI ON
CABI NET VERSI ON
275
4
1
0
2
2
9
1
9
0
230
247
5,5
7
1
7
5
1
9
0
5,5 (4x)
8
10 (2x)
1
5
5
16,5
140
172,5
482,6
465,1 8,75
5,9
8
8
7
6
,
2
210
220,5
241 41
1
5
Typetable ADC II range
19PLUG IN VERSION
DIMENSION DIAGRAMS
Module version Wall mounted cabinet
19-plug in version
ADC II
Benning GmbH & Co. KG Tel. +49 (0)2871 93 - 0 Fax 93 - 380
Mnsterstrae 135 137 D-46397 Bocholt E-Mail: info@benning.de
Type Input voltage Input current Output voltage Output current Dimensions Weight
( V ) ( A ) ( V ) ( A ) H x W x D kg
E 230 G 12/ 20 BWru - ADC/G 230 0,9 12 20 410 x 275 x 190 9
E 230 G 24/ 12 BWru - ADC/G 230 1,6 24 12 410 x 275 x 190 9
E 230 G 24/ 20 BWru - ADC/G 230 3,2 24 20 410 x 275 x 190 10
E 230 G 48/ 6 BWru - ADC/G 230 1,6 48 6 410 x 275 x 190 9
E 230 G 48/ 12 BWru - ADC/G 230 3,2 48 12 410 x 275 x 190 10
E 230 G 60/ 4,8 BWru - ADC/G 230 1,6 60 4,8 410 x 275 x 190 9
E 230 G 60/ 9,5 BWru - ADC/G 230 3,2 60 9,5 410 x 275 x 190 10
E 230 G 110/ 5 BWru - ADC/G 230 3,2 110 5 410 x 275 x 190 10
Type Input voltage Input current Output voltage Output current Dimensions Weight
( V ) ( A ) ( V ) ( A ) H x W x D kg
E 230 G 12/ 20 BWru - ADC/E 230 0,9 12 20 89 x 483 x 240 5
E 230 G 24/ 12 BWru - ADC/E 230 1,6 24 12 89 x 483 x 240 5
E 230 G 24/ 20 BWru - ADC/E 230 3,2 24 20 89 x 483 x 240 6
E 230 G 48/ 6 BWru - ADC/E 230 1,6 48 6 89 x 483 x 240 5
E 230 G 48/ 12 BWru - ADC/E 230 3,2 48 12 89 x 483 x 240 6
E 230 G 60/ 4,8 BWru - ADC/E 230 1,6 60 4,8 89 x 483 x 240 5
E 230 G 60/ 9,5 BWru - ADC/E 230 3,2 60 9,5 89 x 483 x 240 6
E 230 G 110/ 5 BWru - ADC/E 230 3,2 110 5 89 x 483 x 240 6