18.0 EQUIPMENT TO BE SUPPLIED

18.1 The list of items / equipment to be supplied by the Contractor indicated
here is only indicative. Any other equipment considered necessary by the
Contractor for the installation, testing and commissioning of the plant shall
be included in the offer. Also any additional equipment required or
considered necessary during detailed engineering stage, shall form a part
of the scope.



Category I High Voltage Test Instruments
Sl. No. Instrument Range Quantity
(a) High potential test set AC / DC 0 50 kV 1 No.




Category II Miscellaneous Laboratory Instruments
Sl.
No.
Instrument Range Quantit
y
(a) Automated oil test set 0 75 kV 1 No.




Category II Miscellaneous Laboratory Instruments
Sl.
No.
Instrument Range Quantity
(a) Portable secondary injection test set 500VA, 1AMP/
5AMPs Normal;
20AMPS /
100AMPS for 30
secs, on 1/5 Amps
range respectively


(b) Earth resistance tester with
resistivity test facility
0.01 Ohms,500
Ohms in three
ranges

1 No.
(c) Insulation resistance tester
(transistorised)
0-100, 000 Mega
Ohms, 500-1000-
2500-5000 Volts

1 No.

PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 2 of 8

(d) Digital timers (with least count of 0.5
milliseconds)
(a) 0-30-60 Sec. 2 Nos.
(e) Hot stick Upto 11 kV 1 Nos.
Upto 220 kV 1 Nos.
(f) Temperature controlled soldering
iron
50W 2 Nos.
(g) Function Generator (Sine, Square,
Triangle wave / pulse)
1 Hz to 10 MHz. 1 NO.
(h) Earth loop resistance tester (clap on
type)
Earth lead resi 0-
12000 ohms &
current capability 1
mA to 30 Amp
1 No.
(i) Auto-transformers 3 Phase 0-500 Volts, 5kVA 1Nos.
(j) Auto-transformer 1 Phase 0-270 Volts, 4 kVA 1os.
(i) Digital micro-ohm meter 0.1 micro-ohm-1999
Ohm, 100A
2 Nos.
(k) Portable power measurement meter Amp-1A/5A,
Volt 600 V, for
measurement of
KW, KVA, KVAr,
KWh, PF, Amp,
Volt, in 1 ph & 3 ph
system
1 No.

Category III Meters & Accessories
Sl.
No.
Instrument Range Quantity
(a) Three Phase sequence testing
meter
(100 600 V) 1 No.
(b) Clip on Ammeters AC / DC (a) 0-2000-2500-
3000A
1 No.









PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 3 of 8


Category IV Electronic Instruments
Sl.
No.
Instrument Range Quantity
(a) Dual-trace portable storage
oscilloscope
0 250 mega Hz 1 No.
(b) Regulated DC power supply
equipment
Voltage 0-+300V DC, 2
Amps, 0 - + 30V, DC, 2
Amps, 0-+5V 10
Amps, Current 0 2
AMPS DC, 100 VA

4 Nos.
(c) Digital phase angle meter 0 360 deg. 2 Nos.
(d) 3 Phase Impedance relay testing
kit with phase shifting (110V / 1
and 5 AMPS 2 kVA)

1 No.
(e) Digital frequency indicator 0 1000 Hz 2 Nos.
(f) Digital tachometer (non-contact
type)
0,1500,3000,5000,
10000 rpm
2 Nos.
(g) Digital multimeter (Class 0.2) 6 Nos.
All the necessary accessories shall also be supplied with the instruments.
These shall include but not be limited to :

(a) Two meter length power supply cord with plug.
(b) All necessary accessories like jacks, probes, connectors, adapters,
clips, rain jackets, protective covers, shields, carrying / transporting
cases, etc., wherever applicable.
(h) Composite test kit with 0.02 accuracy for testing following:
Distance relays, Differential relays, Over current relays, F/V/I relays,
Ground fault relays, Synchronising devices, Transient playback,
Harmonics generation, Transducers, Energy meters testing /calibration.
Requisite software and Laptop shall be included as a part of test kit.

18.2 SPECIFIC REQUIREMENTS

18.2.1 Category I High Voltage Test Instruments
(a) The test transformers shall be supplied with :

PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 4 of 8

(i) A control desk incorporating all necessary indication, annunciation,
protection and control equipment.

(ii) All necessary cooling equipment if required.
(iii) Mobile base with adequate no. of rollers for easy transport of the
testing unit.

(iv) All necessary accessories for erection, commissioning, normal
operational / testing of all types of equipment, whether specified or
not.

(v) Shall incorporate built-in safety features to ensure complete safety
of operating personnel.

(b) The insulating material used for bushings and top covers shall be as per
BS for Class F/A installation.

18.2.2
Automatic Oil Test Sets

(i) This equipment shall have an output voltage of 0 75 kV variable
AC, continuously rated 1 kVA with class of insulation being A.

(ii) The test set shall be so designed that the short circuit current drawn
from the system exceeds 8 times the rated current. The transformer
test set impedance shall be such that the input MCCB trips within a
suitable time (0.02 sec.) for a secondary short circuit.

Portable Secondary Injection Test Set

This equipment shall be designed to deliver a normal continuously
adjustable current with multirange selector switch for 1, 5, 10, 50 A etc..
The instrument shall have built in ammeter and voltmeter having adequate
range.

Earth Resistance tester with resistivity test facility


PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 5 of 8

This equipment shall be suitable for measuring the ground resistance,
specific soil resistance and ohmic resistances. The equipment shall be
supplied with all necessary accessories and in-built batteries.

Insulation Resistance Tester (Transistorised)

The insulation resistance shall be measurable to a value of 1,00,000 m
in five ranges. The test voltage shall be adjustable at 500V, 1000V,
2500V and 5000V. The tester shall be suitable for an input supply of 240
V, 50 Hz, single phase AC as well as in-built rechargeable batteries. A
guard terminal shall be provided to eliminate error due to surface leakage.
Accuracy shall be 5%, maximum short circuit terminal current 2.5 mA,
nominal S.C current 2 mA. This tester shall also provide Polarisation
Index Measurement.

Digital Timers

The Digital Timer shall have ranges 0 30 to 60 secs and 0 1 to 5 secs.
These timers be suitable for both normally open as well as normally
closed initiating and stopping contacts. The instruments shall be suitable
for operating on 240 V AC, 1 Phase supply as well as on in-built
rechargeable batteries.


Hot Stick

The hot sticks shall be supplied in two different ratings viz. upto 6.6 kV,
220 kV. The insulating handle of stick shall be with Class F / H insulation
as per IEC / BS specifications with scaled detector having high quality
viewing windows. The hot stick should be light weight and portable.


Temperature Controlled Soldering Iron

The soldering iron rated at 50 W having thermostatic temperature control
shall be supplied complete with set of soldering bits of different sizes and
shapes, three spare heating elements & separate stand to rest the
soldering iron while in use.



PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 6 of 8


18.2.3 (a) Category III

Phase sequence Testing Meter

This shall be suitable for testing 3 phase 415V supply and shall be suitably
marked for clockwise and anti-clockwise directions. Any conducting part
of the meter/ shall withstand 2 kV for 1 minute. The operative range of the
meter shall be 100V to 600V.

(b) Clip on Ammeter

The meter shall have a large digital display unit and the jaws shall open
adequately to facilitate introduction of the conductor having a size
corresponding to the maximum current range.

(c) Standard Current Transformers

The current transformers shall be designed for installation on a busbar or
to have the primary conductor threaded through with one or more turns.
The CTs shall have a class of accuracy of 0-1, class of insulation B for
better and a burden of 30 VA.

(d) Digital low resistance ohm-meter

The instrument shall be suitable for measuring the contact resistance of
switch and circuit breaker contacts, winding resistance of transformer &
motor, busbars, etc.. They shall also be suitable to be used in finding
ground faults in electrical equipment, determining temperature co-efficient
and temperature rise by resistance methods, etc..

18.2.4 Category IV

Relay Test Kit


PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 7 of 8

(a) Relay test set shall be suitable for input voltage 240 V, 1 Phase, 50 Hz
and accuracy 1% full scale. Output current range shall be 5,50,100 A.
Overload and short circuit protection shall be provided. Phase angle
adjustment shall be 0-360 deg. The kit shall be computerised, portable
unit and used to test various types of protective relays quickly and more
accurately. The software for testing, measurement and analysis of the
different types of the relays shall be included.

(b) Dual trace portable storage oscilloscope

The oscilloscope shall consist of a CRT, power supply, electron beam
deflection system and the switching circuitry necessary to integrate a
versatile and complete measurement plug-in system. The oscilloscope
shall be provided with communication port to connect to PC (or) memory
storage devices.

(c) Regulated DC Power Supply


Voltage range
(continuously controlled) - 0 to + 300 V DC

Current range
(continously variable) - 0 to 2A DC

Indication - Digital voltage/current
meters integral with the unit

Load regulation - 0.1% variation in voltage
- 0.2% variation in current.

(d) Digital Phase Angle Meter

The phase angle meter shall be so designed that in addition to phase
angle measurement, it measures the values of the voltages / currents in
the two circuits connected. Suitable selector switches shall be provided
for selecting the necessary parameter i.e., it shall measure phase angle
between two voltages, two currents or a voltage and a current.

(e) 3 Phase impedance relay testing kit with phase shifting


PIONEER GAS POWER LTD.
380-425 MW COMBINED CYCLE POWER PLANT


APSIPL-05- EPC-
3-B18
ELECTRICAL SYSTEMS -
ELECTRICAL LABORATORY EQUIPMENT

Page 8 of 8

This shall comprise a supply unit, control unit, fault impedance unit and an
external current transformer. Relay selector switches shall be provided to
facilitate selection of type of fault & phase.

(f) Digital Frequency Meter

The meter shall have a digital read out with a range of 0 1000 Hz. The
least count of the meter shall be 0.01 Hz for frequencies upto 100 Hz and
0.1 Hz for frequencies above 100 Hz and the accuracies being + 0.05 Hz
and + 0.1 Hz respectively.

(g) Digital Tachometer

Tachometer shall be of the photoelectric type with a digital display which
does not necessitate mechanical contact with the machine shaft. A push
to read push button shall be provided and also an LED to indicate when
the light beam is on the target. Adequate memory shall be built in to
hold the last reading for atleast 1 minute.

Alternatively, digital hand tachometer with electronic circuitry and ball
bearing which offers maintenance free operation can also be offered.


(h) Digital Multimeter

These meters shall have built in overload protection and protection against
HV transients. They shall have an audio alarm for continuity testing, a
peak hold feature on current and voltage ranges, automatic polarity and
over range indications. The instrument shall be complete with
rechargeable batteries and charging equipment, adapters, probes, leads,
padded carrying case, etc.. It shall have safety features to prevent
damage to instrument if voltage is applicable inadvertently current or
resistance measuring range.