You are on page 1of 6

WHEN TO SWITCH WHICH SWITCH

IN A FIVE LEVEL SINGLE PHASE CASCADED INVERTER


Martina Calais , Vassilios G. Agelidis , and Michael S. Dymond
Australian Cooperative Research Centre for Renewable Energy (ACRE)
Centre for Renewable Energy and Sustainable Technologies Australia (CRESTA)
School of Electrical and Computer Engineering
Curtin University of Technology
email: pcalaism@cc.curtin.edu.au

PowerSearch Ltd

Abstract
A five level single phase cascaded inverter consists of two full bridges connected in series on the AC
side. Each bridge can create three different voltage levels at its AC output allowing for an overall
five level AC output voltage. Due to switch combination redundancies, there are certain degrees
of freedom of how to generate the five level AC output voltage. This paper presents and discusses
several different cyclic switching methods which minimise the switching frequency, equalise stress
on the devices and minimise the ripple on the DC filter capacitors.

I. INTRODUCTION
Multilevel inverters synthesize the AC voltage from
several different levels of DC voltages. Each additional
DC voltage level adds a step to the AC voltage waveform. By switching the DC voltages to the AC output a
staircase waveform can be produced which approaches
the sinusoidal waveform with minimum harmonic distortion. Compared to a full bridge inverter which can
generate two or three level voltage waveforms at its AC
output, a multilevel inverter has the following advantages:

If the number of DC bus voltage levels is high, a


near-sinusoidal staircase voltage can be generated
with only fundamental frequency switching. Fundamental frequency switching minimises switching
losses and is particularly suitable for high power
high voltage applications such as large induction
motor drives or static VAr compensators, where
GTOs with limited switching frequencies are applied
[1][2][3].
When the number of levels is sufficiently high, harmonic content will be low enough to avoid the need
for filters [1].
High voltages on the DC side do not have to be
blocked by one switching device only, but a number
of switching devices in series (the number of switching devices depends on the chosen multilevel converter topology and the number of levels). Due to
the division of the DC bus in several levels of voltages, switching devices in a multilevel inverter can
be rated at lower voltages compared to switching devices applied in a full bridge inverter [1][4].

Some multilevel converter topologies such as the flying capacitor multilevel converter and the cascaded
multilevel converter provide switch combination redundancies. These redundancies are advantageous
in several ways: For example, they can be used for
balancing the different voltage levels, for minimising the switching frequency, and for employing each
switching device equally, hence avoiding asymmetrical wear and asymmetrical temperature distribution
within the converter [5][1].
Fast dynamic response of a multilevel inverter can be
achieved by switching larger voltage steps to the
output. Due to the flexibility arising from the accessibility of different DC potentials, control schemes
can be tailored depending on the application of the
inverter [5].

Various multilevel topologies, such as the diode


clamped, flying capacitor, magnetic coupled or
cascaded converters, are known from the technical
literature [6][7][1]. In [8] several multilevel topologies
have been compared for the implementation in a
specific application: A transformerless, single phase,
grid connected photovoltaic (PV) system. A five level
cascaded inverter has been identified as a suitable
solution and as part of a joint research project between
the Centre for Renewable Energy and Sustainable
Technologies Australia (CRESTA) and PowerSearch
Ltd a prototype system is now under development. In
this paper two characteristics of the five level cascaded
inverter are investigated: Its switch combination redundancies and the accessibility of different DC voltage
levels. Due to this flexibility, the operation of the
inverter in the grid connected photovoltaic application

can be optimised.
The paper is organised as follows: First the five
level cascaded inverter and its switch combinations
are described in section II. Then three different ways
of when to switch which switch in the inverter (three
different switching sequences) are discussed. First
a solution suggested for a high power application
presented in [5] will be analysed in section III. Based
on this concept, switching sequences for a cascaded
inverter implemented in a transformerless, single phase
PV system have been developed and are described in
section IV. Results of simulations performed using the
simulation package PSCAD/EMTDC (Version 2.00)
[9][10][11] are included. Section V and VI summarise
and conclude the analysis and list the advantages of
each of the switching sequences.

Fullbridge 1

Da1 Sb1

Db1

E1
Sa2

Da2 Sb2

Db2

Dc1

Sd1

Dd1

Dc2

Sd2

Dd2

E2
Sc2

Fullbridge 2

Fig. 1 Cascaded Five Level Inverter.

VI
V

-E
-2E

20

10
time (ms)

Fig. 2 Example of the cascaded inverter output voltage. The


intervals I - VI indicate the different modes the inverter operates in.

State
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Full bridge 1

Full bridge 2

Table 1 Inverter states of cascaded five level inverter.

level voltage can look like is shown in Fig. 2. for a


control signal frequency of 2 kHz. One period (20 ms
for a 50 Hz signal) can be divided into 6 intervals,
each representing a different operational mode of
the inverter. Although e.g. mode I and mode III are
identical with respect to output voltage levels, the
mode information is important for the generation of the
switching signals and in particular for generating an
optimised switching sequence as will be described in
section IV.
The cascaded inverter as shown in Fig. 1 has 16
inverter states which allow bi-directional current flow
and a fixed inverter output voltage. They are listed in
the following is valid:
Table 1. For

v inv
Sc1

IV

II

The five level cascaded inverter as shown in Fig. 1


consists of two single phase full bridges with 4 switching devices each. Each individual full bridge has 16
possible inverter states. Of these 16 inverter states only
4 inverter states allow bi-directional current flow and a
fixed inverter output voltage.
Combining two full bridges with their AC side
connected in series results in the addition of the individual full bridge output voltages. Since each bridge
can create three different voltage levels at its AC output
this allows for an overall five level AC output voltage
of the cascaded inverter. An example of how this five

III

II. A FIVE LEVEL SINGLE PHASE CASCADED INVERTER

Sa1

inv

2E

, four possible states

, one possible state


, four possible states
, one possible state
, six possible states

However, two of the inverter states (states 15 and 16,


across the
see Table 1) creating a voltage
load, switch a positive voltage from one bridge and a
negative voltage from the other bridge resulting in a
cancellation of the voltages only if they are identical.

decrease
ON

As shown above except for generating the voltages and there are degrees of freedom as
how to generate 0, or at the inverter output.
or , each can be generated in four ways, 0 can be
generated in 6 ways. Utilising only 5 of the inverter
states to generate the five level voltage waveform at the
output would not be convenient out of the following
reasons [5]:

The semiconductor switching devices would be used


in an asymmetrical way, with the result that their
thermal problems and wear would be asymmetrical,
too.
The minimum dead times of the semiconductor
switching devices limit the switching frequency of
the inverter. However, with the cascaded inverter
the degrees of freedom given with the many inverter
states can be used to extend the on times of the
semiconductor devices to as long as possible, thus
reducing the problems arising from minimum dead
times. This is an advantage especially for high
power application where GTO devices with low
switching frequency capability are used.

III. A CYCLIC SWITCHING SEQUENCE FOR A


HIGH POWER APPLICATION
The five level cascaded inverter and its control scheme
described in [5] has been implemented in a non conventional high power application: a converter for plasma
stabilisation with a peak power of 3.6 MVA. A cyclic
switching sequence with the following characteristics
is proposed:

a1

b2

a1

b2

c1

d2

c1

d2

OFF

increase

increase

a1

b2

c1

d2

= 0 E
inv
12 2
(State 3)

= -E E
inv
1 2
(State 15)

(State 11)
v
= 0 0
inv
12 22
decrease

a1

b2

c1

d2

=E 0
inv
1 22
(State 1)

How the above objectives are realised is shown in


Fig. 3 as an example for the modes I and III. In
these modes the inverter voltage when it needs to
and when it needs to
be increased takes the level
be decreased takes the level 0. The cyclic switching
sequence in modes I and III cycles through the states
in the following way: 11-3-15-4-14-2-16-1-11-.. (and
so forth). Indicated through shaded areas in Fig. 3 are
the on-states of the switches , , , and , which

c1

d2

inv

=0

11

E
2

decrease

increase

a1

b2

c1

d2

a1

b2

c1

d2

a1

b2

c1

d2

=0
0
inv
11 21
(State 14)

decrease
v

= E -E
inv
1
2
(State 16)

=E
0
inv
1
21
(State 2)

Fig. 3 Cyclic switching sequence as described in [5]. Operation in


modes I and III.

when switched on contribute to an increase in inverter


output voltage. The on-states for the switches , ,
and are complementary to the on-states of , ,
, and .
IV. CYCLIC SWITCHING SEQUENCES FOR
LOW POWER PHOTOVOLTAIC APPLICATIONS
Fig. 4 shows the application of the five level single
Cascaded Inverter

I1

a1
C
1

L inv
V
inv

I2
C

V
L

i inv

E1
b2

The turn-on time and turn-off time of each switching device are spaced out as much as possible. As a
result the frequency of the voltage pulses at the inverter output is four times higher than the switching
frequency of each switch.
The states 15 and 16 are used to generate a zero voltage at the inverter output by switching the two DC
bus voltages to cancel each other out.
The two DC sources are discharged intermittently by
changing from one source to the other after every
fourth switching instant.

b2

(State 4) v

increase
v

a1

Vgrid

c1
2

E2
d2

E 1 I1 I2 E 2

Switching Signals
Current
Controller

MPPT
E 1ref

E 2ref

DC
Voltage
Controller

^i

ref

i inv

ref

Current
Reference Value
Generation

Vgrid

System Control

Fig. 4 A cascaded inverter for a transformerless single phase low


power grid connected photovoltaic system. In the given application
the inverter switches are MOSFETs with body diodes which are
capable of conducting the full rated current of the MOSFET.

phase cascaded inverter in a transformerless gridconnected PV system. One characteristic of this system
which will be discussed in more detail in this section
is the necessity for sufficiently high DC bus voltages.
Due to the step down nature of the topology and since
the system avoids the transformer the sum of the DC

Control signal

a)

The realisation of the above objectives results in a


switching sequence as shown in Fig. 5 (again as an

1.5

p.u.

1
0.5
0
-0.5
Gate signal a1
1.5

b)

1
0.5
0
-0.5
Gate signal b2

c)

1.5
1
0.5
0
-0.5
Gate signal c1

d)

1.5
1

p.u.

1. The switching frequency of each switch is minimal.


To achieve this, one objective when choosing the
switching sequence is to keep switches on as long
as possible.
2. Each switch should be stressed in the same way in
order to achieve equal losses in each switch and with
that an equal temperature distribution.
3. Over one period the amount of power extracted from
both arrays should be the same. Both sources should
be loaded symmetrically in the case of a PV system.
The switching pattern has to take this into account.
It is e.g. not possible to only discharge source to
and
generate a voltage level of
at the output.
4. The ripple in the DC bus capacitors should be minimal since this causes losses and increases cost.

With this optimised switching sequence regarding


DC bus voltage ripple (intermittent source discharge)
and equalising the loading of each switch (equalising
thermal stress over all switches) can be achieved.
Simulation results for one positive half cycle show

p.u.

When considering the cascaded inverter for this


particular application the above described switching
sequence can be further improved. The objective
is to find a switching sequence with the following
characteristics:

Besides optimising the switching sequence within


the modes (I-VI), the switching transitions when
changing from one mode to the other can be optimised.
The aim is here to avoid high frequency switching, but
to leave switches on as long as possible. 6 cases, that is
every changeover from one mode to the next, and all
possible inverter states have to be considered.

p.u.

bus voltages has to be higher than the grid voltage at


all times. Only then power can be transferred from the
PV sub-arrays to the grid.

0.5
0
-0.5
Gate signal d2

e)

1.5

p.u.

decrease

a1

ON

b2

a1

0.5
0

b2

-0.5

OFF

b2

c1

d2

c1
v

d2

c1

= 0 E
inv
12 2
(State 3)

f)

d2

=0
0
inv
12 21
(State 12)

6
4.6

a1

b2

c1

d2

a1

i inv

increase

increase

3.2
1.8
0.4
-1

g)

= 0

inv
decrease

12 22

a1

b2

(State 11)

(State 2)

=E
inv
1

21

decrease

a1

600
450
300
150
0
-150
-300

b2

E
266

h)

inv

E 2

c1

d2
increase

inv

increase

c1

d2

264
262
260
258

=E 0
1 22
(State 1)

a1

c1

b2

a1

d2

c1

b2

=0

inv
11 21
(State 14)

d2

decrease
v

=0 0
inv
11 22
(State 13)

=0
E
inv
11 2
(State 4)

Fig. 5 Optimised cyclic switching sequence for a PV system.


Operation in modes I and III.

example for modes I and III). When comparing Figs. 3


and 5 it can be seen that in Fig. 5 the states 15 and
16 are avoided and states 12 and 13 are used instead.
Also the two sources are discharged intermittently. The
energy is transferred to the AC side by alternating from
source to source every second switching instant.

256

time (ms)

Fig. 6 Simulation results: Polarised Ramptime ZACE current control


method and cyclic switching sequence, =4 mH,

600 F, =5 A, (a) control signal ( 10 kHz),


(b)-(e) gate signals for switches a1, b2, c1, d2 (see Fig. 4)( 2.5
kHz), (f) unfiltered inverter output current , (g) inverter output
voltage , (h) DC bus voltages and .

the cyclic switching sequence in conjunction with the


Polarised Ramptime Zero Average Current Error (Polarised Ramptime ZACE) control method [12] in Fig. 6.
However, as can be seen in Fig. 6, during the
mode changes the di/dt may become very small. Due
to different temperatures but also due to shading effects

10

Due to the problem outlined above it is suggested


to operate the inverter during the transitions from mode
I to mode II, mode II to III, mode IV to V, and mode
V to VI as a normal full bridge in a bipolar way,
switching between zero states and in the positive
half wave (as shown in Fig. 8g) or between zero states
and for the negative half wave respectively. In
the following the transition periods where bipolar operation is necessary will be referred to as intermediate
modes. Fig. 7 indicates these intermediate modes for
400

E max

II

III

voltage ( =196 V) are indicated as well as a grid


voltage with an amplitude of 340 V. It is unlikely that
the voltage difference between the two PV sub-arrays
will be that high in practice, a voltage difference of up
to 20 V is more realistic.
Control signal

a)

1.5

p.u.

1
0.5
0
-0.5
sa1s
1.5

b)

p.u.

1
0.5
0
-0.5
sb2s

c)

1.5

p.u.

1
0.5
0
-0.5
sc1s

d)

1.5

p.u.

1
0.5
0
-0.5
sd2s

e)

1.5

p.u.

1
0.5
0
-0.5

i
f)

inv

4.6
3.2
1.8
0.4
-1

g)

inv

600
450
300
150
0
-150
-300

E
h)

it cannot be guaranteed that the two PV sub-array


operate at the same DC voltages. In fact it is desirable
to operate them individually and to adjust each DC
voltage so that each PV sub-array operates in its
Maximum Power Point (MPP) in order to minimise
mismatch losses. However, operating the two PV
sub-arrays at different voltage levels complicates the
control. Previously it was discussed that the inverter
operates in 6 different modes (see Fig. 2). However,
now when considering different PV sub-array operating
voltages, at the mode changes between mode I and
II, I and III, IV and V, and V and VI control can be
lost if one of the PV sub-array voltages is used to
determine the mode change. For example, in the case
that the PV sub-array with the lower operating voltage
is used to determine the mode change from mode I to
or ),
mode II (instant where
then at the beginning of mode II
.
In order to be able to increase the current through
the inductor (see Fig. 4) the voltage across
the inductor has to be positive, which is ensured:


.
However, to be able to decrease the current the voltage
across the inductor has to be negative. Since the PV
sub-arrays are discharged intermittently two cases can

or
occur:


. The last case
is critical and may lead to loss of control. Under the
same conditions the mode change from mode IV to V
is critical. Similarly, if is used for determining
the mode changes, at the mode changes from mode II
to III and V to VI control can be lost.

265
260
255
250
245
240
235

time (ms)

Fig. 8 Simulation results: Polarised Ramptime ZACE current control


method and cyclic switching sequence considering intermediate
modes, =4 mH,
600 F, =5 A, (a) control

signal ( 10 kHz), (b)-(e) gate signals for switches


a1, b2, c1, d2 (see Fig. 4)( 2.5 kHz), (f) unfiltered inverter
output current , (g) inverter output voltage , (h) DC bus
voltages and .

200

Grid Voltage (V)

->

<-

->

min

<-

->

Intermediate Modes

->

<-

<-

-200

IV

VI

-400
0

10

time (s)

15

20
-3

x10

Fig. 7 Intermediate modes location and length under average grid


voltage amplitudes ( =340 V).

an extreme case: The highest assumed PV sub-array


voltage ( =284 V) and the lowest PV sub-array

By introducing the intermediate modes better controllability is gained which is necessary in the case of the
grid connected application, however, the trade-off is a
higher total harmonic distortion and a broader spectrum
of the output voltage and current waveforms which are
shown in Figs. 8f and g. The simulated case again uses
the Polarised Ramptime ZACE current control method
and allows for different PV array voltages without
loosing control at the mode changes.
V. DISCUSSION
Table 2 summarises the advantages of each of the three
discussed switching sequences. All three methods min-

10

imise the switching frequency, achieve equal switch


stress and load both PV sub-arrays intermittently and
equally. Regarding the desirable minimisation of the
voltage ripple on the DC bus capacitors, methods 2 and
3 are favourable to method 1, because at every second
switching instant the source is changed and not at every
fourth. Method 2 is suitable in a system where the DC
bus voltages are equal. Method 3 can be applied in a
system with un-equal DC bus voltages. Using method
3, at the mode changes, the inverter is operated in a
bipolar way to guarantee controllability. The price for
the controllability is a higher harmonic distortion of the
inverter output current and a slightly higher switching
frequency.
VI. CONCLUSION
To cater for the particular demands of a PV application
a cyclic switching sequence proposed in [5] has been
adjusted so that minimum switching frequencies, minimum ripple on the DC bus capacitors and equal stress
on all switches are obtained. Since equal DC voltages
cannot be guaranteed at all times in the proposed PV
system the inverter states where the two DC voltages
cancel each other out in order to generate a zero
voltage at the inverter output are avoided. When the
DC bus voltages are un-equal, additional constraints
have to be considered. Here loss of control may occur
at the mode changes and a bipolar operation of the inverter in short intervals between the modes is necessary.
VII. ACKNOWLEDGEMENTS
The authors would like to thank Lawrence Borle who
has contributed to this paper with valuable discussions
and his tremendous help with the simulations. The
work described in this paper has been supported by
the Alternative Energy Development Board and the
Australian Cooperative Research Centre for Renewable
Energy (ACRE). ACREs activities are funded by the
Commonwealths Cooperative Research Centres Program. Martina Calais has been supported by an ACRE
Postgraduate Research Scholarship. Thanks also go
to CRESTA and PowerSearch LTD for providing the
research facilities.
VIII. REFERENCES
[1] Lai, J., and Peng, F., Multilevel Converters-A New
Breed of Power Converters, IEEE Transactions on Industry Applications, May/June 1996, vol. 32, no. 3,
pp. 509517.
[2] Peng, F., Lai, J., McKeever, J., and VanCoevering, J.,
A Multilevel Voltage-Source Inverter with Seperate
DC Sources for Static Var Generation, IEEE Transactions on Industry Applications, September/October
1996, vol. 32, no. 5, pp. 11301138.
[3] Tolbert, L., Peng, F., and Habetler, T., Multilevel Converters for Large Electric Drives, IEEE Transactions on
Industry Applications, January/February 1999, vol. 35,
no. 1, pp. 3644.

Method
Sequence by
[5]

Sequence
suitable
for equal DC
bus voltages

Sequence
suitable for
un-equal DC
bus voltages

Advantages
- Switching frequency minimisation
- Symmetrical loading of sub-arrays
- Equal switch stress
- Easy analogue realisation
- Switching frequency minimisation
- Symmetrical loading of sub-arrays
- Equal switch stress
- Ripple on DC bus capacitors minimised
- Symmetrical loading of sub-arrays
- Equal switch stress
- Ripple on DC bus capacitors minimised
- Controllability guaranteed for unequal sub-array voltages

Table 2 Advantages of the three discussed cyclic switching


sequences.

[4] Manjrekar, M., and Venkataramanan, G., Advanced


Topologies and Modulation Strategies for Multilevel Inverters, Proceedings of the 1996 IEEE 27th Annual
Power Electronics Specialists Conference, 1996, vol. 2,
pp. 10131018.
[5] Marchesoni, M., High-Performance Current Control
Techniques for Applications to Multilevel High-Power
Voltage Source Inverters, IEEE Transactions on Power
Electronics, January 1992, vol. 7, no. 1, pp. 189204.
[6] Nabae, A., Takahashi, I., and Akagi, H., A New
Neutral-Point-Clamped PWM Inverter, IEEE Transactions on Industry Applications, September/October
1981, vol. IA-17, no. 5, pp. 518523.
[7] Meynard, T., Fadel, M., and Aouda, N., Modeling of
Multilevel Converters, IEEE Transactions on Industrial
Electronics, June 1997, vol. 44, no. 3, pp. 356364.
[8] Calais, M., Agelidis, V., and Meinhardt, M., Multilevel Converters for Single-Phase Grid Connected Photovoltaic Systems - An Overview, Solar Energy, 1999,
vol. 66, no. 5, pp. 325335.
[9] Manitoba HVDC Research Centre, PSCAD/EMTDC
Manual, Manitoba HVDC Research Centre, 1994.
[10] Gole, A. M., Nayak, O., Sidhu, T., and Sachdev, M., A
Graphical Electromagnetic Simulation Laboratory for
Power Systems Engineering Programs, IEEE Transactions on Power Systems, May 1996, vol. 11, no. 2,
pp. 599606, available on the Internet, www.hvdc.ca.
[11] Nayak, O., Irwin, G., and Neufeld, A., GUI Enhances
Electromagnetic Transients Simulation Tools, IEEE
Computer Applications in Power, January 1995, vol. 8,
no. 1, pp. 1722.
[12] Borle, L., A Three-Phase Grid-Connected Inverter with
Improved Ramptime Current Control in Programmable
Logic, Conference Proceedings of the 1998 IEEE International Conference on Power Electronics Drives and
Energy Systems for Industrial Growth, PEDES 98,
Perth, Australia, December 1998, vol. 1, pp. 452457.

You might also like