Professional Documents
Culture Documents
MicroGrid
A. P. Agalgaonkar, C. V. Dobariya, Student Member, IEEE, M. G. Kanabar, Student Member, IEEE,
S. A. Khaparde, Senior Member, IEEE, and S. V. Kulkarni, Member, IEEE
Abstract— Hybrid Optimization Model for Electric Renew- Ctl Cost of T&D network in $/km
ables (HOMER), developed by National Renewable Energy Lab- Cxmr Total cost of transformers in a MicroGrid in $
oratory (NREL), enables economic analysis for single source and CF Factor relating wind speed and power output of Wind
hybrid Distributed Energy Resources (DERs). However, current
version of HOMER does not support MicroGrid analysis. In Turbine Generator (WTG)
this paper, Economic Analyzer for Distributed Energy Resources eg Energy sell to grid in kWh/year
(EADER) is developed. It finds minimum Cost of Energy (COE) Eann
out
Annual electrical energy output in kWh/year
and optimal mix of DERs with multiple sources and sinks. In eg
max
Maximum power exchange between DERs and grid
addition to single source Distributed Generator (DG) and hybrid Eiout Electrical output of ith DG in kWh/year
DG, EADER is also capable to analyze MicroGrid. EADER
results are validated for single source DG and hybrid DG with Eni Net Calorific Value (NCV) of fuel used by ith DG in
results obtained from HOMER for the same systems. Further, kWh/unit fuel
a sample practical system from Western Maharashtra, India, is Firep Replacement factor for ith DG
analyzed using EADER. The results which consider all practical F Uif Fuel utilized by ith DG in unit fuel/year
constraints are presented and discussed.
hri Heat recovery ratio for ith DG
Index Terms— Combined Heat and Power (CHP), Distributed i DG index
Generation, Economic analysis, MicroGrid. LDG Life of ith DG in years
i
Lrep
i Replacement life of ith DG in years
N OMENCLATURE Lproj Life of project in years
ltl T&D network’s length of MicroGrid in km
ηi Efficiency of ith generator
m Total number of DG types
ρair Density of air at site in kg/m3
P Payback period in years
ρstd Standard density, i.e., 1.225 kg/m3
P 2hi Power to heat ratio of ith DG
Ai Availability of ith generator
PD Total connected load of in kW
Cg Cost of selling power to grid in $/kWh
PG Total power generated in kW
Cann
cap
Annualized capital cost in $/year
P gi Power generation of ith DG
Cann
f
Annualized fuel cost in $/year
P gimax Maximum generation limit of ith DG
Cann
grid
Cost recovered by selling power to grid in $/year
r Interest rate
Cann
in
Annualized cost recovery from consumers in $/year
Ri Rating of ith generator in kW
Cann
mis
Annualized miscellaneous cost in $/year
Si Salvage value of ith DG in $
Cann
onm
Annualized operation and maintenance (O&M) cost
T hout
ann Thermal energy output in kWh/year
in $/year
ws Wind speed in m/s
Cann
rep
Annualized replacement cost in $/year
Cann
xtl
Annualized cost of transformer and transmission lines
in $/year I. I NTRODUCTION
Cicap Capital cost of ith DG in $/kW
Cif
Cionm1
Fuel cost of ith DG in $/unit fuel
O&M cost of ith DG in $/hr
I N India currently, the average peak demand and energy
shortages for all regions taken together are of the order
of 12.39% and 10.32% respectively. Still, more than 80000
Cionm2 O&M cost of ith DG in $/kWh
villages are not electrified [1]. Hence, the Government of
Cirep Replacement cost of ith DG in $/kW
India has emphasized on development of infrastructure with
This work has been supported by Central Power Research Institute (CPRI), top priority given to the power sector. To electrify remote and
Bangalore, India under the project titled “Study of Infrastructure and issues rural areas, it may be difficult as well as uneconomical to
Involved in Implementation of Distributed Generation in Rural India” (as per transmit power over long distances through transmission lines.
sanction order no. CPRI/R&D/RSOP/IITB/2004).
A. P. Agalgaonkar has now joined Energy Technologies, National Thermal On the contrary, single source DG, hybrid DG or MicroGrid
Power Corporation (NTPC) Noida, India (email: apa ntpc@yahoo.co.in). are more favorable to electrify such areas. Single source DG is
C. V. Dobariya, M. G. Kanabar, S. A. Khaparde and S. V. Kulka- an individual Distributed Energy Resource (DER) connected
rni are with Department of Electrical Engineering, IIT Bombay, Mumbai,
India (email: chandv@ieee.org; mital kanabar@iitb.ac.in; sak@ee.iitb.ac.in; to load. The load it serves can be electrical, thermal or
svk@ee.iitb.ac.in). combination of both. Since most of the DERs can directly
0-7803-9525-5/06/$20.00
c 2006 IEEE
supply load without involving T&D network; they reduce hybrid DG. Evolution and modification of EADER routines to
losses and overall initial investment on T&D network during analyze MicroGrid is explained in a later section. The EADER
power transmission. Hybrid DG technology includes integra- evaluates COE by calculating various costs as follows:
tion of two or more DGs and energy storage devices, supplying A. Annualized capital cost
the same load. Some of the common hybrid configurations B. Annualized replacement cost
are, viz., Wind Turbine Generator (WTG)-diesel, WTG-Photo C. Annual energy output
Voltaic (PV) cell, Micro Turbine (MT)-Fuel Cell (FC), WTG- D. Annualized O&M cost
MT, etc. E. Annualized fuel cost
Concept of MicroGrid supersedes all the advantages of F. Annual earning by selling power to grid
single source DG and hybrid DG. Moreover, it also includes all
the advantages of networking, at mini scale. From reliability
point of view it may not be always possible to operate few A. Annualized capital cost
types of DGs like WTG and PV cell, in stand-alone mode. ann
Annualized capital cost (Ccap ), is the cost that needs to be
The MicroGrid concept, as it involves small T&D network, recovered yearly for payback period of P years and interest
efficiently makes use of all location specific DGs. rate r. The main components of Ccap ann
are, Cicap and Capital
A simulink based model similar to Hybrid Optimization Recovery Factor (CRF).
Model for Electric Renewables (HOMER) is reported in [2]. The CRF is a ratio used to calculate the present value of
The model is used for economic analysis and it finds impacts an annuity (a series of equal annual cash flows). The equation
of PV with diesel-battery system for Lime village, Alaska. for the CRF is expressed as,
A numerical algorithm developed in [3] is used for and
unit sizing and cost analysis of wind, PV and hybrid wind- r(r + 1)P
CRF (r, P ) = (1)
PV systems. The feasibility of MicroGrid is justified in [4]. (r + 1)P − 1
Various attributes taken into consideration are Energy Not
Served (ENS) per annum, capital cost, and profit by selling Then, annualized capital cost of DG can be written as,
energy to grid in peak time. m
Economic feasibility study includes calculation of Cost of Cann
cap
= CRF (r, P ) Cicap Ri (2)
Energy (COE), Net Present Cost (NPC), Life Cycle Cost i=1
(LCC), etc. For minimum COE, investment on each type of
DG technology has to be optimized. In this paper, develop-
B. Annualized replacement cost
ment of Economic Analyzer for Distributed Energy Resources
(EADER) software is discussed. The software finds minimum Replacement cost of a DG depends upon the salvage value
COE for variety of available schemes, and selects an optimal of DG after life years. The salvage value of a DG can be
mix of available resources to supply load. EADER facilitates expressed as a function of Sinking Fund Factor (SFF).
analysis of single source DG, hybrid DG as well as MicroGrid. SFF is a ratio used to calculate the future value of a series
A case study of practical system in the State of Maharashtra, of equal annual cash flows. It given by,
India, has been done using EADER. Where, it finds best r
possible combination of wind, bagasse, biomass and natural SF F (r, P ) = (3)
(r + 1)P − 1
gas based DERs to supply energy demands of MicroGrid.
Organization of the paper is as follows. Section II introduces Life of replacement is given by,
basic routines implemented in EADER for analysis of single Lproj
source DG and hybrid DG. Section III gives algorithm for Lrep = LDG
i F loor( ) (4)
i
LDG
i
analysis and elaborates constraints on the objective function.
Section IV compares single source DG and hybrid DG results, where, Floor returns integer part of a real value.
obtained from EADER and HOMER. Section V suggests Replacement factor Firep arises because the component
modifications in basic EADER routines to make it capa- lifetime can be different from the project lifetime. Firep is
ble of analyzing MicroGrid. Section VI briefs features and given by,
limitations of EADER. The details of site in the Western CRF (r, Lproj )
Firep = (5)
Maharashtra for the execution of MicroGrid project is listed CRF (r, Lrep
i )
in Section VII. Results of the analysis are discussed in section
VIII, and section IX concludes the paper. The salvage value of the component at the end of the
project lifetime is assumed to proportional to its remaining
II. EADER D EVELOPMENT life. Therefore the salvage value S is given by,
EADER has been developed in C programming language Lproj − Lrep
to find optimal mix of available resources, which results into Si = Ri Cirep [1 − i
] (6)
LDG
i
minimum COE to consumer. This section explains develop-
ment of EADER which can analyze single source DG and Annualized replacement cost is given by,
Annualized fuel cost now can be calculated as,
m
m
Cann
rep
= Ri Cirep Firep SF F (r, LDG )
i Cann
f
= F Uif Cif (15)
i=1
m i=1
− Si SF F (r, Lproj ) (7)
F. Annual earning by selling power to grid
i=1
Power selling to the grid depends upon the available surplus
power with DGs. Charges recovered by selling power the to
C. Annual energy output grid over a period of one year is expressed as,
Electrical energy output from IC engine, fuel cell, PV cell,
wind etc., will be different. Hence, each type of DG has to be Cann
grid
= eg cg (16)
modeled separately. With all the annualized costs obtained, amount of money
Electrical energy output from ith fuel powered generator recovered from the consumers over a period of one year is
(e.g., bagasse, biomass, natural gas) is given by, expressed as:
Particular DG1 DG2 With additional annual costs taken into consideration, the
EADER HOMER EADER HOMER equation (17) is modified as follows:
cap
Cann 68648.42 68648 77229.47 77229
rep
Cann 8253.74 8254 23248.36 23248
onm Cann
in
= Cann
cap
+ Cann
rep
+ Cann
onm
+ Cann
f
Cann 61056 61056 961920 961920
f uel
Cann 69604.12 69630 280851 279072 + Cann
xtl
+ Cann
mis
− Cann
grid
(22)
Eout 4833600 4833600 3488400 3488400
T hout 24178850 24178850 3445116 3401190
26
1 11
Alamprabhu Pathar
12a
4 2 12
13 18
33 kV 3
Shrenik 19
14a 15a 17a 19a
Feeder 16 18a
8 14
6 7 15 17
5 20a 21
9 8a 20
21a
33 kV 9a 24
Tilawani S/S Chandeshwari/Kumbhoj 10 22a 22
33 kV
double circuit feeder double circuit
33 kV feeder 25 23
Hatkanangle
feeder
Hatkanangle S/S 11 kV non existing lines in the proposed MicroGrid
33 kV Kumbhoj feeder 11 kV existing lines in the proposed MicroGrid
Kumbhoj S/S
11 kV existing lines of utility grid
From Jaysingpur S/S
33 kV existing lines of utility grid
VII. M ICRO G RID IN M AHARASHTRA fied energy resources, and is characterized by adequate load
growth. Maharashtra Energy Development Agency (MEDA)
Different non-conventional energy potentials available in
has declared Alamprabhu Pathar as one of the wind sites,
the State of Maharashtra are shown in table IV. Since the
where good amount of wind power can be tapped off. Presence
cumulative tapped potential is about 10% of the total available
of sugar industries in close vicinity of Alamprabhu Pathar has
potential, there exist opportunities to use the remaining poten-
made it possible to include bagasse based generators as one the
tial for local power generations. As wind, bagasse and biomass
constituents of the MicroGrid. The Alamprabhu Pathar area is
are the renewable energy sources with highest potential in the
well connected to the rest of the Maharashtra by roads. Hence,
State, the MicroGrid likely to consist of DGs based on these
biomass and natural gas can be easily transported up to the
resources. Since wind energy can’t be predicted accurately,
generation point. Around the Alamprabhu Pathar area, there
and bagasse is seasonal, natural gas based MT, IC engine
exist good amount of residential, agricultural, commercial and
and mini gas turbine can play an important role in reliability
industrial consumers. The 11 kV T&D network of MicroGrid
improvement of the MicroGrid. Based on identified resources,
is shown in Fig. 1. The 33 kV distribution network around
Alamprabhu Pathar in the state of Maharashtra has been
Alamprabhu Pathar is not a part of MicroGrid. But, MicroGrid
selected for the execution of the MicroGrid project.
can be connected to grid to 33 kV network at a single
TABLE IV Point of Common Coupling (PCC, not shown in the Figure)
NON - CONVENTIONAL ENERGY POTENTIAL IN M AHARASHTRA AS ON 31st to exchange power between the two. In Fig. 1, numbers
M ARCH 2003 [5] 1 to 26 refer to load/generation points. Nodes 1 and 26
indicate WTGs. Node 12 is a sugar cane industry (Sharad
Source Potential in MW Achievement in MW Sahkari Sakhar Karkhana Ltd.). Majority of industrial load is
Wind 3650 399.35 concentrated on nodes 5 to 10 while, nodes 13 to 25 mainly
Small Hydro 600 226.57 consist of residential, agricultural and commercial loads. The
Bagasse Co-generation 1000 23.50 category-wise consumers as well as other details of MicroGrid
Biomass 781 7.50
are listed in table V.
Municipal Solid Waste 100 0.00
Industrial Waste 210 6.12 VIII. M ICRO G RID A NALYSIS AND R ESULTS
Total 6341 663.05 As mentioned in the previous section, for Alamprabhu
Pathar MicroGrid, it is preferable to have DGs based upon
Alamprabhu Pathar is a hilly area in Kolhapur district in available resources, viz., bagasse, wind, biomass and natural
the State of Maharashtra, India. The site is rich of identi- gas. To form a MicroGrid of available dispersed resources,
TABLE V TABLE VI
M ICRO G RID DATA R ESULT OF M ICRO G RID O PTIMIZATION
Total installed capacity 12000 kW Particular Bagasse Natural gas Biomass Wind
Total electrical load 8907 kW DG (kW) 6000 2400 500 14250
cap
Residential consumers (approx.) 1000 Cann 278026 143338 23169 733680
rep
Commercial consumers (approx.) 20 Cann 33428 17234 2786 88212
Industrial consumers (approx.) 20 onm
Cann 1515888 209207 17716∗ 138541
f
Agricultural consumers (approx.) 320 Cann 1085714 603815 — 0
Length of 11 kV network 48.16 km mis
Cann 105650 54468 8804 278798
Average wind speed 6.58 m/s Eout 17424000 16092872 393683 27708194
at Alamprabhu Pathar T hout 92928000 19215370 629893 0
Grid selling 10% of total load eg 7017430
Cg 0.067∗ $/kWh ∗
The charges include O&M cost and fuel cost.
Reserve capacity 15.775% of installed capacity
Existing generation Bagasse 6000 kW
∗
1 $ = INR 45.
to be optimized. Alamprabhu Pathar hill is approximately
6000 × 1000 m2 area. It has a total wind generation potential
of about 45 MW. But, for the MicroGrid purpose, only few of
one needs to evaluate the amount of investment to be done on the WTGs can be part of the MicroGrid considered in this
each particular type of DG resource, so as to have minimum analysis. Others may be connected to utility grid or other
COE at consumer level. MicroGrid in a nearby area. On the reliability point of view,
As shown in table V, maximum connected electrical load stand-alone WTGs are inferior than natural gas based and
of MicroGrid is 8907 kW. For planning purpose, maximum biomass based generators. Hence, WTG size will be limited up
possible load has to be considered with best possible relia- to supply to utility grid and reserve capacity. For a typical 950
bility. The power exchange with the utility grid under normal kW WTG, upper limit of wind generation is installed capacity
conditions is limited to 10% of the capacity of MicroGrid. The of 14250 kW with 15 generators. Biomass and natural gas
reserve capacity is assumed to be 15.775% of the MicroGrid based generators should be able to supply rest of the load
size. As a consequence, MicroGrid size becomes 12000 kW. even with (N-1) contingency. Hence, maximum installation of
It is assumed that subsidy of 40% on capital cost of each each type of generators has to be at least 8907 kW. Since
DG, is given by the Government . The internal load of the 500 kW biomass based generators are successfully installed
sugar factory is 4000 kW, and its generation capacity of and operated at many places, it is preferable to increase the
6000 kW. When the sugar cane is not available, the sugar biomass generation in the step of 500 kW. Natural gas fuelled
factory remains OFF. As a consequence, the MicroGrid’s total IC engine based DG can be installed with single unit of 300
electrical load reduces to 4907 kW, and generating capacity kW. Accordingly the total installed capacity of each kind of
reduces by 6000 kW during that period. MicroGrid’s month- generation is limited up to 9000 kW. Other generator details
wise connected loads are shown in appendix III. It is assumed are listed in appendix III.
that, natural gas based generator remains OFF in the month
of March, and biomass based generator remains OFF in the
B. Results of proposed MicroGrid
month of May and June.
Investment on transformers is 282708 $. Length of transmis- Analysis shows that, we should install 2400 kW of natural
sion line network for the MicroGrid is 48.16 km. Erecting 11 gas based generators, 500 kW of biomass based generators
kV, pin type ACSR Weasel (0.03) and RSJ pole transmission and 14250 kW of WTGs. The minimum COE comes out to
line of 1 km costs 9619 $. Project life of 25 years and interest be 0.080046 $/kWh. That means total 8 units of natural gas
rate of 0.07 is assumed for the analysis. The payback period based generators, each of 300 kW capacity can be installed at
is assumed to be same as project life. various locations in the MicroGrid. Only one biomass based
generator is required which is of 500 kW capacity. Similarly
A. Deciding maximum limits and incremental step size of each total 15 WTGs should be installed. Table VI shows breakup
generation for EADER costs of different DGs in the MicroGrid. To decide location
of the selected DGs will require further studies.
It is important to give maximum limit as well as correct step
size of each type of DG. More precise step size and accurate
maximum limit would save considerable amount of execution IX. C ONCLUSION
time and memory size required. As mentioned previously, This paper develops economic analyzer EADER, which
MicroGrid already consists of 6000 kW (2 × 3000 kW) is tested for sample systems. The EADER is validated for
bagasse based generation at Sharad Sahkari Sakhar Karkhana single and hybrid DER, and yields very close results com-
Ltd. With that equality constraint, rest of the generation has pared to HOMER. More modifications are made to improve
performance of EADER as compared to HOMER. HOMER
in its present version is unable to analyze MicroGrid. The
results of practical MicroGrid using EADER are presented
which minimize COE and find the optimal mix of proposed
DERs with one DER existing. The slight increase in COE for
MicroGrid as compared to single source DG and hybrid DG
can be justified by increased reliability and self-sufficiency.
Though results seem to promising, EADER can be extended
further to include all possible types of DG technologies.
ACKNOWLEDGEMENT
We are thankful to Mr. Prakash R. Agalgaonkar, chief
engineer Maharashtra State Electricity Board (MSEB), for
providing data and technical discussion.
A PPENDIX I
S INGLE S OURCE DG DATA
X. R EFERENCES
Description Value Description Value
[1] R. G. Yadav, A. Roy, S. A. Khaparde, and P. Pentayya, “India’s fast
DG rating 100 kW Cf 0.02 growing power sector: From regional development to growth of a national
En 30 MJ/kg LDG 20 grid,” IEEE Power and Energy Magazine, pp. 39–48, July 2005.
[2] R. W. Wies, R. A. Johnson, A. N. Agrawal, and T. J. Chubb, “Simulink
C cap 800 hr 1 model for economic analysis and environmental impacts of a PV with
C rep 800 P2h 0.2 diesel-battery system for remote villages,” IEEE Trans. Power Syst.,
vol. 20, no. 2, pp. 692–700, May 2005.
C onm 1.2 η 1
[3] W. D. Kellogg, M. H. Nehrir, G. Venkataramanan, and V. Gerez, “Gen-
eration unit sizing and cost analysis for stand-alone wind, photovotaic,
A PPENDIX II and hybrid wind/PV system,” IEEE Trans. Energy Conversion, vol. 13,
H YBRID DG DATA no. 1, pp. 70–75, Mar. 1998.
[4] A. P. Agalgaonkar, S. V. Kulkarni, and S. A. Khaparde, “Evalutation
Fuel type Bagasse Natural gas of configuration plans for DGs in developing countries using advanced
planning techniques,” IEEE Trans. Power Syst., submitted for publication.
En 30 (M J/kg) 45 (M J/m3 ) [5] “Advisory services and policy document on rural electrification in
C cap 800 900 maharashtra,” Draft report of the consultunts, Maharashtra Electricity
Regulatory Commission (MERC), Tech. Rep., 2005.
C rep 800 900 [6] J. A. P. Lopes, J. T. Saraiva, N. Hatziargyriou, and
C onm 1.2 $/hr 12 $/hr N. Jenkins. (2003) Management of microgrids. [Online]. Available:
http://microgrids.power.ece.ntua.gr
Cf 0.02 $/kg 0.4 $/m3
LDG 20 15
XI. BIOGRAPHIES
hr 1 1
P2h 0.2 1.012564 A. P. Agalgaonkar is currently working towards his Ph.D. degree at Energy
System Engineering, Indian Institute of Technology Bombay, India. He
η 1 1 has now joined Energy Technologies, National Thermal Power Corporation
(NTPC) Noida, India. His research area includes Distributed Generation.
A PPENDIX III
M ICRO G RID DG DATA
C. V. Dobariya is currently working towards his M. Tech. degree at Electrical
Engineering Department, Indian Institute of Technology Bombay, India. His
Particular Bagasse Natural Gas Biomass Wind research area includes Distributed Generation and MicroGrid.
C cap 900 1160 900 1000
C rep 900 1160 900 1000 M. G. Kanabar is currently working towards his M. Tech. degree at Electrical
C onm 0.087 0.013 0.045∗ 0.005 Engineering Department, Indian Institute of Technology Bombay, India. His
research area includes Distributed Generation.
Cf 0.02∗∗ 0.1274∗∗∗ — —
En 2.64+ 9.675++ 3.29 —
S. A. Khaparde is Professor, Department of Electrical Engineering, Indian
LDG 20 20 20 20
Institute of Technology Bombay, India. He is member of Advisory Committee
hr 0.8 0.8 0.8 — of Maharashtra Electricity Regulatory Commission (MERC). His research area
P2h 0.15 0.67 0.5 — includes Distributed Generation and power system restructuring.