ELECTRICAL CASE STUDY

22/ 6.6KV INTERTRIPPING SYSTEM


28/ 7/ 2014
BSR Electrical Team
Intertrippingsystem 22kV/ 6.6kV
Intertripping shall beprovided between associated equipment to correctly isolatefaulted
itemsandtoleavethesysteminapredictableorderly stateafter operationof protection.
Operation of any transformer buchholz or overpressure/gas evolution protection
shall trip the transformer feeder circuit breaker and shall intertrip the associated
downstreamcircuitbreaker
Opening of any feeder circuit breaker, by protection operation or manual opening, shall
intertriptheassociateddownstreamcircuitbreaker
General information
Intertrippingsystem 22kV/ 6.6kV
General information
Intertrippingsystem 22kV/ 6.6kV
History of issue
Fromcommissioning phase, many malfunctioned trips at 6.6kV incomers/bus-tie which
maketheelectrical systemaswell astheRefineryunstable.
TPC/Schneider/ABB did sitesurvey, checked thesystemmany times but they could not
findtheroot causeaswell astheproper countermeasures
Intertrippingsystem 22kV/ 6.6kV
Finding
Blackout PPplantdated30-Mar-2012duetoFiber OpticConverter failure
Outagebusbar B of Subtation4dated02-Mar-2013duetopower supplyfailure
Blackout substation7dated03-Mar-2013duetopower supplyfailure
Blackout substation7dated05-May-2013duetoFiber OpticConverter failure
Incomer B of 8C-UPS-3-1trippedon26-Aug-2013duetoFiber OpticConverter failure
Blackout substation8B dated19-April 2014duetothefiber opticconverter failure
Intertrippingsystem 22kV/ 6.6kV
1.1. Current status of intertripping system :
Feeder A
Substation 01
22kV
6.6kV
MDB08RFR/SM
Tx Rx
Rx Tx
MDB08RFR/SM
FO Cable
Feeder B
Incomer A Incomer B
REF
542plu
s
REF
542plu
s
REF
542plu
s
Transformer A
Transformer B
Power Supply Unit
DC-DC Converter
(110VDC/48VDC)
ABL7 RP4803
Power Supply Unit
DC-DC Converter
(110VDC/24VDC)
ABL7 CEM24
Other substations
1. Upgrade PSU and change manufacturer of FOC
II. Intertripping system 22kV/ 6.6kV
o There is only one power supply unit Malfunction of this power unit could lead to
unwantedtripincomers/bustie. A part or wholeloadsof substationcouldbeblackout (risk).
o CurrentFiber OpticConvertershaveexperiencedmalfunctionbyitself:
+Type : MDB08RFR/SM
+Manufacturer : Equiptrans
Weak point:
II. Intertripping system 22kV/ 6.6kV
1.2. Proposal for improvement the intertrippingsystem :
Thenewtypeof Fiber Optic Converters, whichareequippedwithEmergencySwitchboards, haveno
experiencedmalfunctionsofar.
Feeder A
Substation 01
Substation 07
22kV
6.6kV
2S36 Transmitter
2P02 Input Module
(Weed Instrument)
Tx
Rx
2H09 Receiver
2K02 Output Module
(Weed Instrument)
Feeder B
Incomer A Incomer B
REF
542plu
s
REF
542plu
s
Transformer
A
Transformer B
Power Supply Unit
DC-DC Converter
Power Supply Unit
DC-DC Converter
TVS diode
TVS diode
Power Supply Unit
DC-DC Converter
Power Supply Unit
DC-DC Converter
TVS diode
TVS diode
Next page
Next page
II. Intertripping system 22kV/ 6.6kV
Feeder A
Substation 01
Substation 07
22kV
6.6kV
2H09 Receiver
2K02 Output Module
(Weed Instrument)
Rx
Tx
2S36 Transmitter
2P02 Input Module
(Weed Instrument)
Feeder B
Incomer A Incomer B
REF
542plus
REF
542plus
Transformer
A
Transformer B
Previous page
Previous page
1.2. Proposal for improvement the intertrippingsystem :
II. Intertripping system 22kV/ 6.6kV
o Redundancypower supplyunit Whenever oneof thepower supplyunit fails, theother
will continuously supply power to converter, not effect to operation of Fiber Optic
Converter/Intertripping system. The failure unit will be replaced by a new one without
interruptingthesystem.
o Newtypeof Fiber Optic Converter, whichinstalledinEmergency Switchboard, has not
experiencedmaltrippingsofar:
+Type : 2H09 Receiver and2K02 OutputModule
+Manufacturer : WeedInstrument
o History:
Nomalfunctionof fiber opticconverter hasbeenrecordedsofar
Advantage point:
II. Intertripping system 22kV/ 6.6kV
2. Modify wiring and logic inside protection relay REF542plus of two
incomers for all 6.6kV switchboards as per approved MOC-SS-13-115
BEFORE MODIFICATION
II. Intertripping system 22kV/ 6.6kV
BEFORE MODIFICATION
II. Intertripping system 22kV/ 6.6kV
AFTER MODIFICATION
II. Intertripping system 22kV/ 6.6kV
AFTER MODIFICATION
II. Intertripping system 22kV/ 6.6kV
Benefits:
In case of one incomer is opened by fault or maintenance, the remain incomer will
not be opened by intertripping signal to prevent blackout one substation;
This modification still satisfy the intertrip-interlock philosophy of this project
document no 8474L 000 J SD 1600 001
II. Intertripping system 22kV/ 6.6kV
No Description Schedule
1 - Upgrade to redundancy power
supply unit
- Change manufacturer of
converter
- Substation 7: November 2013
(Substation 7 already proceeded at
first, no issue has been recorded
since November 2013 so far
- Others substation: al ready done
at 2
nd
TA
2 Modify logic and hardwire for
REF542plus
as per approved MOC-SS-13-11
5
2
nd
TA (Apply for all substations)
3. Tentative schedule of modification:
Follow 775/TTr-BDSC dated 23
rd
May 2013 Plan for upgrading of intertripping system
between22kV and6.6/0,4kV, thescheduleof modificationshall beasfollows:
THANK YOU FOR YOUR ATTENTION
E.O.D