• Be familiar with the mechanisms of heat transfer which are encountered in heat
exchangers and other engineering heat transfer problems
• Be able to calculate an overall heat transfer coefficient (or resistance) from
knowledge of individual heat transfer coefficients (or resistances)
• Understand the concept of fin efficiency and be able to determine overall heat
transfer coefficients in geometries involving extended surfaces.
Be able to apply published correlations to determine heat transfer coefficients in
single-phase, boiling and condensing flows. Heat transfer specialists may be able to
quote some correlations for convective heat transfer from memory, but will generally
check their own notes or a published source to find the most appropriate for a
particular application. Students should NOT attempt to learn the correlations given in
this section.
• Have a knowledge of fouling and fouling mechanisms
• Be able to calculate radiative heat transfer for simple geometries
which, for constant area, for example through a plane wall, may be integrated:
2.1
where α is the convective heat transfer coefficient. We will discuss the evaluation of
heat transfer coefficients in Chapter 4
In both cases the negative sign signifies heat transfer is from the higher temperature
to the lower temperature.
Th
ro
Tw1 ri
To
Tw2
Tc Two
Twi
t Ti
Ti
Twi
Two
Two
2.2
There are several resistances to heat transfer between the bulk of the hot fluid and
the bulk of the cool fluid as shown in Fig 2.1. For steady state conditions, the rate of
heat transfer from the hot fluid to the wall, the rate of heat flow through the wall,
and the rate of heat transfer from the wall to the cool fluid must be equal, defining
this as Q& , the surface area of the wall as A, and the heat flux by q& = Q& A ,we can
write:
Q& = −αa A(Th − Tw1 ) or q& = −αa ( Th − Tw1 ) (2.4a)
kA k
Q& = − (Tw1 − Tw 2 ) or q& = − (T − T ) (2.4b)
t t w1 w 2
Q& = −αb A(Tw 2 − Tc ) or q& = −αb (Tw 2 − Tc ) (2.4c)
(The negative signs are included to indicate that energy flows from hot to cold)
Rearranging equations 2.4 gives
q&
= −( Th − Tw1 )
αa
qt
&
= −(Tw1 − Tw 2 ) (2.5)
k
q&
= −( Tw 2 − Tc )
αb
Adding these equations gives:
⎛ 1 t 1 ⎞
⎜⎜ + + ⎟⎟q& = −(Th − Tc ) (2.6)
⎝ α a k αb ⎠
which is equivalent to:
or
with
1 ⎛ 1 t 1⎞
=⎜ + + ⎟ (2.9)
U ⎝ α a k αb ⎠
2.3
1 ⎛ 1 i =n t i 1⎞
=⎜ +∑ + ⎟ (2.10)
U ⎝ α a i =1 k i α b ⎠
By analogy to the analysis of electrical circuits, we may consider the heat flux q& as
analogous to the current I flowing through a series of resistances, r, and the driving
temperature ∆T difference as equivalent to a voltage drop, V,. With reference to the
diagram below:
V1 V2
r1 r2 r3 rn
V1 − V2
I= where R = r1 + r2 + ............rn
R
Th − Tc
q& = − (2.11)
R
1
R=
U
1 t1 t t 1
= + +......+ i +.............+ n + (2.12)
αa k1 ki k n αb
= ra + r1 +..........+ ri +.................. rn + rb
Where the individual rs represent the heat transfer resistance for each boundary.
Often the values of these resistances differ by an order of magnitude or more and it
is permissible to neglect the smaller resistances.
2.4
There are also situations when intermediate temperatures are known, or must be
calculated. For example if the internal surface temperature of the wall illustrated in
Fig. 2.1(a) is known then equations 2.4(b) and (c) may be used to give:
⎛t 1 ⎞
⎜⎜ + ⎟⎟q& = −(Tw1 − Tc ) (2.6(a))
⎝ k α b ⎠
1
q& = − (T − Tc ) (2.13)
1 t 1 h
+ r fa + + r fb +
w
αa kt αb
The terms rfa and rfb representing the fouling resistances, or fouling factors on each
side of the wall.
Even for this simplest of geometries we can write this expression incorporating
fouling resistances in a number of ways, all of which are equally valid, for example:
1 ⎛1 ⎞
= ⎜ + r fa + r fb ⎟ (2.15)
U f ⎝U ⎠
or
1 1 tw 1
= + + (2.16)
U f αaf k t αbf
with the appropriate heat transfer coefficient, α f , for the fouled surface being
calculated from:
1 1
= + rf (2.17)
αf α
2.5
To determine the heat transfer through a tubular element we follow a similar line of
reasoning. As for the plane wall, during steady state conditions the rate of heat flow
into a section of wall must equal the heat flow out at the other side. Furthermore, if
the tube is long and longitudinal temperature gradients are small, we can assume that
heat flow is one dimensional and in the radial direction.
Firstly consider the heat flow and temperature distribution within the tube wall:
For an element radius r and thickness δ r ,
δT
Q& = − kA (2.18)
δr
or, in the limit:
dT
Q& = − kA (2.18a)
dr
For a length l of tube: A = 2π rl
Therefore
dT
Q& = − k 2π rl (2.19)
dr
This may be integrated between the limits ri and ro to give:
2π kl(To − Ti )
Q& = − (2.20)
⎛r ⎞
ln⎜ o ⎟
⎝ ri ⎠
Now if we consider the internal and external thermal resistances we can write a set
of equations:
2π kl
Q& = − (T − Ti )
⎛ ro ⎞ o
(2.21b)
ln⎜ ⎟
⎝ ri ⎠
2.6
Q& ⎛ 1 1 ⎛r ⎞ 1 ⎞
⎜ + ln⎜ o ⎟ + ⎟ = −(To − Ti ) (2.22)
2π ⎝ roα o l kl ⎝ ri ⎠ ri αi l ⎠
As for the wall we may define an overall heat transfer coefficient or “U-value” such
that:
and
1 1 1 ⎛r ⎞ 1
= + ln⎜ o ⎟ + (2.24)
UA 2π roαo l 2π kl ⎝ ri ⎠ 2π riαi l
This implies that, with reference to the internal surface, having area Ai = 2π ri l ,
1 r r r 1
= i + i ln o + (2.25)
U i roαo k ri αi
and, with reference to the external surface, having area Ao = 2π rol ,
1 1 r r r
= i + o ln o + o (2.26)
U o αo k ri riαi
To avoid confusion regarding the area used , it is also possible to work in terms of
unit length:
Q& ⎛ 1 1 ⎛r ⎞ 1 ⎞
⎜ + ln⎜ o ⎟ + ⎟ = −(To − Ti ) (2.27)
l ⎝ 2π roα o 2π k ⎝ ri ⎠ 2π ri αi ⎠
leading to
where
1 ⎛ 1 1 ⎛r ⎞ 1 ⎞
=⎜ + ln⎜ o ⎟ + ⎟ (2.29)
U ′ ⎝ 2π roαo 2π k ⎝ ri ⎠ 2π riαi ⎠
2.7
For a thin walled tube the mean radius may be calculated as rm = (ro + ri ) 2 , the area
is then given by Ai ≈ Ao ≈ A = 2π rml and the tube wall may be considered as a flat
wall, thickness t = ro − ri . The overall heat transfer coefficient and rate of heat
transfer may thus be calculated:
1 ⎛ 1 t 1⎞
=⎜ + + ⎟ (2.30)
U ⎝ αo k αi ⎠
Which is identical to equation 2.6.
If the tube is thin walled and the thermal resistance, t/k, is small compared with the
two film resistances:
1 ⎛ 1 1⎞
=⎜ + ⎟ (2.31)
U ⎝ αo αi ⎠
and
If fouling resistances are to be included, we have already seen that these may be
incorporated in the expression for the overall heat transfer coefficient through a
plane wall by simply adding the resistances. For the thin walled tube this may be
expressed:
1 ⎛ 1 t 1 ⎞
= ⎜ + rfo + + + ri ⎟ (2.33)
U f ⎝ αo k αi ⎠
or:
1 ⎛ 1 t 1⎞
=⎜ + + ⎟ (2.34)
U f ⎝ αo′ k αi′⎠
where
1 1
= + rf (2.35)
α′ α
2.8
It is convenient to use this modified heat transfer coefficient when dealing with thick
walled tubes, and as we shall see later, with all geometries where the heat transfer
areas differ for each stream.
1 1 r r r
= i + o ln o + o (2.36)
U o′ αo′ k ri riαi′
he surface area on one or both sides of a heat exchanger may be increased by the
use of extended surfaces or fins. There is a wide range of geometries employed in
extending the surface in contact with a fluid. Surfaces which are separated from the
2.9
other fluid only by the thin layer of material through which conduction occurs (e.g.
the plane wall or tube discussed above) are referred to as the primary surface of a
heat exchanger. Additional surface which is in contact with one fluid but from which
there is a tortuous conduction path to the other fluid is known as the secondary
surface.
We will first analyse the simplest fin type and then discuss how the results may be
used in more complex geometries. We shall consider a rectangular fin on a plain
surface as shown in Figure 2.3.
If the length, l, and breadth, L, of the fin are large compared to the thickness, b, we
can assume that conduction through the fin is approximately one dimensional.
The heat flow into the element dx at some position, x, from the root of the fin is
given by:
⎛ dT ⎞ ⎛ dT ⎞
Q& x = − kA⎜ ⎟ = − kLb⎜ ⎟ (2.37)
⎝ dx ⎠ ⎝ dx ⎠
2.10
⎛ dQ& ⎞ ⎛ dT ⎞ d ⎛ ⎛ dT ⎞ ⎞
Q& ( x + dx ) = Q& x + ⎜ ⎟ dx = − kLb⎜ ⎟ − ⎜ kLb⎜ ⎟ ⎟ dx
⎝ dx ⎠ ⎝ dx ⎠ dx ⎝ ⎝ dx ⎠ ⎠
(2.38)
⎛ dT ⎞ ⎛ d 2T ⎞
= − kLb⎜ ⎟ − kLb⎜ 2 ⎟ dx
⎝ dx ⎠ ⎝ dx ⎠
The difference between the inflow and outflow by conduction must be equal to the
net outflow of heat from the element to the surroundings:
⎛ d T⎞
2
dQ& = Q& x − Q& ( x + dx ) = kLb⎜ 2 ⎟ dx (2.39)
⎝ dx ⎠
d 2 T d 2θ
defining θ = (T − Ts ) so that = 2 , since Ts is constant, and equating the two
dx 2 dx
expressions for heat loss from the element:
d 2θ 2α
= θ (2.41)
dx 2 kb
2α
m=
kb
The values of the constants M and N are then determined with reference to
appropriate boundary conditions:
At the root of the fin x=0 and the fin temperature is equal to the root temperature,
To.
θ0 = T0 − Ts = M + N (2.44)
The second boundary condition is less obvious, but if the fin is very slender so that
the heat loss from the tip can be neglected, or if the fin is insulated, then, at x=l,
2.11
⎛ dθ ⎞ ⎛ dθ ⎞
Ql = − kLb⎜ ⎟ = 0, or ⎜ ⎟ = 0 (2.45)
⎝ dx ⎠ l ⎝ dx ⎠ l
Combining equations 2.44 and 2.46 gives values for the constants M and N:
e − ml eml
M = θ0 and N = θ0 (2.47)
eml + e − ml eml + e − ml
⎛ e m( l − x ) + e − m ( l − x ) ⎞ ⎛ cosh( m( l − x ) ) ⎞
θ = θ0 ⎜ ⎟ = θ0 ⎜ ⎟ (2.48)
⎝ cosh( ml ) ⎠
− ml
⎝ e +e
ml
⎠
The heat flow from the surface of the fin is equal to the heat flow through the base
of the fin, therefore at xo, using equation 2.45, gives:
⎛ dt ⎞ ⎛ sinh( m( l − x ) ) ⎞
Q& 0 = − kLb⎜ ⎟ = mkLbθ0 ⎜ ⎟
⎝ dx ⎠ 0 ⎝ cosh( ml ) ⎠ x =0
(2.49)
= mkLbθ0 tanh( ml )
Now an ideal fin would have infinite thermal conductivity, hence the entire fin would
have a surface temperature equal to the temperature of the root, and the rate of
heat transfer from the fin would be given by:
2.12
mkLbθ0 tanh( ml )
ηfin = (2.52)
α 2 Llθ0
2α
Remembering that m = , we can write equation 2.52 as:
kb
tanh( ml )
ηfin = (2.53)
ml
If fouling occurs the fouling resistance should be taken into account when evaluating
the heat transfer coefficient used in determining m. i.e.
1 1
= + rf (2.54)
α′ α
It is implicit in the above analysis that the tip of the fin is adiabatic. This
approximation holds if the tip of the fin is not insulated or if it butts on to the tip of
an adjacent fin. However, if there is heat transfer from the tip of the fin then this
may be taken into account by correcting the length of the fin by adding 1/2b, i.e.
lc=l+1/2b. The corrected length may then be used in both the evaluation of fin
efficiency and fin area.
Expressions, often presented in graphical form, are available for the fin efficiency of
many shapes of fin. Examples are given in Figures 2.4 and 2.5.
( )i
Q& = −α′i m fin ,c& x fin area + unfinned area (Ti − Twi )
T − Two
Q& = − wi (2.55)
rw
(
Q& = −α′o m fin ,o x fin area + unfinned area )o (Two − To )
2.13
which may be rearranged to give:
(Ti − To ) 1 1
− = + rw +
Q& (
α ′i η fin x fin area + unfinned area )i (
α ′o η fin x fin area + unfinned area )o
(2.56)
or
1
Q& = (Ti − To )
1 1
+ rw +
(
α ′i η fin x fin area + unfinned area )i (
α ′o η fin x fin area + unfinned area )o
(2.57)
so
−1
⎛ 1 1 ⎞
UA ≡ ⎜ + rw + ⎟
⎝
(
⎜ α ′i η fin x fin area + unfinned area
i
) (
α ′o η fin x fin area + unfinned area )o ⎟
⎠
(2.58)
In applications where fins are employed, it is likely that the purpose is to increase
heat transfer (or reduce temperature difference) It is therefore desirable to make
each term on the right hand side of equation 2.58 small. Normally rw is the smallest
of the terms and, for calculation purposes, may often be neglected. It is more
effective to reduce the larger of the two remaining resistances, especially if they
differ significantly. Therefore, if finning is to be applied to one surface only, it should
be applied to the side with the lower heat transfer coefficient (unless fouling,
corrosion or other considerations render this impracticable). This is clearly seen in
liquid to gas heat exchangers where it is common for the liquid (or evaporating or
condensing fluid) flows inside tubes which are externally finned.
2.14
Figure 2.4 Efficiency of Radial Fins - constant cross section (SI units with l,b in meters)
Figure 2.5 Efficiency of Axial Fins (SI units with l,b meters)
2.15
2.3 Convective heat transfer
We have already applied the relationship:
(
Q& = −αA∆t ≡ −αA T fluid − Twall ) (2.3)
to determine the rate of heat transfer from a surface of area A and at temperature
Twall to a fluid at temperature Tfluid. Representative values of the heat transfer
coefficient, α, may be used in preliminary designs, but it is important that we should
be able to estimate values of α for a particular geometry and flow conditions with
some accuracy if we are to have confidence in a heat transfer calculation, whether it
be a heat exchanger design or calculation of a component temperature. There are
few conditions for which analytical solutions for α are available, and these are not
often encountered in engineering situations. It is therefore usually necessary to rely
upon empirical correlations in the determination of convective heat transfer
coefficients.
Empirical correlations are based upon experimental observations. While the form of
the correlations may have some theoretical or conceptual justification, their accuracy
relies upon the reliability of the experimental observations and the similarity of the
experimental conditions and those to which the correlation is to be applied. It is
obvious that correlations are geometry dependent (e.g. applying to flow inside tubes,
crossflow outside tubes or over flat plates) There are other, less obvious
2.16
transitions, the most important being between laminar and turbulent flow and the
occurrence or otherwise of a phase change. From the designer’s point of view it is
essential that an appropriate correlation is applied, use of a correlation
outside the range of conditions for which it has been experimentally verified is very
dangerous.
2.17
2.3.1 Dimensionless groups and units
Quantity Symbol(s) Dimensions SI Units
Length L,x L m
Time t t s
Mass M M kg
Temperature T,t,θ T K
Absolute Viscosity µ ML-1t-1 kg/ms
Acceleration a Lt-2 m/s2
Coefficient of Expansion β T-1 K-1
Density ρ ML-3 kg/m3
Enthalpy H ML2t-2 J
-2
Force F MLt N
Heat Q ML2t-2 J
-2
Heat Flux q& Mt W/m2
2.18
phase heat transfer. The student should verify that the groups below are indeed
dimensionless. It is possible to devise other groupings by combining the common
groups.
Dimensionless Groups
8τ o
Darcy friction factor f = = 4c f (2.59(a))
ρV 2
τo f
Fanning skin friction coefficient cf = 2 = (2.59(b))
1
2 ρV 4
2
Colburn j factor jh = St Pr 3
(2.59(c))
gβ∆TL3
Grashof Number Gr = (2.59(d))
ν2
αd e
Nusselt Number Nu = (2.59(e))
k fluid
µcp
Prandtl Number Pr = (2.59(f))
k fluid
Rayleigh Number Ra = GrPr (2.59(g))
ρVd e Vde Gd e
Reynolds Number Re = = = (2.59(h))
µ ν µ
q& α Nu
Stanton Number St = = = (2.59(i))
ρVc p ∆T ρVc p RePr
In evaluating the above groups there is often some ambiguity in the choice of values
which must be resolved. The physical dimension for flow over plates is generally
taken as the distance along the plate, for flow in or around ducts it is the hydraulic
or equivalent diameter defined:
4 x Cross sectional area
de = (2.60)
Wetted Perimeter
4π d 2 4
de = =d (2.61(a))
πd
For a square duct, side length x,
2.19
4x2
de = =x (2.61(b))
4x
For flow through an annulus having inner and outer diameters d1 and d2, respectively
the hydraulic diameter may be calculated:
4π (d 22 − d12 ) 4 4π (d 2 − d1 )(d 2 + d1 ) 4
de = = = ( d 2 − d1 ) (2.61(d))
π ( d 2 + d1 ) π ( d 2 + d1 )
2.20
convection. We will therefore concentrate on forced convection, however, for
completeness some correlations which may be used to determine free convection
heat transfer coefficients are briefly discussed. Whether the flow is induced by
natural convection or forced it can be described as either laminar or turbulent.
Similarly, in laminar fluid flow there is no mixing of the fluid and the fluid can be
regarded as a series of layers sliding past each other. If the flow is laminar a thin
filament of dye inserted in the fluid will remain as a thin filament as it follows the
flow.
2.21
Free stream
velocity
Plate
v
where τ is the shear stress. At the wall, the velocity of the fluid must be zero, and
the wall shear stress is given by:
⎛ dv ⎞
τ w = µ⎜ ⎟ (2.65)
⎝ dy ⎠ w
The kinematic viscosity of a fluid is defined:
µ
ν= (2.66)
ρ
(Be careful not to confuse ν and v!! )
In practice, laminar flow is observed at low speeds, in small tubes or channels, with
highly viscous fluids and very close to solid walls.
If the fluid layers seen in laminar flow break up and fluid mixes between the layers
then the flow is said to be turbulent. The turbulent mixing of fluid perpendicular to
the flow direction leads to a more effective transfer of momentum and internal
energy between the wall and the bulk of the fluid. Turbulent flow is the more
common regime for bulk flow in most heat transfer equipment, but laminar flow is
2.22
encountered in highly compact heat exchangers and those handling very viscous
fluids. Even when the bulk of the flow is turbulent a very thin laminar layer exists
close to the wall, this is important when considering processes close to the wall.
It should come as no surprise to the student that the heat transfer characteristics of
laminar and turbulent flows are very different. In forced convection the magnitude of
the Reynolds number provides an indication of whether the flow is likely to be
laminar or turbulent:
For flow over a flat plate, as shown in Fig 2.8 we may determine whether the flow in
the boundary layer is likely to be laminar or turbulent by applying the following
conditions:
⎛ ρV ∞ x ⎞
Re x ⎜ = ⎟ < 10 Laminar flow
5
⎝ µ ⎠
(2.67)
⎛ ρV ∞ x ⎞
Re x ⎜ = ⎟ > 10 Turbulent flow
6
⎝ µ ⎠
where x is the distance from the leading edge of the plate.
V∞
For values of Reynolds number between 105 and 106 the situation is complicated by
two factors. Firstly, the transition is not sharp, it occurs over a finite length of plate.
In the transition region the flow may intermittently take on turbulent and laminar
characteristics. Secondly, the position of the transition zone depends not only upon
the Reynolds number, it is also influenced by the nature of the flow in the free
2.23
stream and the nature of the surface. Surface roughness or protuberances on the
surface tend to trip the boundary layer from laminar to turbulent.
For flow in pipes, channels or ducts the situation is similar to that for a flat plate in
the entry region, but in long channels the boundary layers from all walls meet and
fully developed temperature and velocity profiles are established.
For fully developed flow in pipes or channels the transition from laminar to turbulent
flow occurs at a Reynolds number, based on the channel hydraulic diameter of
approximately 2000. As with the boundary layer on a flat plate, the transition may
occur at higher or lower values of Red. If the flow at entry to the channel contains no
turbulence and the channel is very smooth, laminar flow may be sustained up to
Reynolds numbers of 5-10000. Turbulence may occur at values of Red as low as 1000
but at low Reynolds numbers may decay if induced by, for example, sharp corners.
As we shall see, heat transfer coefficients are generally higher in turbulent flow than
in laminar flow, and higher in the entry region than in the fully developed region.
Heat exchanger designers may therefore incorporate features which either promote
turbulence or lead to a geometry which approximates to many short channels. The
velocity distribution and variation in local heat transfer coefficient observed at entry
to a tube at Red>>2000 is illustrated in Fig. 2.9.
2.24
Figure 2.9 Velocity distribution and variation of local heat transfer
coefficient for turbulent flow near the entrance of a uniformly heated tube
Three values of Nusselt number are given for each geometry, the appropriate value
depending upon the boundary conditions. These are:
• Nu H 1 =Average Nusselt no. for uniform heat flux in flow direction and
uniform wall temperature around perimeter at any cross section
• Nu H 2 =Average Nusselt no. for uniform heat flux both axially and
around the perimeter
• NuT = Average Nusselt no. for uniform wall temperature.
also tabulated are values of the product fRed.
1
The term ducts here encompasses tubes and channels
2.25
Table 2.2 Nusselt number and friction factor for fully developed flow in ducts
2.26
Table 2.3 gives values of the Nusselt number for heat transfer to or from laminar
flow in an annulus with one wall insulated (adiabatic) and the other is maintained at
constant temperature.
Table 2.3 Nusselt number and friction factor for fully developed flow in annuli
Nu ⎛ x dh ⎞
= f ⎜⎜ ⎟⎟
Nu fully developed ⎝ Re dh Pr ⎠
or
Nu x ⎛ x dh ⎞
= f ⎜⎜ ⎟⎟
Nu fully developed ⎝ Re dh Pr ⎠
where Nu is the mean Nusselt number from duct entry to a position x along the
duct and Nux is the local Nusselt number at a distance x from the entry.
Nufully developed is the Nusselt number for fully developed flow for the corresponding
boundary conditions. An example of entrance length effect is given in 2.10.
2.27
Figure 2.10 Ratio of mean Nusselt number from entry to x to fully
developed Nusselt number ( constant temperature wall)
The thermal entry lengths, Le, for the simultaneously developing hydroynamic and
thermal profiles in laminar flow are given by:
Le
≈ 0.037 Redh Pr (Uniform surface temperature)
dh
(2.67)
Le
≈ 0.053 Redh Pr (Uniform heat flux)
dh
For example, the heat transfer coefficient in single-phase turbulent flow is commonly
determined from the Dittus-Boelter equation:
2.28
Nu = 0.023 Re 0.8 Pr n (2.68)
with properties evaluated at the bulk or mean bulk fluid temperature. This gives
results for Nu within 20% for uniform wall temperature and uniform wall thickness
conditions within the following ranges.
A modification to equation 2.68, taking into account the change in viscosity with
temperature in the thermal boundary layer is:
0.14
⎛ µ⎞
Nu = 0.027 Re Pr ⎜ ⎟
0.8 n
(2.69)
⎝ µs ⎠
If evaluating local Nusselt number then the bulk fluid temperature is equal to the
local bulk temperature, i.e. the temperature which would be measured if the fluid at
that station were to be fully mixed. If evaluating the mean Nusselt number over a
length of tube the mean bulk temperature is given by:
Tm,in + Tm,out
Tm = (2.70)
2
Reynolds Analogy
Let us consider a turbulent flow past a wall as shown in Fig. 2.9
Free stream at V, Tf
m
Wall at Tw 2.29
Assume that in unit time, over an area A, a mass m, of fluid moves from the free
stream to the wall and a corresponding mass moves away from the wall. Assuming
that the fluid at the wall is stationary and reaches thermal equilibrium with the wall
we can say:
Transfer of momentum from the fluid to the wall in flow direction = m(V − 0)
(
Transfer of heat from the wall to the fluid = − mcp Tf − Tw )
Remembering that
force = rate of change of momentum
and the shear stress on the wall is equal to the force exerted by the fluid in the flow
direction per unit area:
(
Rearranging and putting ∆T = Tw − Tf )
q& c pτ w
α= = (2.72)
∆T V
showing that the heat transfer coefficient and wall shear stress are closely related. In
dimensionless form we can write equation 2.72 as:
α 1 τw
= (2.72)
ρVc p 2 21 ρV 2
2.30
We will discuss the pressure drop through ducts pipes and fittings in Section 4, but
at this stage it is worth noting that a force balance on a length, L, of circular pipe as
shown in Fig. 2.12 gives:
(p1 − p2 ) Ac = τ w As (2.74)
p1 p2
Ac τw Vm
Vm
Substituting expressions for the cross sectional area, Ac, the surface area, As, and the
wall shear stress from equation 2.59(b)
π D2 1
∆p = ρ Vm2 c f π DL
4 2
(2.75)
2 ρ Vm c f L
2
∆p =
D
Thus, if the heat transfer coefficient and wall shear stress are related, the pressure
drop and heat transfer coefficient are also closely linked.
For turbulent flow in smooth pipes with Reynolds Number up to 105 the Blasius
equation, equation 2.76, gives reasonable results for friction factor, cf, gives:
c f = 0.079 Re0.25 (2.76)
which, for Pr=1 gives very similar results to the Dittus Boelter equation. This is
illustrated in Fig.2.11 which shows calculated values of Nusselt number using Dittus
Boelter equation and the combination of Reynolds analogy and the Blasius equation
as presented in equation 2.77. The Nusselt number for laminar flow with constant
heat flux is also included on Fig. 2.13. It is clear that, for a given Reynolds number the
2.31
value of estimated Nusselt number differs significantly depending whether the flow is
assumed to be turbulent or laminar. This confirms the importance of ensuring that
the appropriate flow type is identified. It also shows that heat transfer enhancement
may be achieved for Reynolds numbers from c1000 to the transition region by
“tripping” the flow to induce turbulence.
The Prandtl Number is the ratio of molecular momentum diffusivity to the thermal
diffusivity of a fluid. It is therefore to be expected that Reynolds Analogy is only valid
for Pr ≈1, since the derivation implied equal momentum and thermal diffusivity.
Alternative correlations
While the Dittus Boelter correlation is widely used, its accuracy is limited. A more
complex (and thus more awkward to use!) correlation is that due to Gnielinsky, this
is regarded as having an accuracy within 6%. With all properties evaluated at the
mean bulk temperature:
( f 8)( Re − 1000) Pr ⎡⎢ ⎛ d ⎞
dh h
2
3 ⎤
⎥
Nu = 1+ ⎜ ⎟
1 + 12.7( f 8) ( Pr − 1) ⎣
dh 1
2
⎢ ⎝ L⎠
2
⎥⎦
3
(2.78)
f = (0.79 ln Re − 164. )
−2
dh
⎡ ⎛d ⎞ 3⎤
2
Nu dh = 0.0214( Re 0.8
− 100) Pr 0. 4
⎢1 + ⎜ h ⎟ ⎥ (2.79(b))
⎢⎣ ⎝ L ⎠ ⎥⎦
dh
⎡ ⎛d ⎞ 3⎤
2
Nu dh = 0.012( Re 0.87
− 280) Pr 0 .4
⎢1 + ⎜ h ⎟ ⎥ (2.79(c))
⎢⎣ ⎝ L ⎠ ⎥⎦
dh
Equations 2.78 and 2.79 give mean Nusselt numbers over the length of the tube. If
applied to fully developed conditions local Nusselt numbers may be obtained by
2.32
dh
setting to zero. Gnielinsky recommended that a further correction may be
L
included to take into account property variations due to temperature. The Nusselt
no calculated using equation 2.78 or 2.79 above should be multiplied by:
0.45 0.11
⎛ Tb ⎞ ⎛ Pr ⎞
⎜ ⎟ for gases or ⎜ b ⎟ for liquids.
⎝ Ts ⎠ ⎝ Prs ⎠
The Gnielinsky correlation was derived for uniform wall temperature, but gives good
results for uniform heat flux conditions. An alternative correlation, based on data for
uniform heat flux was proposed by Pethukov for fully developed flow:
Nu =
( f 8) Re Pr dh ⎛ µ⎞
⎜ ⎟
n
. + 12.7( f 8) ( Pr )
− 1 ⎝ µs ⎠
dh 1
2 2
107 3
(2.80)
f = (0.79 ln Re − 164
. )
−2
dh
Pethukov’s correlation applies when all properties (except µs ) are evaluated at the
bulk temperature and values of the constants used are:
The Dittus Boelter, Gnielinsky and Pethukov correlations apply to a wide range of
fluids, but are inappropriate for liquid metals (Pr<0.1).
2.33
Forced convection over cylinders, rods and tube banks
The boundary layer observed when a fluid flows over a cylinder or rod cannot be
uniquely described as laminar or turbulent. The boundary layer itself is laminar at the
front of the cylinder and, depending upon the Reynolds number, may become
turbulent. Additionally, at all but the lowest Reynolds numbers, the boundary layer
separates from the surface of the cylinder at some point and a wake is formed. The
wake may be laminar or turbulent.
The value of n in equation 2.81 is 0.33. Properties are evaluated at the mean film
temperature Values of c and m are tabulated in Table 2.4
Red c m
4-35 0.895 0.384
35-5000 0.657 0.471
5000-50,000 0.167 0.633
50,000-230,000 0.0234 0.814
It is recommended that the use of equation 2.81 and the constants of Table 2.4 be
restricted to the range 0.5<Pr<10.
For long bars of non cross circular cross section, equation 2.81 may be used with the
characteristic dimension and constants listed in Table 2.5
A correlation based on a wider range of data and valid for RedPr>0.2 and with
properties evaluated at the mean film temperature is:
Red>400.000
2.34
4
Nu d = 0.3 + 1 ⎢1 + ⎜ ⎟ ⎥ (2.82(a))
4 ⎢ ⎝ 282000⎠ ⎥
⎢⎣1 + ( 0.4 Pr ) ⎥⎦
⎡ 3⎤
2
⎣ ⎦
20,000<Red<400,000
0.62 Red2 Pr 3 ⎡ ⎛ Re d ⎞ 2 ⎤
1 1 1
Nu d = 0.3 + 1 ⎢1 + ⎜ ⎟ ⎥ (2.82(b))
⎡1 + (0.4 Pr ) 3 ⎤ 4 ⎢⎣ ⎝ 282000 ⎠ ⎥⎦
2
⎣⎢ ⎦⎥
Red<20,000
1 1
0.62 Red2 Pr 3
Nu d = 0.3 + 1 (2.82(c))
⎡1 + (0.4 Pr ) 3 ⎤ 4
2
⎣⎢ ⎥⎦
Heat exchangers rarely comprise single tubes in crossflow, they usually incorporate
tube banks and the flow differs from that around a single tube in two ways:
• The velocity between the tubes is greater than the free stream velocity
• The flow field on a tube row is influenced by the presence of upstream row(s)
Tube banks may be in-line or staggered, as shown in Fig.2.14 (a) and (b) respectively.
2.35
Column
V∞,T∞
ST
Row
SL
(a) in line
Column
V∞,T∞
Y
X
d
SD
ST
Row
SL
(b) staggered
2.36
Red c m n
10-100 0.9 0.4 0.36
100-1000 0.52 0.5 0.36
1000-200,000 0.27 0.63 0.36
200,000-2,000,000 0.033 0.8 0.4
(a) in line arrangement
Red c m n
10-500 1.04 0.4 0.36
500-1000 0.71 0.5 0.36
1000-200,000 0.35 0.63 0.36
200,000-2,000,000 0.031 0.8 0.36
(b)staggered arrangement
For in line tube banks the maximum velocity may be calculated by considering
conservation of mass, assuming incompressible flow:
V∞ ST
Vmax = (2.84a)
ST − d
For staggered tube banks the maximum velocity may occur either between adjacent
tubes in a row or between one tube and a neighbouring tube in the succeeding row,
i.e. through the planes X or Y marked on fig. (b). Conservation of mass, assuming
incompressible flow, gives:
V∞ ST = VX ( ST − d ) = 2VY ( S D − d ) (2.84b)
Equation 2.83 is valid for 16 or more tube rows. For N rows, where N is less than
16, the mean Nusselt number should be reduced by a factor c1.
NuN
= c1 (2.85)
Nu16
2.37
where c1 is given in Fig . 2.15.
Complex Geometries
For complex geometries it is unlikely that an appropriate correlation is available.
Experimental data for a number of configurations typical of those used in compact
heat exchangers has been published by Kays and London2. If new geometries are to
be developed it is likely that experimental measurements will be required to produce
a correlation. Manufacturers may publish such data, or they may be proprietary.
Sample figures from Kays and London are given as Figs 2.16(a)-(f) - unfortunately,
the data are in American units.
2
Kays W.M.and London A.L.,Compact heat exchangers, McGraw-Hill, 2nd Edition, 1964
2.38
f/4
Figure 2.16 (a) Heat transfer and friction factor for Plain plate-
fin surface 9.03 (h=heat transfer coefficient)
f/4
Figure 2.16 (b) Heat transfer and friction factor for Plain plate-
fin surface 11.1 (h=heat transfer coefficient)
2.39
f/4
Figure 2.16 (c) Heat transfer and friction factor for Plain plate-
fin surface 5.3 (h=heat transfer coefficient)
f/4
Figure 2.16 (d) Heat transfer and friction factor for Plain plate-
fin surface 6.2 (h=heat transfer coefficient)
2.40
f/4
Figure 2.16 (e) Heat transfer and friction factor for finned
circular tubes, surface CF-7.34 (h=heat transfer coefficient)
2.41
2.4 Boiling and Evaporation
2.4.1 Introduction.
Many heat transfer applications involve the evaporation of a liquid. Boiling of a single
substance is a vital part of vapour power and refrigeration cycles. If we are to design
boilers or evaporators we must be able to determine the relationship between the
rate of boiling heat transfer, operating conditions and wall temperature for our heat
exchanger. In this introductory study. This introductory note is limited to the case of
boiling single fluids, but it should be remembered that evaporation occurs frequently
as part of a separation process, in which case the vapour formed has a different
composition from the boiling liquid
While the terms "boiling" and "evaporation" are used loosely to describe the action
of converting a liquid to a vapour by the transfer of energy to the liquid at its
saturation temperature it is necessary to be more precise when describing the
mechanisms involved. Boiling is the addition of heat causing liquid to evaporate and
the vapour to flow away from the heated surface. Evaporation is the conversion of
liquid to vapour which occurs at the liquid vapour interface.
These are analogous to free and forced convection. Boiling outside tube bundles, for
example in a fire-tube boiler, combines elements of both situations- a recirculating
flow is induced through the bundle due to the vapour generation.
2.42
Nucleate Boiling- This involves the formation and growth of bubbles, usually on the
heated surface, the bubbles then leave the heated surface and rise to the surface of
the liquid. Fig.1 illustrates nucleate and film boiling.
Convective Boiling - This mechanism, sometimes referred to as evaporation,
involves transfer of heat from the heated surface through a thin layer of liquid and
evaporation of liquid at the liquid vapour interface.
Film Boiling- This mechanism occurs when the heated surface is blanketed by a film
of vapour, heat transfer is then by conduction through the vapour layer and
evaporation occurs from the liquid in contact with this liquid film.
Fig 2.17 illustrates nucleate and film boiling.
The mechanisms involved in boiling are complex and the relationships used in
design and analysis are almost all empirical or semi-empirical, however, in
formulating and using empirical correlations it is necessary to have an understanding
of the underlying processes.
2.43
Condenser
Vapour
Liquid
Heated Cylinder
(or flat surface)
Since we have a liquid and vapour coexisting in the cylinder both must be at (or
during boiling, very close to,) the saturation temperature of the fluid at the pressure
in the container. If we measure the surface temperature of the heater, T, the
temperature of the fluid, Tsat, the rate of energy supply to the heater, Q& , and the
heater surface area, A, we may carry out a series of tests and plot a graph of log Q& ,
or more usually log q& = log(Q& A) against log ∆Tsat , where ∆Tsat = (T − Tsat ) , often
referred to as the wall superheat.
As the heat flux, q& , is increased while keeping the temperature of the fluid constant,
we would expect the temperature of the rod to increase. The designer of heat
transfer apparatus must be able to determine the relationship between heat flux and
temperature difference.
The relationship between heat flux and wall superheat for a typical fluid is shown
schematically in fig. 2.19.
2.44
H
log( q& ) E
D F
G*
G
C
B
A
B*
log( ∆Tsat )
For the case of controlled heat flux (for example, electric heating) the various
regimes may be described:
For increasing heat flux, in the region 'A'-'B' heat transfer from the heater surface is
purely by single-phase natural convection. Superheated liquid rises to the surface of
the reservoir and evaporation takes place at this surface. As the heat flux is
increased beyond the value at 'B' bubbles begin to form on the surface of the heater,
depart from the heater surface and rise through the liquid this process is referred to
as nucleate boiling. At this stage a reduction of heater surface temperature to 'C'
may be observed. Reducing the heat flux would now result in the heat flux
temperature difference relationship following the curve 'C'-'B*'. This type of
phenomenon, for which the relationship between a dependent and independent
variable is different for increasing and decreasing values of the independent variable,
is known as hysterisis.
After the commencement of nucleate boiling further increase in heat flux leads to
increased heater surface temperature to point 'D'. Further increase beyond the value
2.45
at 'D' leads to vapour generation at such a rate that it impedes the flow of liquid
back to the surface and transition boiling occurs between 'D' and 'E'. At 'E' a stable
vapour film forms over the surface of the heater and this has the effect of an
insulating layer on the heater resulting in a rapid increase in temperature from: 'E' to
'F'. The heat flux at 'E' is known as the critical heat flux. The large temperature
increase which occurs if an attempt is made to maintain the heat flux above the level
of the critical heat flux is frequently referred to as burn-out. However, if physical
burn out does not occur it is possible to maintain boiling at point 'F' and then adjust
the heat flux, the heat flux temperature difference relationship will then follow the
line 'G'-'H'. This region on the boiling curve corresponds to the stable film boiling
regime. Reduction of the heat flux below the value at 'G' causes a return to the
nucleate boiling regime at 'G*'.
The factors which influence the shape of the boiling curve for a particular fluid
include: Fluid properties, heated surface characteristics and physical dimensions and
orientation of the heater. The previous history of the system also influences the
behaviour, particularly at low heat flux.
Clearly several relationships, defining both the extent of each region and the
appropriate shape of the curve for that region, would be required to describe the
entire curve. It is the nucleate boiling region, 'C'-'D' which is of greatest importance
in most engineering applications. However, it is clearly important that the designer
ensures that the critical heat flux is not inadvertantly exceeded, and there are some
systems which operate in the film boiling regime. Many correlations describing each
region of the boiling curve have been published. Additionally, the temperature
difference at which nucleation first occurs, i.e. the temperature at 'C' influences the
boiling regime during flow boiling and the hysterisis.
If the temperature of the heater, rather than the heat flux, was to be controlled then
increasing temperature above that corresponding to the critical heat flux would
result in a decrease in heat flux with increasing temperature from ‘E’ to ‘G’, followed
by an increase along the line G-H. The point ‘G’ is sometimes referred to as the
Liedenfrost Point. Temperature controlled heating of a surface is found in many heat
exchangers and boilers - the temperature of the wall being necessarily below the
2.46
temperature of the other fluid in the heat exchanger. Experimentally, it is difficult to
maintain surface temperatures over a wide range with the corresponding range of
heat fluxes. To obtain boiling curves for varying ∆Tsat it is usual to plunge an ingot of
high conductivity material into a bath of the relevant fluid. The surface temperature
is measured directly and the heat flux can then be calculated from the geometry of
the ingot and the rate of change of temperature.
The explanation for the importance of surface finish lies in the mechanism of bubble
formation. Observation of boiling is difficult because of the vigour with which the
process occurs, high speed photographic or video techniques are necessary to get
anything more than an approximate qualitative overview. However, even this can
give us some insight into the process. Observation of the formation of bubbles in a
carbonated drink in a glass can also be instructive, the following experiment works
best with carbonated mineral water but other drinks can be used. Pour the drink
onto a glass and observe the bubbles. You will note that, once any initial “froth” has
dispersed:
i. Bubbles are formed at the surface of the glass3
ii. Bubbles rise in a chain originating from the same point on the surface.
iii. If the glass is emptied and refilled many of the sites where bubbles form will
correspond to those observed during the first attempt.
This suggests that some feature of the surface encourages bubble nucleation. It has
been observed that nucleation occurs in cavities within the surface, these cavities
contain minute bubbles of trapped gas or vapour which act as starting points for
bubble growth. This is illustrated schematically in Fig. 2.20. When the bubble leaves
the site a small bubble remains in the cavity which acts as the start for the next
bubble.
3
Any bubbles which arise from a point within the bulk of the liquid almost certainly originate at a solid
impurity, for example dust or a particle of organic matter.
2.47
Trapped bubbles
of gas or vapour
Liquid
Surface
Liquid Growing
Bubble
2R
The pressure, pB, inside a bubble is somewhat higher than the pressure in the
surrounding liquid:
2σ
pB = p + (2.86)
r
Where p is the liquid pressure, r is the radius of curvature of the bubble and σ is the
surface tension of the liquid. The radius of curvature is a maximum when the bubble
forms a hemispherical cap over the cavity, i.e. r=R, the radius of the mouth of the
2.48
cavity. This is the condition for pB to be a maximum. If the bubble is to grow then
the wall temperature must be sufficiently high to vapourise the liquid at a pressure pB.
The Clausius-Clapeyron Equation states that the slope of the vapour pressure curve
is given by:
dp h fg
= (2.88)
dT (
vg − v f Tsat )
if vg is very much greater than vf we can simplify this:
dT vg Tsat
= (2.89)
dp h fg
Hence, for the bubble to grow:
2σ vg Tsat
TW > Tsat + (2.90)
Rp h fg
The radius of the cavity and the superheat, ∆T sat , at which nucleation from the
cavity starts can be related:
2σvg Tsat
R= (2.91)
h fg ∆T sat
For water boiling at 1bar ∆T sat is commonly of the order of 5K. Substitution of
values for the properties of water gives a value for the smallest active cavity to be
approximately 6.5 x 10-6m radius. This demonstrates that typical active cavities are of
the order of 1-10µm.
Clearly, real surfaces have a range of cavities of varying size and shape. Surfaces
which are designed to improve boiling heat transfer (enhanced surfaces) are made to
have large numbers of suitable cavities.
2.49
Some useful pool boiling correlations
The symbols used are:
α Heat transfer coefficient W/m2K g acceleration due to gravity m/s2
σ Surface tension N/m Gr Grashof Number
It can be argued that the heat transfer coefficient, defined by α = q& ∆Tsat , is of
limited use when it is not constant, but varies with heat flux (or temperature
difference). However many correlations are given in terms of heat transfer
coefficient.
Where C and m depend on the geometry and whether the induced flow is laminar
or turbulent
Rohsenow (1952)
This is essentially an empirical correlation, but it is instructive to see the way in
which it was derived.
2.50
complicated by the dependence of the heat transfer on the condition and history of
the surface.
It has already been noted that experimental results for nucleate boiling may be
represented by an equation of the form:
q& = a∆Tsat m
This may be rearranged in terms of a heat transfer coefficient, α,
q& (3.93 (b))
α= = a∆Tsatm −1
∆Tsat
m −1
(3.93 (c))
α = bq& m
≡ bq& n
the value of m is generally in the range 3 - 2.33, corresponding to n being in the
range 0.67- 0.7.
An early nucleate boiling correlation is that due to Rohsenow, following the example
of turbulent forced convective heat transfer correlations Rohsenow argued that:
Nu= f(Re,Pr)
αL
Nu =
k
ρUL
Re = (U = Velocity)
µ
µc p
Pr =
k
If the fluid properties are all those for the liquid this still left the problem of choosing
a suitable velocity and representative length, L.
The velocity may be taken as the velocity with which the liquid flows towards the
surface to replace that which has been vapourised:
q&
U = (2.94)
ρ f h fg
and the representative length is given by:
0.5
⎡ σ ⎤
L=⎢ ⎥
⎣⎢ g (ρ f − ρ g )⎦⎥
(2.95)
2.51
The correlation thus produced was:
1
Nu = Re 1− x Pr − y (2.96)
Csf
Which is frequently presented in the form:
x
c pf ∆Tsat ⎡ q& ⎛ σ ⎞
0.5
⎤ ⎡ µ f c pf ⎤
1+ y
= Csf ⎢ ⎜ ⎟ ⎥ ⎢ ⎥
⎜ g (ρ − ρ ) ⎟
(2.97(a))
h fg ⎢ µ f h fg ⎝ ⎠ ⎥ ⎢⎣ k f ⎥⎦
⎣ f g
⎦
For most fluids the recommended values of the exponents were: x=0.33, y=0.7.
This correlation then corresponds to:
q = [Constant depending upon fluid properties and surface] x ∆T 3
( ) ⎞⎟
0.5
⎛g ρ −ρ ⎛ c pf ∆Tsat ⎞
3
q& = µ f h fg ⎜
f g
⎜ ⎟ (2.97(c))
⎜ σ ⎟ ⎜⎝ Csf h fg Pr n ⎟⎠
⎝ ⎠
The value of the constant Csf depends upon the fluid and the surface and typical
values range between 0.0025 and 0.015. Since, for a given value of ∆Tsat the heat flux
is proportional to Csf3 the correlation is very sensitive to selection of the correct
value.
It is arguable that the complexity of the correlation is not warranted because of the
need for this factor.
2.52
Some values of Csf for use in Equation 2.97 and are given in the table below.
Fluid Surface Csf
Water Nickel 0.006
Water Platinum 0.013
Water Copper 0.013
Water Brass 0.006
Carbon Tetrachloride Copper 0.013
Benzene Chromium 0.010
n-Penthane Chromium 0.015
Ethanol Chromium 0.0027
Isopropanol Copper 0.0025
n-Butanol Copper 0.0030
Mostinski (1963)
α = 0106
. pcr0.69 (18
. pr0.17 + 4 pr1.2 + 10 pr10 )q& 0.7 (2.100)
Cooper (1980)
α = 55 pr0.12 ( − log pr )
−0.55
M −0.5 q& 0.67 (2.101(b))
Mostinski and Cooper are both dimensional equations, therefore the units must be
consistent with the constants given. For the forms quoted here pressures are in bar
and heat flux in W/m2, giving heat transfer coefficients in W/m2K.
2.53
Critical Heat Flux:
Kutateladze (1963) & Lienhard et al (1970,1973)
( ( ))
0.25
CHF = q& max = Cρ g0.5 h fg σg ρ f − ρ g
( (
C = 0.13 0.89 + 2.27 exp − 3.44 R Lb ))
0.5
⎛ σ ⎞
Lb = ⎜ ⎟
⎜ g (ρ − ρ ) ⎟
⎝ f v ⎠
( )
0.25
⎡ ρ ρ − ρ gh * d 3 ⎤
Nuv = c ⎢ ⎥
v f g fg
(2.103)
⎢ k g µ g ( ∆Tsat ) ⎥
⎣ ⎦
c=0.62 for cylinders and 0.67 for spheres. Liquid properties are evaluated at the
saturation temperature and the vapour properties at the average of the surface
temperature, Ts, and the liquid saturation temperature, Tsat. The corrected enthalpy
of vapourisation is calculated from:
h *fg = h fg + 0.4c pg ∆Tsat (2.104)
( )
0.25
3 ⎤
⎡ ρv ρ f − ρg gh *fg d rep
Nuv = 0.425⎢ ⎥ (2.105)
⎢ k g µ g ( ∆Tsat ) ⎥
⎣ ⎦
may be used, where the Nusselt Number is based on the representative dimension
drep, defined by:
0.5
⎡ ⎤
σ
d rep =⎢ ⎥
( )
(2.106)
⎢g ρ − ρ ⎥
⎣ f g ⎦
2.54
The situation is further complicated in film boiling because of the high surface
temperatures which may be involved. The radiative heat transferred can be
calculated from:
(
q& rad = σ SB ε r Ts4 − Tsat
4
) (2.107)
where σSB is the Stefan Boltzman constant = 56.7 × 10−9 W / m 2 k 4 and ε r is the
Film boiling is rarely encountered in heat exchangers, the designer usually wants to
ensure that there is no risk of exceeding the internal hear flux within the exchanger.
This is particularly important when reduction in the heat transfer results in an
increase in temperature of the heating medium. Exceeding the critical heat flux in
these circumstances results in a rapid temperature increase, or burnout.
The prediction of heat transfer coefficients in flow boiling is even more difficult (and
often less reliable!) than in pool boiling. In addition to the influence of heat flux (or
temperature difference), fluid and surface properties and geometry we must also
consider the flow velocity and the quality of the fluid.
2.55
Fig 2.22 Regions of convective boiling
Let us first consider the flow patterns and boiling regimes in a vertical tube heated
uniformly along its length. This is illustrated in Fig.2.22.
2.56
• Region F Involves single-phase convection to the vapour.
Flow in horizontal channels yields similar patterns, but the effects of gravity result in
stratification, particularly at low velocities. The resulting patterns are shown
schematically in Figure 2.23.
2.57
Figure 2.23 Flow patterns during boiling in a horixontal tube
As you would expect relationships are required for each of the flow regimes and
heat transfer regions. We will deal only with the annular flow regime which occurs
for vapour quality in excess of a few percent and is therefore the most prevalent
regime in practice. For example, in refrigeration evaporators which receive a vapour
liquid mixture from the expansion valve the flow will be entirely annular.
2.58
Figure 2.24 Variation in heat transfer coefficient Figure
with quality, heat flux and mass flux
In
fact the correlations which we will examine can be used with reasonable accuracy
for the complete range of saturated boiling. All flow boiling correlations are
empirical, but are based upon observations of the mechanisms involved as well as
heat transfer data. Heat transfer in flow boiling can be regarded as being due to one
or both of two mechanisms: namely nucleate boiling and convective boiling. In
general low quality and high heat flux favour nucleate boiling while high quality and
low heat flux lead to convective boiling. High mass flux is conducive to convective
boiling. Figure 2.24 illustrates the nucleate and convective boiling regions.
.
The way in which correlations account for the two mechanisms differ, some add the
contributions for each mechanism, some take only one contribution, and some
combine the contributions so that the effect of the larger is dominant. The general
form of these correlations is illustrated below and in figure 2.25. It must be
remembered that very high heat fluxes can lead to formation of a vapour film,
analogous to that encountered in pool boiling. The analysis presented here assumes
that the heat fluxes encountered are molecular.
2.59
Figure 2.25 Schematic illustration of Correlations
α conv = Fα L
Where the subscripts have the following meanings
nb nucleate boiling contribution
nbp predicted for pool boiling at the same temperature difference from Forster
and Zuber according to Chen)
conv convective boiling contribution
l predicted for the single phase flow of liquid (either all fluid flowing as liquid
or based on the liquid component only) (for Chen this is from Dittus Boelter with
liquid only Reynolds No.)
S and F are factors which are correlated against flow parameters
Enhancement or Substitution (e.g. Shah (1976) )
α = Eα l
E is an enhancement factor, the value of which is given by one of several expressions
depending upon the flow parameters and heat flux.
2.60
Asymtotic (e.g. Liu and Winterton (1988))
α 2 = αnb2 + αconv
2
Examination of Figs 2.22 and 2.25 and the form of typical boiling correlations shows
that the heat transfer coefficient during flow boiling varies significantly as the quality
goes from 0 (pure liquid) to 1 (dry vapour). If the vapour is then superheated there
will be a step change in heat transfer coefficient as the wall dries out. This means
that a stepwise approach must be taken in the design of flow boilers: The local film
heat transfer coefficients and overall heat transfer coefficient must be evaluated at
entry to the channel, the heat transferred over a short length of channel evaluated
thus permitting calculation of the increase in quality over the short length. This
process must be repeated over the length of the tube to determine the total heat
transferred. Clearly this is a very time consuming process and best carried out using
a computer package.
Correlations are available which can be used to give estimates of the mean heat
transfer over a range of vapour qualities, for example the Pierre (1964) correlation:
2.61
⎛ 2 ( x out − xin )∆h fg
n
k ⎞
α =C l ⎜⎜ Re L ⎟⎟ (2.111)
d ⎝ Tube Length ⎠
where C=0.0009 and n=0.5 for exit vapour quality up to 0.9 and C=0.0082
and n=0.4 for higher vapour qualities and exit superheat of up to 6K.
It should also be noted that the concepts of mean temperature difference and
effectiveness covered in Section 5 rely upon an assumption that the heat transfer
coefficient is constant over the entire heat exchanger area.
Finally, in many applications involving boiling, for example fired boilers, the boiling
side heat transfer coefficient is likely to be very much higher than the heat transfer
coefficient from the heating medium to the wall, hence variations in the boiling side
heat transfer coefficient have little influence on the overall heat transfer coefficient.
2.62
2.4.4 Condensation
Condensation involves the formation of a liquid from a vapour due to heat transfer
from the fluid or a change in pressure of the fluid. The various modes of
condensation which may be observed are illustrated in Figure 2.26.
2.63
Modes of condensation
• Filmwise condensation: The condensate forms a continuous film on the cooled
surface. This is the most important mode of condensation occurring in industrial
equipment and is discussed further below.
• Homogeneous condensation: The vapour condenses out as droplets suspended in
the gas phase, thus forming a fog. A necessary condition for this to occur is that the
vapour is below saturation temperature, which may be achieved (as illustrated) by
increasing the pressure as the vapour flows through a smooth expansion in flow
area. In condensers, however, it usually occurs when condensing high-molecular-
weight vapours in the presence of noncondensable gas. Fogs may also form when
cold gas is mixed with vapour, for example, during the mixing warm, humid air with
cold air.
• Dropwise condensation: This occurs when the condensate is formed as droplets
on a cooled surface instead of as a continuous film. High heat transfer coefficients
can be obtained with dropwise condensation, but this is difficult to maintain
continuously In heat exchangers.
• Direct contact condensation: This occurs where vapour is brought directly into
contact with a cold liquid.
• Condensation of vapour mixtures forming immiscible liquids: A typical example of
this is when a steam-hydrocarbon mixture is condensed. The pattern; formed by the
liquid phases are complicated and varied
Filmwise Condensation:
Filmwise condensation occurs when the condensate vapour forms a film on the
surface which runs down the surface, as shown in Fig. 2.27. The film will be laminar
(and amenable to analysis) at the top of the surface, as the film becomes thicker the
laminar flow is not stable and waves form in the film, lower down the surface the
film becomes turbulent. In many heat exchanger applications, it is satisfactory to
assume laminar flow. This gives a conservative estimate of the heat transfer, since
both waves and turbulence lead to an increase in the heat transfer coefficient.
2.64
Fig. 2.27 Schematic representation of filmwise
condensation on a vertical plate
Rogers and Mayhew (1980) present the analysis of filmwise condensation in the
laminar non-wavy region originally derived by Nusselt. This analysis is summarised
below.
The heat ransfer coefficient a distance x from the top of the plate may be calculated
from:
0.25
⎛ h'fg ρ 2f gx 3 ⎞
Nu x = ⎜ ⎟ (2.112)
⎜ 4µ f k f ∆Tsat ⎟
⎝ ⎠
The mean heat transfer coefficient from the top of the plate to some point l below
the top may be calculated from:
0.25
4 ⎛ h fg ρ f gl ⎞
' 2 3
Nu = ⎜⎜ ⎟
3 ⎝ 4 µ f k f ∆Tsat ⎟⎠
2.65
and, for a horizontal tube, diameter d:
0.25
⎛ h fg' ρ f2 gd 3 ⎞
. ⎜⎜
Nud = 103 ⎟⎟
⎝ 4 µ f k f ∆Tsat ⎠
Properties are evaluated at the arithmetic mean film temperature, with the
exception of the latent heat which should be calculated from:
In the absence of the above, the Nusselt Equation for horizontal tubes may also be
used for tubes in the bundles of heat exchangers. However, condensate will drain
from the upper tubes to the lower tubes thus increasing the film thickness on all but
the top tube.
If the liquid flows uniformly then the mean heat transfer coefficient for a bank N
rows deep is given by:
αN
= N − 0.25
α1
and for a tube on the Nth row the heat transfer coefficient is given by:
αN
= N 0.75 − ( N − 1)
0. 75
α1
2.66
In fact, in most practical situations the liquid flows to the lower tubes in rivulets as
shown in (b), and the reduction in heat transfer coefficient is not as marked as
predicted by the above equations.
2.67
(a) (b)
Now, if we consider an element of the film, length dx and an element of the fluid
shaded in figure 2.26 , we can equate the shear force and gravity acting on the
element:
⎛ dU ⎞
τdx = µ ⎜ ⎟ dx = (δ − y) dxρ g (2.118)
⎝ dy ⎠
or
ρg
dU =
µ
(δ − y)dy (2.119)
This can be integrated to find the velocity distribution through the film:
ρg ⎛ y2 ⎞
U= ⎜ δy − ⎟ (2.120)
µ ⎝ 2⎠
The mass of liquid flowing through the film at some distance x from the top is then
given by:
δ δ
ρ2 g ⎛ 2⎞ 2 3
m& = ∫ ρUdy = ⎜ δy − y ⎟dy = ρ gδ
µ ∫⎜ 2 ⎟⎠ 3µ
(2.121)
0 0⎝
2.68
At a distance dx below, when the film thickness has increased by dδ, we can write:
ρ 2 gδ 2
( m& + dm& ) − m& = dm& = dδ (2.122)
µ
Now the heat transferred may be related to the latent heat given up by the
condensing vapour:
& ρ 2 gδ 2
dQ = h fg dm = h fg
& dδ (2.123)
µ
Giving:
∆t ρ 2 gδ 2
dQ& = kdx s = h fg dδ (2.124)
δ µ
or:
0.25
⎛ h'fg ρ 2f gx 3 ⎞
Nu x = ⎜ ⎟
⎜ 4µ f k f ∆Tsat ⎟
⎝ ⎠
(2.112)
If the plate is inclined to the vertical at an angle β to the vertical then we may
substitute g cos β for g.
The mean heat transfer coefficient from x=0 to x=l is given by:
l
1 4 4
α = ∫ α x dx = α l or N u = Nu l . (2.126)
l0 3 3
For a cylinder, diameter d, the effective length or equivalent plate height is l=2.85d.
Any aspect of the geometry or fluid flow which causes the film to break up or
become wavy tends to enhance condensation heat transfer, as does shear due to
high velocity vapour.
2.69
The presence of non-condensable gases, even in small quantities, in a condenser can
have highly detrimental effects on the condenser performance. The non-condensable
gas (usually air) becomes concentrated adjacent to the liquid film, thus forming a
layer through which vapour must diffuse. The partial pressure of the vapour, and
hence its condensing temperature, is reduced by the presence of non-condensables
therefore the temperature at the surface of the film, and consequently the
temperature difference across the film, is reduced.
2.70
2.5 Fouling of Heat Exchangers
Fouling of Mechanisms
The deposition of foreign matter on a heat transfer surface is known as fouling. The
presence of a foulant on a surface introduces an additional thermal resistance
between the surface and the heat transfer fluid. As the layer becomes thicker this
effect becomes more marked and, since the foulant occupies space within the flow
passage, effective diameter of the flow passage decreases with a consequential
increase in pressure drop (or reduction in flow rate). Both of these effects are
undesirable and therefore heat transfer equipment and process conditions must be
designed to minimise the effects of fouling. Measures to mitigate the effects of
fouling may be preventative (eg treatment of cooling water, high fluid flow velocities),
or remedial (eg regular cleaning of the affected surfaces). Additionally, it is usual to
allow for a thermal resistance due to fouling when specifying or designing a heat
exchanger.
Unfortunately, the complex mechanisms involved in fouling are not fully understood
and there is only a limited theoretical background to permit the fouling propensity of
new designs or applications to be predicted. In practice a designer must rely upon
the TEMA fouling factors4 which is additional thermal resistance’s which should be
incorporated into the determination of the overall heat transfer coefficient when
designing a shell-and-tube heat exchanger.
For convenience fouling is generally classified under one of six headings depending
upon the mechanism causing the deposition eg5:
2.71
b) Particulate fouling (silting) occurs when solid particles from the
fluid stream are deposited on the heat transfer surface. Most streams contain some
particulate matter originating from a variety of sources.
c) Biological fouling is caused by the deposition and growth of
organisms on the heat transfer surface.
d) Corrosion fouling is the result of a chemical reaction involving the
heat transfer surface leading to a build up of corrosion products on the surface.
e) Chemical reaction fouling occurs when a reaction involving one
or more constituents in the process fluid results in the formation of a solid layer on
the heat transfer surface. The surface itself is not involved in the chemical reaction.
f) Freezing or solidification fouling occurs when the temperature of
the process fluid is reduced sufficiently to cause freezing at the heat transfer surface.
The above definitions are commonly used. However it must be noted that other
classification are also found in the literature and in specialist publications. For
example, defines scale, microbiological contamination and corrosion corresponding
broadly with (a), (c) and (d) above but reserves the term fouling for deposition of
particulate matter, as in (b) above.
Use of a biocide together with maintenance of the cooling tower to prevent the
establishment and build up of any biological growth can minimise, if not entirely
eliminate, biological fouling. Biocide treatment of the water in cooling tower
systems is essential to eliminate the build up of bacteria which may be harmful to
2.72
health, the best known of these being the legionella bacteria. The materials of
construction of heat exchangers used in cooling water circuits should be chosen so
that corrosion is acceptable, remembering that any corrosion products may act as a
foulant where formed or break away and contribute to particulate fouling elsewhere.
An additional problem associated with compact heat exchanges and related to, but
not normally classified as, fouling must be considered: It is inevitable that the small
flow passages inherent in most forms of compact heat exchanger will be susceptible
to blockage or plugging by large or fibrous particles. Therefore process fluids for
use in PCHE’s must be filtered to ensure that particles of dimensions comparable to
or larger than the passage cross-section do not reach the heat exchanger. This may
require the use of special filtration equipment and/or more rigorous maintenance
then would be normal for shell-and-tube units. For the purposes of this report the
term ‘blockage’ is used to describe the obstruction of flow passages by relatively
large particles.
2.73
Fouling Rate
It is beyond the scope of this course to evaluate the various models which have been
proposed to facilitate the prediction of fouling behaviour under various conditions
but it is necessary to enumerate some of the factors which influence fouling.
Fouling involves the deposition of material onto the heat transfer surface occurring
concurrently with removal of material previously deposited. A simple model, due to
Kern and Seaton, expresses this:
dx
f = a1cu − a2 τW x f (2.127)
dt
Where the first term on the right hand side represents the rate of deposition on the
surface and the second term represents the removal rate.
Implying that the fouling thickness approaches a value x *f asymptotically. The values
a1c u
x*f = (2.129)
a2 τ w
B = a2 τ w (2.130)
Equation 2.129 may be derived from examination of equation 2.127: x *f is the value
of the thickness of the fouling layer at which the rate of deposition onto the surface
is equal to the rate of removal.
2.74
Figure 2.29 Typical fouling curves
This
model is not universally applicable. Several curves of fouling resistance (or thickness)
against time have been observed and some typical shapes are shown in Fig. 2.29, the
Kern-Seaton model applies only to curve B, representing an asymptotic deposit with
no induction period. However, this simple model is adequate as a qualitative
indication of the importance of various parameters in determining the rate and
severity of fouling.
If the fouling follows a curve of the form B or D then the heat exchanger can be
designed for continuous operation with a fouling factor corresponding to the
resistance of the layer at the asymptotic thickness. If the foulant continues to build
up then a permissible resistance should be included in the design and cleaning
scheduled to take place before this level is reached. The existence of an induction
period in many situations may lull the operator into a false sense of security, fouling
2.75
is not immediately apparent but appears after an extended period of operation.
There are two possible explanations for this phenomenon.
• Foulant may not initially adhere to the heat transfer surface and the
layer does not build up until the surface has become conditioned in some way.
• Alternatively, if the layer thickness is inferred from heat transfer
measurements then the existence of a fouling resistance may be masked by an
enhancement of the heat transfer coefficient by roughening of the surface. Indeed, a
net increase in heat transfer (corresponding to an apparently negative heat transfer
coefficient) is sometimes observed during the early stages of a heat exchangers life.
Remembering that the wall shear stress, τ w , increases with mean velocity, u, to a
power greater that l, we can see from equations 2-4 that the fouling rate and final
thickness of the fouling layer can be expected to increase with decreasing velocity.
For this reason it is essential that heat exchanger designers avoid regions of low
velocity in their designs. Designers must also be wary of including too conservative a
fouling factor - it may be self fulfilling. If the incorporation of additional heat transfer
area is accompanied by an increase in flow area and corresponding reduction in fluid
velocity (which in itself will reduce the film heat transfer coefficient), then the
propensity to foul will be greater.
In general the higher the temperature of a surface the greater its propensity to foul.
This is clearly the case for deposition of inverse solubility salts or the products of
decomposition. There are obvious exceptions, for example freezing occurs at low
temperatures as does the condensation of liquids or tars from a gas stream (eg
combustion products). The designer should attempt to ensure a uniform
temperature where possible in a heat exchanger.
2.76
velocity or temperature, they apply only to tubular exchangers and to a limited range
of fluids.
2.77
Table 2.7 Typical film transfer coefficients for shell -and-tube heat exchangers
(taken from Handbook of Heat Exchangers Design by G.F. Hewitt)
2.78
Table 1.2 Typical film transfer coefficients for shell -and-tube heat exchangers
(taken from Handbook of Heat Exchangers Design by G.F. Hewitt)
2.79
Table 2.7 continued. Typical film transfer coefficients for shell -and-tube heat exchangers
(taken from Handbook of Heat Exchangers Design by G.F. Hewitt)
2.80
2.5.1 Example Showing Effect of Fouling
a) What features of gasketed plate heat exchangers make them attractive for use for
processing foodstuffs.
b) The figure below shows a pasteurisation system treating 7600 l/hour of milk. It
incorporates two gasketed plate heat exchangers. The regenerator has 51 thin plates
clamped between end plates. The channels between the plates (including those
between the end plates and heat exchanger plates) may be regarded as rectangular,
having width 300mm and the spacing between the plates is 1mm.
The pasteurisation process requires that the milk leaving the heater and returning to
the regenerator is always at 77oC. When the plates of the regenerator are clean the
milk enters the heater at 65oC. Calculate the height of the plates in the regenerator.
After a period of operation, fouling of the plates occurs and a fouling resistance of
0.0001m2K/W is applied to each surface. Estimate the percentage increase in the rate
of energy supplied to the heater to maintain the milk peak temperature at 77oC.
Calculate the temperature of the milk leaving the plant.
For the plate heat exchanger the heat transfer coefficient may be calculated from:
Nu = 0.2536 Re0.65 Pr 0.4
Properties of milk:
Density 1030kg/m3
Specific heat capacity 3.92kJ/kgK
Dynamic viscosity 1100 x 10-6kg/ms
Thermal conductivity 0.565W/mK
2.81
Milk from Pasteurised
storage at milk
4oC
Regenerator
77oC
Heater
⎛ 2.174 ⎞ −3
⎜ − 6 ⎟ × 2 × 10
Gdh ⎝ 300 × 10 × 26 ⎠
Re = = = 506
µ 1100 × 10 −6
µ Cp 1100 × 10 −6 × 3920
Pr = = = 7.63
k 0.565
Since properties are constant and the same flow in each side:
t
α 1 =α 2 = α for thin plate ≈0
k
2.82
1 1 1
= = ∴U = 4627W / m 2 K
U α1 α2
(m& c p )c = (m& c p )n
∴ Tn ,out = 77 − ( 65 − 4 ) = 16 0 C
Q = UA∆Tm
520 × 10 3
A= = 9.36 m 2
4627 × 12
After Fouling
1 1
= + rf 1 + rf 2
Uf U
1
= + 0.0001 + 0.0001
4627
Uf = 2403W / m 2 k
2.83
Th ,out = Th ,in − (Tc ,out − Tc ,in ) (2)
Th ,in = 77 0 C Tc ,in = 4 0
Tc ,out = 57 0 C
( 77 − 57 ) − ( 77 − 65 )
= 100 ×
Percentage waste 77 − 65
= 67% in
ncrease
Tn ,out = 77 − ( 57 − 4 ) = 24 0 C
2.84
2.6 Heat Transfer by Radiation
Unless at a temperature of absolute zero (i.e 0.0K or -273.15oC, a situation never encountered in
practice) all matter emits electromagnetic radiation. The higher the temperature of the body the
greater is the rate of energy emission. Bodies also absorb at least a proportion of the thermal
radiation which is incident upon them. Therefore if two bodies which are at different temperatures
are placed so that each intercepts radiation from the other then there will be a net interchange of
energy from the hotter to the cooler body. This is commonly referred to as heat transfer by radiation
or radiative heat transfer.
Electromagnetic radiation requires no medium for its propogation and will therefore pass through a
vacuum. Electromagnetic radiation at the frequencies which are of interest for heat transfer (thermal
radiation) will also pass through most gases. For most applications it can be assumed that gases are
transparent to thermal radiation and do not emit thermal radiation. There are, however, some
important exceptions: the influence of the so called “greenhouse gases” in the atmosphere being one
and radiation from flames and combustion products being another.
Before considering the transfer of energy it is necessary to remind ourselves of the nature of the
radiation involved.
We do not need to study the physics of electromagnetic waves in any detail, it is sufficient to know
that they are characterised by their frequency or wavelength. Wavelength is inversely proportional to
frequency:
λ = cv
Where:
λ = wavelength
c = the velocity of light
v = frequency
Frequency is expressed in Hertz (1/s) and velocity in m/s therefore, for consistency of units
wavelength is given in metres. However, in descriptive work the wavelength may ne quoted in cm,
mm or µm.
Fig shows the electromagnetic spectrum and the names associated wih various wavelengths of
radiation. The frequency and hence wavelength depend upon the nature of the source. Radiation in
the wavelength range 0.1-1000 µm ( 10-5-10-1cm) will heat any body on which it is incident and is
known as thermal radiation. Thermal radiation encompasses ultra-violet radiation, visible light and
2.85
infer-red radiation. The visible spectrum falls within the wavelength band 0.38-0.76 µm. The quantity
and frequency of the radiation emitted by a body depends upon the temperature of the body, we
cannot see thermal radiation emitted from a body at a temperature below about 500oC.
Thermal Radiation
Reflected Energy
Reflectivity = =ρ
Incident Energy
Absorbed Energy
Absorbtivity = =α
Incident Energy
Transmitted Energy
Transmissivity = =τ
Incident Energy
(Note symbols – these are widely used in the literature but are also used in other areas of heat
transfer)
ρ + α +τ = 1 (2.131)
For most engineering applications solids are opaque to thermal radiation, i.e. τ=0. Even optically
transparent substances are opaque to all but a narrow range of wavelengths. If τ=0
ρ +α =1 (2.131(a))
2.86
If all the radiation of all frequencies incident on an object is absorbed then the object is known as a
Black Body. (Note: the terms object or body and surface are almost interchangeable in this context,
almost all absorption occurs within a few microns of the surface of an object)
For a black body α = 1 and ρ = 0 . The visual appearance of an object or material is not always a
good guide to its “blackness”. For example snow is almost black to thermal radiation outside the
visible range.
It can be demonstrated that a black body is, for a given size and temperature, the best possible
emitter of radiation.
Consider a small object in a large enclosure:
If the body and the enclosure are at the same temperature then there can be no net exchange of
energy by radiation (or by conduction or convection). This is a consequence of the Second Law of
Thermodynamics, but hopefully it is intuitively obvious.
First assume that the object is a black body. All the energy incident on the body is absorbed. For
equilibrium an equal amount of energy must be radiated by the body. Let this amount be E b A , where
A is the surface area of the body. If the black body is then removed and replaced by a body of the
same shape and size but having a surface such that α < 1 then some of the incident radiation must be
reflected from the surface of the body. The amount of radiation incident on the body will be
unchanged since this depends only on the temperature of the surroundings and the dimensions of the
object. The rate of energy incident upon the body is still E b A and the rate of energy absorption is
αEb A . For thermal equilibrium these must be equal to the rate at which energy is radiated from the
body, EA.
EA = αAE b
(2.132)
α = EE
b
2.87
Since α must be less than one, then E is less than Eb. E is known as the emissive power of the body
and is equal to the energy radiated per unit time per unit surface area of the body. The ratio of the
emissive power of a body to the emissive power of a black body having the same dimensions is known
as the emissivity, ε.
ε = EE (2.133)
b
It can be deduced from the above discussion that the emissivity of a body is equal to its absorbtivity at
a given temperature. The emissivity of a body radiating energy at a temperature T is equal to its
absorptivity at the same temperature , T.
The rate at which energy is radiated from a black body may be determined from the Stefan-Boltzmann
law:
Eb = AσT 4 (2.134)
Where:
Eb = the emissive power W
σ = the Stefan-Boltzmann constant W/m2K4
T = the absolute temperature K
A = the area of the body m2
The Stefan-Boltzman constant has a value 5.67 x 10-8W/m2K4
In practice, no surface is absolutely black to thermal radiation but many surfaces approach the ideal
having emissivities in excess of 0.95.
The surroundings may frequently be considered to behave like a black body. Reference to figure
2.31(a) shows that very little radiation leaving a small object in large surroundings will be reflected
back to the object, therefore the surroundings appear to be black. Similarly a small hole leading to a
relatively large chamber, as shown in figure 2.31(b), will appear black since radiation entering the hole
will not be reflected out. Even if the surfaces in question have high reflectivity, radiation will be
absorbed during multiple reflections.
2.88
When a relatively small object radiates heat to large surroundings at uniform temperature, the net
rate of heat transfer to the body is given by:
The range of wavelengths of the radiation emitted from a black body, as well as the rate of energy
emission depends upon its temperature. Figure 2.32 shows the variation with temperature of
wavelength in terms of the emissive power/micron of wavelength for a black body.
2πhc 2 ⎡ 1 ⎤
E bλ = ⎢ ⎥ (2.136)
λ ⎣ exp(hc λK oT ) − 1⎦
5
and the wavelength, λ max at which the emissive power is a maximum is at a given temperature can be
determined from:
λ max T = c (2.137)
2.89
A body or surface which emits less than a black body but has the same shape spectral distribution, as
shown in figure 2.33 is said to be grey. For a grey surface ε does not vary with temperature, however
in many instances the error introduced by assuming constant emissivity is acceptable.
λ
Fig. 2.33 Spectral distribution for grey body
The emissivities of various surfaces are given in Table 2.8.
Note that for real surfaces the emissivity may vary significantly with temperature. If the body is at T1
and the surroundings are at Ts then when calculating the energy exchange the emmisivity at T1 and the
absorbtivity at Ts should be used. i.e. the net rate of heat transfer to the body is given by:
Selective surfaces are those which have very different values of emmissivity ans absorptivity at
different temperatures are known as selective surfaces. They are particularly useful in solar energy
applications. For solar collectors it is desirable to have a surface with high absorptivity for radiation
emanating from a high temperature source and low emissivity at low temperature (the nature of solar
radiation at the earth’s surface is such that the sun may be approximated as a black body having
temperature ~6000K while the collector surface is at ~350K ) .
2.90
Table 2.8 Emisivities of various surfaces
In general, for any two objects in space, a given object 1 radiates to object 2, and
object 2 radiates to object 1 and both radiate to space. This is illustrated for the
general case in figure 2.34
2.91
Radiation
to space
Radiative
exchange
Radiation
to space
A1, T1
A2, T2
Surface 2
In order to calculate the energy interchange between the two surfaces at different
temperatures it is necessary to calculate both the total quantity of radiation leaving
each surface and the proportion of the radiation which reaches the other surface.
The radiation leaving a black surface is given by equation 2.134.
The proportion of the radiation which is incident on the other surface is given by the
radiation shape factor or view factor, F,. With reference to figure 2.35:,
2.92
For body 1, we know that is the emissive power of a black body, so the energy
leaving body 1 is σA1T14 . The energy leaving body 1 and arriving (and being absorbed
since, by definition, α = 1 for a black body) at body 2 is σA1T14 F1− 2 . The energy
leaving body 2 and being absorbed at body 1 is σA2T24 F2−1 . The net rate of energy
interchange from body 1 to body 2 is:
Note that if the two bodies are at the same temperature T1 = T2 = T then there can be no heat
transfer between them:
2.93
Fig. 2.36 View factors for various geometries (From Fundamentals of heat transfer, F.P.
Incropera and D.P. DeWitt, John Wiley and Sons)
2.94
Fig. 2.37 Graphical representation of view factors
2.95
source. The mathematical manipulation becomes rather complex. We will therefore
limit our considerations to the relatively simple case of infinite parallel plates ( or
long concentric cylinders with a small gap between them) this is shown schematically
in figure 2.40.
A,α1 , ε1 , ρ1 , T1
Multiple
reflection of
radiation
A, α 2 , ε 2 , ρ 2 , T2
(
Q&1 = ε1ε 2σT14 A 1 + (ρ1ρ 2 ) + (ρ1ρ 2 ) + (ρ1ρ 2 ) ................
2 3
)
Similar logic gives:
(
Q& 2 = ε1ε 2σT24 A 1 + (ρ1ρ 2 ) + (ρ1ρ 2 ) + (ρ1ρ 2 ) ................
2 3
)
and the net rate of heat transfer is:
( ) ( )(
Q& = Q& 2 − Q&1 = ε1ε 2σ T24 − T14 A 1 + (ρ1ρ 2 ) + (ρ1ρ 2 ) + (ρ1ρ 2 ) .........
2 3
)
The series
1
1 + (ρ1ρ 2 ) + (ρ1ρ 2 ) + (ρ1ρ 2 ) ........ =
2 3
1 − ρ1ρ 2
ε1ε 2
Q& = σ (T24 − T14 )A
1 − ρ1ρ 2
which may be rearranged with the substitution ρ = (1 − α ) = (1 − ε )
2.96
σ (T24 − T14 )A
1
Q& = (2.141)
⎛1 1 ⎞
⎜⎜ + − 1⎟⎟
⎝ ε1 ε 2 ⎠
This reduces to equation 2.135(a) if one surface is black , and 2.135(b) if both surfaces are black.
Summary Points
2.97