Ceiling cassette fault treatment

Common fault, causes and treatment


Phenomena cause of the malfunction Treatment
Power Line interruption line fault Check on the power lines
Lack of phase;fuse break down Power inspection, the replacement of fuse
Low voltage Voltage tests to identify the reasons
Switch malfunction, contact disconnect Switch with a multimeter check,
Replace a new one if necessary
Pressure relay action, the system pressure is
not normal
The pressure to return to normal, manual reset
Breakdown fan capacitors Replacement after inspection
Compressor jam Repair or replacement
Air conditioner,
fans, compressors
can not work
Thermostat can not work Contact restructuring or inspection, repair or replacement
Motor circuit or short circuit Check with a multimeter resistance, repair or replacement
Traverse circuit or short circuit Re-wiring
foreign body jammed Remove foreign body to restore normal
Capacity attenuation Replacement capacitor
Only the outdoor
fan motor cannot
work
Electronic Control Board no output or bad
contact
Control board replacement
Compressor jam, such as burn around
Resistance
Replacement compressor
No voltage input to the compressor Gradually check the circuit, find out the reasons and repair
Overload protection action check whether the current too
hige, determine the cause and repair
Three-phase power supply short,opposite
phase
Check and repair
Single-phase capacitor attenuation Replacement capacitor
Compressor can
not work
AC contactor malfunction Replacement AC contactor
Foreign body jammed Remove foreign body to restore normal
Capacity malfunction Replacement indoor capacitor
Bad contact Make it good contact
Electronic Control Board malfunction Replacement electronic Control Board
Motor burned down Replacement fan motor
Only the indoor
fan motor cannot
work
Wire short-circuit Find out break point, and wiring
Indoor filter dirty Cleaning filters
Condenser dirty Cleaning the condenser
Lack of refrigerant Charge refrigerant
Refrigerant too much Discharge refrigerant to keep pressure nomal
cooling(heat)
ineffective
Room poor insulation effect Sealed the room
Without refrigerant Find out leakage point,vacuumization and charge refrigerant No cooling
(heating) effect Compressor does not start Find the reasons and make it return to normal
Indoor fan motor does not run Find the reasons and make it return to normal
Four-way valve malfunction Four-way valve replacement
Electronic Control Board malfunction Electronic Control Board replacement
Cooling mode
with hot wind
Four-way valve wire to the wrong line Replacement of sequence
Four-way valve malfunction Four-way valve replacement
Four-way valve burned down Four-way valve replacement
Electronic Control Board malfunction Electronic Control Board replacement
Heating mode
with chilled wind
(with additional
electrical heater)
Four-way valve wiring disconnect Find our the cause and repair
Water outlet pipe for without seal Do water seal
Water outlet pipe does not band or poorly
band
Re-bandaging
Refrigerant pipe exposed outside Bandaging exposed refrigerant pipe
Indoor unit loaded not horizontal Adjustment to be horizontal
Water pan broken Water pan replacement
Water pump malfunction Water pump replacement
Water leakage
Electronic control board malfunction, which
lead to water pump not work
Electronic control board replacement
Copper pipe shell collision Adjusted brass
Foot bolt not tight Tighten bolts foot
Indoor plane fan noise
friction with the chassis
Fan motor or chassis adjustment Abnormal noise
Loose screws, making noise Tighten screws

Error code table
Self- checking
information
LED
self-checking
code
Note Error causes and treatment methods
Defrosting tips
flashing 1
time/1 second
Turning on
display
(running lights)
1normal phenomenon, defrost state lifted, automatically resume to normal
state.
Tip-chill
flashing 1
time/3
seconds
Turning on
display
(running lights)
1, normal phenomenon (in the heating mode)
2, when the coil temperature up to 350 C, automatic discharge.
Room
temperature
sensor fault
flashing 2
times/4
seconds
Shutdown,
protect light
lighting,
running lights
flashing
1, check whether sensor resistance is normal (at normal temperature
resistance at 25
0
C for 5 k , with a multimeter measured in the temperature
change to see the changes in resistance), abnormal requires replacement.
2, check whether the plug-in is good contact with the circuit board.
3, when 1,2 items are normal, the sensor external components or integrated
circuits is damaged.Replacement of the electric control board.
Tube
temperature
sensor fault
flashing 3
times/5
seconds
Shutdown,
protect light
lighting,
running lights
1, check whether sensor resistance is normal (at normal temperature
resistance at 25
0
C for 5 k , with a multimeter measured in the temperature
change to see the changes in resistance), abnormal requires replacement.
2, check whether the plug-in is good contact with the circuit board.
flashing 3, when 1,2 items are normal, the sensor external components or integrated
circuits is damaged.Replacement of the electric control board.
Outdoor Unit
anomaly
flashing 4
times/6
seconds
Shutdown,
protect light
lighting,
running lights
flashing
1, check the compressor windings resistance and whether it is normal
running current.
2, inspection high and low pressure of the units is normal.
3, check whether defrosting circuit is abnormal, the resistance of
temperature sensor is normal.
4, inspection junction end and whether circuit board terminal plug contact
is good.
Indoor evaporator
frost protection
flashing 5
times/7
seconds
Shutdown,
protect light
lighting,
running lights
flashing
1, check whether it is the fan motor normal.
2, whether evaporators and filter is dirty or plugging phenomenon.
3, in heating mode, the four-way valve abnormally work.
Fault feedback
flashing 7
times/9
seconds
Shutdown,
protect light
lighting,
running lights
flashing
1, check the compressor windings resistance and whether it is normal
running current.
2, inspection high and low pressure of the units is normal.
3, inspect whether 3-phase power supply is normal, whether it is lack of
phase sequence.
4, inspection junction end and whether circuit board terminal plug contact
is good.
5, phase sequence checks, whether current detection circuit is fault.
Overheating
protection
flashing 8
times/10
seconds
Shutdown,
protect light
lighting,
running lights
flashing
1,fault effective in heating mode.
2, check whether the fan motor is normal (fan motor power supply,
winding, capacitor, etc.).
3, whether evaporators and filter are dirty or plugging phenomenon.
4, whether air inlet and outlet is short-circuit.
Pump Failure
flashing 9
times/11
seconds
Shutdown,
protect light
lighting,
running lights
flashing
1, inspect whether pump power supply is normal.
2, inspection junction end and whether circuit board terminal plug contact
is good.
3, check whether the water level switching performance is good.
4, whether drainage pump is normal.