You are on page 1of 7

0oc r.

20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

1/7
ABB S.p.A. PPD Unita Operativa ADDA - HV


FAST EARTHING SWITCH










































0oc r. 20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

2/7
ABB S.p.A. PPD Unita Operativa ADDA - HV
INDEX


1. GENERAL....................................................................................................................3
2. DESCRIPTION.............................................................................................................3
2.1 Housing................................................................................................................3
2.2 Contacts...............................................................................................................3
2.3 Mechanism (spring group)..................................................................................3
2.4 View port ..............................................................................................................3
3. Working principle .......................................................................................................3
4. MAINTENANCE...........................................................................................................3
5. DIMENSIONS...............................................................................................................4














CONTENTS OF FIGURES


Figura 1 - FES open position with spring charged .........................................................5
Figura 2 - FES moving.......................................................................................................5
Figura 3 - FES close position with spring discharged....................................................5
Figura 4 - Front view..........................................................................................................6
Figura 5 - lateral view ........................................................................................................6















0oc r. 20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

3/7
ABB S.p.A. PPD Unita Operativa ADDA - HV


1. GENERAL

Fast Earthing Switch SBT/R 145-170 kV consists of three separate poles driven by mechanical
drive BES 7 (see related manual). Energy needed for fast closing operation of earthing switch is
stored in two springs.
2. DESCRIPTION
2.1 Housing
Housing (1) is made in Aluminium casting including two flanges (2) to connect contiguous
components; it is pre-set for operating shaft incoming (3). Housing is closed on side by a cover on
which view port and fixing points for earthing plait are mounted.
2.2 Contacts
They include: a mobile contact (5); contact fingers (6) fastened on the bar (7); contact shaft (3);
fixed contact (8) fastened on the cover (9) where the view port is assembled (10).
2.3 Mechanism (spring group)
Each mechanism is made of: one spring (11) mounted on a spring guide (12) operated by drive
shaft (3) through charging spring shaft (13).
Shock-absorber (14) and lateral plates (15) complete the device.
2.4 View port
The position of mobile contact (5) is visible across a view port (10) mounted on the adjacent cover
(9).

3. WORKING PRINCIPLE

SBT/R is shown in open position (figure 1), with closing spring charged.
Contact is moving slowly till the dead center position (figure 2), overcome this point, mobile contact
begin moving fast to close position (figure 3).

4. MAINTENANCE

For regular condition of exercise no maintenance is required.
The SBT/R can carry out two closing operations at 40 kA - 100kA peak, without any reduction of
insulation level. Subsequentely maintenance is needed and consists in substitution of mobile and
fixed contacts and SF6 gas replacement for gas compartment where FES is allocated.







0oc r. 20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

4/7
ABB S.p.A. PPD Unita Operativa ADDA - HV
5. DIMENSIONS







Dimensions are not binding.
Due to technical improvement afterwards,
ABB P.T. U.O. Adda has the right of
varying dimensions and characteristics
without forewarn

0oc r. 20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

5/7
ABB S.p.A. PPD Unita Operativa ADDA - HV


Figure 1 Fast Earthing Switch open position with spring charged












Figure 2 Fast Earthing Switch moving













Figure 3 Fast Earthing Switch close position with spring discharged














LEGENDA:
1- Housing
2- Flange
3- Operating shaft
4- Fixing point for
earthing plait
5- Mobile contact
6- Finger contact
7- Bar
8- Fixed contact
9- Cover
10-View port
11- Spring
12- Spring guide
13- Charging spring
drive
14-Shock absorber
15- Lateral plates
16- Contact sheet

0oc r. 20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

6/7
ABB S.p.A. PPD Unita Operativa ADDA - HV






















Figura 4 Frontal view

Figura 5 Lateral view


1

2
3
4
5
1

2
LEGENDA:
1- Transmission box
2- Spring Group
3- View port
4- Transmission shaft
5- FES Drive BES 7


0oc r. 20JAZ00103
Rev. A 05/2008 [Al|
Type ol 0ocurerl
Varua|
T|l|e
Fasl Earlr|rg 3W|lcr

7/7
ABB S.p.A. PPD Unita Operativa ADDA - HV

NOTES
If you have comments we kindly ask you to write that here below and send us this page back.
Thank you for your collaboration


























Copyright
We reserve all rights to this document and to the object described therein. The recipient of this document
recognizes these rights and will not without our prior written approval make this document available either in
part or in whole to any third party or use it for any purpose other than that for which it was presented to him.
ABB PT S.p.A

Address
ABB S.p.A PPD U.O. Adda - HV
Via dei Ceramisti
26900 Lodi Italy
tel. +39.0371 452.1
fax +39.0371 452.222
internet : http://www.abb.it

Notes
These instructions describe high-tech high voltage products, and are specifically aimed at explaining the use
of such
products. These instructions are not meant to replace valid regulations, concerning high voltage systems and
appliances, and are intended for use by specialists in the electricity field.