MCCB Relay Setting: Q10: MCCB near PCC Main Room Q1 : Field MCC Room Main MCCB Type of MCCB :Schneider Make LV431650 250A LV431650 circuit breaker Compact NSX250F - TMD - 250 A - 4 poles 4d General Q10- In PCC Q-1 In Filed Range Setting Setting Neutral protection setting 1 x Ir 4t 0.3 0.2 Long time pick-up adjustment type Ir Adjustable 100% 80% Long time pick-up adjustment range 0.7...1 x In 1 0.8 Long time delay adjustment type Fixed [Tr] long-time delay adjustment 120...400 s 1.5 x In 180 120 15 s 6 x Ir 15 15 Short-time pick-up adjustment type Isd Adjustable [Isd] short-time pick-up adjustment range 5...10 x In 9 3 Short-time delay adjustment type Fixed
[Ics] rated service breaking capacity Ics 36 kA conforming to IEC 60947-2 380/415 V AC 50/60 Hz 36kA 36kA
Breaking capacity 36 kA Icu conforming to IEC 60947-2 at 380/415 V AC 50/60 Hz 36kA 36kA
Assumptions & Consideration: Load flow calculation as Per SLD & Data Provide By manufacture of electrical equipments All load simulation assume at 100% load condition ANSI/IEEE Standard 242-1986, IEC 61850, EN 60947-2 IEC 60947-2, NEMA AB1 UL 508