You are on page 1of 35

DOCUMENT CONTROL NUMBER /

2004 Tyco Safety Products PAGE 1 of 35


MX
17A-05-O
5 11/04
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
MX ADDRESSABLE FIRE CONTROLLERS
OPERATING INSTRUCTIONS
LIST OF CONTENTS
1. INTRODUCTION 5
1.1 KEY FUNCTIONS AND FEATURES 5
2. OPERATING INSTRUCTIONS 6
2.1 OPERATORS INDICATORS
AND CONTROLS 6
2.1.1 GENERAL 6
2.1.2 OPERATOR DISPLAY
MODULE 6
2.1.3 OPERATOR CONTROL
MODULE 9
2.1.4 DCM800 DISPLAY CONTROL
MODULE 9
2.2 LCD DISPLAY 11
2.2.1 FIRE WINDOW 11
2.2.2 STATUS WINDOW 11
2.2.3 MAIN WINDOW 11
2.2.4 SOFTKEY WINDOW 11
2.3 NORMAL OPERATION 12
2.3.1 EVENT MONITORING 12
2.3.2 EVENT DISPLAY 12
2.4 OPERATION IN ALARM 12
2.4.1 SYSTEM RESPONSE 12
2.4.2 SOUNDER SILENCING 13
2.4.3 RESETTING THE CONTROLLER 14
2.4.4 MULTIPLE EVENTS 14
2.4.5 PRE-ALARM WARNINGS 14
2.5 OPERATION IN FAULT CONDITION 14
2.5.1 SYSTEM RESPONSE 14
2.5.2 OPERATOR ACTION 14
2.6 FIRE CONTROL KEYS 15
2.6.1 EVACUATE or FIRE ALARM 15
2.6.2 DAY/NIGHT MODE 15
2.6.3 TEST 15
2.7 AUXILIARY DISPLAY DEVICES 15
2.7.1 GENERAL 15
2.7.2 REPEATERS 16
2.7.3 PRINTERS 16
3. CONTROLLER FUNCTIONS 16
3.1 ACCESS LEVELS 16
3.1.1 GENERAL 16
3.2 ENTERING PASSCODES 17
3.3 VALID VALUES 17
3.4 MAIN MENU 18
3.5 ACCEPT EVENTS 18
3.6 VIEW STATUS 18
3.7 ISOLATE/DE-ISOLATE 20
3.8 TIME/DATE 21
3.8.1 SET TIME/DATE 21
3.8.2 SUMMER/WINTER 21
3.9 EVENT LOG 21
3.9.1 VIEW EVENT LOG 22
3.9.2 PRINT EVENT LOG 22
3.9.3 FILTER 22
3.10 VIEW/PRINT STATUS 23
3.10.1VIEW/PRINT POINTS
ISOLATED 23
3.10.2VIEW/PRINT POINTS
UNTESTED/FAILED 23
3.10.3VIEW/PRINT POINT VALUES 23
3.10.4VIEW FAULTS 24
3.10.5VIEW LOOP POINT COUNTERS 24
3.11 SERVICE 25
3.11.1WALK TEST 26
3.11.2MAINTENANCE 28
3.11.3CONFIGURATION 29
4. ROUTINE CHECKS 34
4.1 GENERAL 34
4.2 DAILY CHECKS 34
4.3 WEEKLY CHECKS 34
MX
17A-05-O
5 11/04
PAGE 2 of 35
This page intentionally left blank
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 3 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
F
I
R
E
I
0
S
I
L
E
N
C
E
B
U
Z
Z
E
R
R
E
S
E
T
E
V
A
C
U
A
T
E
S
I
L
E
N
C
E
/
R
E
S
O
U
N
D
D
I
S
A
B
L
E
D
F
A
U
L
T
A
C
T
I
V
A
T
E
D
D
A
Y
M
O
D
E
P
R
E
A
L
A
R
M
D
I
S
A
B
L
E
D
F
A
U
L
T
A
C
T
I
V
A
T
E
D
S
Y
S
T
E
M
F
A
U
L
T
M
A
I
N
S
F
A
U
L
T
P
O
W
E
R
O
N
F
A
U
L
T
D
I
S
A
B
L
E
D
T
E
S
T
G
E
N
E
R
A
L
M
I
S
C
E
L
L
A
N
E
O
U
S
S
O
U
N
D
E
R
S
C
O
N
T
R
O
L
L
E
R
S
I
G
N
A
L
L
I
N
G
D
A
Y
N
I
G
H
T
I
N
V
E
S
T
I
G
A
T
E
D
E
L
A
Y
P
O
W
E
R
F
A
U
L
T
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
L
a
s
t
F
i
r
e
0
0
2
G
e
n
e
r
a
l
Z
o
n
e
0
3
0
B
0
5
5
4
t
h
F
l
o
o
r
W
a
s
h
r
o
o
m
/
W
i
n
d
o
w
F
1
F
2
F
3
F
4
F
5
L
E
D
T
s
t
M
o
r
e
Z
o
n
e
0
0
2
B
0
0
2
1
s
t
F
l
o
o
r
C
o
r
r
i
d
o
o
r
R
o
o
m
1
1
7
F
i
r
s
t
F
i
r
e
I
n
f
o
r
m
a
t
i
o
n
Fig. 1 MINERVA MX Fire Controller - Front Panel
T2000 ONLY
MX
17A-05-O
5 11/04
PAGE 4 of 35
3
DEF
7
PQRS
F5 F4 F3 F2 F1
1
*
2
ABC
6
MNO
9
WXYZ
0
8
TUV
5
JKL
4
GHI
FIRE
FAULT
DISABLED
TEST
PRE ALARM
DAY MODE
ACTIVATED
FAULT
DISABLED
ACTIVATED
FAULT
DISABLED STATUS 1
STATUS 2
GENERAL SOUNDERS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
I
0
POWER ON
MAINS FAULT
SYSTEM FAULT
40 60
59
SILENCE
BUZZER
RESET
INVESTIGATE
DELAY
FUNCTION EVACUATE
SILENCE
RESOUND
DAY
NIGHT
GENERAL SYSTEM SOUNDERS SIGNALLING CONTROLLER
ZONE DISPLAY
1 - Accept Events
2 - Actual Status
3 - (De-) Isolate
4 - Time / Date
5 - Event Log
6 - View/Prn Status
7 - Service
9 - Test Buzzer,
LED's Display
Alarm Count: 0021
SYSTEM
Wed, 01-Mar-00
14:15
Company Name
General
Back
0000
Main menu
SounSIL
Fig. 2 MX2 Fire Controller - Front Cover
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 5 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
1. INTRODUCTION
The instructions given in this document are common to all
the MX range of fire controllers, any differences being
outlined as appropriate This document is written for
Firmware Version 5.0.
The MINERVA MX range, form a comprehensive and
compatible range of modular and flexible EN54 approved
(the MX2 and MX Black Box Panel are additional MX
compatible units which are fully EN54 : Part. 2 and Part. 4
compliant) addressable fire controllers using Tyco MX
Technology
TM
.
Standard MINERVA MX fire controllers include:
MX1000 250 point, 40/80/120/160/200 or
240 zone network capable fire controller 1
loop controller in compact designer housing.
MX4000 1000 point, 40/80/120/160/200
or 240 zone network capable fire controller -
2 to 4 loop controller in compact designer
housing.
MX4000M 1000 point, 40/80/120/160/200
or 240 zone network capable fire controller
2 to 4 loop controller in modular rack style
housing.
T2000 1000 point, 40/80/120/160/200 or
240 zone network capable fire controller - 2
to 4 loop controller in Marine approved
compact housing.
MXR Fully functional repeater in compact
designer housing.
T2000 Marine Full Function Repeater.
MX2-100 - 250 point, 40/80/160/200 or 240
zone network capable fire C.I.E. 1 loop
C.I.E. in housing with integral backup
batteries.
MX2-200 - 1000 point, 40/80/160/200 or
240 zone network capable fire C.I.E. - 2 to 4
loop C.I.E. in housing with integral backup
batteries.
All variants fully comply with the requirements of EN54
parts 2 and 4 and may be installed in a system which
complies with the requirements of BS 5839 : Part 1
(2002). The Marine versions also comply with the
requirements of S.O.L.A.S. and marine Classification
Societies.
1.1 KEY FUNCTIONS AND FEATURES
All MINERVA MX controllers are built around common
hardware and software modules incorporating the following
common functions and features:
An integral 110-250V ac battery backed
power supply providing 24V dc (nominal) at
up to 5A (alarm load) for powering
conventional detection zone interfaces
(DIM800), conventional sounders and
beacons, door release mechanisms and
interface relays and remote full function
repeaters.
Power supply incorporates a 24V DC
charger capable of charging up to 38Ah
batteries to provide up to 72 hours backup
and 30 minutes in alarm (BS 5839 : Part 1)
or 90 hours backup and 15 minutes in alarm.
Full EN54 compliant control switches and
indicators with keyswitch enable and
optional programmable LED indicators and
control switches.
Large backlit 16 line x 40 character LCD
display with detailed and precise
identification of all sectors, zones and
points, comprehensive 95 character
emergency procedure instructions and full
system status indication including counters
of number of points in alarm, fault, disabled
and test mode.
Extensive menu driven and password
controlled operator and engineer functions
including extensive isolate, override, test,
service and diagnostic functions.
System manager and engineer functions
including editing of point descriptions and
viewing/printing of point values including
CO levels, temperatures and detector
obscuration levels.
Optional self-test and verification of
detectors from the controller.
Peer-to-peer communication with up to 98
other controllers providing a seamless
operator interface to all other relevant
defined controllers on the network.
Event log for logging of up to 3000 events
which can be viewed, selected and printed.
Constant monitoring of all detectors and
input circuits and processing of detector
sensor information using standard, CCO and
FastLogic fuzzy logic algorithms.
Long term averaging and condition
monitoring of smoke detectors with dirty
detector identification.
Automatic or manual switching of detector
modes and sensitivities according to changes
in occupancy patterns (day mode) and
variations in fire risk.
Constant fault monitoring of all hardware
components, power supplies, batteries,
relays, sounder and speaker circuits,
addressable loops, detectors and addressable
devices, monitored input circuits, remote
and local communication links.
MX
17A-05-O
5 11/04
PAGE 6 of 35
Communication with up to 250 addresses on
up to 4 detection loops per controller and a
combination of up to 1500 auxiliary I/O,
controller plus 7 full function repeaters and
multiple remote printers.
Signalling, supervision, status and fault
indication of central station alarm signalling
equipment such as BT Redcare STU.
Option for one repeater to be provided from a
remote PC computer using MX-Remote
service and diagnostics software over the
public switched telephone network (PSTN).
Default cause and effect providing computer
control of all outputs, sounders, beacons and
speakers in the event of alarm conditions.
Powerful programmable cause and effect
using the flexible and easily configured
MINERVA group based event/action
programming language.
Synchronisation and multiple output pulse
patterns for phased evacuation of up to 240
zones using Bell Mapping.
Arrangement of points in up to 240 detection
zones per controller.
2. OPERATING INSTRUCTIONS
2.1 OPERATORS INDICATORS
AND CONTROLS
2.1.1 GENERAL
ALL operator controls and indicators are mounted on the front
panel. For the MX/T2000, these are provided by the Operator
Display Module (ODM800 - top module) and the Operator
Control Module (OCM800 - bottom module). The ODM
contains the alphanumeric LCD display, keypad and
Softkeys. The OCM contains the ENABLE KEY,
indicator LEDs and control keys.
For MX2 systems all operator controls and indicators except
the ENABLE KEY are provided by the Display Control
Module (DCM800). The ENABLE KEY is provided
separately at the bottom of the front panel.
2.1.2 OPERATOR DISPLAY MODULE
The Operator Display Module (Fig. 3) contains the following
indicators and controls:
A 640 character backlit LCD alphanumeric
display, arranged in 16 rows of 40 characters.
This is used to display information about the
system status and alarms. The backlight is on
when the keyswitch is set to the enable
position, when a key is pressed or when an
Alarm or Fault is present.
Switches F1 to F5 - used to carry out the
functions displayed on the bottom line of
the LCD display.
An alphanumeric keypad used for entering
access codes, text strings or general
information as follows:
SCROLL UP and SCROLL DOWN keys -
used to scroll through a display or log one
entry at a time. These keys will auto-repeat
if held down, ie, will scroll continuously.
When used in conjunction with the
Configuration menu, the UP key switches
to upper case and the DOWN key to lower
case.
7
PQRS
8
TUV
9
WXYZ
6
MNO
5
JKL
4
GHI
3
DEF
2
ABC
0
1
Used to enter the number 0
Used to enter the number 1 or special
symbols
Used to enter the number 2 or letters A,
B or C
Used to enter the number 3 or letters D,
E or F
Used to enter the number 4 or letters G,
H or I
Used to enter the number 5 or letters J,
K or L
Used to enter the number 6 or letters M,
N or O
Used to enter the number 7 or letters P,
Q, R or S
Used to enter the number 8 or letters T,
U or V
Used to enter the number 9 or letters W,
X, Y or Z
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 7 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
F
i
r
s
t
F
i
r
e
L
a
s
t
F
i
r
e
0
0
2
G
e
n
e
r
a
l
Z
o
n
e
0
0
2
B
0
0
2
1
s
t
F
l
o
o
r
C
o
r
r
i
d
o
o
r
R
o
o
m
1
1
7
Z
o
n
e
0
3
0
B
0
5
5
4
t
h
F
l
o
o
r
W
a
s
h
r
o
o
m
/
W
i
n
d
o
w
F
1
F
2
F
3
F
4
F
5
L
E
D
T
s
t
M
o
r
e
I
n
f
o
r
m
a
t
i
o
n
Fig. 3 MX/T2000 - Operator Display Module
S
O
F
T
K
E
Y
S
S
C
R
O
L
L

U
P
S
C
R
O
L
L

D
O
W
N
A
L
P
H
A
N
U
M
E
R
I
C

K
E
Y
P
A
D
MX
17A-05-O
5 11/04
PAGE 8 of 35
3
DEF
7
PQRS
F5 F4 F3 F2 F1
1
*
2
ABC
6
MNO
9
WXYZ
0
8
TUV
5
JKL
4
GHI
FIRE
FAULT
DISABLED
TEST
PRE ALARM
DAY MODE
ACTIVATED
FAULT
DISABLED
ACTIVATED
FAULT
DISABLED
STATUS 1
STATUS 2
GENERAL SOUNDERS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
I
0
POWER ON
MAINS FAULT
SYSTEM FAULT
40 60
59
SILENCE
BUZZER
RESET
INVESTIGATE
DELAY
FUNCTION EVACUATE
SILENCE
RESOUND
DAY
NIGHT
GENERAL
SYSTEM SOUNDERS SIGNALLING CONTROLLER
ZONE DISPLAY
ALPHANUMERIC
KEYPAD
SCROLL
UP
SCROLL
DOWN
SOFTKEYS
1 - Accept Events
2 - Actual Status
3 - (De-) Isolate
4 - Time / Date
5 - Event Log
6 - View/Prn Status
7 - Service
9 - Test Buzzer,
LED's Display
Alarm Count: 0021
SYSTEM
Wed, 01-Mar-00
14:15
Company Name
General
Back
Main menu
Fig. 4 MX2 - Display Control Module
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 9 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
2.1.3 OPERATOR CONTROL MODULE
The Operator Control Module (Fig. 5) contains the
following indicators and controls:
INDICATORS
GENERAL
2 red General ALARM LEDs.
A yellow General Fault LED.
A yellow General Disablement LED.
A yellow General Test LED.
MISCELLANEOUS
A red Pre-Alarm LED.
A yellow LED to indicate Day Mode.
A yellow LED to indicate customer defined
functions eg, Delay.
A yellow LED to indicate customer defined
functions eg, Fire Doors.
SIGNALLING
A red Signalling Activated LED.
A yellow Signalling Fault LED.
A yellow Signalling Disabled LED.
SOUNDER
A red Sounders Activated LED.
A yellow Sounder Fault LED.
A yellow Sounders Disabled LED.
CONTROLLER
A green Power ON LED.
A yellow Charger Fault LED.
A yellow Processor Fault LED.
A yellow Power Fault LED indicates loss of
mains and back up power (T2000 only).
CONTROLS
ENABLE keyswitch - a two position
keyswitch, with positions normal (0) and
enable (1).
Seven control switches:
SILENCE BUZZER - used to silence
the internal buzzer.
SILENCE/RESOUND - used to silence/
resound external sounders.
EVACUATE (FIRE ALARM T2000) -
used to activate external sounders.
RESET - used to reset the system after
an alarm or event has occurred.
DAY MODE - used to set the system
into the daytime operation mode.
INVESTIGATE DELAY - is used to
end signalling delay time and start the
investigation time.
SPARE - is configurable to customer
requirements.
2.1.4 DCM800 DISPLAY CONTROL
MODULE
The DCM800 (Fig. 4) is used on the MX2 variants to
provide all the functions of the OCM800 and ODM800 as
used in the MX and T2000 variants.
Indicators and controls are defined as for the ODM800 and
OCM800 modules in Section 2.1.2 and 2.1.3. The
DCM800 includes all indicators and controls listed in these
two sections except for the SPARE - FUNCTION KEY
from the ODM800.
MX
17A-05-O
5 11/04
PAGE 10 of 35
F
I
R
E
I
0
S
I
L
E
N
C
E
B
U
Z
Z
E
R
R
E
S
E
T
E
V
A
C
U
A
T
E
S
I
L
E
N
C
E
/
R
E
S
O
U
N
D
D
I
S
A
B
L
E
D
F
A
U
L
T
A
C
T
I
V
A
T
E
D
D
A
Y
M
O
D
E
P
R
E
A
L
A
R
M
D
I
S
A
B
L
E
D
F
A
U
L
T
A
C
T
I
V
A
T
E
D
S
Y
S
T
E
M
F
A
U
L
T
M
A
I
N
S
F
A
U
L
T
P
O
W
E
R
O
N
F
A
U
L
T
D
I
S
A
B
L
E
D
T
E
S
T
G
E
N
E
R
A
L
M
I
S
C
E
L
L
A
N
E
O
U
S
S
O
U
N
D
E
R
S
C
O
N
T
R
O
L
L
E
R
S
I
G
N
A
L
L
I
N
G
D
A
Y
N
I
G
H
T
I
N
V
E
S
T
I
G
A
T
E
D
E
L
A
Y
E
N
A
B
L
E
K
E
Y
S
W
I
T
C
H
C
O
N
T
R
O
L
S
W
I
T
C
H
E
S
T
2
0
0
0
O
N
L
Y
(
P
O
W
E
R
F
A
U
L
T
)
T
2
0
0
0
O
N
L
Y
(
F
I
R
E
A
L
A
R
M
)
Fig. 5 MX/T2000 - Operator Control Module
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 11 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
2.2 LCD DISPLAY
The LCD display is divided into four windows as shown in Fig. 6:
Fire 19 characters x 8 lines
Main 19 characters x 14 lines
Status 19 characters x 5 lines
Softkeys F1, F2, F4 and F5 - 7 characters, F3 - 8 characters
1234567890123456789 1234567890123456789 1
2
3 Main
4 Window
5
6
7
8
9
0
1
2
3
4
1
2
3 Fire
4 Window
5
6
7
8
1
2 Status
3 Window
4
5
S'key 1 S'key 2 S'key 3 S'key 4 S'key 5
Fig. 6
2.2.1 FIRE WINDOW
The fire window in the quiescent mode will display the
product name, date/time and company name.
On detection of an Alarm condition, the fire window will
display First Fire and associated information. For
multiple alarms in the system the fire window will display
the first and last alarms.
The number of alarms is displayed at the right hand side of
line 5 in the fire window.
First Fire
Zone 002 B001
1st Floor Corridoor
Room 117
Last Fire 002
Zone 030 B055
4th Floor
Washroom / Window
2.2.2 STATUS WINDOW
The status window displays the number of faults, isolates
etc.
2.2.3 MAIN WINDOW
The main window displays logs, information text, menus
and device identification.
2.2.4 SOFTKEY WINDOW
The softkey windows change dependant on the option
selected.
MX
17A-05-O
5 11/04
PAGE 12 of 35
2.3 NORMAL OPERATION
When the controller is initially powered up, with no faults or
alarms in the system and the Enable key in the off
position, the following screen is displayed:
2.3.1 EVENT MONITORING
The term event is used to describe a change in system
status that must be acknowledged and/or generates an
output.
Examples of events include:
Mains failure
Detection of a fire condition
Operation of EVACUATE/FIRE ALARM
key
All events trigger a response, the category of which depends
on the event type and will be one of the following (in
priority order):
Full Alarm or Alert
Pre-Alarm
Fault
Isolation
Test Mode
Warning
Information
When an event occurs, it is stored in the event log. The
contents of this log may be displayed in two formats:
Unaccepted and locally accepted events
All events in chronological order of
occurrence
The events are st ored in chronol ogical order wit h
unaccepted events marked as outstanding. The event log
may hold up to 3000 events; in the unlikely occurrence of
the log filling up, the oldest record will be overwritten.
MX Panel
Fri, 17-Mar-00
11:57
Company Name
General
LED Tst Light
2.3.2 EVENT DISPLAY
The display automatically shows the last event of the
category with the highest priority. With Scroll keys, it is
possible to get all events in this category in chronological
order. With Softkey F5 the user can change to another
category (if available).
Important: Category Full Alarm/Alert shows only the first
point of a zone in alarm. If two points of one zone are in
alarm, only the first one which was in alarm will be
displayed. The second alarm can only be accessed via the
menu option View Event Log.
2.4 OPERATION IN ALARM
2.4.1 SYSTEM RESPONSE
When a fire condition is detected, the system responds as
follows:
1) The internal buzzer will sound in a
continuous tone.
2) Both red FIRE LEDs will light.
3) The SOUNDERS and NOTIFICATION
STATUS ACTIVATED red LEDs will
light.
Note: If the alarm is initiated by a detector, there may
be a delay of from 1 to 10 minutes before the
NOTIFICATION STATUS ACTIVATED led
lights. This is to allow time for the alarm to be
investigated and any relevant action taken
before signalling is initiated. A Callpoint set to
evacuate will initiate signalling
immediately. Refer to Section 2.6.3.
4) For the MX controllers, the sounders and
any other configured outputs will be
activated.
5) The LCD will display a message in the
format:
First Fire
Zone 002 B002
1st Floor Corridoor
Room 117
General
Menu
First Fire
Passcode More
001
Information
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 13 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
6) For a T2000 controller, the sounders and any
ot her conf i gur e d out put s wi l l be
activated. If the alarm is not accepted
within the programmed delay period by
pressing the INVESTIGATE DELAY key,
all other sounder outputs will be activated.
The message format is as follows:
Under FIRE:
The top line shows the Zone and Point number of the
device in alarm.
The second line shows the zone description (defined at
configuration).
The third line shows the point description (defined at
configuration).
The fourth line shows the type of alarm.
If no information text is shown:
The fifth line shows date and time.
The sixth line shows the device type.
The seventh line shows the actual CURRENT
temperature (if heat sensor).
Note: The above is only displayed if Extended Alarm
Information has been selected at
configuration.
Under First Fire:
The first three lines from FIRE are
repeated.
The number of alarms is displayed on the
black bar underneath the first fire
information.
2.4.2 SOUNDER SILENCING
When a FIRE ALARM is received, investigate the cause of
the alarm.
WARNING:
WHEN SEARCHING AN AREA FOR THE
SOURCE OF A FIRE ALARM SIGNAL,
WHERE A FIRE ALARM HAS BEEN
INITIATED BY A CARBON MONOXIDE
FIRE DETECTOR, IT MUST BE
REMEMBERED THAT A CARBON
MONOXIDE FIRE DETECTOR MAY
GENERATE AN ALARM BEFORE OTHER
FIRE INDICATORS (SUCH AS SMOKE) ARE
PRESENT.
THIS OCCURS MOST NOTABLY IN DEEP
SEATED FIRES IN DENSELY PACKED
MATERIALS, AREAS WHERE FIRES MAY
OCCUR IN CUPBOARDS AND
STOREROOMS REMOTE FROM
DETECTORS AND WHERE SMOKE
IMPERVIOUS BARRIERS EXIST BETWEEN
THE SEAT OF THE FIRE AND THE
DETECTOR (SUCH AS WITHIN WALL
CAVITIES). THESE FACTORS SHOULD BE
CONSIDERED CAREFULLY BEFORE
DECLARING SAFE ANY AREA WHERE A
CARBON MONOXIDE FIRE DETECTOR
HAS RAISED AN ALARM.
Once the cause of the alarm has been determined and all
appropriate action has been taken, silence the sounders as
follows:
a) Insert the key into the front panel keyswitch
and turn it clockwise to the enable
position.
b) Press SILENCE/RESOUND.
The system will respond as follows:
i) The sounders will be silenced.
ii) The SOUNDER ACTIVATED LED will
extinguish.
iii) All other outputs will remain activated.
iv) The LCD display will remain showing the
t ype of a l a r m a nd t he f ul l z one
identification. The GENERAL display
window will show Sounder SIL.
If it is required to manually resound the sounders, pressing
the SILENCE/RESOUND key will reactivate the
sounders.
MX
17A-05-O
5 11/04
PAGE 14 of 35
2.4.3 RESETTING THE CONTROLLER
Note:
1) When the system is in a Fire Alarm state,
Silence must be operated before Reset is
possible. This interlock is always present
under Fire Alarm condition, even if all sounders
are isolated.
2) The controller should also NOT be reset until
the source of the alarm has been determined
by the Fire Brigade or the cause otherwise
found (and the condition removed).
Once the notes above have been observed, press the
RESET key. The display will show the following message:
Reset
in
Progress...
*
When the count reaches 0 after 17 to 20 seconds, the LCD
will return to the normal display (Section 2.3) if no faults or
other events are present.
2.4.4 MULTIPLE EVENTS
If, when in alarm condition, a second alarm (of another
zone) is received, the system response is dependent on the
nature and source of the second alarm as follows:
a) If the sounders have NOT been silenced, the
following will occur:
i) The internal buzzer will continue to sound
without interruption.
ii) The LCD will continue to display the
alarm message for the FIRST fire alarm
and also the last fire alarm.
iii) The alarm count will be incremented.
2.4.5 PRE-ALARM WARNINGS
If the LCD shows a message including a warning
indication, a pre-alarm condition has been detected by the
controller. This may be indicated for example, if a detector
identifies a build-up of smoke or heat that might result from
a fire, but the alarm threshold has not yet been reached. The
internal buzzer will sound but the sounders and visual fire
indicators will remain inactive at this stage. Proceed as
follows:
a) Accept the event, (if the option is available),
noting the location of the event.
b) Initiate action to deal with the condition
indicated, taking care to determine if the
warning was initiated by a fire condition or
by a system fault.
If the detector subsequently shows an alarm condition, an
alarm will be generated, regardless of whether the pre-
alarm warning was accepted.
2.5 OPERATION IN FAULT CONDITION
2.5.1 SYSTEM RESPONSE
When a Fault condition is detected, the system will respond
as follows:
a) The internal buzzer will pulse.
b) The yellow GENERAL FAULT LED will
light.
c) The LCD backlight will come on and will
display the following type of screen:
The message format is as follows:
The top line shows the Zone and point
number in fault condition.
The second line shows the zone description
(defined in configuration).
The third line shows the point description
(defined in configuration).
The fourth line shows the type of fault.
If no information text is shown:
The fifth line shows the date and time.
the sixth line shows the device type.
The message will continue to be displayed until the
intervention of an operator or the fault is cleared.
2.5.2 OPERATOR ACTION
When a Fault condition occurs, proceed as follows:
a) Press the SILENCE BUZZER key.
The internal buzzer will silence, but the
LED and display will continue to operate as
described.
Zone 000 R10
System Zone
Battery Fault IP
BATTERY FAULT
17-Mar-00 15:00:00
Digital Input
MX Panel
Fri, 17-Mar-00
15:00
Company Name
Flt P 002
General
LED Tst
FAULT
Info More
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 15 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
b) Investigate the source of the fault and where
possible remove.
Note: If the fault cannot be cured, contact your local
supplier and arrange for a service visit.
The fault information will be displayed until the fault is
cleared.
2.6 FIRE CONTROL KEYS
There are six fire control keys on the Operator Control Module
(or Display Control Module for MX2), namely:
SILENCE BUZZER
SILENCE/RESOUND
RESET
DAY MODE
INVESTIGATE DELAY
EVACUATE (FIRE ALARM for Marine)
Only the SILENCE BUZZER key is active without the
Enable key being inserted and turned to the Enabled
position.
The functions of SILENCE BUZZER, SILENCE/
RESOUND and RESET have already been described. The
functions of EVACUATE or FIRE ALARM,
INVESTIGATE DELAY and DAY MODE are described in
the following paragraphs.
2.6.1 EVACUATE or FIRE ALARM
Once enabled by the keyswitch, pressing EVACUATE or
FIRE ALARM will cause the following:
a) The internal buzzer will sound continuously.
b) The red FIRE LEDs will light.
c) The sounders and any other configured outputs
are activated.
d) The LCD will display the following type of
screen:
First Fire
Zone 000 RB002R12
System Zone
Evacuate Button
General
Menu
F I R E
First Fire
Information
Not Available
Info Passcode Level >
001
2.6.2 DAY/NIGHT MODE
In night mode the system activates immediately when an
alarm is received, the internal buzzer, all sounders and
alarm signalling outputs operate.
In day mode, on receipt of an alarm, only the internal
buzzer and sounders are activated immediately. A delay
time is started (default 60 seconds) in which the alarm
message must be acknowledged (Investigate delay
switch) to start the investigation time. If there is no
acknowledgement within this time, the alarm signalling
outputs will be activated.
The investigation time (default 10 minutes) is the time
remaining for staff to carry out investigation of the alarm
source, before the alarm signalling outputs will be
activated.
An evacuate callpoint will initiate an immediate alarm.
Signalling is always immediate if sounder faults exist in
the system.
2.6.3 INVESTIGATE DELAY
The INVESTIGATE DELAY switch is only active when
the controller is in the DAY MODE of operation. If a
Fire Alert is received at the controller, the signalling output
is delayed for 1 minute, if the Investigate Delay switch is
pressed during this period a further delay (configurable
between 1 and 10 minutes) is initiated. This delay allows
for the alarm to be investigated, if it is a false alarm, the
cause of the alarm can be removed and the controller to be
silenced and reset. If the alarm is real, then pressing the
EVACUATE/FIRE ALARM, switch will cause the
signalling output to activate.
2.6.4 TEST
Pressing LED TEST causes all the LEDs and internal
buzzer to operate for a few seconds. If the system includes
a repeater panel, only the panel that is operated is activated.
2.7 AUXILIARY DISPLAY DEVICES
2.7.1 GENERAL
Depending on the configuration of the system, there may
be one or more auxiliary display devices fitted. These
devices may be of the following types:
Repeaters
Printers
The functions of and operating instructions for these
devices are given in the following paragraphs.
MX
17A-05-O
5 11/04
PAGE 16 of 35
2.7.2 REPEATERS
A repeater allows the controller to be operated from a
remote location and provides remote indications of the
state of the controller. The front panel of the repeater is
identical to that of the controller (see Fig. 1) and all
controller operations may be performed at the repeater
panel.
2.7.3 PRINTERS
Refer to the manual supplied with the printer for operating
instructions.
2.7.3.1 LCD REPEATERS
LCD Repeaters can:
Display the alarm and fault messages as
displayed on the Controller on a backlit 4 x
20-character alphanumeric display.
Provide an internal log for up to 150 events.
Provide an internal audible warning of an
event.
Allow the event log to be displayed using
the scroll keys.
Silence the internal buzzer and external
sounder (if fitted) with the key.
3. CONTROLLER FUNCTIONS
As stated, the MX controller has built-in functions. These
functions allow the operator to perform such actions as
viewing the event log, setting the date and time, etc. The
functions are arranged according to sophistication and
access to certain of them necessarily needs to be restricted
to trained staff.
The control of access has been achieved by assigning
functions to Access Levels, each Access Level having an
associ ated numeric passcode. The passcode for a
particular Access Level is defined at system configuration.
MUTE
3.1 ACCESS LEVELS
3.1.1 GENERAL
The access levels available are as follows:
Customer Operator 1 to 7 - 4 digits
Customer Manager 1 - 5 digits
Customer Manager 2 - 6 digits
These access levels are described in the following
paragraphs. A maximum of 99 Passcodes are available
which may be split between Access Levels as required.
Note: The Customer Operator 1 Access Level is
achieved by turning the ENABLE key to the
enable position (ie, a Passcode is not
required).
Table 1 contains Access Levels and Menu Options
available at each level.
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 17 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
Enable
Key
Page
No.
Customer Operator
Customer
Manager
1 2 3 4 5 6 7 1 2
Lamp/Buzzer/LCD Test OFF
Unrestored Events OFF
Information Text OFF
View Events (Scrolling) OFF
MAIN MENU ON 18
Accept Events ON 18
View Status ON 18
Isolate/De-Isolate ON 20
Time/Date ON 21
Set time/Date ON 21
Summer/Winter ON 21
Event log ON 21
View Event Log ON 22
Print Event Log ON 22
Filter ON 22
View/print status ON 23
Points Isolated ON 23
Points Untested/Failed ON 23
Point Values ON 23
View Faults ON 24
Loop Point Counter ON 24
Service ON 25
Walk Test ON 26
Maintenance engineer ON 28
Fire Alarm Cycle Count ON 28
Maintenance Request ON 28
Battery Test ON 28
Software Initialisation Count ON 29
Project Numbers ON 29
Software Versions ON 29
Menu Points ON 29
Configuration ON 29
Change Text ON 30
Table. 1 Menu Options and Access Levels
3.2 ENTERING PASSCODES
In order to avoid repetition, however, the general procedure
for entering a PASSCODE is described as follows:
i) Turn the ENABLE key to the ON
position, press F3 (Passcode), enter your
ID (press F5 Enter if the ID has only one
digit).
3.3 VALID VALUES
The following are values which may be entered for each
option:
* depending on the configuration 40/80/120/160/200 or
240 zones.
Panel Number 1 - 99
Zone Number 1 -
240*
Sector Number 1 - 240
RBus Number 0 - 15
Real Point
Pseudo Point
XBus Point
1 - 24
1 - 8
1 - 96
Local I/O
Real Point
Pseudo Point
IOBus point
Timer Point
User Point
1 - 18
1 - 42
1 - 24
1 - 10
1 - 10
MX
17A-05-O
5 11/04
PAGE 18 of 35
3.4 MAIN MENU
When the system is in quiescent mode (ie, displaying the
date and time), entering a passcode affords the user access
to the main menu. The structure of this menu is shown
below.
The menu shown is for Customer Manager 2 level. Only the
options appropriate to the access level entered will be
displayed.
Each of the options available leads to further menus or
functions, which are described in the following paragraphs.
3.5 ACCEPT EVENTS
Allows displayed events to be accepted. Press 1 from the
maine menu, the following type of screen will be displayed:
Use the F4 Key << and F5 key >> keys to move between
events. Usr F3 Accept to accept an event.
3.6 VIEW STATUS
Allows the status of all points and zones on the system to be
viewed. Press 2 from the Main menu, the following type of
screen will be displayed:
1 - Accept Events
2 - View Status
3 - Isolate/De-Isol
4 - Time / Date
5 - Event Log
6 - View/Print Data
7 - Service
8 - Configuration
9 - Test Buzzer,
LEDs & Display
Alarm Count: 0021
MX Panel
Wed, 01-Aug-00
00:01
Company Name
General
Back
Main menu
Zone 000 R10
System Zone
Battery Fault IP
BATTERY FAULT
01-Mar-00 14:15:02
Digital Input
SYSTEM
Wed, 01-Mar-00
14:15
Company Name
Fault 02
General
Back
Accept Events
1000
Accept >> <<
Point - allows the status of any points on the system (both
inputs and outputs) to be checked.
Point I/P only - allows the status of only input devices to be
checked (eg, detectors).
Point O/P only- allows the status of only output devices to be
checked (eg, sounders, functional bases, etc.).
Zone - allows the total status of all points in a specified zone
to be checked.
Select the required number from the View Status menu, the
following type of screen will be displayed:
Select the type of Point or Zone:
1) Loop Point (Addressable Loop).
2) RBus Point.
3) Local I/O Point.
The following type of screen will be displayed:
Note: If the panel is in a networked system, the panel
number will be shown as in the following
example.
1 - Point
2 - Point I/P only
3 - Point O/P only
4 - Zone
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
View Status
Point
1 - Loop Point
2 - RBus Point
3 - Local I/O Point
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
View Status
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 19 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
Loop Point (Addressable Loop)
Use the +, - and >> keys to select the
required Loop and Point, then press Enter
key.
RBus Point (Remote Bus)
Use the +, - and >> keys to select the
required RBus, Category and Point, then
press Enter key.
Local I/O Point (Field Interface Module)
Use the +, - and >> keys to select the
required Category and Point, then press Enter
key.
The following type of screen will be displayed:
Point Input and Point Output are displayed in the same
format.
The top line shows the selected option.
The second line shows the Zone and Point number of the
device.
The third line shows the Sector description (defined at
configuration).
The fourth line shows the Zone description (defined at
configuration).
The fifth line shows the Point description (defined at
configuration).
The sixth line shows the device type.
Point
Panel
02
Loop
A 001
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
View Status
>> - + Enter
Point
Zone 006 A007
Zone 06
Call alarm in room
CP 820
Input Output
Normal
MX Panel
Wed, 01-Mar-02
14:15
Company Name
General
Back
View Status
Actual Status IP can be in one of the following states:
Normal
Fault
Active
PreAlarm
Actual Status OP can be in one of the following conditions:
On
Off
Pulse 1
Pulse 2
Selecting Zone will display the following type of screen:
Function Keys F3/F4 will decrement/increment the zone
number.
Description
Alarm Yes One or more devices of a
zone in Alarm Mode
Fault Yes One or more devices of the
zone in Fault Mode
Isolate Yes All alarm input devices of the
zone are Isolated
Walk Test Yes All alarm input devices of a
zone in Walk Test
Zone 002
South Building
1st Floor Corridoor
Alarm : NO
Fault : NO
Isolate : NO
Walk Test : NO
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
View Status
_
+
MX
17A-05-O
5 11/04
PAGE 20 of 35
3.7 ISOLATE/DE-ISOLATE
The Isolate/De-isolate option allows the following to be
isolated/de-isolated:
Point Complete 1
Point Input 2
Point Output 3
Zone Detectors 4
Zone Callpoints
(also interrupt devices) 5
Zone Alarm I/Ps 6
Zone Sounders 7
Zone Controls 8
Zone Extinguish 9
Extinguish Controls F2
Fault Signalling F3
Alarm Signalling F4
All Sounders F5
Press 3 from the Main menu. The following screen will be
displayed:
Select the required number from the Isolate/De-Isolate menu,
then select the type of point (as described in Section 3.5):
Loop Point (Addressable Loop)
Use the +, - and >> keys to select the
required Loop and Point, then press Enter
key.
RBus Point (Remote Bus)
Use the +, - and >> keys to select the
required RBus, Category and Point, then
press Enter key.
Local I/O Point (Field Interface Module)
Use the +, - and >> keys to select the
required Category and Point, then press Enter
key.
1 - Point
2 - Point I/P only
3 - Point O/P only
4 - Zone Detectors
5 - Zone Callpoints
6 - Zone Alarm I/Ps
7 - Zone Sounders
8 - Zone Controls
9 - Zone Extinguish
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Isolate/De-Isolate
Alm Sig All SND Flt Sig Ext.Ctl
CAUTION:
Isolating I/O points may break compliance with
EN54. Caution should be exercised when
dealing with mandatory switches and
indicators. Such operations are reserved for
authorised trained personnel only.
The following screen shows an example of Point isolation:
In the Customer Operator access levels, only points on the
addressable loop can be isolated or de-isolated.
Isolations are counted and displayed (eg, Isol 001). If only
the input or output of a point is isolated, this is counted as a
complete isolation of the point.
The following screen shows an example of Zone isolation:
Successes: Number of points that were
De-Isolated
Matches: Number of points in Zone (detectors)
Point Complete
Zone 002 B002
South Building
1st Floor Corridoor
Room 117
801 H
Status IP: Normal
ISOLATED INPUT
1 - Isolate
2 - De-Isolate
MX Panel
Wed, 01-Mar-00
14:15
Company Name
Isola 001
General
Back
Isolate/De-Isolate
Isolation Status
Zone Detectors
Zone 001
Zone 01
Isolate
All
Successes : 003
Matches : 003
MX Panel
Wed, 01-Mar-00
14:15
Company Name
Isola 003
General
Back
Isolate/De-Isolate
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 21 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
The following screen shows an example of All Sounders
isolation:
Successes: Number of sounders (De-)Isolated
Matches: Number of sounders in Zone
3.8 TIME/DATE
Press 4 from the Main menu. The following type of screen
will be displayed:
3.8.1 SET TIME/DATE
Press 1 from the Time/Date menu. The following type of
screen will be displayed:
All Sounders
Successes : 006
Matches : 006
MX Panel
Wed, 01-Mar-00
14:15
Company Name
Isola 006
General
Back
Isolate/De-Isolate
1 - Set Time/Date
2 - Summer/Winter
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Time / Date
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Time / Date
>> - +
Date : 01-Mar-00
Time : 14:15:17
Save
Use the >> key to move the cursor between options, enter
date and time values via the keypad or Softkey F3 (-) and
F4 (+).
Note:
1) When a value has been changed, F5 shows
Save, use this key when all editing has been
completed.
2) Months January to September can also be
entered with the keypad:
1 = January
...................
9 = September
3.8.2 SUMMER/WINTER
Press 2 from the Time/Date menu. The following type of
screen will be displayed:
These screens cannot be changed, the information is
configured in MX CONSYS, use F5 to toggle between
Winter and Summer.
Dates are not shown on a T2000.
3.9 EVENT LOG
Press 5 from the Main menu. The following type of screen
will be displayed:
Summertime MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Summer/Winter
Winter
1 - View Event Log
2 - Print Event Log
3 - Filter
MX Panel
Wed, 09-Aug-00
00:01
Company Name
General
Back
Event Log
MX
17A-05-O
5 11/04
PAGE 22 of 35
3.9.1 VIEW EVENT LOG
This option allows all events in the event log to be viewed
or printed.
Select option 1 from the Event Log menu, the following type
of screen will be displayed:
The latest event is displayed, use the << and >> keys to
scroll through the log and the |<< to move to the back of
the log or the >>| key to move to the front of the log.
EventID - Displays the absolute number of
an event (1 to 65,535). After 65,535 it starts
with 1 again.
0001/0010 - The first number is the actual
position in the event log (1 means it displays
the newest event log entry. The second
number displays the number of entries in the
event log (max. 3,000).
The newest/last event will be displayed when the Event Log
is entered.
3.9.2 PRINT EVENT LOG
Select option 2 from the Event Log menu, the following type
of screen will be displayed:
This menu option is only available if at least one printer is
configured.
Event ID 00010
Zone 000
System Zone
TEST FINISHED
04-Feb-02 19:30:00
- Empty -
Information only
0001/0010
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Event Log
<< >> >> <<
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Event Log
>> - + Print
Destination :
Default Printer
How far back:
to start: 0010
How many entries
required: 0010
Lowest priority
of interest : 00
Print initiated
The destination printer can be selected if more than one
printer is configured.
The priorities available are shown in the following table:
It is always printed from the selected priority (eg, Non Life
Risk) to the Highest Priority (eg, Non Life Risk, Level 12,
Life Risk Alarm and General Alarm).
3.9.3 FILTER
Select option 3 from the Event Log menu, the following
type of screen will be displayed:
It is possible to view and to print the events of single
categories. The category is selected by pressing the
appropriate option number. It is also possible to select
several categories, the selected categories are denoted by a
+ sign.
Press F4 to view the selected categorie(s) as described in
Section 3.8.1 or F5 to print the selected category(s) as
described in Section 3.8.2.
Lowest Priority Information Only
. Level 2
. Expected Events
. Isolates
. Warnings
. Visible Isolate
. Other Faults
. Critical Faults
. Gas Alert
. Alarm Threshold
. Non-Life Risk
. Level 12
. Life Risk Alarms
Highest Priority General Alarm
1 - Fire -
2 - Gas Alert -
3 - Pre Alarm -
4 - Supervisory -
5 - Fault -
6 - Isolate -
7 - Test Mode -
8 - Warning -
9 - Information -
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Event Log
Print View
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 23 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
3.10 VIEW/PRINT STATUS
Allows the following options to be viewed/printed. On
networked systems, the status of any panel on the network
may be viewed/printed:
Points Isolated
Points Untested/Failed (during Walk Test)
Point Values
View Faults (no print option)
Loop Point Counters (no print option)
Select option 6 from the Main menu, the following type of
screen will be displayed:
3.10.1 VIEW/PRINT POINTS ISOLATED
Select option 1 from the View/Print Status menu, the
following type of screen will be displayed:
Note: If the panel is part of a networked system,
another screen is displayed before the above
screen where the panel number may be
selected.
Press F5 Print to print a list of all isolated points.
The F2 Key selects either isolated inputs or isolated outputs.
Points which are completely isolated (input and output) will
be shown in both lists.
1 - Points Isolated
2 - Pts Unt./Failed
3 - Point Values
4 - View Faults
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
View/Print Data
Input
Total : 004
Zone 001 -001 B
Point Text
--------------------
001 -002 B
Point Text
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Points Isolated
Print Output
3.10.2 VIEW/PRINT POINTS UNTESTED/
FAILED
Note: This option only works whilst still in Walktest.
Select option 2 from the View/Print Status menu, the
following type of screen will be displayed:
Note: If the panel is part of a networked system,
another screen is displayed before the above
screen where the panel number may be
selected.
Press F5 to print the Untested/Failed points.
Points which are not tested or points which return the wrong
condition are then listed.
3.10.3 VIEW/PRINT POINT VALUES
Select option 3 from the View/Print Status menu, the
following type of screen will be displayed:
Select the panel number (if the panel is part of a networked
system), loop and point number required.
>> - next field
_ - the number is decremented
+ - the number is incremented
Total : 004
Zone 001 -001 B
Point Text
--------------------
Zone 001 -002 B
Point Text
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Pts Untested/Failed
Print
Panel 02
Loop Point
A 002
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Point Values
Enter >> - +
MX
17A-05-O
5 11/04
PAGE 24 of 35
Pressing F5 displays the following screen:
Press F5 to print the Point Values of the selected loop (not
only the displayed point).
3.10.4 VIEW FAULTS
Select option 4 from the View/Print Status menu, the
following type of screen will be displayed:
This option is view only.
3.10.5 VIEW LOOP POINT COUNTERS
This option is view only. Select option 5 from the View/
Print Status menu, the following screen will be displayed:
Zone 002 B002
South Building
1st Floor Corridoor
Room 117
801H
Real: 801 H (020)
Mode: 1 Sens.: 0
20 C (032)
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Point Values
Print
o
Total : 002
Zone 000 R10
Zone 000 R12
MX Panel
Wed, 01-Jan-00
14:15
Company Name
Flt P 002
General
Back
View Faults
Panel
02
Loop
A
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Loop Point Counters
>> - + Enter
Note: Only the Loop will be shown if the panel is not
networked.
Select the required panel (only if the panel is networked)
and loop, then press the Enter key. The following message
is displayed:
Please Wait...
for approximately 2 minutes until the count is complete, if
no faults are found, the following type of screen will be
displayed:
Configured - the number of points
configured in CONSYS.
There are no multiple reserved point
addresses.
Conditions for PASSED
The number of configured points is equal
the detected count of points on the loop.
There are no unconfigured points.
Detected points from left, right and both
sides are equal.
If all conditions are not satisfied, the ATTENTION screen
will be displayed showing the relevant counters.
Configured - the number of points
configured in CONSYS.
Counter
Loop : A
PASSED
Configured : 010
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Loop Point Counters
Details Scan
Counter
Loop : A
A T T E N T I O N
Configured : 010
Conf. & Ident: 009
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Loop Point Counters
Details Scan
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 25 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
Conf & Ident - shows how many points are
connected, identified and configured on the
loop.
Not Conf. - shows how many points were
identified on the loop but not configured in
CONSYS.
Both Sides/Left Side/Right Side - Shows
how many points on the loop are recognised
by the panel. Left Side and Right Side is
the count from both sides. Both Sides
means the detection of a closed loop.
Note: If the value of Conf & Ident is different to the
number of installed devices, multiple reserved
address may be the cause.
3.10.5.1 DETAILS
Press the Details key (F2), the following type of screen
will be displayed:
All 250 addresses may be displayed using the >> key.
The connection detail of each point is shown by the
following symbols:
Function key F2 scrolls through the loop.
o OK: point connected, configured and
identified (eg, point 33 and points 60 to 64)
Point was configured (in MX CONSYS) but
not connected or identified (eg, point 21)
Point was not configured but connected (eg,
point 6)
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Loop Point Counters
>>
Details
Loop : A
Point 0123456789
0 : ......u...
10 : ..........
20 : .c........
30 : ...o......
40 : ..........
50 : ..........
60 : ooooo.....
70 : ..........
80 : ..........
c
u
3.10.5.2 SCAN
Press the Scan key (F3), the following type of screen will
be displayed:
The points are shown which were detected from both sides
(Left/Right).
They are displayed as follows:
Function key F2 scrolls through the loop.
3.11 SERVICE
Press 7 from the Main menu, the following screen will be
displayed:
Note: The Maintenance and Diagnostics options are
only available at Customer Manager level and
will not be displayed for lower levels.
Empty (not used)
OK: detected from both sides (eg, points 33 and
82)
Only detected from left side (eg, points 4 and 21)
Only detected from right side (eg, 60 to 64)
MX Panel
Wed, 01-Jan-00
14:15
Company Name
General
Back
Loop Point Counters
>>
Left / Right Scan
Loop : A
Point 0123456789
0 : ....l.....
10 : ..........
20 : .l........
30 : ...*......
40 : ..........
50 : ..........
60 : rrrrr.....
70 : ..........
80 : ..*.......
.
*
l
r
1 - Walk Test
2 - Maintenance
3 - Diagnostics
MX Panel
Wed, 09-Aug-00
00:01
Company Name
General
Back
Service
MX
17A-05-O
5 11/04
PAGE 26 of 35
3.11.1 WALK TEST
When selected, this option allows single or multiple points
to be tested without an alarm being raised.
Press 1 from the Service menu.
Only one Walk Test session can be active at one time.
Use the >>, - and + keys to select the required
options. The Panel number is only displayed when it is part
of a networked system.
Depending on the selected settings, the display will
change. The following screen is an example of Area
selected as Point.
To start the Walk Test press F5.
Possible Settings
Panel
Panel selection is only available for panels that are in a
networked system.
Area
All Walk Test of all elements of a specific type.
(Selection in the field Type eg, callpoints).
Zone Walk Test of all elements of a specific type
in a special zone.
Point Walk Test of the input of a single point.
Panel : 01
Area : All
Type : Input
Loop : All
Automatic : NO
Multisensor : Part
MX Panel
Wed, 09-Mar-02
00:01
Company Name
General
Back
Walk test
>> + - Start
Panel : 01
Area : Point
Type : Input
Location : Loop
Zone : 01
Point : 01
Automatic : NO
Multisensor : Part
MX Panel
Wed, 09-Mar-02
00:01
Company Name
General
Back
Walk test
>> + - Start
Type
Loop
Only with Area as All or Zone.
Walk Test of all loops or of a specific loop (A, B, C or D).
Location
Only with Area selected as Point.
Zone
Only with Area selected as Point.
Point
Only with Area selected as Point.
Selection of a specific zone is possible.
Automatic
Only if type selected is detectors.
Lasertest
Lasertest is not used.
Multisensor
It is only possible to select either Automatic, Lasertest
or Multisensor. The panel itself prevents selection of more
than one option.
Input Walk Test of all inputs.
Detectors Walk Test of detectors.
Alarm I/Ps Walk Test of default inputs covered by
supergroup Fire Alarm Inputs SG.
Call Points Walk Test of call points.
Sounders Walk Test of sounders by loop or all
loops plus FIM sounders.
Loop A point on the loop.
Loop Selection of a specific zone is possible.
YES Self test will be carried out by
detectors. The following detectors support
the self test function:
801PH
801CH
801I
NO No self test will be done by the detectors.
Full
Part
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 27 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
Note: If Full Walk Test is selected, both modes of
the detector must be activated (eg, both heat
and optical mode for 801PH).
If Part Walk Test is selected, the detector has
to be activated in the mode in which it is
operating (eg, for 801PH optical and heat, both
modes active, then activation of either the
optical or heat will activate the processing. If
only the heat mode is active, then only
activation of the heat mode will create an
alarm.
3.11.1.1 ALL INPUTS
Select the following settings:
Area: All
Type: Input
Loop: All
Press F5 to start the Walk Test.
The following screen shows an example for the Walk Test
All Inputs option:
Press F3 to display selected settings.
Press F5 to end Walk Test.
Selected: Number of points selected by the test.
Excluded: Number of Points not in Walk Test (ie,
points isolated).
Been Active: Number of points which have been
activated during Walk Test.
Been Clear: Number of points which were not
active when starting Walk Test.
Successful: Number of tested points.
Curr.Active: Points which are currently active.
TestZ001: Number of zones which are in Walk
Test. The pointer is only counted if all
points in a zone are in Walk Test.
All Inputs
Selected : 007
Excluded : 000
Been Active : 005
Been Clear : 007
Successful : 005
Curr.Active : 000
MX Panel
Wed, 09-Mar-02
00:01
Company Name
General
Back
Walk test
Settings End
TestZ 001
CAUTION:
THE FINISHING OF A WALK TEST IS ONLY
POSSIBLE IF ALL POINTS IN THE WALK
TEST ARE INACTIVE.
3.11.1.2 SOUNDERS
Select Sounders in the Type field.
No results will be shown on the display. The selected
sounders will be activated in a pulsing mode.
3.11.1.3 POINT
Select the following settings:
Press F5 to start the Walk Test.
The following screen shows an example for the Walk Test
of Point Input:
Area: Point.
Type: Input (appears automatically).
Location: Loop (appears automatically).
Zone: Required number.
Point: Required number.
Selected: 1, if point is in Walk test.
Excluded: 1, if point is not in Walk Test (ie, if point
is isolated).
Activations: 1, if point was activated during Walk
Test.
Curr.Active: Yes, if point is currently active.
Point I/P only
Zone 006 A007
Zone 06
Call alarm in room
CP820
Selected : 1
Excluded : 0
Activations : 0
Curr.Active : NO
MX Panel
Wed, 09-Mar-02
00:01
Company Name
General
Back
Walk test
Settings End
TestZ 001
MX
17A-05-O
5 11/04
PAGE 28 of 35
Press F3 for a display of selected settings.
Press F5 to end Walk Test.
CAUTION:
THE FINISHING OF A WALK TEST IS ONLY
POSSIBLE IF ALL POINTS IN THE WALK
TEST ARE INACTIVE.
3.11.2 MAINTENANCE
Press 2 from the Service menu. The following type of
screen will be displayed:
3.11.2.1 VIEW FIRE ALARM CYCLE COUNT
When selected, the number of Alarm sequences may be
viewed.
Press 1 from the Maintenance menu. The following type of
screen will be displayed:
TestZ 001 Number of zones which are in Walk
Test. (The pointer is only counted if all
points of a zone are in Walk Test. If one
detector on the zone is switched off, the
pointer is not decreased. In the case of
Walk Test for one point, the pointer is
only decreased if that point is the only
point on the zone).
Total: 000
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Maintenance
Print
Count :
0025
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Fire AL.Cycle Count
3.11.2.2 VIEW/PRINT MAINTENANCE
REQUEST
When selected, this option displays a list of detectors which
are near the limit of their threshold compensation limit.
Press 3 from the Maintenance menu. The following type of
screen will be displayed:
Press F5 to print the Maintenance Request.
3.11.2.3 BATTERY TEST
When selected, this option allows the state of the battery and
the charger current to be displayed.
Press 4 from the Maintenance menu. The following type of
screen will be displayed:
Total : 003
Zone 002 B002
Zone 004 A126
Zone 008 B006
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Maintenance Request
Print
Battery State :
Battery Low
Battery Voltage :
20.764 V
Charger Current :
00.500 A
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Battery Test
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 29 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
3.11.2.4 SOFTWARE INITIALISATION COUNT
When selected, this option allows the number of times the
CPU has been re-initialised information to be displayed.
F5 allows the count to be reset to zero.
3.11.2.5 PROJECT NUMBERS
When selected, this option allows the project and MX
CONSYS information to be displayed.
Press 6 from the Maintenance menu. The following type of
screen will be displayed:
3.11.2.6 SOFTWARE VERSIONS
When selected, the software versions of the following are
displayed:
Firmware
Local I/O
Each Loop
Each MPM
Network card (if fitted)
Press 7 from the Maintenance menu. The following type of
screen will be displayed:
-Firmware 25
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Softw. Init. Count
Reset
Project:
Queen El. Hospital
Consys: V1.0
Created:
21-Jul-00 10:18
Downloaded:
27-Jul-00 08:20
Last User Update:
26-Jul-00 09:10
MX Panel
Wed, 01-Mar-00
00:01
Company Name
General
Back
Project Numbers
Press F5(+) for additional details of the software versions.
3.11.2.7 MENU POINTS
When selected, this option allows any configured point
displayed to be operated by pressing the appropriate number
button, this will toggle from OFF to ON and ON to OFF.
Press 9 from the Maintenance menu. The following type of
screen will be displayed:
3.11.3 CONFIGURATION
Press 8 from the Main menu. The following screen will be
displayed:
-Firmware V 2.0
-Bootrom V 1.1
-Local I/O V 1.0
-Loop A V 1.0
-MPM 00 V 1.1
-Net V 1.5
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Software Versions
+
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Menu Points
>>
Menu Point 1: OFF
Isolate Zone
Menu Point 2: ON
Sensit.Change
Menu Point 3:
-Unconfigured-
Menu Point 4:
-Unconfigured-
ON
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Configuration
1 - Change Text
MX
17A-05-O
5 11/04
PAGE 30 of 35
Menu option 9- Restart will only be displayed if text has
been changed and the changes saved.
RESTRICTIONS ON THE USE OF THE
FOLLOWING OPTION
When using Configuration menu option 1, ALWAYS
commit configuration changes by using Menu option 9 -
Restart before leaving the panel.
Avoid inactivity timeouts.
NEVER use the Back option from the configuration menu
if Menu option 9 - Restart is showing.
If you do not want to commit changes, by using Menu
option 9 - Restart, option, turn the keyswitch to OFF
position to avoid a timeout situation, do NOT USE the
Back option.
Configuration changes across a network are possible, but
changes to more than one panel at a time MUST NOT be
attempted within one session. When a panels configuration
has been changed, it must be restarted using menu option 9
Restart.
Failure to comply with these restrictions may lead to
unpredictable effects or system instability.
3.11.3.1 CHANGE TEXT
Press 1 from the Configuration menu. The following screen
will be displayed:
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Change Text
1 - Point Text
2 - Zone Text
3 - Sector Text
4 - Panel Text
5 - Info Text
3.11.3.2 POINT TEXT MODIFY
Press 1 from the Change Text menu. The following screen
will be displayed:
Select the required loop and point then press Enter. The
following type of screen will be displayed:
>> - copies the old text to the New text position.
- moves the cursor back one position.
+ moves the cursor forward one position.
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
Pressing the scroll up key allows text to be entered in
upper case.
Pressing the scroll down key changes to lower case
text.
The message Save Data? appears and the functions
change F4 to Yes and F5 to No. Selecting F5 allows the
text modifications to be changed.
Selecting F4 Yes displays the message:
Please wait.....
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Point Text Modify
Loop : A
Point : 001
>> - + Enter
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Point Text Modify
Zone 255 -007 A
Old text
Callp. alarm room
New text
>> - + Enter
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 31 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
then the following screen is displayed:
It is now possible to change the text for another Point.
Selecting F1 Back will display the following screen:
Only Change Text and Restart are available allowing
more points to be changed or using Restart to allow the
changes to take effect.
3.11.3.3 ZONE TEXT MODIFY
Press 2 from the Configuration menu. The following screen
will be displayed:
Select the required and press Enter. The following type of
screen will be displayed:
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Change Text
1 - Point Text
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Configuration
1 - Change Text
9 - Restart
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Zone Text Modify
Zone : 001
- + Enter
>> - copies the old text to the New text position.
- moves the cursor back one position.
+ moves the cursor forward one position.
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
The message Save Data? appears and the function change
F4 to Yes and F5 to No. Selecting F5 allows the text
modifications to be changed.
Selecting F4 Yes displays the message:
Please wait.....
then the following screen is displayed:
It is now possible to change the text for another Zone.
Selecting F1 Back will display the following screen:
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Zone Text Modify
Zone : 001
Old text
Zone 01
New text
>> - + Enter
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Change Text
2 - Zone Text
MX
17A-05-O
5 11/04
PAGE 32 of 35
Only Change Text and Restart are available allowing
more points to be changed or using Restart to allow the
changes to take effect.
3.11.3.4 SECTOR TEXT MODIFY
Press 3 from the Configuration menu. The following screen
will be displayed:
Select the required sector, then press Enter. The following
type of screen will be displayed:
>> - copies the old text to the New text position.
- moves the cursor back one position.
+ moves the cursor forward one position.
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Configuration
1 - Change Text
9 - Restart
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Sector Text Modify
Sector : 001
- + Enter
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Sector Text Modify
Sector 001
Old text
Sector 01
New text
>> - + Enter
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
The message Save Data? appears and the function change
F4 to Yes and F5 to No. Selecting F5 allows the text
modifications to be changed.
Selecting F4 Yes displays the message:
Please wait.....
then the following screen is displayed:
It is now possible to change the text for another Sector.
Selecting F1 Back will display the following screen:
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Change Text
3 - Sector Text
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Configuration
1 - Change Text
9 - Restart
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 33 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
3.11.3.5 PANEL TEXT MODIFY
Press 4 from the Configuration menu. The following screen
will be displayed:
Select the required Panel.
>> - copies the old text to the New text position.
- moves the cursor back one position.
+ moves the cursor forward one position.
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
The message Save Data? appears and the function change
F4 to Yes and F5 to No. Selecting F5 allows the text
modifications to be changed.
Selecting F4 Yes displays the message:
Please wait.....
then the following screen is displayed:
It is now possible to change the text for another Panel.
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Panel Text Modify
Panel 00
Old Text
ADT
New Text
Enter
>> - +
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Change Text
4 - Panel Text
Selecting F1 Back will display the following screen:
3.11.3.6 INFO TEXT MODIFY
This option allows Info Text created in Consys to be
modified. Press 5 from the Change Text menu. The
following screen will be displayed:
Using the + and - keys select the Info Text message to
modify, then press Enter.
The following type of screen will appear:
The >> key deletes all text.
The + key advances the cursor one space, the - key goes
one space back.
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Configuration
1 - Change Text
9 - Restart
MX Panel
Wed, 01-Mar-03
14:15
Company Name
General
Back
Info text modify
- +
Enter
Infotext No. : 001
MX Panel
Wed, 01-Mar-03
14:15
Company Name
General
Back
Info text modify
Infotext No. : 001
+ Enter
This zone is in a
Hazardous Area
Special
precautions
are required
-
>>
MX
17A-05-O
5 11/04
PAGE 34 of 35
Use the alphanumeric keys to modify the text, when
finished, press Enter.
The following screen will be displayed:
MX Panel
Wed, 01-Mar-03
14:15
Company Name
General
Back
Info text modify
Infotext No. : 001
Save data?
Yes No
This zone is in a
Hazardous Area
Special
precautions
are required
4. ROUTINE CHECKS
4.1 GENERAL
In order to comply with the requirements of British
Standard BS 5839 Part 1 (1988), the installation must be
checked on a regular basis by a responsible member of staff
to confirm that the controller and all ancillary devices are
operating correctly. The required routine checks are
described in the following paragraphs.
For Marine Systems, carry out routine checks in accordance
with the customers own procedures.
4.2 DAILY CHECKS
Proceed as follows:
a) Ensure the front panel of the controller is
indicating a normal condition (ie, no alarm
or fault LEDs are lit and the LCD is
displaying the date and time).
Note: If the panel is not indicating a normal condition
record the condition in the log book and take
any necessary action.
b) Check that any fault recorded on the
previous day has received attention.
4.3 WEEKLY CHECKS
These checks would normally be carried out by a
responsible member of the customers staff.
WARNING:
WARN ALL PERSONNEL THAT THE
SOUNDERS ARE ABOUT TO BE TESTED.
Proceed as follows:
a) If necessary, clean the front panel of the
controller with a suitable cleansing agent.
b) Set one device (either a callpoint or
detector) from one zone into alarm and
check that the system responds as follows:
The controllers internal buzzer sounds in
a continuous tone.
The two red FIRE LEDs on the
controller front panel light.
The appropriate red FIRE ZONAL LED
flashes (if configured).
The general and zonal sounders operate.
MX
17A-05-O
5 11/04
2004 Tyco Safety Products PAGE 35 of 35
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
The alphanumeric display gives the
location of the alarm.
c) Record the device used to initiate the test in
the site log book and reset the controller.
d) Check the condition of the printout on any
printers attached to the system and replace
the ribbon if it is becoming feint.
e) Ensure that each printer has an adequate
supply of paper.
Any defect should be recorded in the log book and
appropriate action taken.
JM/jm
28
th
November 2004

You might also like