You are on page 1of 7

Pressure-151 Pressure-151

M
o
d
e
l

1
1
3
5
F
Model 1135F
Pressure-to-Current
Converter
Guaranteed 0.2% accuracy
External zero adjustment
Range adjustable from 0
12 to 030 psig
Plug-in circuit board
Overpressure to 150 psig
Dual-compartment housing
Pressure-152
Model 1135F Pressure-to-Current Converter
M
o
d
e
l

1
1
3
5
F
FEATURES
The Model 1135F Fi el d-Mounted P/I Conver ter,
together wi th the Model 1133 rack-mounted versi on,
bri ng unsurpassed per formance and versati l i ty to
the pressure-to-current converter market. Thi s
i nstrument operates on the same vari abl e
capaci tance sensi ng techni que that has made the
Rosemount pressure transmi tter the most widel y
accepted el ectroni c pressure transmi tter i n the worl d
today.
Desi gned for fi el d instal l ati on, the Model 1135F
converts i ncomi ng pneumati c si gnal s i nto an
el ectroni c 420 mA output si gnal . I t i s i deal for
pl ants that are converti ng from pneumati c to
el ectroni c control . I t is al so an excel l ent choi ce for
use in el ectroni c pl ants that moni tor l ocal pneumati c
control l oops i n safety-rel ated areas.
The dual -compartment housi ng desi gn of the
converter permi ts the el ectroni cs and pressure
sensor to be envi ronmental l y i sol ated fr om the fi el d
wi ri ng termi nals, thus increasi ng rel i abi l i ty. A si ngl e
pl ug-i n ampl i fi er board i s readi l y accessi bl e and
easi l y r emoved for repl acement or troubl eshooti ng.
To meet hazardous l ocati on certi fi cati ons, the
el ectroni cs compartment i s desi gned wi th fl ame
arresters l ocated between the internal compartment
and the external por ts l eading to the outsi de
atmosphere.
The range of the Model 1135F i s conti nuousl y
adjustabl e fr om 012 to 030 psi g (083 to 0207
kPa). The orderi ng i nformati on l i sts fi ve factor y
cal i brated ranges, but the conver ter may be factor y
cal i brated to any custom range wi thi n i ts operati ng
l i mi ts. Vari ous materi al and certi fi cati on opti ons are
avai l abl e, i ncl udi ng a di r ect-readi ng output si gnal
meter.
The Model 1135F pressure-to-current conver ter
combi nes proven desi gn, superi or per formance, and
mai ntenance si mpl i ci ty to make i t the fi nest P/I
converter on the mar ket.
OPERATION
I nstrument ai r i s appl i ed to an i sol ati ng
di aphragm on one side of the patented d-Cell

sensor.
An oi l -fi l l fl uid transmi ts the appl i ed pressure to one
side of the sensi ng di aphr agm i n the center of the
d-Cel l sensor. I n a l i ke manner, an atmospheri c
r eference pressure i s transmi tted to the other si de
of the sensi ng di aphragm. The displ acement of the
sensi ng diaphr agm, movi ng a maxi mum of 0.004 i n.
(0.10 mm), is proporti onal to the pressure
di fferenti al across i t. Fi xed capaci tor pl ates on both
sides of the sensi ng di aphr agm conti nuousl y detect
the posi ti on of the sensi ng diaphragm. The
di fferenti al capaci tance between the sensi ng
di aphragm and the capaci tor pl ates i s converted
el ectroni cal l y to a 2-wi re, 420 mA dc si gnal .
Capacitor Plates
Lead Wires
Sensing Diaphragm
Rigid Insulation
Oil Fill
Isolating
Diaphragm
Welded Seals
FIGURE 1. Cross Section of the Rosemount
d-Cell

Sensor.
1
1
5
1

0
1
4
2
A
Rosemount Inc., 2983, 1986, 1994.
May be protected by one or more of the following U.S. Pat. Nos.:
3,793,885; 3,800,413. Other foreign patents issued and pending.
Rosemount Inc.
Pressure-153
M
o
d
e
l

1
1
3
5
F
1
/214 NPT
Conduit Connection
Vent
Zero
Adjustment
Terminal Side
Circuit Side
0.75 (19)
Clearance for
Cover Removal
8.75 (222)
with Optional Meter
6.0
(152)
Optional
Meter
Pneumatic
Connection
1
/4-18 NPT
Female
4.1
(104)
Nameplate
Pneumatic
Connection
1.4
(36)
Certification
Tag
Mounting
Adapter
1
/214 NPT
to
7
/16 UNC
NOTE
Dimensions are in inches (millimeters).
FIGURE 2. Dimensional Drawings for Model 1135.
4.5
(114)
4.1
(104)
1
1
3
5
-
0
4
1
5
A
,
0
4
1
8
A
,
0
4
1
9
A
FIGURE 3. Optional Universal Mounting Bracket.
NOTE
Dimensions are in inches (millimeters).
Pneumatic
Connection
5.75
(146)
4.1
(104)
1.4
(36)
1
1
3
5
-
0
4
1
6
A
,
0
4
1
7
A
4.5
(114)
3.95
(100)
3.25
(83)
1.5
(38)
0.5
(13)
3.75
(95)
2.81
(71)
6.0
(152)
4.0
(102)
1.0 (25)
Pressure-154
Model 1135F Pressure-to-Current Converter
M
o
d
e
l

1
1
3
5
F
SPECIFICATIONS
Functional Specifications
Input
I nstrument ai r, 0 to 12 psi g (0 to 83 kPa) mi ni mum,
0 to 30 psi g (0 to 207 kPa) maxi mum span.
Output
420 mA dc.
Power Supply
External power suppl y requi r ed. Conver ter operates
on 12 to 45 V dc wi th no l oad.
Load Limitations
See Fi gure 4.
Indication
Opti onal 0100% meter wi th 2.3 i n. (58 mm) scal e.
I ndi cati on accuracy i s 2%.
Span
Conti nuousl y adjustabl e between a mi ni mum span
of 0 to 12 psi g (0 to 83 kPa), and a maxi mum of 0 to
30 psi g (0 to 207 kPa).
Zero Suppression
Up to 30% of cal i brated span. External l y adjustabl e.
Ambient Temperature Limits
Operati ng: 20 to 180 F (29 to 82 C)
Stor age: 50 to 250 F (46 to 121 C).
Overpressure Limit
150 psi g (1.03 MPa) maxi mum.
Damping
Ti me constant fi xed at appr oxi matel y 100 ms.
Humidity
0 to 100%rel ati ve humi di ty.
Turn-On Time
Two seconds. No war m-up requi red.
Hazardous Locations Certifications
Factory Mutual (FM) Approvals:
Expl osi on proof for Cl ass I , Di vi si on 1, Groups
B, C, and D. Dust-I gni ti on Proof for Cl ass I I ,
Di vi si on 1, Groups E, F, and G. Sui tabl e for
use in Cl ass I I I , Di vi si on 1, indoor and outdoor
use. NEMA 4X.
Canadian Standards Association (CSA)
Approvals:
Certi fi ed for Cl ass I , Di vi si on 2, Groups A, B,
C, and D; Cl ass I , Di vi si on 1, Groups C and D;
Cl ass I I , Di vi si on 1, Groups E, F, and G; Cl ass
I I I hazardous l ocati ons; CSA encl os ur e 4,
factor y seal ed.
Intrinsic Safety Approvals:
FM and CSA certi fi cati ons opti onal for speci fi c
Cl asses, Di vi si ons, and Groups when
connected wi th approved barri er systems. See
MAN 4458 for FM and CSA approved barri ers
and groups. CENELEC I ntri nsi c Safety
Approval by BASEEFA (EEx i a I I C T4) when
connected wi th CENELEC EEx i a appr oved
bar r i er systems, Vmax 28 V, I max 120 mA.
Performance Specifications
(Performance specifications are derived at zero based,
maximum spans under ambient reference conditions.)
Accuracy
0.20% of cal i brated span, incl udes combi ned effects
of l i neari ty, hysteresi s, and repeatabi l i ty.
Stability
0.20% of upper range l i mi t for si x months.
Temperature Effect
At maxi mum span: 0 to 30 psi g (0 to 207 kPa) the
zer o er r or i s 0.5% of span per 100 F.
Total effect i ncluding span and zero er r or s: 1.0% of
span per 100 F.
At mi ni mum span: 0 to 12 psi g (0 to 83 kPa) the zer o
error i s 1.25% of span per 100 F and the total
effect i s 1.75% of span per 100 F.
Overpressure Effect
Zero shi ft l ess than 0.2% of upper range l i mi t for
150 psi g (1.03 MPa).
Power Supply Effect
Less than 0.005% of cal i brated span per vol t.
Vibration Effect
0.05% of upper range l i mi t per g to 200 Hz i n any
axi s.
Mounting Position Effect
Zero shi ft of up to 1 i nH20 (0.24 kPa) whi ch can be
cal i brated out. Posi ti on has no effect on span setti ng.
L
o
a
d

(
O
h
m
s
)
Operating
Region
1650
1500
1000
500
0
420 mA dc
12 20 30 40
Power Supply (V dc)
Maximum Load = 50 3 (Supply Voltage 12)
FIGURE 4. Load Limitations.
Rosemount Inc.
Pressure-155
M
o
d
e
l

1
1
3
5
F
Physical Specifications
Isolating Diaphragms
316L SST.
Sensor Fittings and Flame Arresters
Brass fi tti ngs wi th bronze arresters are standard.
Stai nl ess steel fi tti ngs and arresters are opti onal .
Mounting
Opti onal uni versal mounti ng br acket for 2-i n.
(5.08-cm) pipe or wal l mounti ng.
Enclosure
Expl osi on-proof, l ow copper al umi ni um housi ng.
NEMA 4X rati ng. Buna-N O-ri ngs.
Paint
Pol yurethane.
Electrical Connection
Scr ew termi nal s for si gnal l ead termi nati on.
I ntegral test termi nal s compati bl e wi th mi ni ature
banana pl ugs. Condui t connecti on is
1
/214 NPT.
Pneumatic Connection
Standard
1
/418 NPT femal e connecti on.
Weight
Converter al one, 5 l b (2.27 kg); wi th mounti ng
br acket, 6 l b (2.72 kg).
1
1
3
5
-
0
2
5
5
E
0
1
A
FIGURE 5. Wiring Connections.
Power
Supply
Signal loop may be grounded
at any point or left ungrounded.
FIGURE 6. Electrical Block Diagram.
1
1
3
5
-
0
1
9
7
B
Demodulator
Feedback
Control Current
Oscillator
Voltage
Regulator
Current
Control
Current
Control
Amplifier
Current
Limiter
Oscill.
Control
Amplifier
Signal
Test
Sensor
+
+

NOTE
Dashes outline reverse polarity protection.
Model 1135F Pressure-to-Current Converter
Pressure-156
M
o
d
e
l

1
1
3
5
F
CIRCUIT SIDE
Housing O-Ring
Housing
Cover
Optional Meter Cover
Amplifier Circuit Board
(Replaceable)
Pneumatic
Connection
1
1
3
5
-
0
4
1
3
A
FIGURE 7. Field-Mounted Pressure-to-Current Converter.
Housing
Cover
Mounting Adapter
1
/214 NPT
to
7
/16 UNC
Meter Zero Adjust
Pneumatic
Connection
1
1
3
5
-
0
4
1
4
A
Terminal Screws
Cover Foam Spacer
Cover Bushing
TERMINAL SIDE
Housing O-Ring
FIGURE 8. Field P/I Optional Meter Assembly.
Meter
Cover
Rosemount Inc.
Pressure-157
M
o
d
e
l

1
1
3
5
F
ORDERING INFORMATION
TABLE 1. Model 1135F Field Mounted Pneumatic-to-Current Converter
Model Product Description
1135F Fiel d Mounted Pneumatic-to-Current Converter
Code Calibrated Pressure
1
2
3
4
5
6
3 to 15 psig (21 to 103 kPa)
3 to 27 psig (21 to 86 kPa)
6 to 30 psig (41 to 207 kPa)
20 to 100 kPa (2.9 to 14.5 psig)
40 to 200 kPa (5.8 to 29 psig)0
Special Range (consult factory)
Code Flame Arrester and Sensor Materials
B
S
Bronze Fl ame Arresters with Brass Fi ttings
Stainless Steel Frame Arresters with Stai nless Steel Fittings
Code Meter
1
2
None Requi red
Meter with Linear Scal e (0 to 100%)
Code Mounting
NB
B1
None Requi red
Universal Mounting Bracket for 2-inch Pi pe or Wall Mounti ng
Code Options
E5
E6
I5
I6
I1
N1
Factory Mutual (FM) Approval s
Canadian Standards Association (CSA) Approvals
Factory Mutual (FM) Non-incendive and Intri nsic Safety Certi fication (both system and enti ty concepts)
Canadian Standard Associati on (CSA) Intrinsic Safety Certi fication when Connected with Approved Barri er Systems
CENELEC Intrinsic Safety Certification
BASEEFA Type N Certificati on
Typical Model Number: 1135F 1 B 1 B1 E5
Tagging
The transmi tter wi l l be tagged, at no charge, i n
accordance wi th customer requi rements. Al l tags are
stai nl ess steel . The standard tag i s wi red to the
transmi tter. Tag character hei ght i s
1
/8 i n. (0.318 cm).
A permanentl y attached tag i s avai l abl e upon
request.
Calibration
Converters are factor y cal i brated to the range
speci fi ed by the customer. Cal i brati on is per formed
at ambi ent temperature and pressure.
Rosemount and the Rosemount logotype are registered trademarks
of Rosemount Inc.
d-Cell is a trademark of Rosemount Inc.

You might also like