ABB ROUTINE Page 1 of 9

TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Customer
ABB S.A. PERU
Customer reference
0601310055-1 DTD.19.07.2013
Breaker type Serial number
EDFSK1-1 700-14-703
Mechanism type Serial number
FSA 1(F) 700-14-703
Standard Test completed
IEC 62271-100 11/13/2013
We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred and with the terms of the contract.
ABB LTD.,
Circuit Breakers Division Tested by: PMR
Reviewed and Approved by
J asmin Desai
ABB ROUTINE Page 2 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Rated data at 20 Deg C
Rated filling pressure for operation at
20 Deg C
0.70 MPa(abs)
Check of rating plates : OK
MECHANISM RESULTS
Resistance in ohms of auxiliary circuits at 30C
Description Values
Closing coil 103
Opening coil 1 99
Opening coil 2 100
Antipumping relay 52280
Density blocking relay 51830
Heater R3 684
All resistances checked : OK
Check of Approved
Wiring acc. To circuit diagram OK
Local/remote operation OK
Counter OK
All adjustments and paint marking OK
Spring charge at nominal voltage
Description Unit Values
Charging time s 10.3
Motor current A 3.3
On-line motor starter does not trip for 10 consecutive operations. OK
Lowest operating voltage
Description Unit Values
Close coil 1 VDC 121
Trip coil 1 VDC 88
Trip coil 2 VDC 88
OK
Power frequency test of auxiliary ci rcuits
1 second 60 Hz 1.0 kV OK
ABB ROUTINE Page 3 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
POLE RESULTS
Resistance in main circuit
Phase Unit Values
A Ohm 33
B Ohm 33
C Ohm 33
OK
Power frequency test
60 seconds 60 Hz to earth: 140/140 kV OK
Overpressure test on each pole 1.05 MPa(abs) OK
Tightness test on each pole OK
OPERATING TEST
Test assumptions
Fill pressure at 20 Deg C 0.70 MPa(abs)
Operations Voltage
level
Motor
VDC
Close 1
VDC
Trip 1
VDC
Trip 2
VDC
5 Close and Open Min 187 187 154 154
5 Close and Open Max 242 242 242 242
5 Close and Open Nom 220 220 220 220
5 Close-Open Nom 220 220 220 220
5 Open-0.3s-Close Nom 220 220 220 220
Operating test
At least 25 operations as above OK
ABB ROUTINE Page 4 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Main Test sequence Close Nom.
Operati on data
Motor Close coil 1 Trip coil -
220 VDC 220 VDC -
Contact times in ms
Main Contact ti me Cl osed/Opened Closed/Opened
A1 51.9
B1 50.9
C1 50.8
Aux. Contact ti me Cl osed/Opened Closed/Opened Aux-Main
1a 56.5 4.6
1b 29.7 -22.2
Travel parameters
Description Unit T1
Travel speed 1 m/s 2.8
Contact Stroke mm 64.0
OverTravel mm 4.1
Rebounce mm 0.8
A1
B1
C1
1a
1b
Ic1
0
10
20
30
40
50
60
70
0
1
0 20 40 60 80 100 120 140
m
m
A
ms
ABB ROUTINE Page 5 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Main Test sequence Open Nom.
Operati on data
Motor Close coil - Trip coil 1
220 VDC - 220 VDC
Contact times in ms
Main Contact ti me Cl osed/Opened Closed/Opened
A1 27.4
B1 27.2
C1 27.3
Aux. Contact ti me Cl osed/Opened Closed/Opened Aux-Main
1a 22.3 -5.1
1b 36.5 9.1
Travel parameters
Description Unit T1
Travel speed 1 m/s 3.4
Contact Stroke mm 64.4
OverTravel mm 3.2
Rebounce mm 2.0
Damping time ms 10.7
T1
A1
B1
C1
1a
1b
Ic1
0
10
20
30
40
50
60
0
1
0 20 40 60 80 100 120 140
m
m
A
ms
ABB ROUTINE Page 6 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Main Test sequence Open Nom.
Operati on data
Motor Close coil - Trip coil 2
220 VDC - 220 VDC
Contact times in ms
Main Contact ti me Cl osed/Opened Closed/Opened
A1 27.0
B1 26.7
C1 26.7
Aux. Contact ti me Cl osed/Opened Closed/Opened Aux-Main
1a 21.7 -5.3
1b 36.0 9.0
Travel parameters
Description Unit T1
Travel speed 1 m/s 3.4
Contact Stroke mm 64.4
OverTravel mm 3.1
Rebounce mm 2.1
Damping time ms 10.8
T1
A1
B1
C1
1a
1b
Ic1
0
10
20
30
40
50
60
0
1
0 20 40 60 80 100 120 140
m
m
A
ms
ABB ROUTINE Page 7 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Main Test sequence Close-Open Nom.
Operati on data
Motor Close coil 1 Trip coil 1
220 VDC 220 VDC 220 VDC
Contact times in ms
Main Contact ti me Cl osed/Opened Closed/Opened
A1 51.7 31.8
B1 51.1 31.5
C1 51.0 32.4
Aux. Contact ti me Cl osed/Opened Closed/Opened Aux-Main
1a 56.5 22.3 4.8
1b 29.9 61.9 -21.8
T1
A1
B1
C1
1a
1b
Ic1
0
10
20
30
40
50
60
70
0
1
0 20 40 60 80 100 120 140 160 180 200 220 240
m
m
A
ms
ABB ROUTINE Page 8 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Main Test sequence Close-Open Nom.
Operati on data
Motor Close coil 1 Trip coil 2
220 VDC 220 VDC 220 VDC
Contact times in ms
Main Contact ti me Cl osed/Opened Closed/Opened
A1 51.6 31.9
B1 50.9 31.8
C1 50.9 32.4
Aux. Contact ti me Cl osed/Opened Closed/Opened Aux-Main
1a 56.1 22.3 4.5
1b 29.7 62.0 -21.9
T1
A1
B1
C1
1a
1b
Ic1
0
10
20
30
40
50
60
70
0
1
0 20 40 60 80 100 120 140 160 180 200 220 240
m
m
A
ms
ABB ROUTINE Page 9 of 9
TEST REPORT
Breaker EDFSK1-1 Order No: 5000023309/10
Mechanism: FSA 1(F) Serial No: 700-14-703
Main Test sequence Open-0.3s-Close Nom.
Operati on data
Motor Close coil 1 Trip coil 1
220 VDC 220 VDC 220 VDC
Contact times in ms
Main Contact ti me Cl osed/Opened Closed/Opened
A1 27.9 324.8
B1 27.6 323.5
C1 27.8 323.4
Aux. Contact ti me Cl osed/Opened Closed/Opened Aux-Main
1a 22.8 333.6 -5.1
1b 36.9 292.7 9.0
T1
A1
B1
C1
1a
1b
Ic1
0
10
20
30
40
50
60
70
0
1
0 50 100 150 200 250 300 350 400
m
m
A
ms