48049-107-01
12/2001
Cedar Rapids, IA, USA
ECN K455
Control Unit Replacement Instructions for MASTERPACT
Circuit Breaker
Retain for future use.
19962001 Schneider Electric All Rights Reserved 1
INSTALLATION
1. Remove power screws and lift off cover.
Remove Old Control Unit 2. Remove wire cover.
DANGER
HAZARD OF ELECTRIC SHOCK, BURN, OR
EXPLOSION
This equipment must be installed and
serviced only by qualified electrical
personnel.
Turn off all power supplying this equipment
before working on or inside equipment.
Always use a properly rated voltage sensing
device to confirm power is off.
Replace all devices, doors and covers before
turning on power to this equipment.
Failure to follow this instruction will result in
death or serious injury.
0
6
3
1
3
3
1
9
0
6
3
1
3
3
2
0
0
6
3
1
3
3
2
1
0
6
3
1
3
3
2
1
0
6
3
1
3
3
2
2
Control Unit Replacement Instructions for MASTERPACT
Circuit Breaker
12/2001 Control Unit Replacement
19962001 Schneider Electric All Rights Reserved 3
6. Place control unit (A) on circuit breaker, tighten screws, (B) and replace
wire cover (C).
0
6
3
1
3
3
3
1
A
0
6
3
1
3
3
3
2
B
62 lb-in
(7 Nm)
0
6
3
1
3
3
3
3
C
Replace Circuit Breaker Cover
0
6
3
1
3
3
2
9
Replace cover.
0
6
3
1
3
3
3
0
13 lb-in
(1.5 Nm)
Replace cover screws.
Control Unit Replacement Instructions for MASTERPACT
Circuit Breaker
12/2001 Control Unit Replacement
19962001 Schneider Electric All Rights Reserved 5
Table 2: STR28D
Testing Procedure Current to Inject*
1. Record the control unit settings.
2. Adjust settings:
long-time
l
r
= 0.8
short-time
l
m
= 1.5
3. Program the injection time to 1500ms.
4. Inject the current pole-by-pole.
5. Reset the control unit to the original settings.
Sensor Rating (A) Current (A)
125 173
150 207
200 276
250 345
300 414
400 552
500 690
600 828
800 1104
1000 1380
1200 1656
1600 2208
2000 2760
2500 3450
3000 4140
3200 4415
4000 5520
5000 5900
6000 8280
6300 8694
*Current injection = [(I
o
x 0.8) x 1.5] + 15%
0
6
3
1
3
3
3
5
Settings
Rating plug = current sensor
(for this test)
l
r
= 0.8
l
m
= 1.5
Control Unit Replacement Instructions for MASTERPACT
Circuit Breaker
12/2001 Control Unit Replacement
19962001 Schneider Electric All Rights Reserved 7
Table 4: STR38S, STR58U Without Residual Ground-fault Protection
(Option T) With or Without Source Ground Return
Ground-fault Protection (Option W)
Testing Procedure Current to Inject*
1. Record the control unit settings.
2. Adjust settings:
long-time
l
r
= 0.8
short-time
I
m
= 1.5
t
m
= 0.1
t
m
-l
2
t = off
3. Program the injection time to 1500ms.
4. Inject the current pole-by-pole.
5. Reset the control unit to the original
settings.
125 173
150 207
200 276
250 345
300 414
400 552
500 690
600 828
800 1104
1000 1380
1200 1656
1600 2208
2000 2760
2500 3450
3000 4140
3200 4415
4000 5520
5000 6900
6000 8280
6300 8694
*Current injection = [(I
o
x 0.8) x 1.5] + 15%
push to reset
I+T L+I
I
L+T
L off
T
L+I+T
I
I1 I2 I3
90%
50%
20%
STR 58 U
Ir tr
90
105
tr
%Ir
.88
.9 .92
.95
.98
1 .8
.85
xIo
60
120 240
480
15
30
at 1.5Ir
Im tm
3
4 5
6
8
10 1.5
2
xIr
.3
.4 .3
.1
.1
.2
on I2t off
.2
0
Ir fault
tr
Im fault
tm
I
fault
Ih
th
t
i
test
+
+
T
R
F
test
Ih 1200A Max th
400
500 600
800
1000
1200 250
320
A
.3
.4 .4
.2
.1
.2
on I2t off
.3
.1
I
8
12 14
19
22
Max. 2
4
xIn
Ic1 Ic2
.86
.9 .93
.95
.98
1 .8
.85
xIr
.7
.8 .85
.95
.5
.6
.9
1
xIr
V
Ir :
Im :
th :
min.
norm
overcurrent
ground
reset V
20%
Ir tr
90
105
tr
%Ir
.88
.9 .92
.95
.98
1 .8
.85
xIo
60
120 240
480
15
30
at 1.5Ir
Im tm
3
4 5
6
8
10 1.5
2
xIr
.3
.4 .3
.1
.1
.2
on I
2
t off
.2
0
Ir fault
tr
Im fault
tm
I
fault
Ih
th
t
i
T
R
Ih 1200A Max th
400
500 600
800
1000
1200 250
320
A
.3
.4 .4
.2
.1
.2
on I
2
t off
.3
.1
I
8
12 14
19
22
Max. 2
4
xIn
Ic1 Ic2
Ir :
Im :
th :
min.
norm
0
6
3
1
3
3
3
7
Rating plug = current
sensor (for this test)
I
r
= 0.8
I
m
= 1.5
t
m
= 0.1
t
m
- I
2
t = off
Electrical equipment should be serviced only by qualified personnel. No responsibility
is assumed by Schneider Electric for any consequences arising out of the use of this
material. This document is not intended as an instruction manual for untrained
persons.