Professional Documents
Culture Documents
(11.8 10
9
)T
3
(17.2 10
12
)T
4
}
Thermal expansion: L/ L1.2 10
5
Tm/m
(100CT800C)
page 6 CICIND Model Code
Steel Grade Steel Grade Steel Grade
Fe 360 Fe 430 Fe 510
C f
yT
/f
y
f
yT
f
yT
/1.1 f
yT
f
yT
/1.1 f
yT
f
yT
/1.1
20 1.000 235 214 275 250 355 323
200 0.880 207 188 242 220 312 284
250 0.832 196 178 229 208 295 269
300 0.778 183 166 214 195 276 251
350 0.717 169 153 197 179 255 231
400 0.647 152 138 178 162 230 209
Table 6.2 Yield stresses of structural steel in MPa
(thicknesses t 16mm)
Note
1) For thicknesses greater than 16mm the yield stress f
y
shall be
reduced according to Table 6.1.
2) For temperatures higher than 350C alloy steels should be
considered.
3) Special attention should be paid to the modulus of elasticity at
high temperatures for stainless steel.
4) Linear interpolation is acceptable
Temperature C 20 200 250 300 350 400
E
T
in GPa 210 202 198 192 185 174
Table 6.3 Youngs Modulus of structural steel at
high temperatures
6.3. Stainless and alloy steels
When metal temperatures are expected to exceed 400C, stainless or
alloy steels should be used.
Ordinary stainless steels (including high molybdenum stainless steel)
have poor corrosion resistance in the presence of condensing
sulphuric or other acids in the range of concentrations and
temperatures normally found within chimneys. These materials are
therefore not recommended in chimneys burning fuels containing
sulphur under conditions of medium or high chemical load, see
paragraph 7.6.3.
When metal temperatures and condensate sulphuric acid
concentrations are expected to be less than 65C and 5% respectively,
the corrosion rates of high molybdenum stainless steels, such as
ASTM Type 316L, are acceptable. Such conditions can be expected
on the external surface at the top (over a height of about 3 diameters)
of any chimney handling high sulphur ue gases.
(Note: the conditions downstream of a ue gas scrubber or the
presence of chlorides in the condensate will radically increase the
corrosion rate, possibly rendering these stainless steels unsuitable for
these applications.)
Ordinary stainless steels are not suitable for use in contact with ue
gases containing alkalis.
In cases where it is not possible to avoid high chemical load on the
internal face of the structural shell, see paragraph 7.6.3, the use of a
protective coating may be considered (see lit[19]). Alternatively, a
steel liner or liners, possibly of titanium or high nickel alloy, is a
possible solution. See section 10 on Steel Liners.
Low copper alloy steels have good resistance to atmospheric
corrosion, except in a marine environment or other environment
where chlorides are present. These steels also show some corrosion
improvement over carbon steel when in contact with ue gases where
acid condensation of SO
2
/SO
3
(not of HCL condensation) is
intermittent only (e.g. during shutdowns of a stack in intermittent
service, its metal temperature being normally above acid dew point).
When the metal temperature is below acid dew point for prolonged
periods, the performance of low copper alloy steels in contact with
ue gases is similar to that of carbon steel.
Where stainless or alloy steel components are connected to carbon
steel, bolted connections are preferred. In order to avoid accelerated
corrosion due to galvanic action, such connections should include
insulating gaskets. Welded connections are permitted, provided
specialist metallurgical control is exercised with regard to weld
procedures, electrode selection, etc.
Care should be taken to use the correct coefficient of expansion for
the grade and temperature of the steel being considered.
7. ACTIONS (EXTERNAL AND INTERNAL)
7.1. Permanent load
The permanent load shall include the weight of all permanent
constructions, ttings, linings, ues, insulation, present and future
loads including corrosion allowance.
7.1.1. Dust load (temporary load )
On some process plants there can be a carry over of ash or dust
burden. This may adhere to the interior surface of the structural shell
or liner and cause an additional dead load. Such cases should be
investigated at the design stage, the calculated load shall be added to
the permanent load calculated in 7.1 above.
7. 2. Wind
7.2.1 General
The wind load on a chimney depends in the rst instance upon the
magnitude of the wind speeds in the area in which the chimney is to
be erected and their variation with height. Apart from that the wind
loads, in the direction of the wind or perpendicular to that direction,
will be inuenced by some or all of the following:
a) local topography
b) the level of turbulence
c) the presence of nearby structures, including chimneys
d) the air density
e) the value of the drag coefficient (shape factor)
f) the values of the natural frequencies of oscillation
g) the amount of structural damping and mass present
h) the conguration of the rst few mode shapes
i) the effect of ladders, platforms, pipes etc.
7.2.2. Wind speed
7.2.2.1. Basic wind speed
The determination of the effective wind pressure is based on the basic
wind speed.
The basic wind speed V
b
, appropriate to the location where the
chimney is to be erected, is dened as follows: It is the mean hourly
speed, measured 10m above ground level in open at country,
without obstructions, at the chimney location, which occurs on
average once every 50 years.
The value of the basic wind must be taken from meteorological
measurement. An indication of values of the basic wind speeds for
various countries may be obtained from the Commentary No.3.
Where the terrain of the location of the chimney is hilly or built-up,
measurements for the determination of V
b
should be taken as near as
possible at a place which is at and open. However, in some very
hilly areas, where at ground is rare, V
b
is sometimes measured at the
chimney location and includes the Topographical factor.
CICIND Model Code page 7
7.2.2.2. Design wind speed
The basis for the determination of the wind loads is the design wind
speed which equals the basic wind speed corrected by three factors
taking into consideration the height of the chimney, the topography
of its surroundings and the existence of adjacent objects. These three
factors are: the height factor k(z), the topographical factor kt and the
interference factor ki.
The design wind-speed is determined by the following expression:
V(z) V
b
k(z) k
t
k
i
{m/s) ... (7.1)
where:
V(z) hourly mean wind speed at elevation z (m/s)
z height above ground level (m)
V
b
basic wind speed (m/s)
k(z) Height factor (z/10)
0.14. This value has been chosen since many chimneys are in
open terrain or project well above the surrounding buildings.
k
t
topographical factor (see 7.2.2.3)
k
i
interference factor (see 7.2.6.1)
If the suitability of a different value of [] can be proved (together with
an appropriate scale factor), it may be used (see Commentary C3.1.3).
7.2.2.3 The inuence of topography
Clause 7.2.2.2 requires the determination of a topographical factor k
t
to account for the increase of mean windspeed over hills and
escarpments in otherwise relatively at terrain (i.e. it is not for use in
mountainous regions). It should be considered for locations closer
than half of the length of the hill slope from the crest or 1.5 times the
height of the cliff.
For certain topographical situations, a method for the determination
of k
t
is given in the following.
k
t
1 0.6 . s for 0.3
k
t
1 2 . s . for 0.05 0.3
k
t
1 for 0.05
Table 7.1 Values of k
t
Where:-
= upwind slope H/L in the wind direction (see Figs. 7.1 & 7.2)
s = factor obtained from Figs. 7.1 & 7.2
H = height of hill or escarpment
x = distance of chimney from crest
z = height of considered position in chimney
L
e
= effective length of the upwind slope, dened in table 7.2
L
u
= actual length of upwind slope in the wind direction
L
d
= actual length of downwind slope in wind direction
Shallow slope (0.05 0.3) Steep slope (0.3)
L
e
L
u
L
e
H / 0.3
Table 7.2 Values of Le
Figure 7.1 Factor s for cliffs and escarpments
Figure 7.2 Factor s for hills and ridges
Figures 7.1 and 7.2 from ENV 1991-2-4 Eurocode 1 Basis of
design and actions on structures wind actions
page 8 Amendment A March 2002 CICIND Model Code
7.2.3. Wind load in the direction of the wind
7.2.3.1. Wind load on isolated chimneys
(For group interference effects, see 7.2.6)
The design wind load w(z) per unit height z is determined by the
following expression:
w(z) w
m
(z) G(N/m) ... (7.2)
where:
w
m
(z) mean hourly wind load per unit height, see formula 7.3
Gthe gust factor, see 7.2.3.3
7.2.3.2. Mean hourly wind load
7.2.3.2.1. Main formula
The mean wind load per unit height is:
w
m
(z) 1/2
a
V(z)
2
C
D
d(z) (N/m) ... (7.3)
where:
a
density of air, see 7.2.3.2.2 (kg/m
3
)
V(z) wind speed at height z, see 7.2.2.2 (m/s)
C
D
shape factor, see 7.2.3.2.3
d(z) outside diameter of the chimney at height z (m)
Note: For z 10m, w
m
(z) w
m
(10)
7.2.3.2.2. Air density
At sea level in temperate climates, the density of air
a
is to be taken as:
a
1.25 kg/m
3
Momentary variations in the density due to atmospheric changes
need not be taken into account.
The air density relevant to a chimney site at an altitude h
1
(m) can be
found from the expression:
a
1.25 (h
1
/ 8000) kg/m
3
... (7.4)
7.2.3.2.3. Shape factor
The shape factor C
D
depends on the Reynolds number Re of the
chimney (see Fig. 7.3), where Re 6.9 10
4
V d, in which
VV(z) is the mean wind speed at the top of the chimney in m/s and
d is the diameter in m.
C
D
1.2 if Re 3 10
5
C
D
1.2 1.36 {log Re 5.48) if 3 10
5
Re 7 10
5
C
D
0 7 if Re 7 10
5
for chimneys with helical vanes C
D
1.4 (see gure 7.3}. C
D
is
applied to the outer diameter of the chimney in the vaned portion and
not the outer dimension of the vanes.
For attachments, including ladders, etc., the area presented to the
wind for each member must use a force coefficient of 1.2 for circular
members and 2.0 for structural shapes. Typical lengths and widths of
ladder members have been taken into account.
Figure 7.3
7.2.3.3 Effect of uctuating part of the wind-speed
The inuence of the uctuating part can be found by multiplying with
the gust factor G.
Ggust factor 1 2 g i {B (E S / )} ... (7.5)
where:
g peak factor (2 log
e
t)
T
3600 f
1
a
air density 1.25kg/m
3
d
1
the diameter (averaged over the top third)
u
1
(z) the mode shape of the rst resonance frequency
c / c
r
damping ratio (see Table 7.4)
h the height of the chimney
If the Scruton number is less than 5, cross-wind oscillations could be
violent. The addition of stabilisers or damping devices (see 7.2.9 and
7.2.10) is mandatory in this case.
If the Scruton number is greater than 5, the designer may choose
between providing stabilisers or damping devices (see 7.2.9 and
7.2.10), or estimating (per 7.2.4.2) the chimneys response and
resulting stresses, ensuring these stresses remain within the limits of
fatigue per 8.5 and that movement does not exceed the limits agreed
per Section 5.4.
7.2.4.2 Estimation of cross-wind amplitudes due to
vortex shedding
The method described in this section for estimating amplitudes
depends upon parameters such as structural damping and
atmospheric turbulence, whose values are not known with certainty.
The results of the calculation should, therefore be treated with care
and should not be assumed to be accurate.
The top amplitude (y) of a chimney moving across the wind because
of vortex shedding depends upon:-
The Scruton Number Sc (see 7.2.4.1 above)
The Strouhal Number St (see 7.2.4.1 above)
The Reynolds Number Re (6.9 10
4
V d)
see 7.2.3.2.3)
The local minimum atmospheric turbulence intensity (I), see
Table 7.3
The chimneys own movement, making the behaviour non
linear
The approximate maximum value of y can be expressed in terms of
two quantities, c
1
and c
2
as follows:-
y K
p
. d
1
. c
1
(c
1
2
c
2
) ... (7.9)
where
d
1
mean diameter over top third of chimney height
c
1
0.08 {1 ( . m
o
) / (K
a
.
a
. d
2
)}
c
2
0.16 .
a
. d
3
. C
a
2
/ (K
a
. m
o
. St
4
. h)
K
p
1.5 when c
1
c
1
2
c
2
0.04
4 when c
1
c
1
2
c
2
0.04
K
a
K
amax
. (1 3 . I)
K
amax
1.5 when Re 10
5
(5.075 0.715 . log
10
Re) when 10
5
Re 5 . 10
5
1.0 when Re 5 . 10
5
C
a
.02 when Re 10
5
(0.07 0.01 . log
10
Re) when 10
5
Re 10
6
.01 when Re 10
6
The value assumed for minimum local turbulence intensity (I) shall
be as listed in Table 7.3.
Chimney Location
Open Sea or Lake shore with at All other terrain Categories
least 5km fetch upwind of water, or
smooth at country without obstacles
Vcr 10m/s 10m/s 7m/s 7m/s
I 0 0.1 0 0.1
Table 7.3
7.2.4.3 Bending Moments due to vortex shedding
In deriving the bending moments associated with the maximum
response amplitude of a chimney due to vortex shedding, the
associated inertial force per unit length [F(z)] should be used.
F(z) (2 f
n
)
2
m(z) y(z) ... (7.10)
Where: m(z) mass per unit length at height z
y(z) maximum amplitude at height z
f
n
natural frequency of nth mode
In deriving the fundamental mode maximum amplitude at height z
from the maximum amplitude at the chimney top (per 7.2.4.2), a
parabolic mode shape may be assumed.
7.2.5. Ovalling
In most cases, a suitably sized stiffening ring at the top of a chimney
will eliminate problems associated with ovalling.
7.2.5.1 Static effect
The uneven wind pressure distribution around the circumference of a
circular cylinder causes bending moments acting on vertical cross-
sections of the shaft. The bending moments have a maximum value of:
M0.08 w
5 sec
(z) d
2
(z) (Nm/m) ... (7.11)
0
h
m(z) u
1
2
(z) dz
0
h
u
1
2
(z) dz
4 . . m
o
c / c
cr
a
d
1
2
page 10 Amendment A March 2002 CICIND Model Code
Where w
5 sec
is the wind pressure at height (z) averaged over 5 sec
(m/s). Note the assumption that 5 sec gust windspeed (m/s) at height
z 1.4 V(z) is safe at all heights.
7.2.5.2 Dynamic effect
Due to vortex excitation ovalling vibration of the shell can occur.
These vibrations can be expected if the frequency of the vortices
(f 2 V S
t
/ d) coincides with an ovalling frequency of the shell.
The fundamental ovalling frequency of unstiffened shells is
determined by:
f
1
(0.5 t / d
2
) . E/
s
... (7.12)
Where EYoungs Modulus of the steel shell
t the average shell thickness (in m) over the top third
d the shell diameter (in m)
s
density of shell material
Substituting typical values of E and
s
, the associated critical
windspeed is then
Vcr 6,500 . t / d m/s ... (7.13)
These vibrations can be reduced sufficiently by stiffening rings. The
distance between stiffeners shall not exceed 9 d. The associated
moment of inertia of the stiffening ring section (together with the
participating length of shell) about its centroid (see g 7.4) must be
larger than:
I 1.75 10
5
d
3
t m
4
... (7.14)
For closer spacing this value of I may be reduced proportionately.
Note These spacing and minimum I requirements should
not be confused with those of stiffeners sometimes required
as reinforcement to resist the static ovalling effect (7.2.5.1) or
to prevent local buckling, either during transport/erection or
as a result of the design wind load (8.3.4).
The participating length of the shell (d . t), but its area must not
exceed that of the stiffener ring (see Fig. 7.4).
Figure 7.4
7.2.6. The increase of wind effects by nearby structures
Interference effects, caused by the presence of a nearby structure
upwind of a chimney, can signicantly increase the chimneys quasi
static wind load in the wind direction, described in 7.2.3 and its
response, normal to the wind direction, described in 7.2.4. If the
interfering structure is itself a chimney, its own response when
downwind of the new chimney should be checked.
7.2.6.1 Effect on wind load in the wind direction
When interference effects are expected from a nearby structure, the
design windspeed per equation 7.1 used to determine the wind load
should be increased by a factor k
i
as dened below:-
a) Where the height of the interfering structure is less than half the
chimney height, k
i
1.0
b) Where the height of the interfering structure is half chimney
height and it is approximately cylindrical in shape, k
i
is
determined from the following expression for values of a/d
between 1 and 30 (see g. 7.5):
k
i
1.2 .0067a/d
a distance of chimney down-wind from the interfering
structure (centre to centre)
d diameter of the interference structure
Fig. 7.5 Effect of interference on downwind loading
7.2.6.2 Effect on cross-wind response
When an approximately cylindrical structure (e.g. another chimney)
is upwind and within 15 diameters of a chimney of similar or smaller
height, aerodynamic Wake Interference effects can considerably
increase the downwind chimneys cross-wind response (the diameter
concerned being that of the interfering structure). The increase is not
yet fully understood, but is thought to be due to increases in both lift
coefficient and negative aerodynamic damping. Note that
aerodynamic stabilisers (e.g. helical spoilers) are ineffective in
controlling response in cases of wake interference.
For a spacing ratio (a/d) greater than 10, the magnication factor k
c
,
applied to response amplitude, calculated per equation (7.12), may be
estimated as follows:-
For a/d 15 :- k
c
1.0
For a/d 10 :- k
c
1.5
k
c
2.5 0.1a/d for a/d between 10 and 15
For a spacing ratio (a/d) less than 10 there is a risk of very large
increases in amplitude. In these circumstances the chimneys structural
damping should be increased (e.g. by the use of a tuned mass damper)
to ensure that the Scruton Number exceeds 25. At this value of Scruton
Number, the amplitude of response is expected to be minimal.
The associated critical windspeed and value of c
2
in equation
(7.12) increase with decreasing values of a/d, due to a reduction in
the value of the Stouhal Number. This can be important in the design
of a tuned mass damper. Fig. 7.6 shows the relationship between
Strouhal Number and a/d.
Centroid of
stiffener and
participating
shell
e
t
d / 2
C
L
d . t
CICIND Model Code Amendment A March 2002 page 11
Figure 7.6 The reduction of Strouhal Number caused by
aerodynamic interference
When the interfering structure or chimney is less than 2 diameters
away, Interference Galloping can cause even greater increases in
the chimneys response. Probably the best solutions in this case
would be either to t tuned mass dampers, or to connect structurally,
the chimney to the interfering structure, using an energy absorbing
connection system.
7.2.7 Damping ratio
The structural damping ratio ( c / c
cr
) without aerodynamic
damping is given in table 7.4.
Type of chimney Damping Ratio
Unlined, uninsulated 0.002
Unlined, externally insulated 0.003
Lined with refractory concrete 0.005
Lined with brickwork 0.015
chimneys with steel liners*:-
26 0.006
28 0.002
Coupled group 0.004
Chimney with tuned mass damper (0.02min) see Appendix 2
Table 7.4
Notes: If rotation of foundation decreases the rst natural frequency
more than about 10% the foundation is considered to be soft
and the damping ratio may be increased by 0.0005.
liner length / liner diameter
* In order to ensure impact damping the gap between the
liner and its restraint should not be greater than 50mm.
The damping for wind loading in wind direction can be increased by
the aerodynamic damping:
c / c
cr
2.7 . 10
6
. V/ (f
1
. t) ... (7.15)
in which:
V is, for wind loading in wind direction, the wind speed V(z) at the
top of the chimney (7.2.2.2)
V0 for cross-wind loading
f
1
is the fundamental natural frequency (7.2.8)
t is the thickness of the wall in the top third.
Where chimneys are lined, t total mass per square metre over the
top third (kg/m
2
) divided by 7850 kg/m
3
7.2.8 The rst and second natural frequencies
The rst natural frequency should preferably be calculated with a
computer program. Care must be taken to include for the effects of
any supporting structure. Assuming a chimney is on a rigid support,
its rst natural frequency may be calculated by dividing it into a
suitable number of sections using the formula (for the rst mode):
f
1
(1 / 2 . ) . [g
e
. m
s
x / m
s
x
2
] (sec
1
) ... (7.16)
in which:
m
s
is the mass of the section including the lining or
covering (in kg)
x is the deection of the same section due to the force equal to
gravity acting normal to the centre-line at the mass centre (m).
g
e
is the value of gravitational acceleration (m/s
2
)
Accurate estimation of the second natural frequency requires the use of
a nite element structural program with a dynamic capability or other
advanced computer program. For a chimney with constant diameter
and thickness, however, the following expression may be used:-
f
2
3.5 . (E. I / m. L
4
) ... (7.17)
Where EYoungs Modulus
I Moment of inertia of cross section
mmass per unit length
7.2.9 Passive Dynamic Control
Steel chimneys must be designed to suppress excessive cross-wind
movement. Several options are available to the designer.
7.2.9.1 Aerodynamic stabilizers
When a chimney stands alone, its cross-wind vibrations can usually
be reduced by aerodynamic stabilizers. The useful effect of three
continuous helical vanes has been proved on many steel chimneys.
The radial width of the vanes must be 10% of the diameter. The pitch
of the vanes should be 5 D. The vanes must be tted over at least the
upper 1/3 of the height. The extra wind drag due to the vanes must be
considered (see 7.2.3.2.3).
Aerodynamic stabilisers will not reduce the wind interference effects
of nearby chimneys or structures.
7.2.9.2. Damping devices
Damping devices are attached to a chimney to increase its structural
damping, thereby signicantly reducing the cross-wind and along-
wind vibrations, including the effects of aerodynamic interference by
other nearby towers or chimneys. Damping devices should he
designed to avoid the need for their frequent routine maintenance.
Most such dampers are mounted near the top of the chimney.
Because of their prole and small size, the associated increase in
wind drag is minimised. The use of damping devices, therefore, has
been proved to be benecial in the design of steel chimneys and they
can be safely retro-tted without incurring signicant increase in
wind drag loads.
Tuned mass dampers provide an extra mass, coupled to the chimney
by an energy absorbing medium, which absorbs the wind induced
energy. Tuned mass dampers have proven effective in reducing self-
generated along wind and cross-wind vibrations and also the effect of
nearby chimneys or structures.
Other chimney damping devices such as hanging chains have also
been successfully used.
page 12 CICIND Model Code
7.2.10 Special chimney designs for damping
Wind tunnel tests, conrmed by analytical means and eld experience,
have allowed dual-wall and multiue chimneys to be designed using
shell-to-shell impact damping, which otherwise would require
aerodynamic stabilisers or mass dampers (see ref. [14] & [15]).
Future special chimney designs and damping devices may prove
effective in preventing excessive wind induced vibrations. These
should have been proven initially by wind tunnel tests and nally by
eld experience before being universally adopted.
7.3. Earthquake loading
The stress due to wind loading on a steel chimney is usually more
than the earthquake stress and, consequently, normal steel chimneys
can resist earthquakes with an intensity of up to modied Mercalli
scale 10 without serious damage. However, in cases where a heavy
mass (e.g. a water tank or a heavy lining) is tted to the upper portion
of the chimney, a special investigation must be made (tanks are
outside the scope of the model code). Guyed chimneys must also be
subject to special investigation.
7.4. Thermal effects
When a chimney is restrained from adopting a deformed shape in
response to differential expansion, bending stresses will be
introduced in the shell. These deformations can be large when a
single unlined chimney carries ue gases from two or more sources
at signicantly different temperatures or if a single side entry source
introduces gases at very high temperatures. In addition, the resulting
differential metal temperature will introduce secondary thermal
stresses. Typical cases of such restraint are to be found in stayed and
guyed chimneys. More information on the derivation of those
stresses may be obtained from the CICIND Model Code for Concrete
Chimneys Part C: Steel Liners.
7.5. Explosions
7.5.1. External explosions
The resistance of steel chimneys to external explosions is very high.
If such explosions can occur in the direct vicinity such that
strengthening for this reason is required, it is outside the scope of this
model code.
7.5.2. Internal explosions
Internal explosions can occur due to the ignition of soot or explosive
gases in the chimney. They are not normally a cause for concern in
the design of a steel chimney. The CICIND Model Code for Concrete
Chimneys Part B, Brickwork Linings provides a reference for the
likely magnitude of explosion overpressures.
7.6. Internal effects governing the chimney design
7.6.1. High temperature ue gases
In the case of bare steel chimneys, having neither an internal liner nor
external insulation, the metal temperature can be assumed to be about
midway between ambient air temperature and that of the ue gas over
the range of ue gas velocities between 5m/s and 15m/s. For ue gas
velocities faster than 15m/s or for steel stacks equipped with either a liner
or external insulation, heat transfer calculations shall be made to
determine the maximum metal temperature of the structural shell. These
calculations shall assume still air and highest anticipated air temperature.
Consideration must be given to the effects of oxidation when the
material being used is close to its temperature limit. This is especially
so with gas turbine exhausts, where levels of excess air can be greater
than those normally experienced. This problem may not be solved
solely by an increase in corrosion allowance as the environment may
be polluted by the corrosion product. Expert advice should be sought
on the choice of suitable material.
7.6.2. Fire
The risk of a chimney re should be assessed. Chimney res can be
caused by ignition of:
1) Unburned fuel carried over from the associated boiler or furnace.
2) Where the associated furnace is in petrochemical service,
unburned hydrocarbon carryover following a furnace tube rupture.
3) Soot, sulphur and other deposits.
During chimney res, the radiant heat loss to atmosphere from a bare
steel chimney is often sufficient to maintain its temperature at a
reasonable level. By contrast an externally insulated steel chimney or
a bare steel chimney close to a reective surface will quickly buckle
during a re. In such cases, if the risk of internal re is signicant, a
refractory concrete internal liner should be installed to provide a
degree of re protection. Typically, a castable refractory lining
following the requirements of Appendix 3 will provide sufficient re
protection for most situations.
7.6.3. Chemical effects
Limited exposure to acid corrosion conditions can be permitted in
chimneys which, for most of the time, are safe from chemical attack.
Providing the ue gas does not contain signicant concentrations of
halogens (see notes (4) & (5) below) the degree of chemical load is
dened in Table 7.5.
Degree of Operating hours per year when
chemical load temperature of the surface in contact with ue
gases is below estimated acid dew point 10C
low 25
medium 25 100
high 100
Table 7.5
Degree of chemical load for gases containing sulphur oxides
Notes:
1) The operating hours in table 7.3 are valid for an S0
3
content of 15
ppm. For different values of S0
3
content, the hours given vary
inversely with S0
3
content. When the S0
3
content is not known,
chimney design should be based upon a minimum S0
3
content
amounting to 2% of the SO
2
content in the ue gas.
2) In assessing the number of hours during which a chimney is
subject to chemical load, account should be taken of start-up and
shut-down periods when the ue gas temperature is below its
acid dew point.
3) While a steel chimney may generally be at a temperature above
acid dew point, care should be taken to prevent small areas being
subject to local cooling and therefore being at risk of localised
acid corrosion. Local cooling may be due to:
air leaks
n cooling of anges, spoilers or other attachments
cooling through support points
downdraft effects at top of the chimney
4) The presence of chlorides or uorides in the ue gas condensate
can radically increase corrosion rates. Estimation of the corrosion
rate in these circumstances depends upon a number of complex
factors and would require the advice of a corrosion expert in each
individual case. However, in the absence of such advice, provided
the concentrations of HCl 30mg/m
3
or of HF5mg/m
3
and if
the operating time below acid dew point does not exceed 25 hours
per year, the degree of chemical load may be regarded as low.
5) Regardless of temperatures, chemical load shall be considered
high if halogen concentrations exceed the following limits:
Hydrogen uoride: 0.025% by weight (300 mg/m
3
at 20C and 1
bar pressure)
CICIND Model Code Amendment A March 2002 page 13
Elementary chlorine: 0.1% by weight (1300 mg/m
3
at 20C and
1 bar pressure)
Hydrogen chloride: 0.1% by weight (1300 mg/m
3
at 20C and 1
bar pressure)
6) Saturated or condensing ue gas conditions downstream of a ue
gas desulphurisation system shall always be considered as
causing High chemical load.
8. DESIGN OF STRUCTURAL SHELL
8.1 Minimum thickness
At the time of construction the minimum thickness of the shell of
carbon steel chimneys shall be 5mm, including the corrosion
allowance.
8.2. Required checks
The steel shell of a chimney shall be checked for:
carrying capacity
serviceability
fatigue (unless the chimney is tted with an effective
dynamic control)
The carrying capacity check shall prove that the forces resulting from
the working loads multiplied by the load factors do not exceed the
resistance of the shell. The check should comprise both the strength and
stability proof. The calculations shall be carried out for the corroded
thickness of the steel (without corrosion allowance). The serviceability
shall be checked under working loads without load factors.
A fatigue check shall be carried out if movement due to vortex
shedding is expected (see 7.2.4).
For unstiffened chimneys with a ratio of L/R50 (where Lheight
of chimney and Rradius), stresses may be safely calculated
assuming beam theory, exural stresses being added vectorially to
ovalling stresses. For unstiffened chimneys (i.e. chimneys without
stiffening rings or substantial anged joints) having L/R50, shell
theory or nite element modelling should be used, considering
exural and ovalling stresses simultaneously. This will lead to
reduction in compression stress at the chimney base or immediately
above changes in chimney diameter, but will increase compression
stresses elsewhere. Similarly, this will lead to increases in tensile
stresses at the base and immediately above a change in chimney
diameter, which will be important in deriving bolt tensions.
The increase in tensile stress in these regions may be approximated
by the expression:-
1 {6 / [(L/R)
2
. (t/R)]}
8.3. Carrying capacity of shell
8.3.1. Load factors and load combinations
The chimney shell shall be designed to resist stresses resulting from
the weight of the chimney and the effect of wind multiplied by the
load factors :
(
i
i
) (
i
*) f
k
... (8.1)
where:
i
*stresses multiplied by load factors
f
k
limit stress of steel
8.3.2. Second order effect
The effect of the displacement of the load application points due to
deformations (second order effect) shall be taken into consideration
if the parameter 0.6, where:-
h (N/ EI)
0.5
... (8.2)
and:
h height of the chimney (m)
N total axial load at the base of the shell
(without load factor) (N)
E I stiffness of the cross section at the base of
the chimney (Nm
2
)
The second order moment M
11
is approximately determined from:-
M
11
M
1
(1
2
/ 8)
Where M
1
is the wind moment at any particular level.
This simplied approximation may only be used when 0.8 and
N
h
/ N0.1. It is not applicable to guyed chimneys.
Where N
h
is the design value of the total vertical load at the top of
the shell.
8.3.3. Biaxial stresses
In areas subjected to biaxial stresses e.g. due to bending moments and
ovalling, the carrying capacity check shall be based on
{*
x
2
*
y
2
(*
x
*
y
) 3 *
2
} f
k
... (8.3)
Note The ovalling stresses are both negative and positive and the
maximum value of expression (8.3) occurs when
*
x
and
*
y
are of
opposite signs.
8.3.4. Stability
The proof of stability of the shell is given if the critical buckling
stress divided by 1.1 is greater than the sum of longitudinal stresses
due to bending and compression:
*N*B
k
/ m ... (8.4)
where:
*N, *B normal and bending compressive stress at
ultimate limit state
m
material factor 1.10
k
critical buckling stress
(1.0 0.412
1.2
) f
y
when 2 ... (8.5a)
0.75 f
y
/
2
when 2 ... (8.5b)
f
y
yield strength of steel at design temperature
f
y
/ (
cr
) ... (8.6)
cr
critical elastic buckling stress 0.605 E t/r ... (8.7)
E Youngs modulus of steel at design temperature
t corroded plate thickness
r radius of the structural shell of the chimney at
section considered
... (8.8)
N
*
N
B
*
B
*
N
*
B
tensile stress per shell theory
tensile stress per beam theory
page 14 Amendment A March 2002 CICIND Model Code
When imperfections w are smaller than 0.01l (Fig. 8.1):
N
0.83 / (1 r / 100t)
0.5
for r/t 212 ... (8.9a)
and:
N
0.7 / (0.1 r / 100t)
0.5
for r/t 212 ... (8.9b)
B
0.189 0.811
N
If the imperfections (w) are between 0.01l and 0.02l (see Fig. 8.1) the
above formulae may be used if
1
is substituted for a:
1
[1.5 w/ 0.02 l] ... (8.9c)
Imperfections (w) greater than 0.02l shall not be permitted.
Stiffeners may be used to increase the shells resistance to buckling.
Guidance on the design of such stiffeners is given in CICIND Model
Code for Concrete Chimneys Part C Steel Liners.
Figure 8.1
8.4. Serviceability of shell
The downwind deection from the centreline of the structural shell
under maximum design wind load must be calculated and reported.
As long as the carrying capacity stresses in the structural shell, or any
liners, is not exceeded, no limit is placed on downwind deection.
So as not to alarm bystanders, the amplitude of deection from the
chimney centreline caused by vortex shedding shall not be greater
than the limit agreed per Section 5.4 of this model code.
8.5. Fatigue check
8.5.1. Basic principles
The fatigue check shall ascertain that the movement due to vortex
shedding does not result in the initiation and gradual propagation of
cracks in the material, especially near welds, thus resulting nally in
the failure of a weakened section. The fatigue of the material depends
essentially on:
the number of stress cycles N
the stress range (
max
min
)
the constructional details
The inuence of the grade of steel as well as that of the
min
/
max
ratio are negligible.
8.5.2. Fatigue strength
The number of load cycles in the cross-wind direction can be
calculated from:-
N 1.26 10
7
TfAe
A
2
where:-
T The required lifetime of the chimney in years
f The resonance frequency
A 4V
cr
/ V
V The design wind velocity V(z) at the top of
the chimney
The amplitude of movement varies, with maximum movement only
representing a small proportion of the total number of cycles. The
effect of fatigue due to all of the load cycles can be expressed by
considering the factored Miner Number M*:-
Where M* . M(
max
/
wn
)
k
(log
e
N)
k
Where:-
max
The maximum stress range due to vortex shedding
wn
The fatigue strength after N cycles (see gs. 8.2 & 8.3)
k the (positive) exponent of the fatigue curves. for steel, k3
Determines the load vs. cycles relationship (V
cr
/ 8)
1.2
Modelling safety factor 1.4
(for temperatures up to 200C)
If the factored Miner Number (M*) is less than 0.2 no cracking will
occur during the required lifetime. Nevertheless, occasionally
movement amplitude may be sufficient to cause alarm. In such cases
the amplitude limitation of Section 5.4 may govern.
Figure 8.2 Fatigue strength of the base material
with respect to the fatigue categories dened in Figure 8.3
8.5.3. Inuence of high temperatures
The few results available show that at 200C fatigue growth rates
may be higher than at room temperature, but at 400C growth rates
are lower than at room temperature. Unless more detailed results
become available the modelling safety factor shall be increased to
1.50 in the range of metal temperatures between 200 to 400C.
8.6. Allowance for corrosion
Allowance for corrosion shall be the sum of the external (CE) and
internal (Cl) allowances given in tables 8.1 and 8.2. This total
allowance shall be added to the thickness of the shell required to
satisfy the specied limits of stress and deection. Internal anges
shall have corrosion allowance Cl and external anges corrosion
allowance CE on all exposed surfaces. The allowances listed in tables
8.1 and 8.2 are for a 20 year lifetime of the chimney. For longer
planned lifetimes, the corrosion allowances should be increased
proportionally. For temporary chimneys, expected to be in service for
less than one year, values of CE and CI 0 are permissible, except
in conditions of high chemical load, when a corrosion allowance of
3mm is required.
For a free-standing chimney with steel liner(s), the internal corrosion
allowance only applies to the internal face of the liner(s). The internal
CICIND Model Code page 15
Figure 8.3 Fatigue resistance of typical details
(continued on pages 16, 17 and 18)
From ENV 1993-3-2 : 1997 Eurocode 3: Design of Steel Structures Part 3.2 Chimneys
Notes to Fig. 8.3
Type of welding:
1. butt welds, when high quality has to be acheived
and veried:
developed root, cap pass counter welding
evenly machined surface in stress direction.
2. butt weld: developed root, cap pass counter welding
3. butt weld:
welded one side only
through-welding of seam root and plane surfaces
secured on opposite side by auxiliary welding aid
e.g. weld-pool backing ceramics or copper rail
4. butt weld: welded one side only
5. T joint by double-bevel butt weld
6. T joint by double Y butt weld with broad root face
7. T joint with special quality double llet weld
8. T joint double llet welds
page 16 CICIND Model Code
CICIND Model Code page 17
page 18 CICIND Model Code
CICIND Model Code page 19
face of the outer shell requires no corrosion allowance, provided a
weather-tight cover is tted over the air space(s) between the liner(s)
and the outer shell.
8.6.1. External corrosion allowance
painted carbon steel 0mm
painted carbon steel under insulation/cladding 1mm
unprotected carbon steel 3mm
unprotected corten or similar steel 1mm
unprotected stainless steel 0mm
Table 8.1. External corrosion allowance (CE)
Note:
The external corrosion allowances quoted in Table 8.1 are suitable for
a normal environment. When a chimney is sited in an aggressive
environment, caused by industrial pollution, nearby chimneys or
close proximity to the sea, consideration should be given to
increasing these allowances.
8.6.2. Internal corrosion allowance
Usual temperature Chemical
of metal in contact load per Internal corrosion allowance
with ue gas table 7.5
65C low not applicable (chem. load always high)*
medium not applicable (chem. load always high)*
high corrosion allowance inappropriate, use other
material*
65C 345C low 2mm**
medium 4mm
*
l
l,u
/ 1.1 1.45
u
... (9.2)
The design bearing stress
*
l
relates to the area obtained by
multiplying the diameter d of the shank by the thickness of the
connected part. Regardless of any preload, the limit stress
l,u
is valid
for edge distances greater or equal 2d in the direction of stress.
Grade
l,u
l,u
/ 1.1
Fe 360 575 525
Fe 430 690 625
Fe 510 815 740
Table 9.2 Limit bearing stress
l,u
in MPa
9.1.2.3. Tension
The limit state is described:
*
t
t,u
/ 1.1 0.73
u,B
... (9.3)
for
t,u
see table 9.3
page 20 CICIND Model Code
Minimum value of Limit tensile stress
tensile strength of preloaded bolts
bolt grade
u,B
t,u
t,u
/1.1
4.6 400 not recommended
5.6 500 not recommended
6.8 600 not recommended
8.8 800 640 580
10.9 1000 800 730
Table 9.3
Limit tensile stress
t,u
in MPa.
Note! The stresses given in Tables 9.2 and 9.3 are for ambient
temperatures. For stresses at elevated temperatures refer to
the factors in column 2 of Table 6.2.
The tensile stress
t
shall be calculated on the nett section.
Owing to their considerable susceptibility to fatigue, connections that
use bolts in tension shall be made with pretensioned high strength bolts.
9.1.2.4. Combined loading
If the external loading results in a combination of tensile stress
t
*
and shear stress * in the bolt, the carrying capacity shall be checked
for the condition:
(* /
u
)
2
(
t
* /
t,u
)
2
1.0 ... (9.4)
This check is not necessary if:
* 0.2
u
or
t
* 0.2
t,u
... (9 5)
9.1.2.5. Deduction for holes
For parts subjected to tension, the following two conditions shall be
checked:
in the gross section, the stress shall not exceed the yield stress f
y
in the nett section, the stress shall not exceed 80% of the tensile
strength
u
9.1.3. Welded connections
The welding standard considered appropriate for steel chimneys is
higher than the minimum standard allowed for other welded
products. An acceptable standard is discussed in 9.1.3.3 below.
9.1.3.1. Full penetration welds
If the quality of the weld is at least equal to that of the parent metal,
full penetration welds have the same resistance as the connected
parts. In this case, no particular checks are necessary. Partial
penetration welds shall be taken as llet welds and calculated as
such. Full penetration welds connecting plates of different
thicknesses have a resistance equal at least to that of the thinnest
plate. Partial penetration of butt welds shall not be permitted.
9.1.3.2. Fillet welds
Regardless of the direction of stress, the two design stresses
w
* and
s
* for llet welds shall be checked:
in the throat section a-a:
w
*
w,u
/ 1.1 0.455
uE
in the contact section s-s:
s
*
s,u
/ 1.1 0.636 f
y
where
uE
is the guarantied minimum value of the tensile strength of
the weld metal and f
y
the yield stress of the parent material.
Throat section Contact section
grade
w,u
w,u
/1.1
s,u
s,u
/ 1.1
Fe 360 255 230 165 150
Fe 430 255 230 180 165
Fe 510 255 230 250 230
Table 9.4. Limit stresses
w,u
and
s,u
for llet welds in MPa
The yield stress, tensile strength, strain at failure and notch toughness of
the weld metal shall exceed minimum values for parent material, and,
failing a specic agreement, shall be at least equal to those of Fe510.
w,u
values given in table 9.4 are valid for electrodes with properties
of steel Fe 510.
CICIND Model Code page 21
9.1.3.3 Weld Testing
While a minimum, taken at random, of 10% of butt welds and llet
welds shall be tested, the weld testing procedures and quality levels shall
be agreed by the client and the builder. The recommendations of levels
Cof ISO 5817 Arc-welded joints in steel guidance on quality levels
and imperfections should be used, but subject to agreement between the
client and builder, local codes may be substituted.
Note The fatigue categories listed in g. 8.3 assume welds are made
to ISO 5817 level C quality standards. If local codes are
used, the weld categories may require appropriate adjustment.
9.2 Flanged connections
The use of high strength bolts is recommended. The centres between
the bolts should be between 4d
b
and 10d
b
, where d
b
is the diameter of
the bolt. However, a distance of 5d
b
is recommended as larger
spacings result in excessively thick anges. The minimum bolt
diameter should be d
b
16mm. The stress in the bolts shall be
calculated taking consideration of the eccentricity of the loading
transmitted by the shell.
Fig. 9.2.1 Normal ange
In the case of along wind: Z*
b
Z* a / w0.73
u,b
A
n
... (9.6)
In the case of cross-vibration (fatigue):
Z
b,f
Z
f
a / w
R
A
n
/ 1.1 ... (9.7)
where:
R
is the fatigue strength for category 35 MPa
A
n
is the stress section of the bolt
If the fatigue load Z
f
is greater than the fatigue strength divided by
1.10, a joint with contact areas shall be used (see lit. [22] and g.
9.2.2). The pretension of the bolts should provide a sufficient force
Z
A
to prevent the fatigue in the bolt material:
Z
A
0.73
u,b
A
n
w/a Z
f
... (9.7)
Fig. 9.2.2 Prestressed ange, suitable for vibrating conditions
It should be noted that the change of the type of connection to one
with proled contact areas may reduce the damping ratio used in
estimating along and across-wind response. The tting of gaskets to
the anges of structural shells is not permitted.
9.3. The support at the base
Self-supporting steel chimneys are normally based on a reinforced
concrete foundation or a steel structure. The foundation or structure
is loaded by an overturning moment, normal force and shear force
through the base plate and anchor bolts.
9.3.1. Anchor bolts
When fatigue due to vortex shedding is anticipated anchor bolts
should be prestressed. Measures must be taken to ensure that the
prestressing is not lost during the lifetime of the chimney. An
anchorage device shall be attached to the bottom end of the bolt.
The maximum bolt stress should not exceed 73% of the tensile
strength of the material of anchor bolt. Alternative satisfactory
methods may be used at the designers discretion when no response
to vortex shedding is anticipated.
9.3.2. Grouting
After the chimney has been erected and plumbed (with the use of
steel shims which remain in position) the space between the base
plate and concrete foundation must be lled with nonshrink grout.
The compressive strength of the grout must be equal to or greater
than the compressive strength of the concrete.
9.3.3 Temperature effects
Consideration must be given to the effect that radiant or conducted
heat will have upon a concrete foundation. This is particularly
relevant to chimneys serving gas turbines or other high temperature
exhaust systems.
There is the possibility of the foundation being damaged if an
adequate heat barrier is not installed. In the majority of situations
insulation to contain or deect radiant heat will suffice.
10. STEEL LINERS
Steel liners inside steel chimneys shall be designed to satisfy the
requirements of CICIND Model Code for Concrete Chimneys
Part C Steel Liners. Advice on the design of steel liners in steel
chimneys is given in Appendix 3 to this Model Code.
11. CONSTRUCTION
11.1 General
The following will be observed during shop and site construction as
appropriate.
11.2. Structural shell
The tolerances in the fabrication of the shell shall be as follows:
Flat plate prior to rolling shall be laid out and squared to within
1mm in length, width and on each diagonal.
A chimney section, with anges welded in place, shall be fabricated
within a tolerance of 3mm on circumference and diagonal. If
possible, these measurements shall be made while the shells axis is
vertical. If this is not possible, the shell shall be adequately braced.
Peaking of a cylinder from a true circle at weld seams shall not
exceed 3mm, as measured by a 450mm long template, centred at the
weld and cut to the cylinders design radius. Other imperfections
shall be within the limits stated in section 8.3.4 of this model code
and assumed by the designer.
Vertical butt weld seams shall be staggered a minimum of 200mm
from eachother.
Misalignment between plates shall not exceed 1mm.
page 22 CICIND Model Code
11.3 Structural Flanges and opening reinforcement
These shall be fully welded to the structural shell. Intermittent
welding shall not be allowed.
Flanges shall be at and normal to the chimney axis. Before bolting, the
maximum gap width on the line of the shell, between matching pairs of
anges, shall be 1mm. Before bolting, the gap at the outer edges of the
anges shall not exceed 1.5mm per 100mm width of ange.
Note: These tolerances may be ignored if the anges are bolted together
before they are welded to their respective shell sections. Their orientation
shall be marked prior to their being dismantled after welding.
11.4 Stiffening Rings
If the design permits the use of intermittent welding, crevices
exposed to weather or ue gases shall be sealed.
11.5 Baseplate
The baseplate and all base reinforcement shall be fully welded to the
structural shell and to each component.
The base plate shall be perpendicular to the shell plate within 0.5.
11.6 Straightness
Adjoining cylinder sections shall be welded together straight in the
longitudinal direction to a tolerance of 12mm per 10m of shell
length.
Flanges shall be welded to the structural shell within a perpendicular
tolerance of 0.5.
11.7 Erection tolerance
The departure of the chimney from the vertical on erection shall not
exceed 25 mm or 1/600 of the height, whichever is the greater at any
point.
12. SURFACE PROTECTION
The exterior and interior surfaces of a steel chimney may be
protected from attack by weather and corrosive gasses by various
methods. Specications for different types of protection are given in
Appendix 3. See also CICIND Chimney Protection Coatings Manual.
13. OPENINGS
The width of a single opening shall not exceed two-thirds of the
diameter of the structural shell of the chimney.
Where large apertures are cut in the shell plates, as for gas inlets or
inspection panels, a structural analysis of the stresses shall be made
and compensating material provided, as required, to ensure that the
stresses specied in this Model Code are not exceeded. As a result, it
may be necessary to incorporate stiffeners around the opening. When
longitudinal stiffeners are used, their design shall include the effects
of circumferential bending stresses in the shell, above and below the
opening. Also they shall be long enough to distribute stresses into the
main area of the shell without overstress. (Note: this may generally
be deemed to be satised if the stiffeners project above and below the
opening a distance at least 0.5 times the spacing of the stiffeners.).
The ends of the longitudinal stiffeners should be tapered in a radial
direction (see cases 16.1 3 in Fig. 8.3).
Additional horizontal stiffeners may be used to absorb the
circumferential bending stresses. These stiffeners may be attached
between the longitudinal stiffeners, at the holes edge and at the end
of the longitudinal stiffeners.
A suggestion for stiffeners is given in the Commentaries for this
Model Code.
Smaller apertures in the shell plates, not equipped with stiffeners,
shall have the corners radiused to a minimum of 10 t, where t is the
thickness of the plate.
The effect of openings upon the chimneys stiffness should be taken
into account when determining the chimneys natural frequencies.
14 GUYED AND STAYED CHIMNEYS
A stayed chimney is dened as one which derives lateral (but not
vertical) support from another structure. A guyed chimney derives
lateral support from guy ropes.
The foregoing structural design rules are valid for self-supported
chimneys, acting as cantilevers, xed at their bases, with or without
liners. Some of the rules (e.g. those related to thermal and chemical
load) are relevant also to chimneys that are guyed or stayed. Rules
governing the structural design, related to wind or earthquake loading
do not, however, apply to these chimneys.
14.1 Stayed chimneys
Stayed chimneys are supported laterally at one or more elevations
above their bases. The number of lateral supports will be governed by
buckling considerations per section 8.3.4 above and by the need to
avoid oscillations due to vortex shedding, but shall be kept to the
minimum possible. To avoid vibrations due to vortex shedding, the
natural frequencies should ensure that V
cr
(assuming
S0.2) 1.2 maximum windspeed at the relevant elevation (10
minute mean). The prime concern of the design should be to ensure
that vertical expansion is not restricted.
In designing the shell and lateral supports, the forces induced by the
restraint of differential thermal expansion shall be considered.
Differential expansion can be expected if two or more gas streams of
differing temperatures enter the chimney at different points. Guidance
on the determination of these forces may be found in CICIND Model
Code for Concrete Chimneys, Part C Steel Liners.
The design of the supporting structure is outside the scope of this
Model Code.
14.2 Guyed Chimneys
Design rules for Guyed chimneys are given in Appendix 4 to this
Model Code
15. PROTECTION AGAINST LIGHTNING
A steel chimney can be considered as a continuous metal structure
and thus be used as its own lightning protection system.
Consequently it requires no air termination or down conductor. It is
sufficient to ensure that the conduction path is electrically continuous
and that it is adequately earthed.
16. ACCESS LADDERS
A specication for access ladders and hooks is given in Appendix 5.
17. AIRCRAFT WARNING LIGHTS
It is advisable to contact the local aeronautical authority for the area
if the chimney is to be built within an aerodrome safe guarding area
as local conditions and restrictions may apply.