Professional Documents
Culture Documents
an air-conditioned system of more than 10kWr; and/or
a ventilation system with an air-flow rate of more than 1000L/s; and/or
heating systems of more than 10Kw
heating
.
Cl. J5.4
(A)
Please provide certification that systems providing heating or chilling for air-
conditioning systems will
have any piping, vessels, heat exchangers or tanks containing heated or
chilled fluid insulated in accordance with Specification J 5.4 (other than
those covered by Minimum Energy Performance Standards MEPS); and
where water is circulated by pumping at 2L/s
be designed so that the total of the motor shaft power to the air-
conditioning pump does not exceed:
2
3W/m for a building not more than 500m
4W/m
2
; and
2
for a building more than 500m
2
.
if the system contains more than one boiler, chiller or coil, be capable of
stopping the flow of water to those not operating.
Trevor R Howse & Associates Pty Ltd
- 30 -
Cl.
J5.4(B)
y
complying with table J5.4a, when tested in accordance with AS 7190.
Please provide certification that a boiler must achieve a thermal efficienc
J5.4(C)
g
g
b when tested in accordance with AS/NZS 3823.1.2 at test
condition T1.
Cl. Please provide certification that package air-conditioning equipment, includin
a split unit and a heat pump, will have an energy efficiency ration complyin
with table J5.4
J5.4(D)
ve an
g with table J5.4c when determined in
accordance with ARI 550/590.
Cl. Please provide certification that a refrigerant chiller over 125kWr will ha
energy efficiency ratio complyin
J5.4(E)
at rejected
from the refrigerant when determined in accordance with ARI 460.
Cl. Please provide certification that any air cooled condenser fan motor, (other than
one that is part of package air-conditioning equipment listed in part (c) above),
will not use more than 15W of motor shaft power for each kW of he
J5.4(F)
certification that the fan of a cooling tower will not use
of motor shaft power for each L/s of
, 590 W of motor shaft power for each L/s of cooling
water circulated.
Cl. Please provide
more than
if a propeller or axial fan, 310 W
cooling water circulated; and
if a centrifugal fan
J5.4(G)
certification that the fan of a closer circuit cooler will not use
of motor shaft power for each L/s of
, 670 W of motor shaft power for each L/s of cooling
water circulated.
Cl. Please provide
more than
if a propeller or axial fan, 500 W
cooling water circulated; and
if a centrifugal fan
J5.4(H)
certification that the fan of a evaporative condenser will not use
of motor shaft power for each kW of
, 22 W of motor shaft power for each kW of cooling
water circulated.
Cl. Please provide
more than
if a propeller or axial fan, 18W
cooling water circulated; and
if a centrifugal fan
J5.4(I)
er
n 150W of pump motor shaft
power for each L/s of spray water circulated.
Cl. Please provide certification that the spray water pump of a closed circuit cool
or evaporative condenser will not use more tha
Cl. J5.5
such as a stove in a commercial kitchen or a chemical bath in a
riable speed fan; and
Be designed to minimize the exhausting of conditioned air.
PLY TO
Please provide certification that a miscellaneous exhaust system with an air
flow rate of more than 10,000L/s (that is associated with equipment having a
variable demand
factory), will
Have the means for the operator to
reduce the energy used by the provision of a va
stop the motor when the system is not needed.
NOTE THAT THE ABOVE REQUIREMENTS DO NOT AP
lation is needed to balance the required
where air flow must be maintained for safe operation.
a sole-occupancy unit of a class 3 parts of a building; or
where additional exhaust venti
outside air for ventilation; or
Trevor R Howse & Associates Pty Ltd
- 31 -
Cl. J6.2
(A)
Provide certification that artificial lighting will
not exceed the maximum lamp power density of table J6.2a; or
in a bathroom, dressing room or the like, provide an average artificial light
source efficacy of not less than 40 Lumens/W.
Note that the maximum lamp power density in table J6.2a may be increased
by
30% for area of less than 20m
2
floor area; and
(other than class 3 buildings) 40% where artificial lighting is switched by a
motion detector or a corridor lighting timer in accordance with
Specification J6; and
15% where artificial lighting is switched (in response to varying natural
lighting levels) by a daylight sensor and dynamic lighting control device in
accordance with Specification J6.
Cl.
J6.2(B)
In the class 6, 7a and 9b parts of the building please provide certification that
for artificial lighting
the aggregate design illumination load will not exceed the sum of the
allowances obtained by multiplying the area of each space by the
maximum illumination power density in table J6.2b and dividing by
the illumination power density adjustment factor in table J6.2c (where
applicable).
In the class 6, 7a and 9b parts of the building please provide certification
that the aggregate design illumination power load in 1(i) above is the sum
of the design illumination power loads in each of the spaces served.
Cl.
J6.2(C)
In the class 6, 7a and 9b parts of the building please provide certification that
when determining the design illumination power load, {see (B) above}, that the
following will be used:
where there are multiplying lighting systems serving the same space
the total illumination power load of all systems; or
for a control system that permits only one system to operate at a time,
the design illumination lower load is
based on the highest illumination power load; or
determined by the formula {HxT/2 +P x (100-T/2)} as
detailed within this clause of the BCA.
Cl. J6.2
(notes)
Note: the requirements of (A) and (B) do not apply to:
Emergency lighting in accordance with Part E4.
Signage and display lighting within cabinets and display cases.
A heater where the heater also emits light.
Cl. J6.3
(A)
Please provide certification that artificial lighting will be individually operated
by a switch or other control device.
Trevor R Howse & Associates Pty Ltd
- 32 -
Cl.
J6.3(B)
Please provide certification that an occupant activated device, such as a room
security device, a motion detector in accordance with Specification J6 or the
like, will be provided in the sole-occupancy units of the class 3 parts of the
building to cut power to artificial lighting, air-conditioner, local exhaust fans
and bathroom heater, when the sole-occupancy unit is unoccupied.
Cl.
J6.3(C)
Please provide certification that an artificial lighting switch will
be located in a visible position
in the room or space being switched; or
in an adjacent room or space from where the lighting being switched is
visible.
not operate lighting within an area of more than
250m
2
for a space of not more than 2,000m
2
floor area; or
1,000m
2
for a space of more than 2,000m
2
floor area.
Cl.
J6.3(D)
Please provide certification that artificial lighting in a building or storey of a
building of more than 250m
2
will be controlled by
a time switch in accordance with Specification J6; or
an occupant sensing device such as a
security card reader; or
a motion detector in accordance with Specification J6.
Cl.
J6.3(E)
Please provide certification that artificial lighting adjacent windows will be
switched separately from artificial lighting not adjacent windows.
Cl.
J6.3(F)
NOTE
Note: The requirements of (A)(B)(C)(D) and (E) do not apply to the following:
emergency lighting in accordance with Part E4.
Cl.
J6.4(A)
Please provide certification that artificial lighting for any interior decorative and
display lighting will be controlled
separate controls to that of other artificial lighting; and
by a time switch in accordance with Specification J6 (only applicable
where the display lighting exceeds 7kW).
Cl.
J6.4(B)
Provide certification that window display lighting will be controlled separately
from other display lighting.
Cl.
J6.5(A)
Provide certification that artificial lighting around the buildings perimeter will
be controlled by either a daylight sensor or a time switch in accordance with
Specification J6; and
when the total perimeter lighting load exceeds 100 W
have an average light source efficacy of not less than 60 Lumens/W; or
be controlled by a motion detector in accordance with Specification J6
Trevor R Howse & Associates Pty Ltd
- 33 -
Cl.
J6.5(A)
(cont.)
when used for decorative purposes (such as faade lighting or signage
lighting), have a separate time switch in accordance with Specification J6.
Note: the requirements of (2) above do not apply to
emergency lighting in accordance with Part E4.
Cl. J6.6 Provide certification that power supply to any boiling water or chilled water
storage units will be controlled by a time switch in accordance with
Specification J6.
Cl. J7.2 Please provide certification that any hot water system used for food preparation
and sanitary purposes will be designed and installed as per Section 8 of AS/NZS
3500.4.
CL. NSW
J8.2
Please provide certification that access for maintenance will be provided to
all services and their components including:
Time switches and motion detectors.
Room temperature thermostats.
Plant thermostats such as on boilers or refrigeration units.
Outside air dampers.
Reflectors, lenses and diffusers of light fittings.
Heat transfer equipment.
all adjustable or motorized shading devices.
Author: Verified
DRAFT DRAFT
J ason Storer Hayden L Howse
Technical Manager Managing Director
for Trevor R. Howse & Associates Pty Ltd for Trevor R. Howse & Associates Pty Ltd
Trevor R Howse & Associates Pty Ltd