You are on page 1of 6

ABB AG

RTU560

Remote Terminal Unit

Connections and Settings

Analog Input 23AE23




Application, characteristics and technical data have
to be taken from the hardware data sheet:

23AE23 1KGT 150 573
Operation
The 23AE23 board scans analog current- or voltage
signals and prepares them for the RTU560 on the
basis of predefined parameters.
Processing functions
The micro controller EAP (Ein-/ Ausgabe -
Prozessor / Input- output processor) controls the
A/D converter and reads the digitized analog meas-
ured value. The configuration parameters are
loaded by the CMU (communication unit). The used
processing functions of the 23AE23 are defined by
the RTU560.
In general the 23AE23 board can process the fol-
lowing functions per input channel.
Zero value supervision
Switching detection
Smoothing
Cyclic transmission to the CMU independent
from threshold supervision
Threshold supervision
Input signal conversion
The A/D converter operates by the sigma-delta
method. Each input signal is internally converted
with 16 bit resolution. This high resolution allows to
scan some input ranges with one shunt. With the
information about the to be scanned input range set
by the switch registers S1 to S3, the 23AE23 board
can do the calculation for the 11 bit resolution for
100 %.
The sigma-delta method allows a high suppression
of line-frequency and line-harmonics interference
voltages. This is still specified by a deviation from
the nominal line-frequency of up to 10 %. On this
occasion the suppression is still >45 dB.
The 23AE23 transmits the measured value with 12
bit plus sign to the CMU. The scaling to the telecon-
trol transmission protocol presentation is done by
the CMU.
With a ninth internal measuring channel the
23AE23 does an automatic zero calibration at
each cycle. The A/D converter uses the result as
an rating factor.
Settings
Input signal range
A measuring range can be differently configured
for each of the eight channels. Therefore the
configuration has to be done for all eight chan-
nels. For each channel:
the switch registers S1 to S3 AND
the jumper X5x1
should be configured to the same measuring
range. Only if jumper and switch register setting
corresponds the 23AE23 scans and converts the
measuring value correct.
The configuration of jumper X5x1 is shown in
Table 1. Hereby is x =the to configure channel.
Table 2 shows the corresponding settings for
switch register S1 to S3 and the corresponding
position of jumper X5x1. For channel 5 =20 mA
as an example it should be set:
X551 jumper 5 =position 1-2
S3-5 =OFF
S2-5 =ON
S1-5 =ON
The firmware of the 23AE23 uses the position of
switch register S1 to S3 for the scaling and cal-
culation to the nominal measuring range. In ad-
dition it identifies by the position which rating
value it should use.
Doc-No.: 1KGT 150 574 V000 1 1
ABB AG


Connections and Settings 23AE23 RTU560


Measuring
range
S3 - x S2 - x S1 - x X5x1
2 mA
5 mA
10 mA
20 mA
1
O
N
OFF
1
O
N
OFF
2
OFF
1
O
N
OFF
1
O
N
OFF
1
O
N
ON
1
O
N
OFF ON
1
O
N
OFF
1
O
N
OFF
1
O
N
ON
1
O
N
ON
40 mA
1
O
N
ON
1
O
N
OFF
1
O
N
OFF
The configuration of S1-x to S3-x and X5x1 should
correspond to each other
1 2 3
ON
OFF
ON
x =1 to 8 =input channel
X5x1
S1
S2
S3
1 2 3
2 V
1
O
N
ON
1
O
N
OFF
0 ... 20 V
1
O
N
ON OFF
not used
1
O
N
ON
1
O
N
ON
1
O
N
ON
1
O
N
ON
1
O
N
ON
1
O
N
1 2 3
1 2 3
1 2 3
1 2 3
4
1 2 3
1 2 3
1
O
N
1
O
N
1 2 3
1 2 3
5 6 7 8
Measuring
range
S3 - x S2 - x S1 - x X5x1
2 mA
5 mA
10 mA
20 mA
1
O
N
1
O
N
OFF
1
O
N
1
O
N
OFF
2
OFF
1
O
N
1
O
N
OFF
1
O
N
1
O
N
OFF
1
O
N
1
O
N
ON
1
O
N
1
O
N
OFF ON
1
O
N
1
O
N
OFF
1
O
N
1
O
N
OFF
1
O
N
1
O
N
ON
1
O
N
1
O
N
ON
40 mA
1
O
N
1
O
N
ON
1
O
N
1
O
N
OFF
1
O
N
1
O
N
OFF
The configuration of S1-x to S3-x and X5x1 should
correspond to each other
1 2 3
ON
OFF
ON
x =1 to 8 =input channel
X5x1
S1
S2
S3
1 2 3
2 V
1
O
N
1
O
N
ON
1
O
N
1
O
N
OFF
0 ... 20 V
1
O
N
1
O
N
ON OFF
not used
1
O
N
1
O
N
ON
1
O
N
1
O
N
ON
1
O
N
1
O
N
ON
1
O
N
1
O
N
ON
1
O
N
1
O
N
ON
1
O
N
1
O
N
1 2 3 1 2 3
1 2 3 1 2 3
1 2 3 1 2 3
1 2 3 1 2 3
44
1 2 3 1 2 3
1 2 3 1 2 3
1
O
N
1
O
N
1
O
N
1
O
N
1 2 3 1 2 3
1 2 3 1 2 3
55 66 77 88

Pos. X5x1 Measuring range
1
1 2 3
x
20 mA
40 mA
2
1 2 3
x
2 mA
5 mA
10 mA
2
1 2 3
x

2 V
20 V
x =1 to 8 for the respective channel

Table 1: Configuration jumper X5x1

Table 2: Configuration S1 to S3 and X5x1




2 Doc.No.: 1KGT 150 574 V000 1
ABB AG


RTU560 Connections and Settings 23AE23


Configuration of line-frequency
Beside the information about the configured meas-
uring range the information about the line-frequency
is requested for the A/D-conversion. The configured
line-frequency is valid for all eight channels. There-
fore jumper X401 has to be configured.

Line-
frequency
Conversion
time per input
Scan cycle
per
23AE23 board
60 Hz
50 Hz
16,6 Hz
62,5 ms
72,5 ms
202,5 ms
500 ms
580 ms
1620 ms

Fig. 1: Configuration of line-frequency
the A/D converter is not
nges at the factory. During the calibra-
of the board. The 23AE23

Factory calibration
An on-site calibration of
necessary.
The 23AE23 will be calibrated for all channels and
measuring ra
tion the firmware calculates a rating value per
measuring range and channel and stores this rating
value in an EEPROM. The rating values are pro-
tected by a checksum.
The 23AE23 checks the checksum of all rating val-
ues during initialization
does not start operation if one or more of these
checksum are wrong. The 23AE23 stays passive,
that means the CMU does not detect the board and
indicates it with "board out of operation". The LED
"ST" flashes in addition with approx. 3 Hz.
Signaling
The board monitors and checks its functionality
as well as the dialog via the peripheral bus. De-
tected errors are indicated and/or transmitted by
the board:
by the red LED "ST" on the front plate
by diagnostic messages
in the process signal messages (signal
status)
The "ST" LED indicates board errors, peripheral
bus errors and/or A/D converter failures.
The "ST"-LED indicates:
board runs initialization procedure
board has detected a memory error
(RAM or EPROM)
X401
16.6 Hz
3 2 1
60 Hz
3 2 1
50 Hz
3 2 1
X401
16.6 Hz
3 2 1
16.6 Hz
3 2 1 3 2 1
60 Hz
3 2 1
60 Hz
3 2 1 3 2 1
50 Hz
3 2 1
50 Hz
3 2 1 3 2 1
micro controller faulty
no dialog via the peripheral bus for at least
two minutes. The board is not polled by
the PBP (Peripheral Bus Processor) of
CMU.
A/D converter faulty
flashing with 3 Hz:
rating values in the EEPROM faulty
Each configured measuring value will be indi-
cated faulty by the CMU for the listed errors.


















Doc.-No. 1KGT 150 574 V000 1 3
ABB AG


Connections and Settings 23AE23 RTU560


ADC
M
u
l
t
i
p
l
e
x
e
r
D
A
20 mA
+EA81
- EA80
2
1
+EA11
- EA10
+EA21
- EA20
+EA31
- EA30
Signal-
conditioning
Micro-
controller
EPROM
RAM
E A P
ST
Signal-
conditioning
Signal-
conditioning
3
s
u
p
p
r
e
s
s
o
r

c
i
r
c
u
i
t
2 V
20 V
2 mA
5 mA
10 mA
40 mA
X581
u
R
T
U
P
e
r
i
p
h
e
r
a
l
B
u
s
.....
ADC
M
u
l
t
i
p
l
e
x
e
r
D
A
20 mA
+EA81
- EA80
2
1
+EA11
- EA10
+EA21
- EA20
+EA31
- EA30
Signal-
conditioning
Micro-
controller
EPROM
RAM
E A P
ST
Signal-
conditioning
Signal-
conditioning
3
s
u
p
p
r
e
s
s
o
r

c
i
r
c
u
i
t
2 V
20 V
2 mA
5 mA
10 mA
40 mA
X581
u
R
T
U
P
e
r
i
p
h
e
r
a
l
B
u
s
ADC
M
u
l
t
i
p
l
e
x
e
r
D
A
20 mA
+EA81
- EA80
2
1
+EA11
- EA10
+EA21
- EA20
+EA31
- EA30
Signal-
conditioning
Micro-
controller
EPROM
RAM
E A P
ST
Signal-
conditioning
Signal-
conditioning
3
s
u
p
p
r
e
s
s
o
r

c
i
r
c
u
i
t
2 V
20 V
2 mA
5 mA
10 mA
40 mA
X581
u
R
T
U
P
e
r
i
p
h
e
r
a
l
B
u
s
.....

Fig. 2: Logic block diagram

ig. 3: Board layout with setting positions
X401
23AE23
10/
1/10 V
20 mA
1/2,5
10 mA
1
2
3
4
5
6
7
8
O
F
F
S3
1
2
3
4
5
6
7
8
O
F
F
S2
1
2
3
4
5
6
7
8
O
F
F
S1
X5x1
8
7
6
5
4
3
2
1
3 2 1
1 2 3
1
2
3
4
5
6
7
8
O
N
60 50 162/3
X401
23AE23
10/
1/10 V
20 mA
1/2,5
10 mA
1
2
3
4
5
6
7
8
O
F
F
S3
1
2
3
4
5
6
7
8
O
F
F
S3
1
2
3
4
5
6
7
8
O
F
F
S2
1
2
3
4
5
6
7
8
O
F
F
S2
1
2
3
4
5
6
7
8
O
F
F
S1
1
2
3
4
5
6
7
8
O
F
F
S1
X5x1
8
7
6
5
4
3
2
1
3 2 1 3 2 1
1 2 3
1
2
3
4
5
6
7
8
O
N
60 50 162/3

F
4 Doc.No.: 1KGT 150 574 V000 1
ABB AG


RTU560 Connections and Settings 23AE23



23TP21 23ET23 Signal Identification
Sub connector Identification Meaning
1 z32 EA10- Analog input 1 -
2

b32 EA11+ Analog input 1 +
3 d32 EA20- Analog input 2 -
4 z30 EA21+ Analog input 2 +
5 b30 EA30- Analog input 3 -
6 d30 EA31+ Analog input 3 +
7 z28 EA40- Analog input 4 -
8 b28 EA41+ Analog input 4 +
9 d28 EA50- Analog input 5 -
10 z26 EA51+ Analog input 5 +
11 b26 EA60- Analog input 6 -
12 d26 EA61+ Analog input 6 +
13 z24 EA70- Analog input 7 -
14 b24 EA71+ Analog input 7 +
15 d24 EA80- Analog input 8 -
16 z22 EA81+ Analog input 8 +
17 A (Faston 6,3) A Cable shield
18 b22 Not used
19 d22 Not used

Subrack terminal connection: 23AE23
ET23 TP21
b z d b z d d b z
ET23 ET23 TP21 TP21
b z d b z d b z d d b z d b z

Placement of signal terminal connectors on subracks
Doc.-No. 1KGT 150 574 V000 1 5
ABB AG


Connections and Settings 23AE23 RTU560



Connection diagram 23TP21 subrack

ABB AG
Power Technologies Division
Power Technology Systems

Kallstadter Str. 1, 68309 Mannheim
Telephone +49 (0) 621 381 - 7592
Fax +49 (0) 621 381 - 7622
www.abb.de/pt Subject to alteration
6 Doc.No.: 1KGT 150 574 V000 1