You are on page 1of 26

1st Subm.

17-Apr-11
Md. Giasuddin
Foundation Design Calculation of Tower Type 2DT6 For
Soil Category-2
Submission
Status
Date
AUTHORITY NAME & SIGN DATE Paper Size Language Total Sheets
DESIGNED BY
Md. Giasuddin
17-Apr-11 For approval A4 English 13
CHECKED BY
Md. Giasuddin
For construction Scale : N/A
Revision
1st Sub.
APPROVED BY As Built
SUBMISSION SOUGHT
Document No. :
PGCB/230kV/TL/B-C/Lot-3/Des.Cal/Local/08
Designed By Description Approved By
EMPLOYER :
POWER GRID COMPANY OF
BANGLADESH LTD.
CONTRACTOR :
SANERGY CO.
NAME OF PROJECT :
DESIGN-BUILD AND TRUNKEY CONTRACT FOR CONSTRUCTION OF 230kV BIBYANA -
COMILLA TRANSMISSION LINE (LOT-3)
POWER GRID COMPANY OF BANGLADESH LIMITED
Contents Page No.
1. General. 03
1.1 Foundation Loads 03
Foundation of Tower Type 2DT6 for SC-2
FOR BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
1.2 Geotechnical Information 03
1.3 Foundation Strength Factors 03
1.4 Factored Foundation Loads 03
1.5 Codes & Standards Considered 03
1.6 Material Properties 03
1.7 Geometrical Data of the Tower 2DT6 03
1.8 Layout Plan Of the Foundation 04
2. Residual Shear Calculation 04
3. Foundation Geometry 05
4 : Design Calculation for Pile 05
4.1 - Pile Design Load Against Compressive Load 05
4.2 - Pile Design Load Against Uplift 05 g oad ga Up 05
4.3 - Minimum Length of Pile Group Against Uprooting 05
4.4 - Check for pile head deflection 06
4.5 - Ultimate Stress on Pile Section 07
Section-5 :Structural Design of Chimney & Pile Cap 07
5.1 - Design of Chimney 07
5 2 D i f Pil C 08 5.2 - Design of Pile Cap 08
5.2.1.- Check Punching of cleats 08
5.2.1.a Check For Compression 08
5.2.1.b Check For Uplift 08
5.2.2 - Check cap thickness for Flexural Shear 08
5.2.3.- Check for position of Piles 08
5.2.4 - Check for Bending Moment 09
5.2.5 - Reinforcement Calculation 09
5.2.5.1 - Bottom Reinforcement 08
5.2.5.2 - Top Reinforcement 09
5.2.5.3 -Vertical Reinforcement Around The pile cap 09
5.2.5.4 -Horizontal Reinforcement Around The pile cap 10
6 - Structural Design of Pile 10
6.1 Design of upper segment of pile 10
6.1.1 Design for Compression Plus Bending 10
6.1.2 Design for Tension Plus Bending 10
6.2 Calculation to Find Point of Zero Moment in the Pile 10
Annexure-1 12
Annexure-2 13
Giasuddin Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR
1. General.
1.1 Foundation Loads :
Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
The objective of this generic design is to compute loads on individual pile top, length of fixity of pile and is to design pile, pile cap and chimney. If not
mentioned otherwise, values with suffices x, y and z indicate three global directions with outward positive.
F
z
( kN ) F
x
(kN) F
y
(kN)
3154.98 893.33 831.62
2840.17 893.33 831.62
1.2 Geotechnical Information:
Items
Max Compression Case
Max Uplift Case
Ultimate Loads Along Global Direction ( Pull and Thrust Vertical)
Angle of Int. Friction, = 32 Degree
Soil Density = 18 kN/Cum.
Soil Submerged Density = 8 kN/Cum.
Frustum angle = 15 Degree; As per techinical specification
1.3 Foundation Strength Factors :
2DL 2D1
Applied Loading Case
Strength Factor
2D25 2DT6
1.4. Factored Foundation Loads.
Factored Loads by using Foundation Strength Factor from Appendix (7.A2),Volume 2 of 3
F ( kN ) F (kN) F (kN)
2DL, 2D1
1.35 1.23
Factored Ultimate Loads Along Global Direction ( Pull and Thrust Vertical)
2D25, 2DT6
For All Load Cases
Items F
z
( kN ) F
x
(kN) F
y
(kN)
4259.22 1206.00 1122.69
3834.23 1206.00 1122.69
1.5 Codes & Standards Considered :
ACI
BS 8110
Max Long. Case in Uplift
Max Long. Case in Comp.
Items
1.6 Material Properties and Clear Cover :
28 days cube strength of concrete for Pile; fc' = 30 Mpa.
28 days cube strength of concrete for Pile-Cap; fc' = 25 Mpa.
Corresponding cylinder strength of concrete for Pile-Cap; fc' = 21.25 Mpa.
Yield Strength Reinforcing Steel ;fy = 415 Mpa.
Concrete Clear Cover at top and sides of Cap & Column is = 50 mm.
Concrete Clear Cover for sides of Pile is = 75 mm.
Unit Weight of Concrete = 24 kN/Cum.
1.7 Geometrical Data of the Tower 2DT6 :
Face Slope = = 13.306 Degree.
Diagonal Slope = = 18.493 Degree.
Md. Giasuddin Page 3 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
1.8 Layout Plan Of the Foundation
450 1800 1800 450
4
5
0
450 1800 1800 450
4
5
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
4500
CP
4
5
0
4500
4
5
0
4500
4
5
0
4500
4
5
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
Layout Plan of Foundation
450 1800 1800 450
4
5
0
450 1800 1800 450
4
5
0
2. Residual Shear Calculation :
F
xleg
F
yleg
F
xRes
= F
x
-F
xleg
F
yRes
= F
y
-F
yleg
Max Compression Case 4259.22 1007.31 1007.31 1206.00 1122.69 198.69 115.38
Max Uplift Case 3834.23 906.80 906.80 1206.00 1122.69 299.20 215.89
Vertical Loads
F
z
( kN )
Items
Residual Shear ( kN )
F
x
(kN) F
y
(kN)
Leg Shear ( kN ) = F
z
*Tano
Md. Giasuddin Page 4 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
3. Foundation Geometry :
Size of the column = 900 mmX900 mm.
Dia of the Pile, Dp = 600 mm.
h'' = 280.5 mm.
h' 400 h' = 400 mm.
f = 300 mm.
Pile Center to center Distance = 1800 mm.
Height of column, h = 700 mm.
Length/Width of the Cap, L/B = 4500 mm.
Cap Thickness, t = 1250 mm.
No. of Pile Per Leg = 8 Nos
Weight Calculation
Weight of Column, Wcol = 13.61 kNs.
Weight of Pad, Wpad = 607.5 kNs.
Weight of Superimposed Soil, Ws =109.35 kNs.
Bouyant Weight of Column, W'col = 7.94 kNs
Bouyant Weight of Pad, W'pad = 354.38 kNs
Bouyant Weight of Superimposed Soil, W's = 48.6 kNs
Loads on Pile top :
Foundation Layout Detail Typical Pile Cap Section
For Maximum Comp.
Resultant Compressive Load = Rzc =Fz+ 1.35*(Wcol+Wpad+Ws) = 5157.69 kNs.
Moment Mx = Moment for Leg and Residual Shear = Fxleg*0.0 + FxRes*(t+h+h''-0.15) =376.12 kN.m
Moment My = Moment for Leg and Residual Shear = Fyleg*0.0 + FyRes*(t+h+h''-0.15) = 218.41 kN.m
For Maximum Uplift :
Resultant Uplift = Rzt=Fz - W'col - W'pad - W's = 3423.31 kNs
Moment Mx = Moment for Leg and Residual Shear = Fxleg*0.0 + Fxres*(t+h+h''-0.15) = 566.39 kN.m
Moment My = Moment for Leg and Residual Shear = Fyleg*0.0 + Fyres*(t+h+h''-0.15) = 408.68 kN.m
4 : Design Calculation for Pile :
Reaction of pile with applied vertical loads and biaxial bending moment can be expressed by the following equation:
y
V x
V 2 2
M *d1y
R M *d1x
R =
8 dix diy

Where , d1x and d1y denote the distances from pile center to cap center along X or Y Direction. In this case d1x=d1y= 0.9 m.
6*1.8^2 = 19.44 Sqm.
4.1 - Pile Design Load Against Compressive Load :
Maximum compresive load that a pile will be imposed can be expressed by :
So Rcmax = 699.76 kNs. ( Pile weight is to be considered during Pile schedule)
4.2 - Pile Design Load Against Uplift :

= =
2 2
diy dix
y
zc x
Cmax 2 2
M *d1y
R M *d1x
R =
8 dix diy
+ +

g g p
Maximum compresive load that a pile will be imposed can be expressed by :
So Rtmax = 518.2 kNs. ( Pile weight is to be considered during Pile schedule)
4.3 - Minimum Length of Pile Group Against Uprooting :
Soil body to Resist Uplift
Say minimum length of pile =8 m
Depth of pile, d = 9.625 m. So a = d/2 = 4.813 m.
The base size of the soil frustum at the lowest point b' = 4.2m X4.2 m
The base size of the soil frustum at Mid Height ; b =4.979 m X4.979 m
Average Area = (4.2^2+4.979^2)/2 =21.22 sqm.
y
zt x
Tmax 2 2
M *d1y
R M *d1x
R =
8 dix diy
+ +

Md. Giasuddin Page 5 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
So Frustum Volume = 21.22 * 4.8125 =102.12 cum
The upper soil volume = 4.979^2*4.813= 119.32 cum
Total soil Volume = 221.44 Cum
Total weight of soil body = 221.44*8=1771.52 kN
Skin resistance of pile group is Given by :
GL
Q =2*( ) * * L B H f +
Ks =1 ;( soil to soil co-efficient of earth pressure)
P
d
=yd, o = o= 32 Degree
y = Submerged Density of soil = 8 kN/Cum.
Pd =8 *9 625 = 77 kNs
a
su
s
Q =2*( ) * *
Where L and B are the overall length and width of pile group,
H is the depth of soil block and f is the unit skin friction
1
which is given by
2
s
s d
L B H f
fs K p Tano
+
=
Pd 8 9.625 77 kNs.
So fs = 24.06 kN/Sqm.
L= B = b' = 4.2 m and H = d = 9.625 m.
So Qsu = 3890.5 kNs
Allowable capacity (FS=1.5) = 3774.68 kNs
Resultant Uplift = 3423.31 kNs.
Which is less than 3774.68 kNs So OK.
Ultimate uplift capacity of pile group = Skin Resistance +
Submerged Weight of soil body = 5662.02kNs.
b
d
L
Which is less than 3774.68 kNs So OK.
4.4 - Check for pile head deflection:
For Max Compression:
Fx = Leg Shear = 1007.31 kN
Fy = Leg Shear = 1007.31 kN
Passive resistance by Cap Only ( Same in x and y face)
135 47 kN
a
1
Passive resistance by Pile Cap is k *(1 55+0 30)*1 25*4 5 = = 135.47 kN
3.25
=Submerged density of soil =8 kN/Cum.
Net Fx = Leg Shear = 871.84 kN
Net Fy = Leg Shear = 871.84 kN
Vres=Sqrt.(871.84^2+871.84^2)=1232.97 kN
Lateral Load carried by a single Pile = 154.12 kN
b'
GL
Cap Top
3
0
0
p
1+sin
Where k = Co-efficient of passive earth pressure =
1-Sin
o
o
=
p
Passive resistance by Pile Cap is k *(1.55+0.30)*1.25*4.5 =
2
=
For Max Uplift:
Fx = Leg Shear = 906.8 kN
Fy = Leg Shear = 906.8 kN
Net Fx = Leg Shear = 771.33 kN
Net Fy = Leg Shear = 771.33 kN
Vres=Sqrt.(771.33^2+771.33^2)=1090.83 kN
Lateral Load carried by a single Pile = 136.35 kN
Design shear carried by a single Pile Qmax = 154.12 kN
Kp h
Cap Bot.
1
2
5
0
Design shear carried by a single Pile Qmax 154.12 kN
For fixed head pile depth of fixity is given by
L
f
/T = 2.15; (Ref. to figure no 2 , appendix C of IS: 2911) For fixed head piles .
K1 = 0.146 For Submerged Medium Dense Sand
Where ; 25742.96 Mpa = 257430 kg/sqcm.
636172.5 cm4 EI = 163769889855 kg.sqcm.
So T = 257.03 cm = 2.57 m
So depth of fixity, Lf = 5.53 m
Deflection, Y = Q*(Lf)^3/12EI = 1.326 cm. = 13.26 mm; Which is less than 25mm, So OK.
5
Where, 1 and T EI K =
4700 '
c
E f = =
4
64
d
I
r
= =
Kp h
Passive Pressure on Cap
Md. Giasuddin Page 6 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
4.5 - Ultimate Stress on Pile Section
For Max Compression
For fixed head long pile :
Moment M=m.M
F
= 0.82*Q*Lf/2 =
For Max Compression M = 349.44 kN.m
For Max Uplift M = 309.15 kN.m
For Max Compression.
Q = Hu = 154.12 kN.
So Mu = 349.44 kN.m
For Max Uplift
Q = Hu = 136.35 kN.
So Mu = 309.15 kN.m
Ultimate loads on Single Pile :
Compressive load = Rc = 699.76 kN
Uplift load = Rt = 518.2 kN
For Max Compression ultimate Moment , Mu = 349.44 kN.m
For Max Uplift ultimate Moment , Mu = 309.15 kN.m
Section-5 : Structural Design of Chimney & Pile Cap
5.1 - Design of Chimney :
Ultimate Compression = 4259.22 kN
50% of Ult. Compression = 2129.61 kN
Residual shear :
F
xmax
= 299.20 kN
F
ymax
= 215.89 kN
Resultant F
xy
= 368.96 kN
M = Fxy* 0.793 = 292.6 kN.m. 1 of 12 of dia. 20 mm y
P
u
= 2129610.00 N
M
u
= 292582755.1 N.mm
D = 900.00 mm
b = 900 mm
d' = 66 mm
d'/D = 0.073 mm
f
ck
= 25.0 Mpa
f
y
= 415.0 Mpa
P
u
/f
ck
bD =
0.105
M
u
/f
ck
bD
2
=
0.016
For the above values, graph ( see annexure-1 ) shows that no rebar is needed.
As per Code Min Rebar Required = 0.004*900^2 = 3240 mm2
Consider Bar Dia. 20 mm
Provide 12 nos 20mm dia.
Embedded Length of Rebar.
C i t b i t d b th b i hi F 2129 61 kN
Column Section
Compression to be resisted by the rebars in chimney = Fz = 2129.61 kN
Total Nos. of reinforcement is 12 of dia 20 12mm.
As per BS 8110, Ultimate bond stress in compression bars u
u
is given by : u
u
=0.5fc' Mpa
So Uu = 2.3 Mpa. So Development length ld required = 1228 mm.
Cap thgickness is = 1250 mm and Clear Cover at bottom = 75 mm
Let Chimney rebar rest on the bottom mesh of cap. So Embedded length provided = 1250-75-32 = 1143 mm which is more than requirement, so Ok.
s
d d
u
F
Development length l is given by : l = ;where o is the total perimeter of all rebars, Fs=Fz
u o

Md. Giasuddin Page 7 of 13 Date : 17 April '11


POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
5.2 - Design of Pile Cap :
5.2.1.- Check Punching of cleats:
5.2.1.a Check For Compression:
Ultimate Compression = 4259.22 kN
Compression to be carried by cleats = 50% of Comp.= 2129.61 kN
Consider 4 cleat group with 4 three cleats in each group. The size of cleats is 150X150X20 ; length 160 .
The Capacity P of each cleat is given by :
Where , b = Length of Angle Shear Connector = 160 mm
t = Thickness of Angle Shear Connector = 20 mm
r = Radius of fillet = 40 mm
Load Carried by each Cleat =0.5* Ccomp./16 = 133.1 kN
1/ 2
1.19 ' ( / 2)
.
1 19 '
c
y
P f b t r x
F
x t w r t
f
= + +

= s


w = width of angle shear connector = 150
( Ref. : Art.7.6.2, Design of Latticed Steel Transmission Structures; Published by The American Society of Civil Engineers)
x = 68.19 mm; So P = 537.47 kN >133.1 kN So OK .
5.2.1.b Check For Uplift:
Ultimate Uplift = 3834.23 kN
Consider 4 cleat group with 4 three cleats in each group. The size of cleats is 150X150X20 ; length 160 .
Load carried by each cleat = 239 64 kN
1.19
c
f

Load carried by each cleat = 239.64 kN
The Capacity P of each cleat is given by :
Where , b = Length of Angle Shear Connector = 160 mm
t = Thickness of Angle Shear Connector = 20 mm
r = Radius of fillet = 40 mm
w = width of angle shear connector = 150
x = 68.19 mm; So P = 537.47 kN >239.64 kN So OK .
1/ 2
1.19 ' ( / 2)
.
1.19 '
c
y
c
P f b t r x
F
x t w r t
f
= + +

= s


5.2.2 - Check cap thickness for Flexural Shear :
Total shear acting at a distance d/2 from the face of the column = 3*Rmax; Where Rmax=Rc or Rt whichever is larger.
Rmax = 699.76 kN
So Total Shear,Vc =2*699.76 =1399.52 kN
Where, b = 4500 mm
Consider clear cover 75 and dia of Bar 16 mm , So d ( Outer Layer) = 1250-75-8 =1167 mm , where d is the effective depth of cap.
d ( Inner Layer) = 1250-75-16 - 8 = 1151 mm
dave = ( 1167+1151 )/2 = 1159 mm dave. = ( 1167+1151 )/2 = 1159 mm
So, Vc = Vc/bd = 0.27 Mpa
5.2.3.- Check for position of Piles :
Distance from pile edge to pile cap edge, x = 200 mm
Distance from pile center to pile cap edge = 500 mm
Diameter of punching plane, y = 800 mm
AS per ACI Shear Stress applied to concrete should be less than 0.17f'c Mpa. In present case which is coming 0.93 Mpa. This is greater than applied
stress so consideration is quite Ok.
Perimeter of punching plane = PI()*800 =2513 mm
So area of concrete to resist punching of pile = 2513*200 = 502600 Sq.mm
Punching stress developed = Rmax*1000/502600 = 1.39 Mpa
Where Rmax is the Maximum pile reaction = Rcmax = 699.76 kN
AS per ACI Shear Stress applied to concrete should be less than 0.34f'c Mpa. In present case
which is coming 1.52 Mpa. This is greater than applied stress, 1.39 Mpa, so consideration is quite
Ok.
Md. Giasuddin Page 8 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
5.2.4 - Check for Bending Moment :
So M
max
=3*R
max
*x' , Where x' = 1.350 m p
b
= 0.02187
M
max
= 1889.4 kN.m. p
max
= 0.75* p
b
= 0.01640194
Maximum moment acting at the face of the column=2*Maximum pile reaction*distance between pile center to column face.
f p
b
' 600
=0.85*0.85*
600
c
y y
f
f f +
290.70 mm Which is less than d
provide
; so OK
5.2.5 - Reinforcement Calculation :
5.2.5.1 - Bottom Reinforcement :
2
1 0.59 ...; 0.9
'
y
u y
c
f
M f bd Where
f
p
op o

= =


(1 0.59 )
'
u
y
y
c
M
d
f
f b
f
p
op
. = =

Consider clear cover 75 and dia of Bar 16 mm , So d (Outer Layer) = 1250-75-8 = 1167 mm; where d is the effective depth of cap.
Compressive pile reactions will produce tension at the bottom of the cap.
Mdes = 1889.352 kN.m
Assuming depth of stress block, a = 22.7 mm
Area of steel, As = M*1000000/(0.9*fy*(d-a/2)) =4439 mm2.
(Ref. -Design of concrete structure, By-Nilson & Winter,Page 83 ,10th Ed.)
d ( Inner Layer) = 1250 -75 -16 - 8 = 1151 mm
dmin = MIN( 1151,1167) = 1151 mm
42 Nos. of Dia. 16 mm along both dic.
Check for a
a = As*fy/(.85*fc'*b) = 22.7 mm
Consideration is OK, So As = 4439 mm2.
But Min Rebar Required = 0.0015bt = 8437.5 mm2
Consider bar Size = 16 mm
So Nos. of Bars = 42 Nos
5.2.5.2 - Top Reinforcement :
Consider clear cover 50 and dia of Bar 16 mm , So d (Outer Layer) = 1250 -50-8 = 1192 mm
Where d is the effective depth of cap from Cap Bottom to Rebar center at Top.
Tensile pile reactions will produce tension at the top of the cap.
So Mu= 2*Rt*x' , Where x' = 1.35 m 42 Nos. of Dia. 16 mm along both dic.
Mdes = 1399.14 kN.m
Assuming depth of stress block, a = 16.4 mm
d = Min(1192,1176) = 1176 mm
d ( Inner Layer) = 1250 -50-16 - 8 = 1176 mm
Cap Reinforcement Plan at Bottom
Area of steel, As = M*1000000/(0.9*fy*(d-a/2)) = 3208 mm2
(Ref. -Design of concrete structure, By-Nilson & Winter,Page 83 ,10th Ed.)
Consideration is OK, So As = 3208 mm2
Min Rebar Required = 0.0015bt = 8437.5 mm2
Consider bar Size = 16 mm
So Nos. of Bars = 42 Nos
a = As*fy/(.85*fc'*b) = 16.4 mm
Check for a
5.2.5.3 -Vertical Reinforcement Around The pile cap :
Total uplift to be resisted by the vertical rebars around the pile cap = Fz = 3834.23 kN
So As = Fz*1000/0.7/Fy = 13198.73 mm2
Total Nos. of top reinforcement is 168 whose total area is 33778 mm2.
So if all top bars are bent downwards this will be good enough for uplift.
As per BS 8110, Ultimate bond stress in tension bars uu is given by : Uu = 0.4fc' = 1.84 Mpa
So Development length ld required = 247 mm
Provide all top bars bent downwards for the half depth of the cap.It will be suffient for development length.
Cap Reinforcement Plan at Top
s
d
u
F
Development length ld is given by : l = ;where o is the total perimeter of all rebars, Fs=Fz
u o

Md. Giasuddin Page 9 of 13 Date : 17 April '11


POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
5.2.5.4 -Horizontal Reinforcement Around The pile cap :
Provide 5 nos. of 10mm dia bar around the cap distributed along the whole depth with 300 mm lapping at the joint.
6 - Structural Design of Pile
Ultimate loads on Single Pile : Ultimate loads on Single Pile :
Compressive load = Rc = 699.76 kN
Uplift load = Rt = 518.2 kN
Ultimate Moment For Maximum Compression , Mu = 349.44 kN.m
Ultimate Moment For Max Uplift , Mu = 309.15 kN.m
6.1 Design of upper segment of pile
6.1.1 Design for Compression Plus Bending g p g
Pile diameter, h = 600 mm
A
c
= r/4h
2
= 282743.3 Sqmm.
v
c
= 1.5
Pile Section at Upper Segment
1.5
1.5
1.5
c
c c
c
c c
tot y c
c c
N
f A
M
f A h
A f
A f
v
v
v

v
u

=



=



=


N = Normal Load = 699760.00 N
f
c
= 30.00 MPa
M = Moment = 349440000.00 N.mm
so v = 0.082
And = 0.069
For above values of v & u = 0.2 ( From chart of Annexure-2 )
So A
tot
= 1.5uA
c
f
c
/v
c
f
y
= 4087.9 Sqmm.
Rebar Dia = 25 mm
Pile Section at Lower Segment
So Nos. of Bar = 9 Nos.
6.1.2 Design for Tension Plus Bending
N = Normal Load = 518200.00 N
f
c
= 30.00 MPa
M = Moment = 309150000.00 N.mm
so v = 0.061
And = 0.061
For above values of v & u = 0.28 ( From chart of Annexure-2 )
Hu
So A
tot
= 1.5uA
c
f
c
/v
c
f
y
= 5723.0 Sqmm.
Rebar Dia = 25 mm
So Nos. of Bar = 12 Nos.
Provide 13 nos. of dia. 25mm.
Length of fixity is 5.53 meter. ( Ref. to clause4.4 - Check for pile head deflection: )
6.2 Calculation to Find Point of Zero Moment in the Pile
For safe dissipation of moment at the point of fixity designed rebar is extended by 1.97 meter
below the point of fixity. Hence length of upper segment of the pile is 7.5 meter.
S
e
g
m
e
n
t

L
e
n
g
t
h

o
f

p
i
l
e
3.25
Hu ( for Uplift ) = 136.35 kN
So Moment =-0.1 at a distance 7.237 m from Pile Top
Since Tension plus Bending combination requires more reinforcement than that of compression
plus bending combination, Uplift case is taken into consideration.
p
1+sin
Where k = Co-efficient of passive earth pressure =
1-Sin
o
o
=
Kp h
h
=

1
s
t

Passive Pressure on Pile
p
1
Moment at aheight is * k h*h*Pile Dia*h/3 =0.0
2
u
h H h =
Md. Giasuddin Page 10 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
h = 7.237 m and Pile Dia = 0.6 m
Upper segment considered = 7.5 meter
Rebar Requirement to Resist Tensile force :
Acting tension at any point = Tension at pile top - Frictional Resistance by Soil
Skin Friction is given by = 0.5*K
s
*P
d
*tand*A
s
(h should be measured from GL but 1st segment of pile is
considered Conservatively)
g y
s d s
Where; K
s
=0.7, d= o = 32 Degree
Submerged Density of soil = 8 KN/Cum
Pd=7.5 *8 = 60 kN/Sqm
As=PI()*0.6*7.5 = 14.14 Sqm
So, Frictional Resistance by soil=0.5*0.7*60*Tan15*14.14 = 185.55 kN
Net Tension at the point = 518.2 - 185.55 = 332.65 kN
Tensile Force to be resisted = 332650 N
Consider no tension to be resisted by concrete that means all tensile forces shall be resisted by rebar only.
Yield Strength of Rebar = 415 Mpa
So Tensile Strength Can be considered as = 0.7*415=290.5 Mpa
So Rebar area required to resist Tensile force = 332650 / 290.5 = 1146 mm2
Minimum Rebar for pile section is = 0.004*X-Sectinal area of pile = 1131 mm2.
6 nos. of dia 16 mm for the lower segment is ok from structural point and minimum requirement as well.
Md. Giasuddin Page 11 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
Annexure-1: Reinforcement Chart for Chimney
Md. Giasuddin Page 12 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-2 FOR Foundation of Tower Type 2DT6 for SC 2 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
Annexure-2: Reinforcement Chart for Pile
Md. Giasuddin Page 13 of 13 Date : 17 April '11
1st Subm. 17-Apr-11
Md. Giasuddin
Foundation Design Calculation of Tower Type 2DT6 For
Soil Category-3
Submission
Status
Date
AUTHORITY NAME & SIGN DATE Paper Size Language Total Sheets
DESIGNED BY
Md. Giasuddin
17-Apr-11 For approval A4 English 13
CHECKED BY
Md. Giasuddin
For construction Scale : N/A
Revision
1st Sub.
APPROVED BY As Built
SUBMISSION SOUGHT
Document No. :
PGCB/230kV/TL/B-C/Lot-3/Des.Cal/Local/09
Designed By Description Approved By
EMPLOYER :
POWER GRID COMPANY OF
BANGLADESH LTD.
CONTRACTOR :
SANERGY CO.
NAME OF PROJECT :
DESIGN-BUILD AND TRUNKEY CONTRACT FOR CONSTRUCTION OF 230kV BIBYANA -
COMILLA TRANSMISSION LINE (LOT-3)
POWER GRID COMPANY OF BANGLADESH LIMITED
Contents Page No.
1. General. 03
1.1 Foundation Loads 03
Foundation of Tower Type 2DT6 for SC-3
FOR BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
1.2 Geotechnical Information 03
1.3 Foundation Strength Factors 03
1.4 Factored Foundation Loads 03
1.5 Codes & Standards Considered 03
1.6 Material Properties 03
1.7 Geometrical Data of the Tower 2DT6 03
1.8 Layout Plan Of the Foundation 04
2. Residual Shear Calculation 04
3. Foundation Geometry 05
4 : Design Calculation for Pile 05
4.1 - Pile Design Load Against Compressive Load 05
4.2 - Pile Design Load Against Uplift 05 g oad ga Up 05
4.3 - Minimum Length of Pile Group Against Uprooting 05
4.4 - Check for pile head deflection 06
4.5 - Ultimate Stress on Pile Section 07
Section-5 :Structural Design of Chimney & Pile Cap 07
5.1 - Design of Chimney 07
5 2 D i f Pil C 08 5.2 - Design of Pile Cap 08
5.2.1.- Check Punching of cleats 08
5.2.1.a Check For Compression 08
5.2.1.b Check For Uplift 08
5.2.2 - Check cap thickness for Flexural Shear 08
5.2.3.- Check for position of Piles 08
5.2.4 - Check for Bending Moment 09
5.2.5 - Reinforcement Calculation 09
5.2.5.1 - Bottom Reinforcement 08
5.2.5.2 - Top Reinforcement 09
5.2.5.3 -Vertical Reinforcement Around The pile cap 09
5.2.5.4 -Horizontal Reinforcement Around The pile cap 10
6 - Structural Design of Pile 10
6.1 Design of upper segment of pile 10
6.1.1 Design for Compression Plus Bending 10
6.1.2 Design for Tension Plus Bending 10
6.2 Calculation to Find Point of Zero Moment in the Pile 10
Annexure-1 12
Annexure-2 13
Giasuddin Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR
1. General.
1.1 Foundation Loads :
Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
The objective of this generic design is to compute loads on individual pile top, length of fixity of pile and is to design pile, pile cap and chimney. If not
mentioned otherwise, values with suffices x, y and z indicate three global directions with outward positive.
F
z
( kN ) F
x
(kN) F
y
(kN)
3154.98 893.33 831.62
2840.17 893.33 831.62
1.2 Geotechnical Information:
Items
Max Compression Case
Max Uplift Case
Ultimate Loads Along Global Direction ( Pull and Thrust Vertical)
Angle of Int. Friction, = 30 Degree
Soil Density = 17 kN/Cum.
Soil Submerged Density = 7 kN/Cum.
Frustum angle = 15 Degree; As per techinical specification
1.3 Foundation Strength Factors :
2DL 2D1
Applied Loading Case
Strength Factor
2D25 2DT6
1.4. Factored Foundation Loads.
Factored Loads by using Foundation Strength Factor from Appendix (7.A2),Volume 2 of 3
F ( kN ) F (kN) F (kN)
2DL, 2D1
1.35 1.23
Factored Ultimate Loads Along Global Direction ( Pull and Thrust Vertical)
2D25, 2DT6
For All Load Cases
Items F
z
( kN ) F
x
(kN) F
y
(kN)
4259.22 1206.00 1122.69
3834.23 1206.00 1122.69
1.5 Codes & Standards Considered :
ACI
BS 8110
Max Long. Case in Uplift
Max Long. Case in Comp.
Items
1.6 Material Properties and Clear Cover :
28 days cube strength of concrete for Pile; fc' = 30 Mpa.
28 days cube strength of concrete for Pile-Cap; fc' = 25 Mpa.
Corresponding cylinder strength of concrete for Pile-Cap; fc' = 21.25 Mpa.
Yield Strength Reinforcing Steel ;fy = 415 Mpa.
Concrete Clear Cover at top and sides of Cap & Column is = 50 mm.
Concrete Clear Cover for sides of Pile is = 75 mm.
Unit Weight of Concrete = 24 kN/Cum.
1.7 Geometrical Data of the Tower 2DT6 :
Face Slope = = 13.306 Degree.
Diagonal Slope = = 18.493 Degree.
Md. Giasuddin Page 3 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
1.8 Layout Plan Of the Foundation
450 1800 1800 450
4
5
0
450 1800 1800 450
4
5
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
4500
CP
4
5
0
4500
4
5
0
4500
4
5
0
4500
4
5
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
4
5
0
0
900
9
0
0
1
8
0
0
1
8
0
0
Layout Plan of Foundation
450 1800 1800 450
4
5
0
450 1800 1800 450
4
5
0
2. Residual Shear Calculation :
F
xleg
F
yleg
F
xRes
= F
x
-F
xleg
F
yRes
= F
y
-F
yleg
Max Compression Case 4259.22 1007.31 1007.31 1206.00 1122.69 198.69 115.38
Max Uplift Case 3834.23 906.80 906.80 1206.00 1122.69 299.20 215.89
Vertical Loads
F
z
( kN )
Items
Residual Shear ( kN )
F
x
(kN) F
y
(kN)
Leg Shear ( kN ) = F
z
*Tano
Md. Giasuddin Page 4 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
3. Foundation Geometry :
Size of the column = 900 mmX900 mm.
Dia of the Pile, Dp = 600 mm.
h'' = 280.5 mm.
h' 400 h' = 400 mm.
f = 300 mm.
Pile Center to center Distance = 1800 mm.
Height of column, h = 700 mm.
Length/Width of the Cap, L/B = 4500 mm.
Cap Thickness, t = 1250 mm.
No. of Pile Per Leg = 8 Nos
Weight Calculation
Weight of Column, Wcol = 13.61 kNs.
Weight of Pad, Wpad = 607.5 kNs.
Weight of Superimposed Soil, Ws =103.28 kNs.
Bouyant Weight of Column, W'col = 7.94 kNs
Bouyant Weight of Pad, W'pad = 354.38 kNs
Bouyant Weight of Superimposed Soil, W's = 42.53 kNs
Loads on Pile top :
Foundation Layout Detail Typical Pile Cap Section
For Maximum Comp.
Resultant Compressive Load = Rzc =Fz+ 1.35*(Wcol+Wpad+Ws) = 5150.22 kNs.
Moment Mx = Moment for Leg and Residual Shear = Fxleg*0.0 + FxRes*(t+h+h''-0.15) =376.12 kN.m
Moment My = Moment for Leg and Residual Shear = Fyleg*0.0 + FyRes*(t+h+h''-0.15) = 218.41 kN.m
For Maximum Uplift :
Resultant Uplift = Rzt=Fz - W'col - W'pad - W's = 3429.38 kNs
Moment Mx = Moment for Leg and Residual Shear = Fxleg*0.0 + Fxres*(t+h+h''-0.15) = 566.39 kN.m
Moment My = Moment for Leg and Residual Shear = Fyleg*0.0 + Fyres*(t+h+h''-0.15) = 408.68 kN.m
4 : Design Calculation for Pile :
Reaction of pile with applied vertical loads and biaxial bending moment can be expressed by the following equation:
y
V x
V 2 2
M *d1y
R M *d1x
R =
8 dix diy

Where , d1x and d1y denote the distances from pile center to cap center along X or Y Direction. In this case d1x=d1y= 0.9 m.
6*1.8^2 = 19.44 Sqm.
4.1 - Pile Design Load Against Compressive Load :
Maximum compresive load that a pile will be imposed can be expressed by :
So Rcmax = 698.83 kNs. ( Pile weight is to be considered during Pile schedule)
4.2 - Pile Design Load Against Uplift :

= =
2 2
diy dix
y
zc x
Cmax 2 2
M *d1y
R M *d1x
R =
8 dix diy
+ +

g g p
Maximum compresive load that a pile will be imposed can be expressed by :
So Rtmax = 518.96 kNs. ( Pile weight is to be considered during Pile schedule)
4.3 - Minimum Length of Pile Group Against Uprooting :
Soil body to Resist Uplift
Say minimum length of pile =9 m
Depth of pile, d = 10.625 m. So a = d/2 = 5.313 m.
The base size of the soil frustum at the lowest point b' = 4.2m X4.2 m
The base size of the soil frustum at Mid Height ; b =5.247 m X5.247 m
Average Area = (4.2^2+5.247^2)/2 =22.59 sqm.
y
zt x
Tmax 2 2
M *d1y
R M *d1x
R =
8 dix diy
+ +

Md. Giasuddin Page 5 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
So Frustum Volume = 22.59 * 5.3125 =120.01 cum
The upper soil volume = 5.247^2*5.313= 146.27 cum
Total soil Volume = 266.28 Cum
Total weight of soil body = 266.28*7=1863.96 kN
Skin resistance of pile group is Given by :
GL
Q =2*( ) * * L B H f +
Ks =1 ;( soil to soil co-efficient of earth pressure)
P
d
=yd, o = o= 30 Degree
y = Submerged Density of soil = 7 kN/Cum.
Pd =7 *10 625 = 74 375 kNs
a
su
s
Q =2*( ) * *
Where L and B are the overall length and width of pile group,
H is the depth of soil block and f is the unit skin friction
1
which is given by
2
s
s d
L B H f
fs K p Tano
+
=
Pd 7 10.625 74.375 kNs.
So fs = 21.47 kN/Sqm.
L= B = b' = 4.2 m and H = d = 10.625 m.
So Qsu = 3832.4 kNs
Allowable capacity (FS=1.5) = 3797.57 kNs
Resultant Uplift = 3429.38 kNs.
Which is less than 3797.57 kNs So OK.
Ultimate uplift capacity of pile group = Skin Resistance +
Submerged Weight of soil body = 5696.36kNs.
b
d
L
Which is less than 3797.57 kNs So OK.
4.4 - Check for pile head deflection:
For Max Compression:
Fx = Leg Shear = 1007.31 kN
Fy = Leg Shear = 1007.31 kN
Passive resistance by Cap Only ( Same in x and y face)
109 27 kN
a
1
Passive resistance by Pile Cap is k *(1 55+0 30)*1 25*4 5 = = 109.27 kN
3.00
=Submerged density of soil =7 kN/Cum.
Net Fx = Leg Shear = 898.04 kN
Net Fy = Leg Shear = 898.04 kN
Vres=Sqrt.(898.04^2+898.04^2)=1270.02 kN
Lateral Load carried by a single Pile = 158.75 kN
b'
GL
Cap Top
3
0
0
p
1+sin
Where k = Co-efficient of passive earth pressure =
1-Sin
o
o
=
p
Passive resistance by Pile Cap is k *(1.55+0.30)*1.25*4.5 =
2
=
For Max Uplift:
Fx = Leg Shear = 906.8 kN
Fy = Leg Shear = 906.8 kN
Net Fx = Leg Shear = 797.53 kN
Net Fy = Leg Shear = 797.53 kN
Vres=Sqrt.(797.53^2+797.53^2)=1127.88 kN
Lateral Load carried by a single Pile = 140.99 kN
Design shear carried by a single Pile Qmax = 158.75 kN
Kp h
Cap Bot.
1
2
5
0
Design shear carried by a single Pile Qmax 158.75 kN
For fixed head pile depth of fixity is given by
L
f
/T = 2.15; (Ref. to figure no 2 , appendix C of IS: 2911) For fixed head piles .
K1 = 0.146 For Submerged Loose Sand
Where ; 25742.96 Mpa = 257430 kg/sqcm.
636172.5 cm4 EI = 163769889855 kg.sqcm.
So T = 257.03 cm = 2.57 m
So depth of fixity, Lf = 5.53 m
Deflection, Y = Q*(Lf)^3/12EI = 1.366 cm. = 13.66 mm; Which is less than 25mm, So OK.
5
Where, 1 and T EI K =
4700 '
c
E f = =
4
64
d
I
r
= =
Kp h
Passive Pressure on Cap
Md. Giasuddin Page 6 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
4.5 - Ultimate Stress on Pile Section
For Max Compression
For fixed head long pile :
Moment M=m.M
F
= 0.82*Q*Lf/2 =
For Max Compression M = 359.93 kN.m
For Max Uplift M = 319.67 kN.m
For Max Compression.
Q = Hu = 158.75 kN.
So Mu = 359.93 kN.m
For Max Uplift
Q = Hu = 140.99 kN.
So Mu = 319.67 kN.m
Ultimate loads on Single Pile :
Compressive load = Rc = 698.83 kN
Uplift load = Rt = 518.96 kN
For Max Compression ultimate Moment , Mu = 359.93 kN.m
For Max Uplift ultimate Moment , Mu = 319.67 kN.m
Section-5 : Structural Design of Chimney & Pile Cap
5.1 - Design of Chimney :
Ultimate Compression = 4259.22 kN
50% of Ult. Compression = 2129.61 kN
Residual shear :
F
xmax
= 299.20 kN
F
ymax
= 215.89 kN
Resultant F
xy
= 368.96 kN
M = Fxy* 0.793 = 292.6 kN.m. 1 of 12 of dia. 20 mm y
P
u
= 2129610.00 N
M
u
= 292582755.1 N.mm
D = 900.00 mm
b = 900 mm
d' = 66 mm
d'/D = 0.073 mm
f
ck
= 25.0 Mpa
f
y
= 415.0 Mpa
P
u
/f
ck
bD =
0.105
M
u
/f
ck
bD
2
=
0.016
For the above values, graph ( see annexure-1 ) shows that no rebar is needed.
As per Code Min Rebar Required = 0.004*900^2 = 3240 mm2
Consider Bar Dia. 20 mm
Provide 12 nos 20mm dia.
Embedded Length of Rebar.
C i t b i t d b th b i hi F 2129 61 kN
Column Section
Compression to be resisted by the rebars in chimney = Fz = 2129.61 kN
Total Nos. of reinforcement is 12 of dia 20 12mm.
As per BS 8110, Ultimate bond stress in compression bars u
u
is given by : u
u
=0.5fc' Mpa
So Uu = 2.3 Mpa. So Development length ld required = 1228 mm.
Cap thgickness is = 1250 mm and Clear Cover at bottom = 75 mm
Let Chimney rebar rest on the bottom mesh of cap. So Embedded length provided = 1250-75-32 = 1143 mm which is more than requirement, so Ok.
s
d d
u
F
Development length l is given by : l = ;where o is the total perimeter of all rebars, Fs=Fz
u o

Md. Giasuddin Page 7 of 13 Date : 17 April '11


POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
5.2 - Design of Pile Cap :
5.2.1.- Check Punching of cleats:
5.2.1.a Check For Compression:
Ultimate Compression = 4259.22 kN
Compression to be carried by cleats = 50% of Comp.= 2129.61 kN
Consider 4 cleat group with 4 three cleats in each group. The size of cleats is 150X150X20 ; length 160 .
The Capacity P of each cleat is given by :
Where , b = Length of Angle Shear Connector = 160 mm
t = Thickness of Angle Shear Connector = 20 mm
r = Radius of fillet = 40 mm
Load Carried by each Cleat =0.5* Ccomp./16 = 133.1 kN
1/ 2
1.19 ' ( / 2)
.
1 19 '
c
y
P f b t r x
F
x t w r t
f
= + +

= s


w = width of angle shear connector = 150
( Ref. : Art.7.6.2, Design of Latticed Steel Transmission Structures; Published by The American Society of Civil Engineers)
x = 68.19 mm; So P = 537.47 kN >133.1 kN So OK .
5.2.1.b Check For Uplift:
Ultimate Uplift = 3834.23 kN
Consider 4 cleat group with 4 three cleats in each group. The size of cleats is 150X150X20 ; length 160 .
Load carried by each cleat = 239 64 kN
1.19
c
f

Load carried by each cleat = 239.64 kN
The Capacity P of each cleat is given by :
Where , b = Length of Angle Shear Connector = 160 mm
t = Thickness of Angle Shear Connector = 20 mm
r = Radius of fillet = 40 mm
w = width of angle shear connector = 150
x = 68.19 mm; So P = 537.47 kN >239.64 kN So OK .
1/ 2
1.19 ' ( / 2)
.
1.19 '
c
y
c
P f b t r x
F
x t w r t
f
= + +

= s


5.2.2 - Check cap thickness for Flexural Shear :
Total shear acting at a distance d/2 from the face of the column = 3*Rmax; Where Rmax=Rc or Rt whichever is larger.
Rmax = 698.83 kN
So Total Shear,Vc =2*698.83 =1397.66 kN
Where, b = 4500 mm
Consider clear cover 75 and dia of Bar 16 mm , So d ( Outer Layer) = 1250-75-8 =1167 mm , where d is the effective depth of cap.
d ( Inner Layer) = 1250-75-16 - 8 = 1151 mm
dave = ( 1167+1151 )/2 = 1159 mm dave. = ( 1167+1151 )/2 = 1159 mm
So, Vc = Vc/bd = 0.27 Mpa
5.2.3.- Check for position of Piles :
Distance from pile edge to pile cap edge, x = 200 mm
Distance from pile center to pile cap edge = 500 mm
Diameter of punching plane, y = 800 mm
AS per ACI Shear Stress applied to concrete should be less than 0.17f'c Mpa. In present case which is coming 0.93 Mpa. This is greater than applied
stress so consideration is quite Ok.
Perimeter of punching plane = PI()*800 =2513 mm
So area of concrete to resist punching of pile = 2513*200 = 502600 Sq.mm
Punching stress developed = Rmax*1000/502600 = 1.39 Mpa
Where Rmax is the Maximum pile reaction = Rcmax = 698.83 kN
AS per ACI Shear Stress applied to concrete should be less than 0.34f'c Mpa. In present case
which is coming 1.52 Mpa. This is greater than applied stress, 1.39 Mpa, so consideration is quite
Ok.
Md. Giasuddin Page 8 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
5.2.4 - Check for Bending Moment :
So M
max
=3*R
max
*x' , Where x' = 1.350 m p
b
= 0.02187
M
max
= 1886.8 kN.m. p
max
= 0.75* p
b
= 0.01640194
Maximum moment acting at the face of the column=2*Maximum pile reaction*distance between pile center to column face.
f p
b
' 600
=0.85*0.85*
600
c
y y
f
f f +
290.51 mm Which is less than d
provide
; so OK
5.2.5 - Reinforcement Calculation :
5.2.5.1 - Bottom Reinforcement :
2
1 0.59 ...; 0.9
'
y
u y
c
f
M f bd Where
f
p
op o

= =


(1 0.59 )
'
u
y
y
c
M
d
f
f b
f
p
op
. = =

Consider clear cover 75 and dia of Bar 16 mm , So d (Outer Layer) = 1250-75-8 = 1167 mm; where d is the effective depth of cap.
Compressive pile reactions will produce tension at the bottom of the cap.
Mdes = 1886.841 kN.m
Assuming depth of stress block, a = 22.6 mm
Area of steel, As = M*1000000/(0.9*fy*(d-a/2)) =4433 mm2.
(Ref. -Design of concrete structure, By-Nilson & Winter,Page 83 ,10th Ed.)
d ( Inner Layer) = 1250 -75 -16 - 8 = 1151 mm
dmin = MIN( 1151,1167) = 1151 mm
42 Nos. of Dia. 16 mm along both dic.
Check for a
a = As*fy/(.85*fc'*b) = 22.6 mm
Consideration is OK, So As = 4433 mm2.
But Min Rebar Required = 0.0015bt = 8437.5 mm2
Consider bar Size = 16 mm
So Nos. of Bars = 42 Nos
5.2.5.2 - Top Reinforcement :
Consider clear cover 50 and dia of Bar 16 mm , So d (Outer Layer) = 1250 -50-8 = 1192 mm
Where d is the effective depth of cap from Cap Bottom to Rebar center at Top.
Tensile pile reactions will produce tension at the top of the cap.
So Mu= 2*Rt*x' , Where x' = 1.35 m 42 Nos. of Dia. 16 mm along both dic.
Mdes = 1401.19 kN.m
Assuming depth of stress block, a = 16.4 mm
d = Min(1192,1176) = 1176 mm
d ( Inner Layer) = 1250 -50-16 - 8 = 1176 mm
Cap Reinforcement Plan at Bottom
Area of steel, As = M*1000000/(0.9*fy*(d-a/2)) = 3212 mm2
(Ref. -Design of concrete structure, By-Nilson & Winter,Page 83 ,10th Ed.)
Consideration is OK, So As = 3212 mm2
Min Rebar Required = 0.0015bt = 8437.5 mm2
Consider bar Size = 16 mm
So Nos. of Bars = 42 Nos
a = As*fy/(.85*fc'*b) = 16.4 mm
Check for a
5.2.5.3 -Vertical Reinforcement Around The pile cap :
Total uplift to be resisted by the vertical rebars around the pile cap = Fz = 3834.23 kN
So As = Fz*1000/0.7/Fy = 13198.73 mm2
Total Nos. of top reinforcement is 168 whose total area is 33778 mm2.
So if all top bars are bent downwards this will be good enough for uplift.
As per BS 8110, Ultimate bond stress in tension bars uu is given by : Uu = 0.4fc' = 1.84 Mpa
So Development length ld required = 247 mm
Provide all top bars bent downwards for the half depth of the cap.It will be suffient for development length.
Cap Reinforcement Plan at Top
s
d
u
F
Development length ld is given by : l = ;where o is the total perimeter of all rebars, Fs=Fz
u o

Md. Giasuddin Page 9 of 13 Date : 17 April '11


POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
5.2.5.4 -Horizontal Reinforcement Around The pile cap :
Provide 5 nos. of 10mm dia bar around the cap distributed along the whole depth with 300 mm lapping at the joint.
6 - Structural Design of Pile
Ultimate loads on Single Pile : Ultimate loads on Single Pile :
Compressive load = Rc = 698.83 kN
Uplift load = Rt = 518.96 kN
Ultimate Moment For Maximum Compression , Mu = 359.93 kN.m
Ultimate Moment For Max Uplift , Mu = 319.67 kN.m
6.1 Design of upper segment of pile
6.1.1 Design for Compression Plus Bending g p g
Pile diameter, h = 600 mm
A
c
= r/4h
2
= 282743.3 Sqmm.
v
c
= 1.5
Pile Section at Upper Segment
1.5
1.5
1.5
c
c c
c
c c
tot y c
c c
N
f A
M
f A h
A f
A f
v
v
v

v
u

=



=



=


N = Normal Load = 698830.00 N
f
c
= 30.00 MPa
M = Moment = 359930000.00 N.mm
so v = 0.082
And = 0.071
For above values of v & u = 0.2 ( From chart of Annexure-2 )
So A
tot
= 1.5uA
c
f
c
/v
c
f
y
= 4087.9 Sqmm.
Rebar Dia = 25 mm
Pile Section at Upper Segment
So Nos. of Bar = 9 Nos.
6.1.2 Design for Tension Plus Bending
N = Normal Load = 518960.00 N
f
c
= 30.00 MPa
M = Moment = 319670000.00 N.mm
so v = 0.061
And = 0.063
For above values of v & u = 0.3 ( From chart of Annexure-2 )
Pile Section at Lower Segment
Hu
So A
tot
= 1.5uA
c
f
c
/v
c
f
y
= 6131.8 Sqmm.
Rebar Dia = 25 mm
So Nos. of Bar = 13 Nos.
Provide 14 nos. of dia. 25mm.
Length of fixity is 5.53 meter. ( Ref. to clause4.4 - Check for pile head deflection: )
6.2 Calculation to Find Point of Zero Moment in the Pile
For safe dissipation of moment at the point of fixity designed rebar is extended by 2.97 meter
below the point of fixity. Hence length of upper segment of the pile is 8.5 meter.
S
e
g
m
e
n
t

L
e
n
g
t
h

o
f

p
i
l
e
3.00
Hu ( for Uplift ) = 140.99 kN
So Moment =-0.1 at a distance 8.194 m from Pile Top
Since Tension plus Bending combination requires more reinforcement than that of compression
plus bending combination, Uplift case is taken into consideration.
p
1+sin
Where k = Co-efficient of passive earth pressure =
1-Sin
o
o
=
Kp h
h
=

1
s
t

Passive Pressure on Pile
p
1
Moment at aheight is * k h*h*Pile Dia*h/3 =0.0
2
u
h H h =
Md. Giasuddin Page 10 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
h = 8.194 m and Pile Dia = 0.6 m
Upper segment considered = 8.5 meter
Rebar Requirement to Resist Tensile force :
Acting tension at any point = Tension at pile top - Frictional Resistance by Soil
Skin Friction is given by = 0.5*K
s
*P
d
*tand*A
s
(h should be measured from GL but 1st segment of pile is
considered Conservatively)
g y
s d s
Where; K
s
=0.7, d= o = 30 Degree
Submerged Density of soil = 7 KN/Cum
Pd=8.5 *7 = 59.5 kN/Sqm
As=PI()*0.6*8.5 = 16.02 Sqm
So, Frictional Resistance by soil=0.5*0.7*59.5*Tan15*16.02 = 192.61 kN
Net Tension at the point = 518.96 - 192.61 = 326.35 kN
Tensile Force to be resisted = 326350 N
Consider no tension to be resisted by concrete that means all tensile forces shall be resisted by rebar only.
Yield Strength of Rebar = 415 Mpa
So Tensile Strength Can be considered as = 0.7*415=290.5 Mpa
So Rebar area required to resist Tensile force = 326350 / 290.5 = 1124 mm2
Minimum Rebar for pile section is = 0.004*X-Sectinal area of pile = 1131 mm2.
7 nos. of dia 16 mm for the lower segment is ok from structural point and minimum requirement as well.
Md. Giasuddin Page 11 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
Annexure-1: Reinforcement Chart for Chimney
Md. Giasuddin Page 12 of 13 Date : 17 April '11
POWER GRID COMPANY OF BANGLADESH LIMITED
Foundation of Tower Type 2DT6 for SC-3 FOR Foundation of Tower Type 2DT6 for SC 3 FOR
BIBYANA - COMILLA 230kV TRANSMISSION LINE (LOT-3)
Annexure-2: Reinforcement Chart for Pile
Md. Giasuddin Page 13 of 13 Date : 17 April '11