Professional Documents
Culture Documents
with c
f,o
= 2 for all cases. The end
effect is calculated from clause 7.13, which uses table 7.16 and figure 7.36 to obtain the factor. Section 1
is valid for signs as all will be less than 15 m long. We read the rule in this case as = 2 l/b, which is
where this method is more conservative than the National Annex. Fig 7.36 gives a reduction factor
based on the aspect ratio with a solidity ratio of 1 being valid for signboards.
2.10 The National Annex to BS EN 1991-1-4 will replace table 7.16 (ref. 1) with table NA.5 (ref. 3). This
results in a change of formula for the slenderness ratio to: = l/b.
2.11 The limit values are as follows:
Code l/b
c
f
EN 1991-1-4 1 2 0.63 1.26
NA to BS EN 1991-1-4 1 1 0.6 1.2
EN 1991-1-4 30 60 0.9 1.8
NA to BS EN 1991-1-4 60 60 0.9 1.8
Using this method no signs will have a c
f
close to 1.8.
2.12 It is important to note here that the reference height used in the design of elements is to the top
of the element and not the centre of the area as it is for signs. This does not directly affect the
calculations for c
f
but may be relevant when considering this method for use on signs.
Design wind load to BS EN 1991-1-4
2.13 The examples in Appendix C show the detailed method for calculating wind load to
BS EN 1991-1-4 and its UK National Annex. There are two methods for calculating c
e
(z). Both are based
on the current (August 2007) draft National Annex to BS EN 1991-1-4. The first uses formula NA.3 using a
terrain category of II, which does not use distance from the shoreline. The second method uses the
shortened formula where orography is not significant and the factor for c
e
(z) is taken from table NA.7 for
a known distance from the shoreline. The example calculations use the look up table NA.7, which is
simpler to use.
2.14 The wind speeds are defined by the wind map in the National Annex (ref. 3). The height to the
centroid is defined in BS EN 1991-1-4 fig 7.21 (ref. 1) and used in equation 4.8 in clause 4.5, which is then
used in clause 5.3 equation 5.3. The wind force is therefore defined using the height to the centre of the
sign. Note that equation 4.8 is replaced by equation NA.3 in clause NA 2.17 in the National Annex.
2.15 BS EN 1991-1-4 equation 5.3 clause 5.3 uses a structure factor c
s
c
d
which is calculated in equation
6.1 in Clause 6.3.1. This factor is not used in the calculations as it is considered insignificant for traffic
signs. The National Annex to BS EN 1991-1-4 clause NA 2.20 (ref. 3) gives guidance on the calculation of
c
s
c
d
, which for most signs will be near 1.0.
2.16 The examples do not include the orography factor calculated to clause 4.3.3. This is rarely
significant but should be included at the calculation of q
p
(z). For areas with potential for wind funnelling
expert advice must be sought.
Wind Load values from the National Annex to BS EN 12899:2007
2.17 The wind values given in Table NA.2 are based on calculations using both BS EN 1991-1-4 methods
and taking the more conservative result. The height bands were reviewed to get the most efficient wind
10 SIGN STRUCTURES GUIDE
value for each region. The limit on overall sign height of 7 m was chosen because HA standards require
signs taller than this to have design and check certificate signed by a chartered engineer.
2.18 The wind values assume category II terrain roughness. Terrain categories are defined in
BS EN 1991-1-4:2005, clause 4.3.2, and category II and higher are the predominate terrain roughness
parameters in the country. The wind load values would be excessively conservative if they all were
based on the higher category I or 0. The values given cover the majority of situations with limitations of:
maximum altitude; wind velocity grouping, etc. If a particular site falls in terrain category I or 0 then
detailed design will be required. Exposure factors are related to the height, the smaller the height the
greater the effect of the terrain roughness (terrain category). The relationship is not one that can be
simplified into a general rule.
2.19 The reference heights for the wind values in the National Annex are from ground level to the top
of the sign, rather than to the centroid. If the height to the centroid of the sign(s) is greater than H,
then the limiting overall heights 4 m and 7 m in the table should be reduced to 3 m and 5.25 m
respectively (unfortunately these heights are incorrectly stated as 3.25 m and 5 m in Note 7 to table NA.2
in the BS EN 12899-1:2007 National Annex).
2.20 The wind load values for a distance greater than 5 km from the shoreline in table NA.2 are valid
except in the following areas: the small area approximately 10 miles to the south of Cape Wrath in north-
west Scotland, Cornwall west of Falmouth, and Ynys Mn (Isle of Anglesey) in Wales. These areas should
be treated as if they were entirely within 5 km of the shoreline.
2.21 The example calculations are based on the wind load values in the National Annex to BS EN 12899-
1:2007. The values for c
f
in the lookup table in the National Annex are based upon the EN 1991-1-4
procedure for thin structural elements, which is an improvement on the conservative value of 1.8
recommended for signboards. The method used to calculate c
f
is in accordance with BS EN 1991-1-4
which is slightly more conservative than the method in its National Annex. In the example calculations
we have not shown interpolation from the table for c
f
though it would be acceptable.
2.22 The table NA.2 gives a maximum sign height of 7 m, which is rarely exceeded in practice. For the
higher signs the designer should use the more rigorous method, as on trunk roads these will require
certification as Category 0 structures in accordance with BD 2/05.
2.23 The Wind Load values in Table NA.2 are subject to the following caveats:
The values are only valid up to an altitude of 250 m.
The values are only relevant where there is no local funnelling effect, or significant orography as
defined in clause 4.3.3 and Annex A.3 of BS EN 1991-1-4 (cliffs / escarpments or sites with local
funnelling effects).
SIGN STRUCTURES GUIDE 11
3. BACKGROUND INFORMATION ON SUPPORT DESIGN
3.1 The Ultimate Limit State (ULS) load effects are a combination of bending moment, shear and
occasionally torsion. These are generally all at maximum at the top of the connection to the foundation.
At the Serviceability Limit State (SLS) the structure has not permanently failed but is not performing
adequately, in the case of a traffic sign because it is deflecting too much in the wind. For the less
harmful SLS a lower wind pressure is used and the partial action (safety) factor is 1.0.
3.2 The design effects are calculated from simple analysis of loads on a cantilever including the load
factors.
3.3 The designer should have access to the characteristic properties of the proposed supports. These
can be developed from first principles by calculating the section area, second moment of area, etc., or
from the manufacturers published properties for individual products. The characteristic property is
defined as that which 95% of the products will achieve (not the average). This is calculated by statistical
analysis of test results when carried out. These values are reduced by a factor
m
(given in Table 7 of BS
EN 12899:2007) to allow for the variability of the material. The selection of the support is based on the
simple criterion that the capacity of the post must be greater than the load effect.
3.4 The example calculations take no account of wind pressure on the supports themselves, i.e. on the
area below the sign plate that is exposed to wind. It has been shown that this has about 2% effect on
the overall loads based on a height to the centroid of the sign, which is conservative. This is considered
insignificant. If the designer wishes to include a value to allow for this it is suggested that use of
f3
=1.05
would be adequate.
3.5 The calculations do not show an example where torsion may be significant. This may occur where
the sign plate is positioned eccentrically to a single post or where the sign is part shielded by an
obstruction that eliminates wind loading on part of it, or when a point load of 500 N (class PL3) on the
extremity of the sign is considered. The use of an eccentricity of 0.25 the width of the sign
(recommended in BS EN 1991-1-4 clause 7.4.3 (2)) is considered excessive. It is suggested that the
maximum torsion is achieved with the maximum wind loading on the area of sign plate one side of the
post and that the associated bending be calculated using wind on only this area and not the whole sign.
Where torsion is significant the sign support should be checked for a combined load effect.
3.6 The shear capacity check is given but in practice it is likely only to be significant for large signs at low
mounting heights.
3.7 The deflection calculation is different to the previous method to BS 873, as it is checked at the top of
the sign where maximum deflection occurs, not at the centroid. As the acceptable deflection is
expressed in millimetres per metre height, this makes little difference in practice.
12 SIGN STRUCTURES GUIDE
4. FOUNDATION DESIGN
Design of spread foundations
4.1 The design of spread foundations is based on the calculation of stability against sliding and
overturning of the base and maximum bearing pressure, while ignoring all passive resistance of the soil.
The design uses unfactored loads and resistance and the factor of safety for overturning and sliding is
calculated. These are considered safe if the factor of safety is greater than 1.5. The maximum bearing
pressure is calculated on the assumption of poor soils, as experience has shown that little investigation
is carried out prior to installing signs. It is good practice, but not essential, to aim for the resulting force
to be within the middle third of the base. The equations for the alternative cases where the reaction is
inside or outside the middle third will not be correct if the wrong one is chosen. For example, if q
min
is
negative the reaction is outside the middle third. The most efficient base is achieved with minimum
depth and length (parallel to the sign face), and increasing the width (parallel to the road) to achieve
stability. It is recommended that bases for posts are reinforced to accommodate bending effects and
pull-out of anchorages where used. This may be omitted for smaller signs and squarer bases where it
can be shown that bending is not significant.
4.2 The allowable bearing pressure used in the calculations is the minimum value which permits
design to proceed with limited ground investigations. It is possible to improve upon this for known
founding material.
Design of planted foundations to BD 94/07
4.3 Planted foundations are based upon the method in the Highways Agency standard BD 94/07,
which is also used for the design of lighting column bases. The design uses unfactored loads and
resistance and calculates the factor of safety for overturning of the foundation. The stability of this type
of foundation relies on the passive resistance of the soil surrounding the foundation which must be well
compacted, and the required factor of safety is the lesser value of 1.25. For this reason we do not
recommend the use of planted foundations on a slope or near ditches or excavations without consulting
a structural or geotechnical engineer.
SIGN STRUCTURES GUIDE 13
APPENDIX A: Table NA.2 of National Annex
The IHIE regrets that for copyright reasons is not possible to include
table NA.2 in this version downloaded from the Internet. To obtain a
copy of the Guide containing table NA.2 please contact the IHIE at:
deputy@ihie.org.uk
British Standards can be obtained in PDF or hard copy formats from the BSI online shop:
www.bsigroup.com/shop, or by contacting BSI Customer Services for hard copies only:
tel: 020 8996 9001, email: cservices@bsigroup.com
14 SIGN STRUCTURES GUIDE
The IHIE regrets that for copyright reasons is not possible to include
table NA.2 in this version downloaded from the Internet. To obtain a
copy of the Guide containing table NA.2 please contact the IHIE at:
deputy@ihie.org.uk
SIGN STRUCTURES GUIDE 15
The IHIE regrets that for copyright reasons is not possible to include
table NA.2 in this version downloaded from the Internet. To obtain a
copy of the Guide containing table NA.2 please contact the IHIE at:
deputy@ihie.org.uk
16 SIGN STRUCTURES GUIDE
APPENDIX B: Flowchart for Determining Wind Load
Start
Is the site
exposed / subject to
local funnelling ?
Is Height
3 m ?
Is Height
5 . 2 m ?
Is Height
4 m ?
Is Height
7 m ?
1 : Calculate aspect ratio and look up c
f
( Table NA 2 )
2 : Look up partial action factors ( Tab le NA 2 )
3: Calculate Wind Actions
4 : Look up partial material factors (Table NA 2)
5 : Calculate post resistance, using factored strength & properties.
Look up wind class using
table NA 2 H = 4 m for
location and distance from
shoreline
Look up wind class using
Table NA 2 H = 7 m for
location and distance from
shoreline
Height to Centroid
H ?
Design to EN 1991-1-4
using 10 minute mean reference
speeds
Are wind
load actions < post
resistance ?
Finish
N
N N N
Y
N
Y
Y
Y
Y
N
N
Y
Y
SIGN STRUCTURES GUIDE 17
APPENDIX C: EXAMPLES
Introduction
Two examples are examined: a small circular sign on a single support with a planted foundation, and a
rectangular sign on two supports with a more conventional spread foundation.
For each sign, the wind load is determined using both the simplified method of the National Annex to BS
EN 12899-1 (section 1), and the more rigorous alternative method of BS EN 1991-1-4 (section 2). This
enables the two approaches to be compared for complexity and results. These examples do not take
into account the point load of 0.5 kN (class PL3 recommended in the 12899 National Annex). This is only
likely to be critical for smaller signs on a single post, for which its effect should be checked.
Whichever method is used to obtain it, the basic wind load is converted into a wind force for each of the
states to be examined (section 3). These are used in section 4 for checking the sign supports. Finally, in
section 5, the chosen foundation is assessed.
EXAMPLE 1: a circular sign with a planted foundation
Mounting height above ground h
m
2.0 m
Width of sign face l 0.9 m
Height of sign face b 0.9 m
Total height = h
m
+ b H 2.9 m
Height to centroid of sign area = h
m
+ b/2 z 2.45 m
Depth of post buried above foundation h
b
0
Foundation: support planted in plain concrete:
minimum diameter of foundation in the ground.
planting depth of foundation.
D
P
Location Surrey, England,
not within 5 km of the sea,
nor a very exposed site on
cliff / escarpment, nor in a
site subject to wind
funnelling.
18 SIGN STRUCTURES GUIDE
Example 1 Section 1: Basic Wind Load using BS EN 12899 National Annex
1. Look up wind load for site
H = 2.9 m height, therefore Basic Wind Load, w
b
= 1.0 kN/m
2
(Used in section 3 below.)
Table NA 2
Example 1 Section 2: Basic Wind Load using BS EN 1991-1-4
1. Look up fundamental value of basic wind velocity
v
b,0
= v
b,map
c
alt
= 21.51.25 = 26.88 m/s Eqn NA1
where
v
b,map
= value of the fundamental basic wind velocity before the
altitude correction is applied. (21.5 m/s selected from map)
c
alt
= altitude factor
c
alt
= 1 + 0.001 A = 1 + 0.001250 = 1.25
A = Altitude of the site (m) above mean sea level (250 m in this
example)
Figure NA1
Eqn NA2a
2. Assess Terrain Orography
Not very exposed site on cliff/escarpment or in a site subject to local
wind funnelling. Therefore c
o
= 1.0
Fig NA2
3. Determine Design Life Requirement
( ) ( )
( ) ( )
n
K
p K
c
=
98 . 0 ln ln 1
1 ln ln 1
prob
= 0.96 Eqn 4.2
where
p = design annual probability of exceedence
p = 1/design life = 1/25 = 0.04 (for signs design life is 25 years)
K = Shape parameter = 0.2
n = exponent = 0.5
NA 2.8
4. Basic Wind Velocity
prob b,0 season dir b
c v c c v =
v
b
= 1.01.026.880.96 = 25.8 m/s
Eqn 4.1 & Note 4
where
dir
c = directional factor = 1.0
season
c = season factor = 1.0
NA 2.6
NA 2.7
SIGN STRUCTURES GUIDE 19
5. Basic Velocity Pressure
2
b b
2
1
v q = = 0.51.22625.80
2
= 0.408 kN/m
2
Eqn 4.10
where = air density = 1.226 kg/m
3
NA 2.18
6. Peak Velocity Pressure
( ) 45 . 2
e,flat
c = 1.66
Fig NA7
( ) ( )
b e,flat p
q z c z q = = 1.660.408 = 0.68 kN/m
2
NA 2.17
Modified formula where orography is not significant (c
o
= 1.0)
for z = 2.45m and country terrain category, flat and 5km from the
shore
7. Basic Wind Load
w
b
= ( ) z q
p
= 0.68 kN/m
2
(Used in section 3 below.)
(This falls within BS EN 12899-1:2007 class WL3, but use of these
classes is no longer recommended.)
Example 1 Section 3: Wind Force (for either method)
1. Determine force coefficient
= effective slenderness ratio of sign or aspect ratio
= l/b or b/l = 0.9/0.9 = 1.0
Therefore c
f
= 1.26
Table NA 2
2. Identify Partial Action factors for Loads
fl
ULS (Bending and Shear)
fl
= 1.35
SLS (Deflection and stability)
fl
= 1.0
Table NA 2
Additional factor
f3,
taken as 1.0, but could alternatively be 1.1
(see paragraph 2.3.)
3. Calculate wind design pressure w
e,d
on the sign
w
e,d
= w
b
c
f
fl
f3
where
w
b
is the basic wind pressure from section 1 or 2 above.
The section 1 value of 1.0 kN/m
2
will be used for the remainder
of this example
.
20 SIGN STRUCTURES GUIDE
w
e,d
(ULS) = 1.01.261.351.0 = 1.70 kN/m
2
w
e,d
(SLS) = 1.01.261.01.0 = 1.26 kN/m
2
4. Calculate Total Design Wind Force
F
w,d
= w
e,d
A
ref
(A
ref
= area of sign)
Clause 5.3 BS EN
1991-1-4
F
w,d
(ULS) = 1.70
2
2
9 . 0
= 1.08 kN
F
w,d
(SLS) = 1.26
2
2
9 . 0
= 0.80 kN
5. Wind Force Equivalent to 1-year Return Period
The wind velocity for calculating the temporary deflection is 75% of the
reference wind velocity, as it is based upon a 1 year mean return period.
Clause 5.3.2.1
EN 12899
F
w,d (1 year)
= F
w,d
(SLS) 0.75
2
= 0.80 0.75
2
= 0.45 kN
(If EN 1991-1-4 method is used, the calculated values are:
F
w,d
(ULS) = 0.74 kN F
w,d
(SLS) = 0.55 kN F
w,d (1 year)
= 0.31 kN )
Use above forces in Sections 4 & 5
Example 1 Section 4: Support design (for either method)
1. Ultimate Design Load
F
w,d
(ULS) = 1.08 kN Section 3 above
2. Ultimate Load Effects
Ultimate design bending moment per post, M
d
M
d
= Wind force lever arm to foundation / number of posts
= F
w,d
(ULS) (z+h
b
) / n
= 1.08(2.45 + 0.0) / 1 = 2.65 kNm
where n = number of posts
Ultimate design shear per post, V
d,
= Wind force / number of posts
V
d
= F
w,d
(ULS) / n = 1.08/1 = 1.08 kN
SIGN STRUCTURES GUIDE 21
3. Support Properties
Circular Hollow Section, CHS 76.1 3.2 (S275 steel) is anticipated
Characteristic member capacities
M
c
= 4.22 kNm
P
v
= 72.6 kN
Steelwork design
guide to BS 5950-
1:2000. Volume 1
Part C
4. Partial Material Factor for Sign Support
m
=
1.05 for steel sections (elongation > 15%)
NA to EN 12899
Table NA.2
5. Ultimate Capacity Check
Ultimate bending capacity = M
c
/
m
=
4.22 / 1.05 = 4.02 kNm
4.02 kNm > 2.65 kNm OK
(If EN 1991-1-4 method is used, the calculated bending effect is 1.81 kNm)
Ultimate shear capacity = P
v
/
m
=
72.6 / 1.05 = 69.14 kN
69.14 kN > 1.08 kN OK
(If EN 1991-1-4 method is used, the calculated shear effect is 0.74 kN)
6. Temporary Deflection Calculation
F
w,d (1 year)
= 0.45 kN Section 3 above
Uniformly distributed load along sign face = F
w,d (1 year)
/ b
F
w,d (1 year)
/ b = 0.45/0.9 = 0.5 kN/m
where b = height of the sign face
Maximum deflection at top of sign (bending),
Clause 5.3.3
EN 12899
[ ]
4
b m b
3
b m
4
b
year) (1 w,d
) ( ) ( ) ( 4 ) ( 3
24
/
h h h H h h h H
n EI
b F
+ + + + +
=
Steel Designers
Manual
(Deflection table
for cantilevers)
where
E = Elastic modulus of structural steel, taken as 205 10
3
N/mm
2
I = Moment of inertia
= 48.8 cm
4
(for CHS 76.1 3.2) = 48.8 10
4
mm
4
n = number of posts
H, h
b
and h
m
as illustrated on diagram
Steelwork design
guide to BS 5950-
1:2000. Volume 1
Part B1
22 SIGN STRUCTURES GUIDE
[ ]
4 3 4
4 3
) 0 2000 ( ) 0 2900 ( ) 0 2000 ( 4 ) 0 2900 ( 3
1 10 8 . 48 10 205 24
5 . 0
+ + + + +
=
= 28.19 mm
Deflection per linear metre, =
) (
b
h H +
=
) 0 9 . 2 (
19 . 28
+
= 9.72 mm/m
Maximum temporary deflection taken as TDB4 = 25 mm/m
NA to EN 12899
Table NA.2
25 mm/m > 9.72 mm/m OK
(If EN 1991-1-4 method is used, the calculated deflection is 6.61mm/m)
EN 12899
Table 16
Conclusion:
CHS 76.1 3.2 (S275) is sufficient for the design.
A smaller section might also be suitable.
Notes:
Design forces may also include the moment and shear force from the loads
applied on the post(s).
Torsion has not been calculated. This should be considered for signs that are
fixed eccentrically, or where a significant area could be shielded from the wind
or where buffeting from traffic can occur.
Example 1 Section 5: Foundation Design to BD 94/07
1. Un-factored Design Load
F
w,d
(SLS)
= 0.80 kN Section 3 above
2. Ground Resistance Moment, Mg
10
3
g
P D G
M
=
BD 94/07
Clause 11.5
where
G is a factor dependent on the ground in which the support is planted
(in kN/m
2
per m). Refer to BD 94/07 Table 3 for typical values of G.
D is the minimum diameter of the support and its surrounding concrete
in the ground (in m).
P is the planting depth
Try foundation design D = 0.35m, P = 0.8m
SIGN STRUCTURES GUIDE 23
Assume Poor ground condition, G taken as 230 kN/m
2
per m Table 3
12 . 4
10
8 . 0 35 . 0 230
3
g
=
= M kNm
3. Destabilising Moment, MDS
The destabilising moment is calculated about a fulcrum point located at
1/ 2 of the planting depth below ground.
Clause 11.4
lever arm = )]
2
1
( [ P h z
b
+ +
where
z, h
b
and n are as defined before
P is the planting depth
M
DS
= F
w,d
lever arm to fulcrum point / number of posts
= F
w,d
)]
2
1
( [ P h z
b
+ + / n
= 1 / ) 8 . 0
2
1
0 45 . 2 ( 80 . 0 + + = 2.41 kNm
s;d
M
DS
= 1.252.41 = 3.01 kNm
where
s;d
is the model factor = 1.25 Clause 11.4
4. Capacity Check
M
g
= 4.12 kNm >
s;d
* M
DS
= 3.01 kNm OK Clause 11.6
Conclusion:
A foundation of un-reinforced concrete, 0.35 m diameter with 0.8 m planting
depth is satisfactory.
Note:
The design above does not apply to foundations on slopes, where stability of
the ground needs to be taken into account. In such instances, specialist
geotechnical advice should be sought.
Clause 11.1
24 SIGN STRUCTURES GUIDE
EXAMPLE 2: a rectangular sign with a spread foundation
Location Londonderry, Northern Ireland not within 5 km of the sea, nor very exposed site on cliff /
escarpment, nor in a site subject to wind funnelling
Mounting height above ground h
m
1.5 m
Width of sign face l 4.0 m
Height of sign face b 2.5 m
Total height = h
m
+ b H 4.0 m
Height to centroid of sign area = h
m
+ b/2 z 2.75 m
Depth of post buried above foundation h
b
75 mm
Spread foundation:
length of foundation parallel to sign
width of foundation perpendicular to sign
thickness of foundation
L
W
T
Example 2 Section 1: Basic Wind Load using BS EN 12899 National Annex
1. Look up wind load for site
H = 4.0m height, therefore Basic Wind Load Value, w
b
= 1.2 kN/m
2
(Used in section 3 below.)
Table NA.2
SIGN STRUCTURES GUIDE 25
Example 2 Section 2: Basic Wind Load using BS EN 1991-1-4
1. Look up fundamental value of basic wind velocity
v
b,0
= v
b,map
c
alt
= 26.251.217 = 31.95 m/s Eqn NA1
where
v
b,map
= value of the fundamental basic wind velocity before the
altitude correction is applied. (26.25 m/s selected from map)
c
alt
= altitude factor
c
alt
= 1 + 0.001 A = 1 + 0.001217 = 1.217
A = Altitude of the site above mean sea level (217 m in this
example)
Figure NA1
Eqn NA2a
2. Assess Terrain Orography
Not very exposed site on cliff/escarpment or in a site subject to local
wind funnelling. Therefore c
o
= 1.0
Fig NA2
3. Determine Design Life Requirement
( ) ( )
( ) ( )
n
K
p K
c
=
98 . 0 ln ln 1
1 ln ln 1
prob
= 0.96 Eqn 4.2
where
p = design annual probability of exceedence
p = 1/design life = 1/25 = 0.04 (for signs design life is 25 years)
K = Shape parameter = 0.2
n = exponent = 0.5
NA 2.8
4. Basic Wind Velocity
prob b,0 season dir b
c v c c v =
v
b
= 1.01.031.950.96 = 30.67 m/s
Eqn 4.1 & Note 4
where
dir
c = directional factor = 1.0
season
c = season factor = 1.0
NA 2.6
NA 2.7
5. Basic Velocity Pressure
2
b b
2
1
v q = = 0.51.22630.67
2
= 0.577 kN/m
2
Eqn 4.10
where = air density = 1.226 kg/m
3
NA 2.18
6. Peak Velocity Pressure
( ) 75 . 2
flat e,
c = 1.74
Fig NA7
26 SIGN STRUCTURES GUIDE
( ) ( )
b e,flat p
q z c z q = = 1.740.577 = 1.00 kN/m
2
NA 2.17
Modified formula where orography is not significant (c
o
= 1.0)
for z = 2.75m and country terrain category, flat and 5km from the
shore.
7. Basic Wind Load
w
b
= ( ) z q
p
= 1.00 kN/m
2
(Used in section 3 below.)
(This is equivalent to BS EN 12899-1:2007 class WL5, but use of these
classes is no longer recommended.)
Example 2 Section 3: Wind Force (for either method)
1. Determine force coefficient
= effective slenderness ratio of sign or aspect ratio
= l/b = 4.0 / 2.5 = 1.6
Therefore c
f
= 1.30
Table NA 2
2. Identify Partial Action factors for Loads
fl
ULS (Bending and Shear)
fl
= 1.35
SLS (Deflection and stability)
fl
= 1.0
Table NA 2
Additional factor
f3,
taken as 1.0, but could alternatively be 1.1
(see paragraph 2.3).
3. Calculate wind design pressure w
e,d
on the sign
w
e,d
= w
b
c
f
fl
f3
where
w
b
is the basic wind pressure from section 1 or 2 above.
The section 1 value of 1.2 kN/m
2
will be used for the remainder
of this example
.
w
e,d
(ULS) = 1.21.301.351.0 = 2.11 kN/m
2
w
e,d
(SLS) = 1.21.301.01.0 = 1.56 kN/m
2
4. Calculate Total Design Wind Force
F
w,d
= w
e,d
A
ref
(A
ref
= area of sign)
Clause 5.3 BS EN
1991-1-4
F
w,d
(ULS) = 2.114.02.5 = 21.1 kN
F
w,d
(SLS) = 1.564.02.5 = 15.6 kN
SIGN STRUCTURES GUIDE 27
5. Wind Force Equivalent to 1-year Return Period
The wind velocity for calculating the temporary deflection is 75% of the
reference wind velocity, as it is based upon a 1 year mean return period.
Clause 5.3.2.1
EN 12899
F
w,d (1 year)
= F
w,d
(SLS) 0.75
2
= 15.6 0.75
2
= 8.78 kN
(If EN 1991-1-4 method is used, the calculated values are:
F
w,d
(ULS) = 17.6 kN F
w,d
(SLS) = 13.0 kN F
w,d (1 year)
= 7.31 kN )
Use above forces in Sections 4 & 5
Example 2 Section 4: Support design (for either method)
1. Ultimate Design Load
F
w,d
(ULS) = 21.1 kN Section 3 above
2. Ultimate Load Effects
Ultimate design bending moment per post, M
d
M
d
= Wind force lever arm to foundation / number of posts
= F
w,d
(ULS) (z+h
b
) / n
= 21.1(2.75 + 0.075) / 2 = 29.80 kNm
where n = number of posts
Ultimate design shear per post, V
d
V
d
= Wind force / number of posts
= F
w,d
(ULS) / n
= 21.1 / 2 = 10.55 kN
3 Support Properties
Circular Hollow Section, CHS 168.35.0 (S275) is anticipated
Characteristic member capacities
M
c
= 33.7 kNm
P
v
= 254 kN
Steelwork design guide
to BS 5950-1:2000.
Volume 1 Part C
28 SIGN STRUCTURES GUIDE
4. Partial Material Factor for Sign Support
m
=
1.05 for steel sections (elongation > 15%)
NA to EN 12899
Table NA2
5. Ultimate Capacity Check
Ultimate bending capacity = M
c
/
m
=
33.7 / 1.05 = 32.10 kNm
32.10 kNm > 29.80 kNm OK
(If EN 1991-1-4 method is used, the calculated bending effect is 24.79 kNm)
Ultimate shear capacity = P
v
/
m
=
254 / 1.05 = 241.90 kN
241.90 kN > 10.55 kN OK
(If EN 1991-1-4 method is used, the calculated shear effect is 8.78 kN)
6. Temporary Deflection Calculations
F
w,d (1 year)
= 8.78 kN Section 3 above
Uniformly distributed load along sign face = F
w,d (1 year)
/ b
F
w,d (1 year)
/ b = 8.78 / 2.5 = 3.51 kN/m
where b = height of the sign face
Maximum deflection at top of sign (bending), Clause 5.3.3 EN 12899
[ ]
4
b m b
3
b m
4
b
year) (1 w,d
) ( ) ( ) ( 4 ) ( 3
24
/
h h h H h h h H
n EI
b F
+ + + + +
=
Steel Designers
Manual (Deflection
table for cantilevers)
where
E = Elastic modulus of structural steel, taken as 20510
3
N/mm
2
I = Moment of inertia
= 856 cm
4
(for CHS 168.35.0) = 85610
4
mm
4
n = number of posts
H, h
b
and h
m
as illustrated on diagram
Steelwork design guide
to BS 5950-1:2000.
Volume 1 Part B1
[ ]
4 3 4
4 3
) 75 1500 ( ) 75 4000 ( ) 75 1500 ( 4 ) 75 4000 ( 3
2 10 856 10 205 24
51 . 3
+ + + + +
=
= 32.07 mm
Deflection per linear metre, =
) (
b
h H +
=
) 075 . 0 0 . 4 (
07 . 32
+
= 7.87 mm/m
SIGN STRUCTURES GUIDE 29
Performance Class
NA to EN 12899
Table NA.2
Maximum temporary deflection taken as TDB4 = 25 mm/m
25 mm/m > 7.87 mm/m OK
(If EN 1991-1-4 method is used, the calculated deflection is 6.56 mm/m)
EN 12899 Table 16
Conclusion:
2 no. CHS 168.3 5.0 (S275) are sufficient for the design.
(If EN 1991-1-4 method is used, a support size of CHS 139.7 6.3 with
M
c
= 27.8 kNm, P
v
= 261 kN and I = 589 cm
4
is suitable.)
Notes:
Design forces may also include the moment and shear force from the
loads applied on the post(s).
Torsion has not been calculated. This should be considered for signs
which are fixed eccentrically on the posts, where a significant area could
be shielded from the wind or where buffeting from traffic can occur.
Example 2 Section 5: Foundation Design to BS 8002 and BS 8004
1. Un-factored Design Load
F
w,d
(SLS) =15.6 kN
Section 3
above
2. Assumptions
Presumed allowable ground bearing pressure = 80 kN/m
2
BS 8004
Table 1
Friction factor, taken as 0.5
(typical value for concrete against gravel, loose sand and firm clay)
BS 8002
Clause 3.2.6
Unit weight of reinforced concrete g
con
taken as 24 kN/m
3
3. Foundation dimensions
Try foundation dimensions L = 3.0 m, W = 1.7 m, T = 1.2 m
L, W and T as illustrated and defined above.
Foundation self-weight, N = 3.0 1.7 1.2 24 = 146.88 kN
30 SIGN STRUCTURES GUIDE
4. Overturning Check
Overturning moment, M
over
= Design loadlever arm to the foundation base
M
over
= F
w,d
(z + h
b
+ T) = 15.6 (2.75 + 0.075 + 1.2) = 62.79 kNm
Restoring moment, M
rest
= N W / 2
M
rest
= 146.88 1.7 / 2 = 124.85 kNm
Factor of safety = 124.85 / 62.79 = 1.99 > 1.5 OK
5. Bearing Pressure Check
Eccentricity of resulting force, e = M
over
/ N = 62.79 / 146.88 = 0.43 m
W/6 = 1.7 / 6 = 0.28 m
0.43 > 0.28 e > W/6 reaction is outside the middle third
Maximum bearing pressure, q
max
=
) 2 ( 3
4
e W L
N
q
max
=
) 43 . 0 2 7 . 1 ( 0 . 3 3
88 . 146 4
= 77.71 kN/m
2
q
max
< allowable
bearing pressure, 80 kN/m
2
OK
Note: if e < W/6, use these formulae:
q
max
= )
6
1 (
W
e
WL
N
+ q
min
= )
6
1 (
W
e
WL
N
q
min
must be 0
6. Sliding Check
Sliding force, F
w,d
= 15.6 kN
Sliding resistance = N = 146.88 0.5 = 73.44 kN
Factor of safety = 73.44 / 15.6 = 4.7 > 1.5 OK
Conclusion:
Foundation with L = 3.0m, W = 1.7m and T = 1.2m is sufficient for the design.
A spread foundation should be reinforced unless it is shown that the bending and
shrinkage effects are negligible. In general foundations for smaller CHS posts
(88.9 mm diameter or less) do not need reinforcement.
Refer to Example 1 for planted bases, which are often an economical alternative.
SIGN STRUCTURES GUIDE 31
APPENDIX D: REFERENCES
1. BS EN 1991-1-4: 2005, Eurocode 1: General Actions Wind Actions.
2. BS EN 12899-1:2007 Fixed, vertical road traffic signs Part 1: fixed signs.
3. National Annex to BS EN 1991-1-4, Eurocode 1: Actions on Structures. Draft dated August 2007.
4. BS 6399:1997, Loading for Buildings, Part 2 Code of practice for Wind loads.
5. BS 8002:1994, Code of practice for earth retaining structures
6. BS 8004:1986, Code of practice for foundations
7. Steelwork design guide to BS 5940-1:2000 (vol 1)
8. Steel Designers Manual, Steel Construction Institute, Blackwell Publishing, 2005
9. BS EN 12767:2007, Passive safety of support structures for road equipment.
10. National Annex to BS EN 12767:2007, Passive safety of support structures for road equipment.
11. TD 19/06 (vol 2, sect 2, part 8 of Design Manual for Roads and Bridges), Highways Agency.
12. National Annex to BS EN 12899-1:2007 Fixed, Vertical Road Traffic Signs.
13. BD 94/07 (vol 2, sect 2, part 1 of Design Manual for Roads and Bridges), Highways Agency.
14. Free software for determining both the appropriate wind load and suitable steel support sections
using the methods described in this booklet (SignLoad Designer) is available from Buchanan
Computing: www.BuchananComputing.co.uk.
Disclaimer:
The Institute of Highway Incorporated Engineers and the contributors which produced this Guide have endeavoured to ensure the accuracy of
its contents. However, the guidance and recommendations given should always be reviewed by those using the guidance in the light of the
facts of their particular case and specialist advice should be obtained as necessary. No liability for negligence or otherwise in relation to this
Guide and its contents can be accepted by the Institute, the Contributors, its servants or agents.
Contributing
organisations
Highways Agency
Buchanan Computing
Mott MacDonald