You are on page 1of 5

www.aemc.

com Technical Assistance (800) 343-1391


Monitor your energy usage
& costs locally or from
anywhere in the world!
Models PEL 102 & PEL 103
POWER QUALITY ANALYZERS, METERS & LOGGERS
Power & Energy Loggers PEL 100 Series
SPECIFICATIONS
MODELS PEL 102 & PEL 103
GENERAL
Sampling Frequency 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz)
Data Storage Rate 1 per second
Demand Period Storage Rate User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes)
Recorded Parameters
(Single- and Poly-Phase)
V, I, W, VA, var, PF, Tan, Wh, VAh, VARh, THD (V and I),
Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF
Event Log Tracks and records status changes and error messages along with recorded data
Front Panel Indicator LEDs Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status
Storage Capacity 2GB SD card (included) is used for storage. SD cards (up to 2GB); SDHC cards (4 to 32GB)
formatted FAT32 are supported
INPUTS Voltage 3 voltage input channels via 4mm safety banana jacks
Current 3 current input channels via custom 4 pin jacks that accept AEMC

probes and sensors


ELECTRICAL
VOLTAGE MEASUREMENT RANGE RESOLUTION * ACCURACY (% of Reading)
50/60Hz 42.5 to 69Hz 0.1Hz
Single-Phase RMS Voltages 10 to 1000Vrms 0.1V 0.2% Rdg 0.2V
Phase-to-Phase RMS Voltages 17 to 1700Vrms 0.1 to 1V 0.2% Rdg 0.4V
400Hz 340 to 460Hz
Single-Phase RMS Voltages 10 to 600Vrms 0.1V 1% Rdg 1V
Phase-to-Phase RMS Voltages 17 to 1200Vrms 0.1 to 1V 1% Rdg 1V
DC 100 to 1000V 0.1V 1% Rdg 3V (typical)
PT Ratios Programmable from 50V to 65,0000V 0.01V to 0.1V
CURRENT MEASUREMENT
Current Probe: MiniFlex

Sensor MA193*** 200mA to 100Arms 1 to 100mA 1.2% 50mA


0.8A to 400Arms 10 to 100mA 1.2% 0.2A
4A to 2000Arms 0.1 to 1A 1.2% 1A
20A to 10,000Arms 0.1 to 10A 1.2%
CT Ratios Programmable from 1:1 to 25,000:1 (probe dependent)
POWER MEASUREMENTS
Active Power (P)* -2 to 2GW 0.001W 0.5% Rdg 0.005% Pnom
Reactive Power (Q)* -2 to 2Gvar 0.001var 1% Rdg 0.01% Qnom
Apparent Power (S)* 0 to 2GVA 0.001VA 0.5% Rdg 0.005% Snom
Power Factor -1 to +1 0.001 0.05
Tangent (active/reactive power ratio) -3.2 to +3.2 0.001 0.02
ENERGY MEASUREMENTS
Active Energy (EP) 0 to 4 x 10
18
1Wh 0.5% Rdg
Reactive Energy (EQ) 0 to 4 x 10
18
1varh 2% Rdg
Apparent Energy (ES) 0 to 4 x 10
18
1Vah 0.5% Rdg
THD 655%
Individual Harmonics 1 to 50 displayed in percentage; 1 to 7 at 400Hz
External Supply 110V/250V (10%) @ 50/60Hz; 400Hz
Back-Up Power Source/Charge Time Rechargeable 8.4V NiMH battery pack / Approximately 5 hours
Battery Life 30 minutes minimum, 60 minutes typical
MECHANICAL
Communication Ports USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **
Dimension/Weight 10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / <1kg
Case/Index of Protection Double insulated, rubber over-molded, polycarbonate UL94 V1 rated / IP54 non operating
Mounting/Security Embedded magnets on back side, keyhole slot on back side / Kensington anti-theft system
DISPLAY
Display Type for Model PEL 103 2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with
adjustable brightness and contrast
ENVIRONMENTAL / SAFETY
Operating Temperature/Relative Humidity 50 to 122F (10 to 50C) / up to 85%
Storage Temperature -4 to 122F (-20 to 50C) with batteries; -4 to 158F (-20 to 70C without batteries)
Safety Rating/CE Rating Complies with IEC 61010-1:Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III / 600V CAT IV, Pollution Degree 2 / Yes
* Maximum value is current probe dependent.
** Computers with Class II Bluetooth will restrict range to 40 ft. Computers without Bluetooth will require a Class I or Class II Bluetooth radio adapter.
*** Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.
Visit the PEL 100 Series
website for more
information on
software,
specifcations
and more!

Special
product
features

M
E
A
SUR
E
S
R
E
MOT
E
T
R
ACK
S
E
N
E
R
G
Y C
O
S
T
D
E
MA N
D
M
O
N
I TOR
I
N
G
' ' ''' ' '
$
V1 V2 V3 N 1000V CAT III 600V CAT IV I1 I2 I3
POWER & ENERGY LOGGER
MODEL PEL 103
ON/OFF START/STOP
NEW!
Technical Assistance (800) 343-1391 www.aemc.com
CATALOG NO. DESCRIPTION
2137.51 Power & Energy Logger Model PEL 102 (no LCD w/3 MA193-10-BK Sensors)
2137.52 Power & Energy Logger Model PEL 103 (with LCD w/3 MA193-10-BK Sensors)
2137.61 Power & Energy Logger Model PEL 102 (no LCD or Sensors)
2137.62 Power & Energy Logger Model PEL 103 (with LCD, no Sensors)
Large Functional Displays
Models PEL 102 & PEL 103
FEATURES
Simple to use, single-, dual (split-phase)
and three-phase (Y, ) power & energy
loggers
Designed to work in 1000V CAT III and
600V CAT IV environments and fits in
many distribution panels
Power measurements: VA, W and var
Energy measurements: VAh, Wh
(source, load) and VARh (4 quadrants)
DataView

software for configuring


real-time communication with a PC and
report generation with pre-defined or
user defined templates
Ethernet compatible
Minimal programming required
Displays stored measurements display or via
Bluetooth (Class 1 - communicates up to
300 ft) to a PC or the Android based
mobile application
Satisfies the requirements of
NEC Code 220.87
Measures AC/DC
(current probe dependent)
SPECIFICATIONS
MODELS PEL 102 & PEL 103
GENERAL
Sampling Frequency 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz)
Data Storage Rate 1 per second
Demand Period Storage Rate User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes)
Recorded Parameters
(Single- and Poly-Phase)
V, I, W, VA, var, PF, Tan, Wh, VAh, VARh, THD (V and I),
Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF
Event Log Tracks and records status changes and error messages along with recorded data
Front Panel Indicator LEDs Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status
Storage Capacity 2GB SD card (included) is used for storage. SD cards (up to 2GB); SDHC cards (4 to 32GB)
formatted FAT32 are supported
INPUTS Voltage 3 voltage input channels via 4mm safety banana jacks
Current 3 current input channels via custom 4 pin jacks that accept AEMC

probes and sensors


ELECTRICAL
VOLTAGE MEASUREMENT RANGE RESOLUTION * ACCURACY (% of Reading)
50/60Hz 42.5 to 69Hz 0.1Hz
Single-Phase RMS Voltages 10 to 1000Vrms 0.1V 0.2% Rdg 0.2V
Phase-to-Phase RMS Voltages 17 to 1700Vrms 0.1 to 1V 0.2% Rdg 0.4V
400Hz 340 to 460Hz
Single-Phase RMS Voltages 10 to 600Vrms 0.1V 1% Rdg 1V
Phase-to-Phase RMS Voltages 17 to 1200Vrms 0.1 to 1V 1% Rdg 1V
DC 100 to 1000V 0.1V 1% Rdg 3V (typical)
PT Ratios Programmable from 50V to 65,0000V 0.01V to 0.1V
CURRENT MEASUREMENT
Current Probe: MiniFlex

Sensor MA193*** 200mA to 100Arms 1 to 100mA 1.2% 50mA


0.8A to 400Arms 10 to 100mA 1.2% 0.2A
4A to 2000Arms 0.1 to 1A 1.2% 1A
20A to 10,000Arms 0.1 to 10A 1.2%
CT Ratios Programmable from 1:1 to 25,000:1 (probe dependent)
POWER MEASUREMENTS
Active Power (P)* -2 to 2GW 0.001W 0.5% Rdg 0.005% Pnom
Reactive Power (Q)* -2 to 2Gvar 0.001var 1% Rdg 0.01% Qnom
Apparent Power (S)* 0 to 2GVA 0.001VA 0.5% Rdg 0.005% Snom
Power Factor -1 to +1 0.001 0.05
Tangent (active/reactive power ratio) -3.2 to +3.2 0.001 0.02
ENERGY MEASUREMENTS
Active Energy (EP) 0 to 4 x 10
18
1Wh 0.5% Rdg
Reactive Energy (EQ) 0 to 4 x 10
18
1varh 2% Rdg
Apparent Energy (ES) 0 to 4 x 10
18
1Vah 0.5% Rdg
THD 655%
Individual Harmonics 1 to 50 displayed in percentage; 1 to 7 at 400Hz
External Supply 110V/250V (10%) @ 50/60Hz; 400Hz
Back-Up Power Source/Charge Time Rechargeable 8.4V NiMH battery pack / Approximately 5 hours
Battery Life 30 minutes minimum, 60 minutes typical
MECHANICAL
Communication Ports USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **
Dimension/Weight 10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / <1kg
Case/Index of Protection Double insulated, rubber over-molded, polycarbonate UL94 V1 rated / IP54 non operating
Mounting/Security Embedded magnets on back side, keyhole slot on back side / Kensington anti-theft system
DISPLAY
Display Type for Model PEL 103 2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with
adjustable brightness and contrast
ENVIRONMENTAL / SAFETY
Operating Temperature/Relative Humidity 50 to 122F (10 to 50C) / up to 85%
Storage Temperature -4 to 122F (-20 to 50C) with batteries; -4 to 158F (-20 to 70C without batteries)
Safety Rating/CE Rating Complies with IEC 61010-1:Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III / 600V CAT IV, Pollution Degree 2 / Yes
* Maximum value is current probe dependent.
** Computers with Class II Bluetooth will restrict range to 40 ft. Computers without Bluetooth will require a Class I or Class II Bluetooth radio adapter.
*** Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.
IP
Rated
54
R
AT I N
G
S
AFETY
ETHERNET
TM
Measurement Mode
Android App Available!
Information Mode
Max Mode Harmonic Mode
Hook up, voltage and current ratios and
aggregation period can be congured from
the front panel of the PEL 103.
Max values for voltage, current (including
neutral current), power and harmonics.
Total Harmonic Distortion (THD) can be
displayed by phase or phase to phase.
Neutral current THD can also be displayed.
Real-time updates are displayed for voltage,
current, power, frequency, power factor and
tangent.
PRODUCT INCLUDES
PEL 102 & PEL 103 Kit
Small classic tool bag, three MiniFlex

MA193-10-
BK sensors, 5 ft USB cable, four black test leads
and alligator clips, power cord, 12 color-coded ID
markers, Multifix mounting system,
safety card, sensor
compliance sheet,
2GB SD-Card with
USB-SD-Card
reader, quick start
user guide, and USB
stick supplied with
DataView

software
and user manual.
Congure Measurements
and Recordings

Display Data in Real-Time

For Use on any Device with an


Android Platform
www.aemc.com Technical Assistance (800) 343-1391
POWER QUALITY ANALYZERS, METERS & LOGGERS
Optional Accessories
SENSOR TYPE CURRENT RANGE
ACCURACY
(TYPICAL)
TYPICAL
ERROR
ON AT
50/60HZ
MAX
CONDUCTOR
SIZE
USED WITH
MODEL
LIMITED
RANGE IF
USED WITH
MODEL
MiniFlex

MA193 *
100mA to 3000AAC
1% 0
2.75"
(70mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
MR193
1 to 1000AAC
1 to 1300ADC
2.5% -0.80
1.6"
(41mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
SR193
1 to 1200AAC
0.3% +0.2
2.05"
(52mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
AmpFlex

193 *
100mA to 12,000AAC
1% 0
7.64"
(190mm)
or
11.46"
(290mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
MN93
0.5 to 240AAC
1% +0.8
0.78"
(20mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
MN193
100A 200mA to 120AAC 1% +0.75
0.78"
(20mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
5A 5mA to 6AAC 1% +1.7
Battery operated
24" or 36" sensor
Technical Assistance (800) 343-1391 www.aemc.com
CATALOG NO. DESCRIPTION
1201.51 AC/DC Current Probe Model SL261 (BNC)
2137.78 AC/DC Current Probe Model J193-BK
2140.37 Adapter US 110V Power Adapter (eliminates need for batteries) 8220 & 8230 only
2140.28 AC Current Probe Model MR193-BK
2140.32 AC Current Probe Model MN93-BK
2140.33 AC Current Probe Model SR193-BK
2140.34 AmpFlex

Sensor

24" Model 193-24-BK
2140.35 AmpFlex

Sensor 36" Model 193-36-BK
2140.36 AC Current Probe Model MN193-BK
2140.48 MiniFlex

Sensor 10" Model MA193-10-BK
2140.49 AC/DC Current Probe Model J93-BK
2140.74 AmpFlex

Sensor 18" (Waterproof - IP67) Model A196-18-BK
POWER QUALITY ANALYZERS, METERS & LOGGERS
Optional Accessories
SENSOR TYPE CURRENT RANGE
ACCURACY
(TYPICAL)
TYPICAL
ERROR
ON AT
50/60HZ
MAX
CONDUCTOR
SIZE
USED WITH
MODEL
LIMITED
RANGE IF
USED WITH
MODEL
SL261 **
100A 5 to 100AAC/DC 4% 0.5
0.46"
(11.8mm)
PEL 102
PEL 103
8333
8336
8220
8230
8435
10A 50mA to 10AAC/DC 3% 1
J93
50 to 3500AAC
50 to 5000ADC
1% 1
2.83"
(72mm)
Busbar:
5 x 1.69"
(127 x 43mm)
PEL 102
PEL 103
8333
8336
8435
N/A
J193
50 to 3500AAC
50 to 5000ADC
1% 1
2.83"
(72mm)
Busbar:
5 x 1.69"
(127 x 43mm)
PEL 102
PEL 103
N/A
A196-18
10 to 10,000AAC 2% 0
5.73"
(145mm)
8435 N/A
* Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.
Note: Refer to the power meters product user manual for complete specifications.
** AC/DC Current Probe BNC Adapter
for Model SL261 only
Catalog #2140.40
Battery operated
Battery operated
Powered by meter
18" sensor IP67
www.aemc.com Technical Assistance (800) 343-1391
Configure all functions of the Power Quality Meters
Display and analyze real-time data on your PC
Configure functions and parameters from your PC
Customize views, templates and reports to your exact needs
Create and store a complete library of configurations that
can be uploaded as needed
Zoom in and out and pan through sections of the graph to
analyze the data
Download, display and analyze recorded data
Display waveforms, trend graphs, harmonic spectrums,
text summaries, transients, event logs and stored alarms
Print reports using standard or custom templates you design
Free updates are available on our website www.aemc.com
Data Analysis and Reporting Software for Power Quality Meters
DATAVIEW


Software for Power & Energy Loggers
Typical DataView

Functional, Digital & Graphical Displays


Clear and easy setup of all functions from one
tabbed dialog box.
Display power and energy parameters
both instantaneous and total.
Display harmonics in a text table from harmonic
0 (DC) through the 50
th
.
Display real-time Phasor diagrams.
Includes unbalance for both voltage and current.
Display real-time waveforms by phase,
parameter or total.
Display all harmonics from 1
st
to 50
th
in bar graph
form for voltage, current and power.

You might also like