MCCB Relay Setting:
Q10: MCCB near PCC Main Room
Q1 : Field MCC Room Main MCCB
Type of MCCB :Schneider Make LV431650 250A
LV431650 circuit breaker Compact NSX250F - TMD - 250 A - 4 poles 4d
General Q10- In PCC
Q-1 In
Filed
Range Setting Setting
Neutral protection setting 1 x Ir 4t 0.3 0.2
Long time pick-up adjustment type Ir Adjustable 100% 80%
Long time pick-up adjustment range 0.7...1 x In 1 0.8
Long time delay adjustment type Fixed
[Tr] long-time delay adjustment 120...400 s 1.5 x In 180 120
15 s 6 x Ir 15 15
Short-time pick-up adjustment type Isd Adjustable
[Isd] short-time pick-up adjustment
range
5...10 x In 9 3
Short-time delay adjustment type Fixed



[Ics] rated service breaking capacity
Ics 36 kA conforming to IEC
60947-2 380/415 V AC 50/60 Hz
36kA 36kA



Breaking capacity
36 kA Icu conforming to IEC
60947-2 at 380/415 V AC 50/60
Hz
36kA 36kA

Assumptions & Consideration:
Load flow calculation as Per SLD & Data Provide By manufacture of electrical
equipments
All load simulation assume at 100% load condition
ANSI/IEEE Standard 242-1986, IEC 61850, EN 60947-2
IEC 60947-2,
NEMA AB1
UL 508