You are on page 1of 8

Electric Heat Tracing

INSTALLATION PROCEDURES
Electric Heat Tracing
1
Illustration A: Typical Heat Tracing Installation
1
Power cable.
2
1
T
TED (EEx ed)
or TC (IND)
T (EEx d)
Circuit switch with indication lamp (padlockable).
2
Thermostat
3
(if applicable)
With Terminator ZT (EEx ed) it is possible to connect
two heating cables into the thermostat.
3
Heating cable. 5
4 Junction box.
Maximum 3 heat tracers through junction box
support base tting and 2 power cables through side
entries of enclosure. For junction boxes supplied
without support base ttings, the maximum is 4 total
tracers plus power cables.
Voltage Indication Lamp (VIL).
(If applicable)
6
End termination
ET-6 and ET-60 for BSX, RSX, VSX
ET-8 and ET-80 for KSX, HTSX, HPT and FP
7
T
(if applicable)
Notes . . .
1. All heat-traced lines must be thermally insulated.
2. Due to the risk of electrical shock, arcing and re caused by product damage or improper usage installation or maintenance, a ground-fault protection device is required for all heat
tracing circuits. Bond the metal sheath/braid of the heat tracing cable to a suitable earth terminal.
3. Thermostatic control is recommended for all freeze protection and temperature maintenance heat tracing applications.
T
ZT
INSTALLATION PROCEDURES
2
Site Practice . . .
1. Provide protective clothing, and other protective equipment needed to isolate employees from potential arc ash and shock
hazards identied in the analysis.
2. Provide training to employees for understanding the purpose/function of the electrical heat tracing and the electrical power
supply/control equipment, and how to recognize and avoid the hazards associated with operation and maintenance.
3. Apply safe work practices including the following:
Identify the circuit or equipment to be de-energized and all possible sources of electrical energy supplies to the specfc
circuit or equipment.
Disconnect both legs of the power supply cable at the circuit breakers, disconnect switches, and any other applicable
points.
Apply lockout/tagout devices according to established procedures.
Visually verify that the circuit disconnect devices are open prior to connecting power cable to heat tracers.
Test for absence of voltage with an approved voltmeter (where the voltmeter is tested on a known circuit voltage
prior to and immediately following application).
For protection against accidental energizing of supply conductors, apply temporary jumpers rated for the available fault
duty between each supply conductor and ground.
Notes . . .
1. Refer to the heating cable product specication sheets for temperature ratings as limited by the manufacturer.
2. For foundation heating with RSX, refer to Form TEP0059.
3. For foundation heating with FP, refer to Form TEP0079.
Complete Electric Heat Tracing System . . .
Types of Heating Cables
1
. . .
1. Self-Regulating Heating Cables:
BSX (refer to Form TEP0067U)
1725 II 2 G & D Ex e II T5 or T6 DEMKO 02ATEX0132424, IECEx UL 06.0013 Ex e II T5 or T6
RSX 15 (refer to Form TEP0048U)
2

1725 II 2 G Ex e II T4 to T6 KEMA 07ATEX0179, IECEx KEM 07.0052 Ex e II T4 to T6
HTSX (refer to Form TEP0074U)
1725 II 2 G & D Ex e II T2 or T3 DEMKO 02ATEX0120790, IECEx UL 06.0004 Ex e II T2 or T3
KSX (refer to Form TEP0072U)
1725 II 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67 T200C to T85C FM 07ATEX0027, IECEx FMG 06.0009 Ex e II T3 to T6,
Ex tD A21 IP66/IP67 T200C to T85C
VSX (refer to Form TEP0008U)
1725 II 2 G & D Ex e II T3 DEMKO 02ATEX0152667, IECEx UL 05.0008 Ex e II T3
2. Power-Limiting Heating Cable:
HPT (refer to Form TEP0011U)
1725 II 2 G Ex e II T2 to T6, II 2 D Ex tD A21 T300C to T85C FM 07ATEX0028, IECEx FMG 06.0006 Ex e II T2 to T6
3. Parallel Constant Watt Heating Cable:
FP (refer to Form TEP0016U)
3

1725 II 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67 T200C to T85C FM 07ATEX0016, IECEx FMG 06.0008 Ex e II T3 to T6,
Ex tD A21 IP66/IP67 T200C to T85C
4. Series Constant Watt Heating Cables:
TES (refer to Form TEP0063U)
1725 II 2 G EEx edm IIC T2 To T6 LCIE 00ATEX6014X
TESH (refer to Form TEP0070U)
1725 II 2 G EEx edm IIC T2 To T6 LCIE 00ATEX6014X
Electric Heat Tracing
Proposed End-of-Circuit
Location
Pipe Support
Cable Allowance for
In-Line Heat Sinks
Proposed Power
Connection Location
3
Before Installing Cable . . .
1. Before removing the heating cable from the reel, an in-
sulation resistance test should be conducted. The cable
should be tested with a test voltage of at least 500 Vdc.
However, for polymer insulated heating cables, 2500 Vdc
is recommended. The minimum acceptable level should
not be less than 20 megohms. All test results should be
documented.
Testing should occur at the following stages of installation.
While the cable is still on the reel
After installing heating cable
After installation of thermal insulation
Prior to connecting cable to power
As part of a routine maintenance program
2. Be sure all piping and equipment to be traced is completely
installed, pressure tested and painted (if applicable)
3. Surface areas where heat tracing is to be installed must be
reasonably clean. Remove dirt, rust and scale with a wire
brush and oil and grease lms with a suitable solvent.
Initial Installation . . .
1. Begin temporary installation at the proposed end-of-
circuit location and lay out heating circuit on the pipe,
allowing extra cable for the power connection and for
any splice locations
3
. Refer to Illustration B for temporary
installation.
2. Make heating cable allowances for valves, anges, elbows
and supports as per the applicable drawings, refer to
pages 4 and 5 of these installation procedures.
Notes . . .
1. Termination kits to fabricate heat tracing circuits are not addressed in these
installation procedures. Refer to the specic installation instructions included
with the kits.
2. For foundation heating, see installation instructions Form 10A081.
3. Minimum bending radius of heating cable is 32 mm (except HPT is 57 mm,
FP is 19 mm, TESH is 5 x OD).
Read and carefully follow all installation procedures when
installing a Thermon electric heat tracing system
1
. Product
certications and performance of heat tracing system is
dependant upon proper installation with certied Thermon
components.
The system must be installed in accordance with the
regulations EN IEC 60079-14 and IEC 62086-2 for hazardous
areas (where applicable). The system installation must also
comply with all local and national electrical codes.
Applications . . .
1. Electric heat tracing cables are used for freeze protection
2

and/or temperature maintenance of piping, tanks and
instrumentation.
2. Heat tracing cables may be installed in ordinary (nonclas-
sied) and hazardous (classied) locations depending on
the specic cable options and approvals. See Types of
Heating Cables on page 2.
Receiving, Storing and Handling . . .
1. Identify the heating cable to ensure the proper type and
quantity have been received. The cable model number
will be visible on parallel heating cables (on braided
cables, the information is printed on the jacket below the
braid); factory-fabricated series circuits will have an im-
printed l.D. tag with pertinent data. Compare information
on heating cable with packing slip and purchase order to
verify receipt of correct shipment. For date of production,
contact Thermon.
2. Visually inspect materials for damage incurred during
shipment. Report damages to the carrier for settlement.
3. Store in a dry place. Keep ends of heating cable dry and
sealed before and during installation
Caution: Do not connect power to heating
cable while it is still on the reel or in a
shipping carton.
Illustration B: Temporary Installation
INSTALLATION PROCEDURES
Illustration D: Pipe Support Illustration C: Pipe Elbow
Illustration E: Pipe Flange
Attachment Tape
(Typical)
Heating Cable Attachment Tape
(Typical)
Heating Cable
Support
Length
3 Min.
(8 cm)
3 Min.
(8 cm)
Attachment Tape
(Typical)
Heating Cable
12 Max.
(30 cm)
Note: Flange allowance will vary based on method of
insulating ange and adjacent piping.
4
Installation on Elbows, Supports and Flanges . . .
1. Install heating cable in accordance with Illustrations C, D
and E below. Secure heating cable to piping using attach-
ment tape rated at the application temperature.
2. Elbows: Locate the cable on the outside radius of an
elbow to provide sufcient heat to compensate for the
added piping material. Secure the cable to the pipe on
each side of the elbow with attachment tape.
Caution: Do not use metal pipe straps or tie
wire to attach heating cable. Use approved
attachment tape only.
3. Pipe Supports: of diameter > 2 require additional heat-
ing cable, allow two times the length of the pipe support
plus an additional 8 cm of heating cable. (In process tem-
perature maintenance systems the pipe supports must be
isolated from the pipes. In winterizing systems, Thermon
highly recommends to isolate the pipe supports from the
pipes)
4. Flanges: Allow cable to be looped around pipe on each
side of and adjacent to the ange. Heating cable must
maintain contact with ange when bending around pipe
anges to compensate for additional heat loss.
Electric Heat Tracing
Attachment Tape
(Typical)
Heating Cable
Heating Cable Serpentined on Valve
Attachment Tape
(Typical)
Heating Cable
Temporary Loop of Cable on Valve
Circuit Layout on Pump
Heating Cable Serpentined on Pump
Heating Cable
Attachment Tape
(Typical)
5
Installation on Valves and Pumps . . .
1. Install heating cable in accordance with Illustrations F and
G below. Secure heating cable to piping using attachment
tape rated at the application temperature.
2. Additional cable is required to provide extra heat at
valves, pumps and miscellaneous equipment to offset the
increased heat loss associated with these items. Refer to
Table 1 for estimated cable requirements for installation
on typical valves and pumps.
3. Install heating cable on valves and pumps utilizing a
looping technique (this allows the valve or pump to be
removed if required). Crossing series heating cable over
itself should be avoided.
4. Refer to the product specications sheet for minimum
bend radius for the specic cable type. Do not exceed
bend radius when completing installation.
Table 1: Valve and Pump Allowances
Illustration F: Typical Valve Detail
Illustration G: Typical Pump Detail
e z i S e p i P
) m m ( n i
e p y T e v l a V
d e d l e W d e g n a l F d e w e r c S
) m ( t f ) m ( t f ) m ( t f
e p y T p m u P
d e g n a l F d e w e r c S
) m ( t f ) m ( t f
) 2 1 ( ) 5 1 . ( 5 . ) 0 3 . ( 1 0 ) 0 3 . ( 1 ) 1 6 . ( 2
) 9 1 ( ) 3 2 . ( 5 7 . ) 6 4 . ( 5 . 1 0 ) 6 4 . ( 5 . 1 ) 1 9 . ( 3
) 5 2 ( 1 ) 0 3 . ( 1 ) 1 6 . ( 2 ) 0 3 . ( 1 ) 1 6 . ( 2 ) 2 2 . 1 ( 4
) 2 3 ( 1 ) 6 4 . ( 5 . 1 ) 1 6 . ( 2 ) 0 3 . ( 1 ) 1 9 . ( 3 ) 7 3 . 1 ( 5 . 4
) 0 4 ( 1 ) 6 4 . ( 5 . 1 ) 6 7 . ( 5 . 2 ) 6 4 . ( 5 . 1 ) 1 9 . ( 3 ) 2 5 . 1 ( 5
) 0 5 ( 2 ) 1 6 . ( 2 ) 6 7 . ( 5 . 2 ) 1 6 . ( 2 ) 2 2 . 1 ( 4 ) 8 6 . 1 ( 5 . 5
) 0 8 ( 3 ) 6 7 . ( 5 . 2 ) 7 0 . 1 ( 5 . 3 ) 6 7 . ( 5 . 2 ) 2 5 . 1 ( 5 ) 3 1 . 2 ( 7
) 0 0 1 ( 4 ) 2 2 . 1 ( 4 ) 2 5 . 1 ( 5 ) 1 9 . ( 3 ) 4 4 . 2 ( 8 ) 5 0 . 3 ( 0 1
) 0 5 1 ( 6 ) 3 1 . 2 ( 7 ) 4 4 . 2 ( 8 ) 7 0 . 1 ( 5 . 3 ) 7 2 . 4 ( 4 1 ) 8 8 . 4 ( 6 1
) 0 0 2 ( 8 ) 0 9 . 2 ( 5 . 9 ) 5 3 . 3 ( 1 1 ) 2 2 . 1 ( 4 ) 9 7 . 5 ( 9 1 ) 1 7 . 6 ( 2 2
) 0 5 2 ( 0 1 ) 1 8 . 3 ( 5 . 2 1 ) 7 2 . 4 ( 4 1 ) 2 2 . 1 ( 4 ) 2 6 . 7 ( 5 2 ) 3 5 . 8 ( 8 2
) 0 0 3 ( 2 1 ) 7 5 . 4 ( 5 1 ) 3 0 . 5 ( 5 . 6 1 ) 2 5 . 1 ( 5 ) 4 1 . 9 ( 0 3 ) 6 0 . 0 1 ( 3 3
) 0 5 3 ( 4 1 ) 9 4 . 5 ( 8 1 ) 4 9 . 5 ( 5 . 9 1 ) 8 6 . 1 ( 5 . 5 ) 7 9 . 0 1 ( 6 3 ) 9 8 . 1 1 ( 9 3
) 0 0 4 ( 6 1 ) 5 5 . 6 ( 5 . 1 2 ) 1 0 . 7 ( 3 2 ) 3 8 . 1 ( 6 ) 1 1 . 3 1 ( 3 4 ) 2 0 . 4 1 ( 6 4
) 0 5 4 ( 8 1 ) 7 7 . 7 ( 5 . 5 2 ) 3 2 . 8 ( 7 2 ) 8 9 . 1 ( 5 . 6 ) 4 5 . 5 1 ( 1 5 ) 6 4 . 6 1 ( 4 5
) 0 0 5 ( 0 2 ) 9 6 . 8 ( 5 . 8 2 ) 4 1 . 9 ( 0 3 ) 3 1 . 2 ( 7 ) 7 3 . 7 1 ( 7 5 ) 9 2 . 8 1 ( 0 6
) 0 0 6 ( 4 2 ) 6 3 . 0 1 ( 4 3 ) 7 9 . 0 1 ( 6 3 ) 4 4 . 2 ( 8 ) 3 7 . 0 2 ( 8 6 ) 5 9 . 1 2 ( 2 7
) 0 5 7 ( 0 3 ) 9 1 . 2 1 ( 0 4 ) 0 8 . 2 1 ( 2 4 ) 5 0 . 3 ( 0 1 ) 8 3 . 4 2 ( 0 8 ) 0 6 . 5 2 ( 4 8
INSTALLATION PROCEDURES
Table 2: Attachment Tape Allowance
90
90
90 90
Single Cable Installation Dual Cable Installation Triple Cable Installation
Pipe Wall
Temperature Sensor
(Typical)
90 90
e z i S e p i P
) m m ( n i
" 1 - "
) 5 2 - 2 1 (
" 1
) 2 3 (
" 1
) 0 4 (
" 2
) 0 5 (
" 3
) 0 8 (
" 4
) 0 0 1 (
" 6
) 0 5 1 (
" 8
) 0 0 2 (
" 0 1
) 0 5 2 (
" 2 1
) 0 0 3 (
" 4 1
) 0 5 3 (
" 6 1
) 0 0 4 (
" 8 1
) 0 5 4 (
" 0 2
) 0 0 5 (
" 4 2
) 0 0 6 (
" 0 3
) 0 5 7 (
f o h t g n e L
l l o R / e p i P
e p a T f o
) m ( t F
' 0 6 3
) 7 . 9 0 1 (
' 0 6 2
) 2 . 9 7 (
' 0 2 2
) 0 . 7 6 (
' 0 8 1
) 9 . 4 5 (
' 0 5 1
) 7 . 5 4 (
' 0 2 1
) 6 . 6 3 (
' 0 9
) 4 . 7 2 (
' 0 7
) 3 . 1 2 (
' 0 6
) 2 . 8 1 (
' 0 5
) 2 . 5 1 (
' 0 4
) 2 . 2 1 (
' 5 3
) 7 . 0 1 (
' 0 3
) 1 . 9 (
' 5 2
) 6 . 7 (
' 0 2
) 0 . 6 (
' 5 1
) 6 . 4 (
90
90
Heating Cable
(Typical)
Temperature Sensor
(Typical)
Heating Cable
(Typical)
6
Completing the Installation . . .
1. Begin nal cable attachment by securing the end-of-
circuit termination kit and working back toward the power
supply. Power connections, splice connections, and end-
of-circuit termination kits are specied for each type of
heat tracer substitutions are not allowed.
Flexible heating cables are to be installed using attach-
ment tape rated at the application temperature. Circum-
ferential bands of tape should be installed at maximum
30 cm intervals to keep the cable in proper contact with
the pipe. Refer to Table 2 below for the number of rolls
of attachment tape required based on the pipe diameter
1
.
If applicable, refer to installation details provided with
the project drawings or contact Thermon for additional
information regarding installation.
2. In addition to the circumferential tape requirements, a
continuous covering of aluminum foil tape may be re-
quired when:
Spray or foam urethane
2
thermal insulation will be
applied.
Heat tracing nonmetallic piping.
Design requirements dictate the use of aluminum tape
to improve heat transfer.
3. Complete splice connections (if required) in accordance
with the installation instructions provided with the splice
kit.
Illustration H: Heating Cable vs. Sensor Location
4. Install power connection kit in accordance to the detailed
installation instructions provided with the kit. Power con-
nection kits are provided for pipe mounting or for wall
mounting.
5. While making the power connection kits, but before mak-
ing the nal connection to power, repeat the megger test.
The cable should be tested with a test voltage of at least
500 Vdc. However, for polymer insulated heating cables,
2500 Vdc is recommended. The minimum acceptable
level should not be less than 20 megohms.
6. For ambient controlled power, the heating circuit should
be connected directly to the switched power feed wiring.
7. For pipewall sensing thermostatic control, the heating cir-
cuit is to be connected in series with the control contacts
with a maximum load of 16A. The pipewall sensing ther-
mostat may require more than one support point.
8. Secure temperature sensor (if required) to pipe utilizing
attachment tape. Locate temperature sensor as shown in
Illustration H.
Notes . . .
1. Table 2 assumes circumferential bands every 12 (30 cm) along the length of the
process piping.
2. Verify exposure temperature of heating cable versus curing temperature of insulation.
Form PN 50207U-0509 Thermon Manufacturing Co.
Circuit Protection Requirements . . .
1. Over-current protection (typically circuit breakers) is
required for each branch circuit. This protection must iso-
loate all power conductors from the supply.
2. For typical installations (with TT and TN grounding
systems), a means of protection against earth faults is
required that includes a residual-current protective device
for each branch circuit. For xed-level ground-fault circuit
interrupters (such as GFCI circuit breakers), a minimum
30 mA trip level is recommended. The preferred trip
level for adjustable devices is 30 mA above any inherent
capacitive leakage characteristic of the heater as speci-
ed by the heat tracing supplier. Where conditions of
maintenance and supervision ensure that only qualied
persons will service the installed systems, and continued
circuit operation is necessary for the safe operation of
the equipment or processes, earth-fault detection without
interruption is acceptable if alarmed in a manner to assure
an acknowledged response.
3. For IT grounding systems, a means of protection against
earth faults is required that includes an electrical insula-
tion monitoring device that shall disconnect the supply
whenever the electrical resistance is not greater than 50
ohms/volt of rated voltage.
Thermal Insulation . . .
1. Before installing thermal insulation, megger testing should
be conducted. The cable should be tested with a test volt-
age of at least 500 Vdc. However, for polymer insulated
heating cables, 2500 Vdc is recommended. The minimum
acceptable level should not be less than 20 megohms.
2. The need for properly installed and well-maintained ther-
mal insulation cannot be overemphasized. Without insula-
tion, heat losses are generally too high to be offset by a
conventional heat tracing system.
3. In addition to piping and in-line equipment such as pumps
and valves, all heat sinks must be properly insulated. This
includes pipe supports, hangers, anges and, in most
cases, valve bonnets.
4. Regardless of the type or thickness of insulation used, a
protective barrier should be installed. This protects the
insulation from moisture intrusion, physical damage and
helps ensure the proper performance of the heat tracing
system. Seal around all penetrations through the thermal
insulation.
5. Apply Electric Heat Tracing Caution labels to the insula-
tion vapor barrier on 3 m (10) intervals or as required
by code or specication. The labels are supplied with
Thermon connection kits.
Final Inspection and Documentation . . .
1. After the installation of the thermal insulation and weather
barrier but BEFORE ENERGIZING THE HEATING CIR-
CUIT, the megohmmeter test should be repeated. This
should call attention to any damage to the heating cable
that may have occurred during the insulation installation.
2. It is recommended that the circuit be temporarily en-
ergized so that the volts, amps, pipe temperature and
ambient temperature may be recorded. Take the values
after 15 minutes of energizing. This information may be
of value for future reference and should be maintained for
the historical operating data log.
3. Stabilized design can be used for self-regulating heating
cables to assign a lower T-class through the use of the
Thermon CompuTrace software or Thermon Engineering.
4. Stabilized design can be used for power-limiting and
constant watt heating cables without a limiting device to
determine the T-class through the use of the Thermon
CompuTrace software or Thermon Engineering.
5. The maximum temperatures provided by Thermons Com-
puTrace software and by Thermon engineering are calcu-
lated to the methods and requirements of IEC 62086-2
and IEC 60079-30-2.
6. If stabilized design is used, the end user must record the
system parameters and the area T-class, and keep these
records for the time the heating cable is in operation.
7. Inspect system on a regular basis at least once per year.
Record all information after conducting test. If the system
fails any test, refer to Thermons Maintenance and Trouble
Shooting Guide for assistance. De-energize circuits affected
and make the necessary repairs immediately.
8. Verify the setting of the maximum control device, if pro-
vided to limit the T-rating for the circuit design, to insure
it limits the maximum surface temperature to be in com-
pliance with clause 4.4.3 of IEC 60079-30-1.
Maintenance and Repair . . .
1. Refer to form TEP0066-Electric Heat Tracing Maintenance
and Trouble Shooting Guide.
THERMON . . . The Heat Tracing Specialists

www.thermon.com
Corporate Headquarters
100 Thermon Dr.

PO Box 609
San Marcos, TX 78667-0609

USA
Phone: +1 512-396-5801
European Headquarters
Boezemweg 25

PO Box 205
2640 AE Pijnacker

The Netherlands
Phone: +31 (0) 15-36 15 370
For the Thermon ofce nearest you
visit us at . . .
www.thermon.com

You might also like