You are on page 1of 12

BULLETIN 401

JULY, 2007

HIGH PRESSURE
BACKWARD-CURVED FANS

HIGH-EFFICIENCY

Capacities to 170,000 CFM Static pressures to 40WG


Temperatures to 750F.
THE NEW YORK BLOWER COMPANY
7660 Quincy Street
Willowbrook, IL 60527-5530

Visit us on the Web: http://www.nyb.com


Phone: (800) 208-7918 Email: nyb@nyb.com

HP BACKWARD-CURVED FANS
Size 271 Arrangement 1
HP Backward-curved Fan,
clockwise, Bottom
Horizontal.

Standard high efficiency,


HP Backward-curved
Fans for clean air and
light particulate-laden
applications.
DESIGN FEATURES

backward-curved wheel constructed of


Single-thickness,
high-strength, low alloy steel for dependable operation in
moist or light particulate-laden airstreams.

Wheel sizes from 24 to 89 blade diameters.


Capacities to 170,000 CFM.
Pressures to 40WG.
Mechanical efficiency to 84%.
Temperatures to 750F.
Choice of direct-drive or belt-drive arrangements.
construction eliminates the need for
Integral-base
erection of independent bearing pedestals and

field
sole
plates...complete factory-assembled units up to Size 661
are test run and balanced prior to shipment.

in clockwise and counterclockwise rotations in


Available
any of seven standard discharge positions.

CONSTRUCTION FEATURES
Flanged inlet and outlet-standardon all sizes...furnished
with bolt holes for ease of installation.
Lifting eyes-standardon all sizes for ease of handling.
Shaftinghigh quality, close tolerance, turned, ground, and
polished.
Shaft sealceramic-felt shaft seals standard on all fans
...multiple seal elements compressed between metal backing
plate and retainer.
Precision balancingall HP Backward-curved wheels are
statically and dynamically balanced before final assembly...after final assembly all fans are given a final balance
check on a rigid test bed at the specified running speed.
Size 491 Arrangement 1
HP Backward-curved Fan,
counterclockwise, Top Horizontal,
with evase.

Copyright 2007 by The New York Blower Company.

Heavy-duty spherical roller bearingsselected for long life


through applicable speed range.
Standard two-coat paint systemtwo coats of medium
green industrial enamel...301F.750F. Heat Fans are coated with high-temperature paint.
PAGE 2

BACKWARD-CURVED WHEELS
Backward-curved wheelsrugged, all-welded wheels designed for clean air
applications but capable of handling light particulate-laden or moist airstreams.
Air-handling efficiencies of the HP Backward-curved Fans are higher than
common radial fans and, therefore, offer lower noise levels. See pages 79 for
performance information, or use nyb Electronic Catalog Software for more
specific details.

ELECTRONIC CATALOG
Fan-selection program corrects for altitude, temperature, rarefication, adjusts
maximum safe speed for wheel width, and generates performance curves.
Also includes complete product literature, guide specifications, installation and
maintenance literature, Engineering Letters, web-site launch, and a listing of
New York Blower sales representatives.

SAFETY EQUIPMENT

Belt guards, inlet and outlet guards, shaft and bearing guards, and coupling guards
are available from The New York Blower Company. Contact your nyb representative
for further information.

NOTE: Safe operation of air-moving equipment is dependent


on proper installation and maintenance including selection
and use of appropriate safety accessories for the specific
installation. The system designer must consider providing
guards for all exposed moving parts as well as protection from
access to high-velocity airstreams. Improper application,
installation, maintenance, or safety-guard selection can create

danger to life and limb of personnel. Users and/or installers


should read Recommended Safety Practices For Air Moving
Devices as published by the Air Movement and Control
Association International, 30 West University Drive, Arlington
Heights, Illinois 60004, which is included with the packing
slips for all shipments from nyb and available on request.

ARRANGEMENT FLEXIBILITY
ARRANGEMENT

Overhung wheel on shaft and bearing


assembly isolates fan bearings from
airstream. Normally this arrangement is
used for V-belt-drive fans which provides
flexibility in fan performance.
Available in 24 to 66 wheel diameters.
Maximum temperature:
Standard fan: 300F.
Heat fan: 750F.

ARRANGEMENT

Wheel mounted directly on motor shaft


to provide the most compact design.
Elimination of shaft and bearings for
minimum maintenance. Narrow-width
wheel designs permit higher speeds and
pressures.
Available in 24 to 49 wheel diameters.
Maximum temperature: 180F.
PAGE 3

ARRANGEMENT

Similar to Arrangement 1 but with integral


motor base to accommodate motor and
coupling.
Available in 24 to 89 wheel diameters.
Maximum temperature:
Standard fan: 300F.
Heat fan: 750F.

ACCESSORIES
FLANGES
COMPANION
Designed to fit flush with fan inlet and outlet flanges,

Size 491 Arrangement 1


HP Backward-curved Fan,
counterclockwise, Top Horizontal,
with inlet box and external
outlet damper.

provided with a matching hole pattern.

EVASE
Aerodynamically designed evase provides attached
flow for maximum static pressure regain and
reduced outlet velocities.

DRAIN
Welded tank flange [FPT],
11 2 located at the lowest
point in the housing scroll.
DOOR
CLEANOUT
Two types of gasketed door available...bolted: closely

spaced studs keep door securely sealed...raised


bolted: allows for insulation when desired, door
raised 2 from the fan housing.
BOX
INLET
Minimizes entry

losses normally associated with


90 turns at or near fan inlet...also available with
parallel-blade damper for efficient volume control.

SEALS
SHAFT
Ceramic-felt shaft

seals consist of compressed


ceramic felt elements standard on Arrangements 1
and 8. Lubricated lip seals [Buna-N, Teflon, and
Viton] and gas-purgeable mechanical seals are also
available. Consult your nyb representative for availability.

Size 271 Arrangement 1


HP Backward-curved Fan,
clockwise, Bottom Horizontal,
with external inlet damper
and evase.

[Teflon is a registered trademark of DuPont]


[Viton is a registered trademark of DuPont Dow Elastomers.]

DAMPERS
INLET
External vane construction

provides prespun air


effect to control fan performance efficiently...not
available for use with inlet box...maximum temperature: 750F.

ISOLATION
VIBRATION
Rubber-in-shear or spring-type isolation mounted to

rugged structural unitary base reduces the transmission of vibration to the mounting structure.
BASE
UNITARY
Arrangement 1 fan,

motor, and guards can be


mounted and shipped on a rugged, structural-steel
base. Factory-assembled and run-tested prior to
shipment.

DAMPERS
OUTLET
Heavy-gauge parallel-blade or opposed-blade outlet

ACCESSORIES
OTHER
Also available from nyb are drive components such

dampers are available for volume control. Two standard temperature ranges: 300F. and 800F.

PAGE 4

as motors, couplings, and v-belt drives as well as


a variety of preventive-maintenance products including vibration detectors, bearing-temperature detectors, and zero-speed switches.

MODIFICATIONS
Size 271 Arrangement 1
HP Backward-curved Fan,
clockwise, Bottom Horizontal,
with external inlet damper,
unitary base, belt guard,
shaft and bearing guard,
motor and drive.

COATINGS
Cost-effective protective coatings under a variety of
trade names are available to increase the fans
resistance to adverse, corrosive environments.
STUDS
INSULATION
2-inch long weld-studs located on 12-inch centers

on all surfaces of housing exterior. . . recommended


for use with field-installed insulation . . . studs are
normally mild steel; stainless steel available on
request.
CONSTRUCTION
HEAT-FAN
Standard Arrangement 1 and 8 HP Backward-curved

Fans are designed to handle airstreams to 300F.


HP Backward-curved Fans handling 301F. to 750F.
airstreams are furnished with shaft cooler and shaft
cooler guard, and all surfaces are coated with hightemperature paint.
NOTE: Contact nyb when the intended service
involves a temperature rate change exceeding 20F.
per minute.
AND
NARROW-WIDTH
CONSTRUCTION

SPECIAL DIAMETER
Size 271 Arrangement 1
HP Backward-curved Fan,
clockwise, Bottom
Horizontal, with
inlet box, evase,
and external outlet
damper.

Wheel and housing widths and wheel diameter can


be adjusted to meet volume and pressure requirements at most efficient operating point.
CONSTRUCTION
SPLIT-HOUSING
Provides for wheel and shaft removal...split portion

can be removed without disturbing the inlet or outlet connections. This modification is standard on
Sizes 731 891.
CONSTRUCTION [SRC]
SPARK-RESISTANT
Intended to minimize the potential for any two or

more fan components to generate sparks within the


airstream by rubbing or striking during operation.
The following types are available:
AMCA A [AIRSTREAM] SRC

To include all airstream parts constructed of a


spark-resistant alloy...maximum temperature: 200F.
AMCA B [WHEEL] SRC

To include the fan wheel constructed of a sparkresistant alloy and a buffer plate around the housing
shaft-hole opening...maximum temperature: 200F.

ALLOYS
SPECIAL
HP Backward-curved Fans are available with various

AMCA C [BUFFER] SRC

To include a spark-resistant alloy buffer affixed to


the housing interior adjacent to the wheel backplate, a spark-resistant alloy inlet cone, and a
buffer plate around the housing shaft-hole opening...maximum temperature: 650F.

grades of stainless steel for corrosive, non-abrasive


airstream contaminants. Wheels can be furnished
in Alloy 2205 stainless steel to maintain required
operating speeds. Consult nyb if other materials are
required.

ALL TYPES SRC

Fan is to be so constructed such that no bearings,


drive components, or electrical apparatus are located in the airstream...the user must electrically
ground all fan and system components.
Refer to Engineering Letter 15 for the full meaning
and limits of spark-resistant construction.

SUPPORT
TECHNICAL
nyb has developed numerous engineering and applica-

PAGE 5

tion support tools for system designers and operators.


For further information, contact your local nyb sales
representative or visit our web site at www.nyb.com.

HP BACKWARD-CURVED FANS
SPEED CAPABILITIES
Maximum safe operating speeds are shown in
Chart I for HP Backward-curved Fans with the
standard high-strength steel wheel and the standard shaft and bearings as listed. Substitution of
alternate wheel alloys, or modifications to the
standard shaft and bearing selection, may alter
the maximum safe speed.
Chart II provides safe speed correction factors
for various temperatures and the common alternate wheel alloys. These factors apply to the
wheel safe speeds listed in Chart I.
Example: A Size 361 HP Backward-curved Fan
with an Alloy 2205 wheel operating at a maximum airstream temperature of 600F. will have a
maximum safe operating speed of 1700 RPM
[2500 x .68].

CHART I

MAXIMUM SAFE SPEEDS


HP BACKWARD-CURVED FAN WHEELS, SHAFTS, AND BEARINGS
Arrangement 1

Arrangement 8

Fan size

Maximum
safe speed
[at 70F.]

Shaft
diameter

Bearing
type*

Shaft
diameter

Bearing
type*

241
271
301

3750
3600
3050

23 16
23 16
27 16

P-LB6835
P-LB6835
P-LB6839

23 16
23 16
27 16

P-U335
P-U335
P-U339

331
361
401

2780
2500
2260

211 16
215 16
215 16

P-LB6843
P-LB6847
P-B22447

27 16
211 16
215 16

P-U339
P-U343
P-U347

441
491
541
601

2000
1870
1690
1530

37 16
37 16
315 16
315 16

P-B22455
P-B22455
P-B22463
P-B22463

215 16
37 16
37 16
37 16

P-B22447
P-B22455
P-B22455
P-B22455

661
731
801
891

1390
1260
1140
1030

47 16
NA
NA
NA

P-B22571
NA
NA
NA

315 16
315 16
47 16
415 16

P-B22463
P-B22463
P-LB6871
P-LB6879

NA Not available. *nyb reserves the right to substitute bearings of equal rating.
Link-Belt bearings are shown for reference.
NOTE: Higher safe speeds and static pressures are available with narrow-width
construction; consult nyb.

CHART II

TEMPERATURE CORRECTION FACTORS


FOR MAXIMUM SAFE SPEEDS

DENSITY CORRECTIONS
CALCULATING FANS AT
TEMPERATURES OTHER
THAN 70F
When a fan handles air at 70F, it is operating at
.075 pounds per cubic foot. When a fan handles
other than standard air, a density correction
factor must be considered. Static pressure and
brake horsepower vary inversely as the absolute
temperature. For convenience, Chart Ill gives factors
for correcting pressure and brake horsepower.

Standard
steel wheel

Aluminum

Stainless
316

Stainless
347

Alloy
2205

-50
70
200

1.00
1.00
0.97

1.00
1.00
0.97

0.64
0.64
0.61

0.63
0.63
0.61

0.85
0.85
0.79

300
400
500

0.94
0.91
0.88

0.58
0.56
0.54

0.59
0.57
0.56

0.76
0.73
0.70

600
700
750

0.85
0.81
0.80

0.53
0.52
0.51

0.55
0.54
0.54

0.68

CHART III
TEMPERATURE
CORRECTIONS

Temp.F.
0
20
40
60
70
80
100
120
140
160
180
200
300
400
500
600
750

EXAMPLE
1. Require 15,000 CFM at 12SP at 300F at
sea level.
2. Chart III indicates 1.43 factor for 300F
3. Select the fan for 17.2SP [12 x 1.43] at
70F.
4. Divide 70F brake horsepower by 1.43 to
determine BHP at conditions.

CALCULATING FANS AT
ALTITUDES OTHER THAN
SEA LEVEL [29.92 in. Hg]
If speed, capacity, and temperature are kept constant, static pressure and horsepower will vary
directly as the density of the air. The method
for correcting the altitude is the same as for
temperature except using the factors in Chart IV.

Materials of construction

Airstream
temperature
[F.]

Factor
.87
.91
.94
.98
1.00
1.02
1.06
1.09
1.13
1.17
1.21
1.25
1.43
1.62
1.81
2.00
2.28

CHART IV
ALTITUDE [ft.]
CORRECTIONS
Alt.
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
7000
8000
9000
10000

Factor
1.00
1.02
1.04
1.06
1.08
1.10
1.12
1.14
1.16
1.18
1.20
1.23
1.25
1.30
1.35
1.40
1.45

NOTE: If correction factor for both temperature and altitude


is required, multiply factors from Charts III and IV together:
3000 and 600F. 1.12 x 2.00 = 2.24 [combined factor].
PAGE 6

USING CAPACITY TABLES


1. Ratings are based on standard 70F. air at a density of .075
pounds per cubic foot. See page 6 for density correction factors.

The capacities shown in the tables on pages 79 are based on


belt-drive selections. For a required performance, the tables provide a means of determining fan size, outlet velocity, speed, and
brake horsepower. Performance shown includes the effects of
the evase discharge. For capacities without evase, and for directdrive fan performance (including sizes 731 to 891), use nyb
Electronic Catalog software [see description on page 3]. To
obtain a copy contact your New York Blower sales representative
or nyb at www.nyb.com.

WITH

SIZE 241
CFM

OV

4000
4850
5700
6550
7400
8250
9100
9950
10800

1596
1935
2275
2614
2953
3292
3631
3970
4310

12"SP

OV

5000
6000
7000
8000
9000
10000
11000
12000
13000

1631
1958
2284
2610
2936
3263
3589
3915
4241

OV

6000
7250
8500
9750
11000
12250
13500
14750
16000

1600
1934
2267
2601
2934
3268
3601
3934
4268

OV

7000
8500
10000
11500
13000
14500
16000
17500
19000

1530
1858
2185
2513
2841
3169
3497
3824
4152

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2078
2141
2228
2341
2477
2624
2771
2927
3092

9.36
11.3
13.5
16.0
19.1
22.6
26.4
30.8
36.1

2359
2408
2484
2573
2682
2814
2956
3100
3253

12.7
15.0
17.7
20.7
24.0
28.0
32.4
37.1
42.6

2611
2657
2711
2786
2887
2999
3125
3269
3414

16.1
19.0
21.9
25.3
29.3
33.6
38.3
43.9
49.8

2842
2885
2938
3005
3084
3179
3291
3425
3561

19.6
23.1
26.6
30.4
34.7
39.3
44.4
50.4
56.7

3056
3093
3142
3199
3262
3352
3456
3572
3704

23.1
27.2
31.2
35.4
39.8
45.1
50.8
56.9
63.8

3268
3291
3341
3388
3444
3530
3618
3720

27.0
31.3
36.2
40.7
45.4
51.3
57.2
63.6

3358
3392
3437
3481
3534
3610
3690

28.8
33.6
38.7
43.4
48.4
54.2
60.2

3453
3484
3514
3568
3628
3694

30.7
35.7
40.7
46.1
51.5
57.3

3554
3564
3607
3659
3707

32.8
37.7
43.3
48.9
54.3

3639
3665
3691
3743

34.7
40.2
45.7
51.7

WITH

12"SP

Wheel diameter: 27.0"


Wheel circumference: 7.07'

EVASE
16"SP

20"SP

24"SP

28"SP

[ ]

Maximum BHP = 2.14 RPM


1000

Capacity outlet area: 3.07 ft.2


32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1889
1953
2030
2131
2248
2376
2508
2644
2789

11.6
14.0
16.6
19.6
23.2
27.3
31.8
37.0
43.0

2149
2191
2256
2338
2432
2553
2678
2803
2935

15.8
18.5
21.7
25.3
29.1
33.9
39.2
44.7
50.9

2376
2418
2473
2537
2615
2713
2830
2954
3084

20.0
23.5
27.1
31.1
35.4
40.4
46.2
52.6
59.7

2583
2626
2667
2729
2800
2884
2979
3095
3218

24.3
28.6
32.5
37.2
42.2
47.7
53.5
60.4
68.0

2774
2816
2855
2901
2968
3037
3132
3233
3343

28.7
33.7
38.3
43.1
48.7
54.5
61.4
68.4
76.2

2964
2997
3028
3078
3132
3199
3275
3371

33.4
38.9
44.1
49.7
55.6
62.0
68.9
76.8

3045
3076
3117
3155
3209
3275
3344

35.5
41.3
47.2
52.8
58.9
65.7
72.7

3129
3159
3199
3235
3289
3346

37.9
43.9
50.2
56.1
62.5
69.3

3219
3247
3273
3320
3373

40.5
46.8
53.0
59.7
66.4

3304
3324
3350
3398

43.0
49.4
55.9
63.1

WITH

12"SP

Wheel diameter: 30.0"


Wheel circumference: 7.85'

EVASE
16"SP

20"SP

24"SP

28"SP

[ ]

Maximum BHP = 3.63 RPM


1000

Capacity outlet area: 3.75 ft.2


32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1693
1746
1816
1907
2016
2131
2249
2374
2504

14.0
16.8
20.0
23.8
28.3
33.4
38.9
45.4
52.8

1923
1969
2022
2096
2181
2285
2402
2515
2637

18.9
22.5
26.3
30.7
35.5
41.2
47.9
54.6
62.5

2136
2168
2213
2278
2348
2437
2538
2654
2767

24.2
28.3
32.7
37.9
43.3
49.5
56.4
64.6
73.0

2322
2355
2394
2445
2510
2587
2679
2779
2892

29.3
34.5
39.5
45.0
51.4
58.2
65.8
74.1
83.6

2503
2523
2562
2607
2662
2732
2814
2906
3007

34.9
40.5
46.5
52.6
59.3
67.0
75.2
84.1
93.9

2670
2693
2725
2765
2809
2872
2949
3032

40.5
47.1
53.9
60.6
67.6
75.8
85.0
94.5

2746
2767
2799
2837
2889
2937
3015

43.3
50.2
57.4
64.5
72.4
80.1
90.0

2827
2846
2876
2913
2957
3012

46.3
53.5
61.1
68.8
76.5
85.2

2895
2915
2946
2984
3027

48.9
56.5
64.7
72.8
81.0

2966
2987
3019
3047

51.8
59.8
68.4
76.5

WITH

SIZE 331
CFM

24"SP

BHP

SIZE 301
CFM

20"SP

[ ]

Maximum BHP = 1.32 RPM


1000

Capacity outlet area: 2.51 ft.2

RPM

SIZE 271
CFM

3. For a given selection, check the required fan speed at the


maximum operating temperature against the maximum safe
speeds shown in Chart I on page 6.

Wheel diameter: 24.5"


Wheel circumference: 6.41'

EVASE
16"SP

2. Performance shown is for HP Backward-curved Fans with


evase discharges, with outlet ducts, and with or without
inlet ducts.

12"SP

Wheel diameter: 33.0"


Wheel circumference: 8.64'

EVASE
16"SP

20"SP

24"SP

28"SP

[ ]

Maximum BHP = 5.85 RPM


1000

Capacity outlet area: 4.58 ft.2


32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1532
1576
1639
1718
1810
1915
2022
2131
2248

16.4
19.6
23.5
28.0
33.0
39.0
45.6
52.9
61.7

1746
1782
1831
1888
1966
2057
2159
2266
2372

22.3
26.4
31.0
35.9
41.7
48.3
56.0
64.5
73.5

1933
1965
2007
2055
2119
2196
2289
2387
2494

28.3
33.4
38.7
44.4
51.0
58.2
66.6
75.7
86.2

2111
2135
2174
2214
2269
2335
2414
2502
2601

34.6
40.6
46.9
53.2
60.5
68.5
77.4
87.0
98.0

2267
2297
2327
2362
2407
2473
2538
2623
2712

40.8
48.1
55.2
62.2
69.9
79.3
88.5
99.4
111

2420
2437
2474
2505
2549
2602
2662
2734

47.5
55.2
63.8
71.7
80.3
89.9
100
111

2493
2508
2544
2574
2610
2664
2719

50.9
59.0
68.1
76.5
85.1
95.2
106

2562
2583
2607
2638
2674
2729

54.3
63.1
72.1
81.2
90.2
101

2636
2650
2674
2705
2742

58.1
66.9
76.5
86.2
95.8

2705
2712
2732
2766

61.8
70.6
80.4
90.8

Performance shown is for HP Backward-curved Fans with evase discharges, with outlet ducts, and with or without inlet ducts. BHP does not include
belt losses. Highlighted area indicates maximum mechanical efficiency.
PAGE 7

WITH

SIZE 361
CFM

OV

8750
10500
12250
14000
15750
17500
19250
21000
22750

1560
1872
2184
2496
2808
3120
3432
3744
4056

12"SP

EVASE
16"SP

OV

11000
13000
15000
17000
19000
21000
23000
25000
27000

1612
1906
2199
2492
2785
3078
3371
3665
3958

OV

14000
16250
18500
20750
23000
25250
27500
29750
32000

1678
1948
2218
2487
2757
3027
3297
3566
3836

OV

16000
19000
22000
25000
28000
31000
34000
37000
40000

1585
1882
2180
2477
2774
3071
3368
3666
3963

OV

19500
23250
27000
30750
34500
38250
42000
45750
49500

1573
1875
2178
2480
2782
3085
3387
3690
3992

32"SP

34"SP

36"SP

38"SP

40"SP

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1379
1431
1487
1556
1637
1730
1822
1919
2017

20.1
24.0
28.1
33.0
38.9
46.0
53.8
62.8
72.2

1564
1606
1656
1712
1781
1858
1946
2042
2134

27.4
32.3
37.3
42.7
49.3
56.7
65.4
75.6
86.5

1733
1761
1809
1860
1919
1983
2063
2151
2241

35.2
40.6
46.9
53.3
60.2
68.0
77.5
88.3
99.9

1885
1911
1952
2000
2046
2112
2175
2255
2341

43.2
49.5
56.8
64.3
71.5
80.6
89.8
101
114

2035
2051
2081
2128
2173
2230
2290
2360
2442

52.0
58.8
66.5
75.2
83.7
93.1
103
115
128

2173
2184
2211
2250
2289
2349
2401
2464

60.9
68.5
77.1
86.5
95.7
107
117
129

2246
2273
2304
2352
2400
2454

73.3
82.4
91.7
103
113
124

2311
2329
2361
2404
2454

78.6
87.5
97.5
108
120

2369
2388
2422
2465

83.4
92.9
104
115

2430
2450
2476

88.7
98.9
109

WITH

12"SP

Wheel diameter: 40.25"


Wheel circumference: 10.5'

EVASE
16"SP

20"SP

24"SP

[ ]

Maximum BHP = 15.2 RPM


1000

Capacity outlet area: 6.82 ft.2

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1258
1302
1352
1412
1480
1556
1637
1718
1802

25.2
29.7
34.5
40.2
46.8
54.5
63.6
73.5
84.3

1423
1460
1504
1553
1606
1675
1750
1829
1909

34.2
39.8
45.7
52.0
58.9
67.7
77.6
88.7
101

1573
1601
1639
1686
1734
1789
1857
1929
2006

43.7
50.1
57.1
64.7
72.4
81.2
91.9
104
117

1716
1736
1770
1810
1853
1904
1963
2027
2098

54.0
61.1
69.3
77.7
86.4
96.1
107
120
133

1849
1863
1888
1928
1972
2015
2067
2127
2189

64.7
72.5
81.2
91.2
102
112
123
136
151

1971
1982
2007
2034
2075
2121
2172
2221

75.5
84.4
94.3
104
116
128
141
153

2038
2039
2064
2092
2127
2169
2216

81.9
90.3
101
112
123
136
148

2098
2116
2145
2175
2220

96.8
107
119
130
144

2150
2170
2193
2233

103
114
125
139

2205
2217
2243

109
120
133

WITH

12"SP

Wheel diameter: 44.5"


Wheel circumference: 11.7'

EVASE
16"SP

20"SP

24"SP

[ ]

Maximum BHP = 25.2 RPM


1000

Capacity outlet area: 8.34 ft.2

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1148
1185
1225
1274
1334
1396
1463
1530
1597

32.2
37.2
42.4
48.8
56.6
65.0
75.0
85.9
97.4

1294
1328
1363
1403
1448
1503
1566
1631
1695

43.4
49.9
56.4
63.4
71.1
80.7
91.6
104
117

1426
1455
1487
1526
1563
1613
1661
1721
1786

55.0
62.7
70.6
79.1
87.4
98.0
109
122
136

1552
1577
1601
1636
1673
1714
1761
1814
1869

67.5
76.4
85.0
94.7
105
115
127
141
155

1676
1684
1708
1739
1779
1817
1854
1903
1955

81.4
89.7
99.8
111
123
135
146
161
176

1783
1799
1817
1843
1875
1911
1952
1992

94.6
105
116
128
141
154
168
182

1842
1849
1861
1889
1923
1957
1995

102
113
123
136
150
163
178

1894
1903
1915
1938
1968

109
121
132
145
159

1949
1950
1965
1982

117
128
140
153

1996
1999

124
136

WITH

12"SP

Wheel diameter: 49.0"


Wheel circumference: 12.8'

EVASE
16"SP

20"SP

24"SP

[ ]

Maximum BHP = 42.8 RPM


1000

Capacity outlet area: 10.1 ft.2

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1024
1057
1093
1137
1190
1245
1301
1362
1429

36.7
43.3
50.1
58.1
67.8
78.3
89.7
103
119

1162
1190
1219
1257
1301
1352
1402
1459
1516

50.0
58.2
66.4
75.8
86.5
98.9
112
126
142

1284
1310
1334
1370
1407
1449
1499
1549
1604

63.6
73.8
83.5
94.8
106
119
134
150
168

1398
1419
1446
1471
1504
1544
1589
1636
1689

77.9
89.6
102
113
126
141
157
175
194

1500
1519
1545
1570
1600
1633
1674
1721
1770

92.1
106
120
134
148
163
181
200
221

1608
1618
1638
1665
1692
1723
1758
1801
1846

109
123
138
155
170
187
205
226
248

1652
1660
1682
1711
1732
1766
1798
1838

116
130
147
165
181
199
217
238

1700
1708
1728
1751
1782
1811
1839

124
140
157
175
194
213
231

1744
1749
1768
1794
1820
1846

132
148
166
185
205
223

1790
1798
1810
1832
1861

141
158
175
195
216

WITH

SIZE 541
CFM

28"SP

RPM

SIZE 491
CFM

24"SP

BHP

SIZE 441
CFM

20"SP

[ ]

Maximum BHP = 9.35 RPM


1000

Capacity outlet area: 5.61 ft.2

RPM

SIZE 401
CFM

Wheel diameter: 36.5"


Wheel circumference: 9.56'

12"SP

Wheel diameter: 54.25"


Wheel circumference: 14.2'

EVASE
16"SP

20"SP

24"SP

[ ]

Maximum BHP = 71.1 RPM


1000

Capacity outlet area: 12.4 ft.2

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

925
952
987
1029
1077
1128
1180
1237
1298

44.9
52.6
61.5
71.7
83.6
97.0
111
128
148

1047
1073
1103
1136
1179
1223
1271
1324
1376

60.8
71.0
81.8
93.3
107
122
138
157
177

1159
1183
1208
1236
1272
1312
1356
1407
1455

77.6
90.3
103
116
131
148
166
187
208

1264
1282
1306
1332
1361
1396
1439
1484
1533

95.4
110
125
140
156
174
195
217
242

1357
1374
1397
1418
1449
1477
1517
1558
1604

113
130
147
164
183
201
224
247
274

1448
1457
1482
1505
1528
1559
1594
1631
1675

132
149
170
190
209
231
255
280
308

1493
1503
1522
1540
1570
1599
1631
1666

142
161
181
201
224
247
270
296

1536
1543
1556
1584
1610
1635
1664

152
171
191
215
239
261
285

1582
1585
1600
1616
1645
1673

163
182
204
226
252
277

1620
1621
1639
1657
1682

172
192
216
240
266

Performance shown is for HP Backward-curved Fans with evase discharges, with outlet ducts, and with or without inlet ducts. BHP does not include
belt losses. Highlighted area indicates maximum mechanical efficiency.
PAGE 8

WITH

SIZE 601
CFM

OV

24000
28500
33000
37500
42000
46500
51000
55500
60000

1589
1887
2185
2483
2781
3079
3377
3675
3974

EVASE

12"SP

16"SP

OV

29500
35000
40500
46000
51500
57000
62500
68000
73500

1604
1903
2202
2501
2801
3100
3399
3698
3997

20"SP

24"SP

[ ]

Maximum BHP = 118 RPM


1000

Capacity outlet area: 15.1 ft.2

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

835
861
893
931
970
1015
1063
1112
1167

54.9
64.4
75.3
87.8
101
117
134
154
178

950
970
995
1027
1063
1102
1146
1192
1238

75.1
87.1
99.6
114
130
148
168
190
213

1046
1066
1092
1118
1149
1184
1222
1266
1311

94.9
110
126
142
160
179
200
226
252

1141
1156
1181
1203
1231
1261
1298
1337
1380

117
134
153
171
191
212
236
262
291

1225
1239
1259
1282
1308
1336
1370
1406
1446

138
158
179
200
223
246
272
300
332

1311
1321
1336
1356
1380
1408
1437
1470
1508

162
184
207
230
255
281
309
338
371

1347
1356
1372
1394
1420
1444
1471
1502

173
196
220
246
274
300
328
358

1391
1392
1411
1428
1451
1477
1503

187
209
235
261
289
318
346

1428
1431
1444
1464
1483
1507

199
223
249
277
305
334

1467
1479
1495
1517

236
264
292
323

WITH

SIZE 661
CFM

Wheel diameter: 60.0"


Wheel circumference: 15.7'

Wheel diameter: 66.0"


Wheel circumference: 17.3'

EVASE

12"SP

16"SP

20"SP

24"SP

[ ]

Maximum BHP = 190 RPM


1000

Capacity outlet area: 18.4 ft.2

28"SP

32"SP

34"SP

36"SP

38"SP

40"SP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

764
785
816
848
889
929
971
1019
1070

68.0
79.2
92.6
107
125
145
165
191
221

864
885
909
938
969
1008
1048
1090
1134

92.0
107
123
140
159
182
207
234
264

956
972
993
1019
1048
1083
1118
1158
1199

117
135
153
174
196
221
248
278
311

1036
1054
1073
1095
1122
1150
1185
1221
1260

142
164
186
209
234
260
290
322
358

1118
1129
1149
1167
1192
1219
1251
1280
1321

171
194
220
245
273
302
335
367
408

1192
1203
1219
1239
1258
1284
1309
1343
1375

199
225
254
284
313
345
377
416
455

1229
1234
1252
1269
1289
1313
1340
1372

214
240
271
301
333
366
401
441

1261
1267
1281
1300
1322
1344
1372

227
255
286
319
354
388
426

1298
1302
1317
1332
1352
1375

243
272
306
339
374
411

1329
1334
1349
1366
1383

257
289
324
360
396

Performance shown is for HP Backward-curved Fans with evase discharges, with outlet ducts, and with or without inlet ducts. BHP does not include
belt losses. Highlighted area indicates maximum mechanical efficiency.

MATERIAL SPECIFICATIONS [INCHES,


Size

241
271
301
331
361
401
441
491
541
601
661
731
801
891

Housing
Side and
Side
scroll
channels
3 16
3 16
1 4

3-4.1#
3-4.1#
3-4.1#
4-5.4#
4-5.4#
4-5.4#
4-5.4#
4-5.4#
5-6.7#
5-6.7#
5-6.7#
5-6.7#
5-6.7#
5-6.7#

1 4
1 4
1 4
1 4
1 4
1 4
1 4
1 4
1 4
1 4
1 4

Base bars

Base angles

Inlet flange angles

3 x 38
3 x 38
3 x 38
4 x 12
4 x 12
4 x 12
4 x 12
4 x 12
5 x 58
5 x 58
5 x 58
5 x 58
5 x 58
5 x 58

3 x 2 x 316
3 x 2 x 316
3 x 2 x 316
4 x 3 x 14
4 x 3 x 14
4 x 3 x 14
4 x 3 x 14
4 x 3 x 14
5 x 312 x 516
5 x 312 x 516
5 x 312 x 516
5 x 312 x 516
5 x 312 x 516
5 x 312 x 516

112 x 112 x 316


112 x 112 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316

Bearing
Outlet flange angles pedestal

114 x 114 x 316


114 x 114 x 316
112 x 112 x 316
112 x 112 x 316
112 x 112 x 316
112 x 112 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316
2 x 2 x 316

POUNDS , WR

IN LB - FT

Wheel
Blades

Backplate

3 8
3 8
3 8

3 16
3 16
3 16

3 8
3 8
3 8

3 16
3 16
1 4

3 8
3 8
3 8
3 8

1 4
1 4
1 4
1 4

3 8
3 8
3 8
3 8

1 4
3 8
3 8
3 8

7 GA
7 GA
7 GA
7 GA
1 4
1 4
1 4
1 4
1 4
1 4
1 4
3 8
3 8
3 8

Bare fan weight [lbs.]


Weight [lbs.]* WR2 [lbs.-ft.2]*

105
120
140
160
240
335
390
450
530
625
895
1390
1645
1960

Arr. 1

47
66
98
141
256
439
641
926
1374
2052
3358
6685
9867
14452

0830
0965
1244
1584
1924
2185
2686
3086
3850
4486
5567

* Wheel weight and WR2 will change with special diameter and narrow-width construction. Consult nyb.
Bare fan weights for Arr. 4 and Arr. 8 fans are available on application. Consult nyb.
C

FLANGED OUTLET
AND EVASE

FLANGED INLET
Furnished as standard
with holes on
vertical centerline.

D
A

1. Mounted flush with edge of housing


outlet.
2. Furnished as standard with holes on
4 centers from centerlines.

M
B

DIMENSIONS [INCHES]

DIMENSIONS [INCHES]
A

Size
Fan

Evase

Fan

241 23
323 4
271 25
36
301 273 8 391 2

15
161 4
173 4

3 4

331 303 8 44
361 331 4 481 2
401 361 2 53

193 4
211 2
233 8

441
491
541
601

397 8
443 4
487 8
535 8

581 4
647 8
711 4
78

7 8
251 2
285 8 11 8
311 4 11 8
341 8 11 8

367 8
403 4
447 8
495 8

661
731
801
891

585 8
643 8
707 8
771 2

857 8
941 2
1031 2
114

37
401 2
443 8
483 8

545 8
603 8
667 8
731 2

3 4
3 4
7 8
7 8
7 8

11 8
11 8
11 8
11 8

M
Evase

Standard holes
Sides
Top/ Size
Fan Evase bottom

201 2 301 4 121 2


221 2 331 2 133 4
247 8 37
151 4

5
7
7

9
9
9

3
3
3

7 16

273 8 41
163 4
301 4 451 2 181 2
331 2 50
203 8

7
9
9

11
11
13

3
5
5

7 16

551 4
607 8
671 4
74

221 2 9
245 8 11
271 4 11
301 8 13

15
15
17
19

5
5
7
7

7 16

817 8
901 2
991 2
110

33
361 2
403 8
443 8

21
23
25
29

9
9
9
11

9 16

Dimensions will vary with narrow-width construction.

15
15
17
19

Tolerance: 1 8

7 16
7 16
7 16
7 16
9 16
9 16
9 16
9 16
9 16
9 16

PAGE 9

Holes

Inside
diameter

Bolt
circle

Outside
diameter

Number

Diameter

241
271
301

213 4
243 8
267 8

231 2
261 8
291 8

243 4
273 8
307 8

16
16
16

9 16

331
361
401

291 2
327 8
361 8

313 4
351 8
383 8

331 2
367 8
401 8

16
16
16

9 16

441
491
541
601

401 8
437 8
487 8
537 8

423 8
461 8
511 8
561 8

441 8
477 8
527 8
577 8

16
24
24
24

9 16

661
731
801
891

593 8
661 8
725 8
805 8

615 8
683 8
747 8
827 8

633 8
701 8
765 8
845 8

24
32
32
32

9 16

Size

9 16
9 16
9 16
9 16
9 16
9 16
9 16
9 16
9 16
9 16

Tolerance: 1 8

DIMENSIONS [INCHES] Not to be used for construction unless certified.


ALL ARRANGEMENTS
Size

241
271
301
331
361
401
441
491
541
601
661
731
801
891

BB

DD

2012
2212
25
2712
31
3312
37
40
44
4812
53

2012
2212
25
2712
31
3312
37
40
44
4812
53
59
6512
72

48
5234
58
6458
7212
7812
8718
95
10518
11518
12778
14138
15434
17258

2258
25
2734
3012
3334
3718
41
4518
50
5514
6034
6718
7418
8134

2038
2238
2478
2738
3014
3312
3678
4034
4478
4958
5458
6038
6678
7312

3014
3312
37
41
4512
50
5514
6078
6714
74
8178
9012
9912
110

1638
18
20
22
2438
2634
2958
3212
36
3934
4334
4838
5338
5878

2658
2938
3234
3578
3934
4334
4838
5314
5878
6518
7112
7918
8712
9638

Arr. 1

Arr. 8

Arr. 1

18
20
22
24
26
30
33
35
36
38
40
NA
NA
NA

18
20
22
24
26
30
33
35
36
38
40
42
44
46

3618
3938
4278
4838
5218
58
6318
6714
7278
7734
8258
8818
94
100

2818
3078
3414
3778
4134
4534
5038
5514
6138
6758
74
8158
90
9878

734
838
918
1038
1114
1214
1314
1438
1618
1758
19
2034
2234
2434

14
1538
1738
19
2012
2114
23
24
27
29
31
33
40
45

TH/TAD

BH/BAU

UB/TAU

DB

2114
2312
2614
2834
3134
35
3834
4212
47
52
57

2834
3134
3514
3834
4234
4714
5214
5714
6312
7014
77

2434
2714
3014
3314
3634
4012
4434
4914
5412
6014
6614

See Table for Sizes 731


through 891 below.

Arr. 1

Arr. 8

1914
2118
2358
2578
2858
3112
3478
3838
4238
4678
5112
57
63
6938

41
4434
4834
5334
58
6438
70
7458
7934
8518
9012
NA
NA
NA

41
4434
4814
5234
5612
6338
6812
7258
7714
8318
88
9312
9938
10638

17
1812
2014
2214
2414
26
2812
31
3334
3714
4012
4412
5078
5514

1512
1678
1878
21
2212
2314
25
26
2912
3112
3312
3512
4212
4712

2078
23
2558
2818
3118
3414
3778
4158
4618
51
56
62
6812
7512

K
Arr. 1

Arr. 8

5
5
5
6
6
6
6
6
7
7
7
7
7
7

512
6
612
7
712
8
812
9
912
10
1012
NA
NA
NA

512
6
6
6
6
7
7
7
7
8
8
8
8
9

3338
3658
4034
4478
50
5458
6038
6578
7234
8014
88
9758
10818
119

2458
2718
3018
3318
3658
4038
4458
4918
5438
6018
6618
73
8034
89

1734
1912
2134
2378
2638
2618
3218
3538
3918
4314
4712
5212
5818
64

NA Not available.
Size

241
271
301
331
361
401
441
491
541
601
661
731
801
891

2134
2438
2678
2912
3278
3618
4018
4378
4878
5378
5938
6618
7258
8058

1212
1334
1514
1634
1812
2038
2212
2458
2714
3018
33
3612
4038
4438

S
Arr. 1

Arr. 8

1758
1958
2158
2358
1278
1478
1638
1738
1778
1878
1978
NA
NA
NA

1758
1958
2158
2358
1278
1478
1638
1738
1778
1878
1978
2078
2178
2278

Base holes
Arr. 1

8-34
8-34
8-34
8-34
10-1
10-1
10-1
10-1
10-1
10-1
10-1
NA
NA
NA

NA Not available.

SIZES 731 through 891 only ARRANGEMENT 8


Size

731
801
891

TH

TAD

BH

A
BAU

UB

TAU

DB

6314
70
77

5834
6514
7134

8512
9412
104

7912
88
9634

7312
8114
8912

6814
7512
8314

59
6512
72

SS
Arr. 8

Base holes
Arr. 4
Arr. 8

ARRANGEMENT 4/8

15.0
18.4
22.2

Wheel diameter
[inches]

Wheel circumference
[feet]

73
8034
89

19.1
21.1
23.2

22.5
27.4
33.4

ARRANGEMENT 8 ONLY

Size

Frame
size

N
Arr. 4

NN
Arr. 8

Arr. 4

Arr. 8

S
Arr. 4

241

364TS
365TS
404TS
405TS

2138
2238
2318
2458

5678
5778
60
6112

3678
3778
3858
4018

6618
6718
6914
7034

1778
1878
1958
2118

1434
1514
1638
1718

7-34
7-34
7-34
7-34

11-34
11-34
11-34
11-34

271

404TS
405TS
444TS
445TS

2318
2458
2714
2914

6318
6458
6858
6678

3978
4138
44
46

73
7412
7812
7634

1958
2118
1178
1278

1658
1738
1914
1838

7-34
7-34
9-34
9-34

11-34
11-34
11-34
11-34

444TS
445TS
447TS
449TS

2714
2914
2914
3334

7138
6958
6958
7318

4512
4712
4712
52

82
8014
8014
8334

1178
1278
1278
1518

1914
1838
1838
2018

9-34
9-34
9-34
9-34

11-34
11-34
11-34
11-34

331

444TS
445TS
447TS
449TS

2714
2914
2914
3334

7418
7238
7238
7578

48
50
50
5412

8612
8434
8434
8814

1158
1258
1258
1478

19
1818
1818
1978

9-34
9-34
9-34
9-34

11-34
11-34
11-34
11-34

361

364T
365T
404T
405T

2138
2238
2318
2458

6838
6938
7112
73

4378
4478
4558
4718

8158
8258
8434
8614

1738
1838
1918
2058

2118
2158
2234
2312

7-1
7-1
7-1
7-1

13-1
13-1
13-1
13-1

401

404T
405T
444T
445T

2318
2458
2714
2914

7712
79
8278
8478

4712
49
5158
5358

9158
9318
9718
9918

1918
2058
1158
1258

2414
25
27
28

7-1
7-1
9-1
9-1

13-1
13-1
13-1
13-1

441

444T
445T
447T

2714
2914
3234

87
89
9212

5334
5534
5914

10214
10414
10734

1158
1258
1438

2734
2834
3012

9-1
9-1
9-1

13-1
13-1
13-1

491

445T
447T
449T

2914
3234
3834

92
9512
10012

5778
6138
6738

10838
11178
11678

1258
1438
1738

2914
31
3312

9-1
9-1
9-1

13-1
13-1
13-1

301

Outlet area [sq. ft.]


Fan
Evase

PAGE 10

Size

Frame
size

NN
Arr. 4

O
Arr. 8

SS
Arr. 4

Base holes
Arr. 8

541

445T
447T
449T

9438
9778
10278

113
11612
12112

2914
31
3312

13-1
13-1
13-1

601

445T
447T
449T

9834
10214
10714

11878
12238
12738

3014
32
3412

13-1
13-1
13-1

661

445T
447T
449T

10214
10534
11034

12334
12714
13214

3034
3212
35

13-1
13-1
13-1

731

445T
447T
449T

106
10912
11412

12914
13234
13734

3118
3278
3538

13-1
13-1
13-1

801

445T
447T
449T

10978
11338
11838

13518
13858
14358

3158
3338
3578

13-1
13-1
13-1

891

445T
447T
449T

11478
11838
12338

14218
14558
15058

3258
3438
3678

13-1
13-1
13-1

Dimensions may vary with narrow-width construction.


NOTE: For fan sizes larger than 49, motors typically
exceed NEMA frame sizes. Therefore, dimensions
must be on application.

Tolerance: 1 8

DRAWINGS

Dimensions not to be used for construction unless certified.


H
J

ARRANGEMENT

S
TW

L
(I.D.)

G
B

TW

U
P

D
M

DD

BB

F
D

1 Omitted on Sizes 24 through 33.

F
D

ARRANGEMENT

DD

BB

TW

TW

B
L
(I.D.)

F
D

1 Omitted on Sizes 24 through 33.

ARRANGEMENT

SS

BB
B

TW

L
(I.D.)

DD

TW

U
P

D
M

NN
2 Base bars form flanged outlet on Down Blast.
M, D, and DD are outside housing dimensions. J is from housing side over inlet. L is inside diameter.

FAN DISCHARGES VIEWED FROM DRIVE SIDE


C

F
G

CW TH

CW BH

TOP HORIZONTAL

BOTTOM HORIZONTAL

CW DB

CW TAD

CW BAU

CW TAU

CCW TH

CCW BH

UP BLAST

DOWN BLAST

TOP ANGULAR DOWN

BOTTOM ANGULAR UP

TOP ANGULAR UP

TOP HORIZONTAL

BOTTOM HORIZONTAL

CW UB

Clockwiseangular discharges at 45

F
B

CCW UB

CCW DB

CCW TAD

UP BLAST

DOWN BLAST

TOP ANGULAR DOWN

CCW BAU
BOTTOM ANGULAR UP

CCW TAU
TOP ANGULAR UP

Counterclockwiseangular discharges at 45

Down Blast and Top Angular Down discharge positions must be evaluated for clearance of accessories such as unitary base, outlet damper, evase, etc. Consult nyb with specific details.
The New York Blower Company has a policy of continuous product development and reserves the right to change designs and specifications without notice.

PAGE 11

COMPLETE SELECTION OF
AIR-MOVING EQUIPMENT
The New York Blower Company offers
thousands of different types, models, and
sizes of air-moving equipment. Contact
your nyb representative for assistance in
identifying the best fan for your application.

AIR-HANDLING
[AXIAL]
For the ideal handling of clean
to moderately dirty airstreams.
Commercial and industrial HVAC,
drying and cooling systems, fume
extraction, and process-heat
removal are typical applications.

DUST/MATERIAL
HANDLING
Wide range of duty available
with unique fan lines capable
of handling light dust to heavy
material. Typical applications
include dust-collection and
high-pressure process along
with material-conveying.

AIR-HANDLING
[CENTRIFUGAL]
Designed for clean to moderately
dirty gas streams. Commercial
and industrial HVAC, process
cooling, light material-conveying,
heat removal, and dryer exhaust
are just a few of the numerous
sample applications

FIBERGLASS
REINFORCED
PLASTIC [FRP]
Choice of performance and duty for
corrosive gas streams. Applications
include chemical process, wastewater
treatment, laboratory hood exhaust,
and tank aeration.

CUSTOM PRODUCTS
Designed for unique applications. Variety of configurations,
temperatures, flows, and pressures. Wide range of
modifications and
accessories are
available to
meet the most
demanding
specifications.

Leading the industry forward since 1889

ROOF VENTILATORS
Including both hooded and upblast ventilators,
propeller fans, and centrifugal roof exhausters.
These units are ideal for industrial, commercial,
and institutional applications.

HEATING
PRODUCTS
Industrial-duty steam
unit heaters with steam
heating coils are available
for facility heating and
process-heat transfer.

PROCESS/FAN
COMPONENTS
Plug fans, plenum fans, wheels, inlet cones,
and housings for a wide variety of OEM
applications. Process/fan components are
used in air-handling units, ovens, dryers,
freezer tunnels, and filtration systems.

You might also like