You are on page 1of 38

1 SECVT Technical Bulletin

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Commissioning an SECVT Quick Start Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SECVT and N2 Tunneling Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
N2 Tunneling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Serial to Ethernet Converter (SECVT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Supported NAEs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
N2 Tunneling and Network Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SECVT User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UI Status Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UI Configuration Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Commissioning an N2 Tunneling Application Overview . . . . . . . . . . . . . . . . . . . . . . . . 12
Guidelines for Commissioning an SECVT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connecting to, Accessing, and Navigating the SECVT UI . . . . . . . . . . . . . . . . . . . . . . . 14
Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DNS Implementation Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DHCP Implementation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Connecting to the SECVT and Accessing the UI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Navigating the SECVT UI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Checking the SECVT Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Commissioning an SECVT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Setting the Serial Network Attributes on the RS485 Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Setting the Ethernet Network Attributes on the Network Tab . . . . . . . . . . . . . . . . . . . . . . . 23
Changing the SECVT Logon Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Setting the SECVT Date and Time Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
SECVT
Technical Bulletin
MS-SECVT-0
Code No. LIT-1201790
Software Release 4.0
Issued March 17, 2008
Supersedes February 28, 2008
SECVT Technical Bulletin 2
Configuring the NAE for N2 Tunneling over Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Configuring the NAE to Communicate with Tunneled N2 Devices . . . . . . . . . . . . . . . . . . . 28
Troubleshooting the SECVT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SECVT LED Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SECVT LED Test Sequence at Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Determining Network Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Determining the N2 Message Path Using the Trace Routing Test . . . . . . . . . . . . . . . . . . . 32
Determining the NAE Message Timeout Using the PATHPING Test . . . . . . . . . . . . . . . . . 32
Determining N2 Device Status Using HVAC PRO in Pass Through Mode . . . . . . . . . . 34
SECVT Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Serial to Ethernet Converter (SECVT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
SECVT Technical Bulletin 3
SECVT
Technical Bulletin
Document Introduction
This document describes how to access, commission, operate, and troubleshoot the
Serial to Ethernet Converter (SECVT), and how to configure a supported Network
Automation Engine (NAE) to communicate with remote N2 devices via the
SECVT. This document also provides a brief overview of the N2 Tunneling over
Ethernet feature for Metasysnetworks.
This document does not describe how to locate or install the SECVT. Also, this
document does not describe Ethernet network concepts or N2 network concepts.
See Related Documentation for additional information related to applying the
SECVT and the N2 Tunneling over Ethernet feature to your Metasys network.
Related Documentation
Table 1: SECVT and N2 Tunneling over Ethernet Related Documentation
(Part 1 of 2)
For Information on See Document LIT or Part Number
Features, Benefits, and Applications of
the SECVT
Serial to Ethernet Converter Product
Bulletin
LIT-1201835
Applying, Locating, Mounting, and
Wiring the SECVT
SECVT Installation Instructions Part No. 24-10093-4
Worksheet for Gathering Required
Information for Commissioning an
SECVT and N2 Tunneling Application
Network Information Worksheet for
Commissioning the SECVT
LIT-12011170
Locating, Mounting, Wiring, and
Starting up an NAE55 Series
Supervisory Device
NAE55/NIE55 Installation Instructions Part No. 24-10051-0
Connecting, Accessing the User
Interface (UI), Commissioning, and
Troubleshooting an NAE
NAE Commissioning Guide LIT-1201519
Integrating N2 Field Controllers into a
Metasys Network
N2 Integration with the NAE Technical
Bulletin
LIT-1201683
N2 Network Design and Installation
Principles
N2 Communications Bus Technical
Bulletin
LIT-636018
Ethernet Network Design and
Installation Principles for Metasys
Networks
N1 Ethernet/IP Network Technical
Bulletin
LIT-6360175
Definitions and Routine Operating
Procedures for Metasys System
Software and UI
Metasys system Help
LIT-1201793
1
Metasys System Common Terms and
Acronyms
Metasys System Extended
Architecture Glossary Technical
Bulletin
LIT-1201612
SECVT Technical Bulletin 4
Using the System Configuration Tool
(SCT) Software, Creating, Editing, and
Downloading Archive Databases
SCT Technical Bulletin LIT-1201534
Using HVAC PRO and Pass Though to
View and Diagnose N2 Device Status
Using HVAC PRO Software in Pass
Through Mode chapter in the HVAC
Pro Users Guide
LIT-63750402
General Network and Information
Technology (IT) Definitions, Concepts,
Recommendations, and Requirements
Network and IT Guidance for the BAS
Professional Technical Bulletin
LIT-12011279
1. This LIT number represents a print friendly version of the Help.
Table 1: SECVT and N2 Tunneling over Ethernet Related Documentation
(Part 2 of 2)
For Information on See Document LIT or Part Number
SECVT Technical Bulletin 5
Commissioning an SECVT Quick Start Guide
Figure 1: Commissioning an SECVT and
N2 Tunneling Application Quick Start Guide
SECVT Technical Bulletin 6
SECVT and N2 Tunneling Overview
The SECVT, in conjunction with a supported NAE, enables N2 Tunneling over
Ethernet on Metasys networks. N2 Tunneling increases N2 application flexibility,
allows you to integrate remote N2 devices into the Metasys network, and reduces
the need for hardwired RS485 protocol N2 Buses. See Serial to Ethernet
Converter (SECVT) and Supported NAEs for more information on the SECVT and
the supported NAE models.
The SECVT and the supported NAEs are designed to convert N2 protocol data and
tunnel the converted data over Ethernet networks. Figure2 shows a simple
Metasys network with remote N2 devices communicating with a supported NAE
over a Local Area Network (LAN).
You can apply N2 Tunneling to almost all Ethernet LANs. You can also apply
N2Tunneling to Wide Area Networks (WANs) that meet N2 Tunneling
performance guidelines. See N2 Tunneling and Network Performance.
N2 Tunneling
N2 Tunneling enables remote N2 field devices to exchange N2 data with supported
NAEs across Ethernet networks. N2 Tunneling eliminates the need for a dedicated
hardwired N2 Bus between the remote N2 devices and the supported NAE. The
SECVT and a supported NAE enable N2 Tunneling over Ethernet.
N2 Tunneling is accomplished by packaging the N2 protocol data in Universal
Datagram Protocol (UDP) packets, which makes the N2 data appear on the
network as Ethernet data. Supported devices (SECVTs and NAEs), on either end
of the tunneled transmission, convert N2 data to UDP packets and UDP packets
back to N2 data.
Figure 2: Simple Metasys Network with N2 Devices Hardwired to a Supported NAE and
Remote N2 Field Devices Tunneled over Ethernet via an SECVT to the NAE
Internet
Firewall
Web Browser
on a Desktop
Computer
Ethernet
Network
Web Browser
on a Computer
NAE5512
or
NAE5513
SECVT
N2 Field
Controllers
T
U
N
N
E
L
_
O
V
E
R
V
I
E
W
N2 Data Tunneled
over Ethernet
Remote
N2 Field
Controllers
N2 Data
Traffic Over
RS-485 Bus
N2 Data
Traffic Over
RS-485 Bus
SECVT Technical Bulletin 7
N2 Tunneling on a Metasys network is virtually transparent to the user. Procedures
for accessing, configuring, controlling, and monitoring N2 field devices via an
NAE are the same for tunneled N2 devices and N2 devices hardwired to the NAE
N2network trunk. Figure3 shows a simple N2 Tunneling application and the
relationship between tunneled N2 devices, hardwired N2 devices, and the NAE
N2trunks.
Serial to Ethernet Converter (SECVT)
The SECVT is designed to convert serial N2 protocol data to UDP packets and
tunnel the N2 data across Ethernet networks to supported NAE supervisory
devices. The SECVT also receives N2 data tunneled as UDP packets from the
assigned NAE. The SECVT then converts the UDP packets back to N2 data and
routes the N2 data on to the appropriate N2 device on the SECVT N2 Bus.
The SECVT is compliant with Ethernet standards and designed to operate on
10Mb or 100 Mb Ethernet networks.
You can connect up to 32 N2 devices in an N2 device cluster on the SECVT
N2Bus. Simple N2 device clusters are shown in Figure3. The SECVT and
N2Tunneling over Ethernet feature do not affect the N2 device limits for
supported NAE models. See Table2.
The number of SECVTs that can be associated to an N2 trunk is limited by the
number of N2 devices mapped to that N2 trunk. For example, an N2 trunk on a
supported NAE supports up to 100 N2 devices; therefore, up to 100 SECVTs, each
connected to one N2 device, can be associated to an N2 trunk on a supported NAE
that does not have any hardwired N2 devices connected to the N2 trunk.
Figure 3: Simplified N2 Tunneling over Ethernet Application
Illustrating the Association of N2 Devices to the NAE N2 Network Trunks
Ethernet
Port
FC A
Port
FC B
Port
N2 Trunk 2 N2 Trunk 1
N2 Fi eld
Device 1
N2 Fi eld
Device 8
N2 Fi eld
Device 5
N2 Fi eld
Device 4
N2 Fi eld
Device 6
N2 Fi eld
Device 7
N2 Fi eld
Device 3
N2 Fi eld
Device 2
Remote N2 Device Cluster
Tunneled to N2 Trunk 1
Ethernet Network
RS-485 RS-485
RS-485
RS-485
Remote N2 Device
Tunneled to N2 Trunk 2
Standard N2 Field Trunks
N2 Fi eld Devices 1, 6, 7, and 8 are mapped to N2 Trunk 1
N2 Fi eld Devices 2, 3, 4, and 5 are mapped to N2 Trunk 2
SECVT
F
ig
:
N
2
_
T
U
N
N
L
_
S
C
H
M
SECVT
SECVT Technical Bulletin 8
Supported NAEs
The Network Automation Engine (NAE) is a Web-based supervisory device that
monitors and controls Building Automation System (BAS) field controllers and
devices on Metasys networks. The NAE also provides Web-based access to BAS
network trunks, controllers, and field devices on the Metasys network.
Supported NAE models are designed to tunnel N2 data over Ethernet to and from
remote N2 field devices via an SECVT. To apply N2 tunneling to a Metasys
network, an NAE that supports tunneling must be installed on the network.
Currently two NAE models support the N2 tunneling feature out-of-the-box: the
MS-NAE5512-0 and MS-NAE5513-0 models.
You can upgrade non-tunneling NAE55 models (only) to supported N2Tunneling
models in the field by purchasing Part No. MS-NAETUNL-8 ToggleTunnel utility,
which converts an NAE55 to an NAE55 model with the N2 Tunneling feature
enabled.
The N2 trunk and device limits for supported NAE55 models are the same for
hardwired N2 devices, tunneled N2 devices, or any combination of hardwired and
tunneled N2 devices. See Table2. The NAE55 object capacity can also limit the
number of N2 devices in your N2 Tunneling application.
An NAE5512 or NAE5513 with Metasys Release 3.1 software supports two
methods of Internet Protocol (IP) address assignment: static and Dynamic Host
Configuration Protocol (DHCP).
Note: If you encounter communication issues, we recommend using static
address assignment.
Ethernet Port
S
E
C
V
T
180
7.1
127
5.0
58
2.3
N2 Bus Pluggable
Terminal Block
Mounting
Clips (3)
Restore Defaults
Button (Recessed)
End-of-Line
(EOL)
Switches
Figure 4: Serial to Ethernet Converter, Physical Features
and Dimensions, mm (in.)
SECVT Technical Bulletin 9
N2 Tunneling and Network Performance
Your networks performance and data capacity can limit N2 Tunneling
applications on your network. The NAE and SECVT are compliant with Ethernet
standards, and both devices can operate on 10 Mb or 100 Mb networks.
N2Tunneling is designed to operate on most LAN applications and on WAN
applications that maintain certain network performance criteria. See Table10 on
page33 for N2 Tunneling performance guidelines.
A networks data capacity rarely limits N2 Tunneling applications. The N2 data
transmission between an SECVT and an NAE consumes very little bandwidth, less
than 0.5% of the usable bandwidth on a 10 Mbps Ethernet network.
The primary limiting factor on most N2 Tunneling applications is the time it takes
for tunneled data packets to traverse the network (and network devices) between
an SECVT and a supported NAE. Routers, firewalls, Network Address Translators
(NATs), and other network devices can delay the transfer of tunneled packets.
Significant packet delays may result in N2 devices periodically going offline to the
supported NAE.
Note: If you are using static IP addresses, and your network uses NATs to
communicate across the Internet, the NATs must provide static internal and
external IP addresses. If you are using Dynamic Host Configuration
Protocol (DHCP) to assign addresses to SECVTs that communicate across
networks that use NAT, your DHCP server should be configured to always
allocate the exact same IP address to the SECVT's MAC addresses. This
configuration makes these SECVTs behave as if they have static IP
addresses, although they have DHCP addresses (sometimes called
Dynamically Assigned, Statically allocated addresses from a DHCP
server). Dynamic network address translation may result in N2 device
offline conditions.
Table 2: N2 Tunneling Features and Devices on NAE55 Models
N2 Tunneling Features and
Devices
Standard
Non-Tunneling
NAE55 Models
N2 Tunneling over
Ethernet with
SECVTs
Number of N2 Trunks 2 2
Number of N2 Trunks That Support N2
Tunneling
0 2
Number of N2 Devices Supported on
an N2 Trunk
Up to 100
(Hardwired to FC Bus
Only)
Up to 100
(Hardwired and/or
Tunneled over Ethernet)
Number of Converters Supported on
an N2 Trunk
Up to 100
Number of N2 Devices Supported on
a Converter N2 Bus Cluster
N/A Up to 32
Simultaneous Support of N2 Devices
That Are Hardwired and Tunneled
over Ethernet
No Yes
Simultaneous Support of N2 Devices
That Are Hardwired and Tunneled
over Ethernet
No Yes
SECVT Technical Bulletin 10
On LAN applications, tunneled packets typically traverse only in-house routers.
Since the delay on in-house routers on a LAN is usually a few milliseconds, the N2
data transfer is unaffected.
On WAN applications, the tunneled packets may have to traverse firewalls, NATs,
and third-party routers, all of which can significantly delay N2 data transfer
causing the transfer time to exceed the required message timeout value.
Before installing the devices on large LANs and all WANs, we recommend testing
the message cycle time between the subnet on which the NAE resides and the
subnets on which any SECVTs reside. Install the NAE and SECVT on your
network on subnets that exhibit the shortest message cycle times. A successful
N2Tunneling application requires a total message cycle time of less than 1,000ms
between the NAE and SECVT. See Determining Network Performance for more
information on testing your network.
We also recommend providing the customers network administrator or IT
department with a copy of the Network Information Worksheet for Commissioning
the SECVT (LIT-12011170). The worksheet is used to determine network
performance and the viability of an N2 tunneling application on the customer
network. The worksheet is also used to gather the IP network address information
required for commissioning and connecting SECVTs on the customers network.
The frequency of offline conditions on N2 Tunneling applications increases as the
transfer time between the NAE and SECVT increases. When applying the N2
Tunneling feature to network applications that approach the N2 Tunneling
performance limits, we recommend using only those N2 devices and applications
that can operate independently of the NAE and the Metasys system. See Table10
on page33.
After your N2 Tunneling application is set up, fluctuating network traffic loads and
changes to the network may adversely affect N2 data transfer time. Retest your
N2Tunneling application to verify the total message cycle time whenever N2
devices go offline.
SECVT User Interface
The SECVT has a browser-based UI for commissioning and monitoring the
Converter. Access the SECVT UI using MicrosoftInternet Explorer Version 6.0
or later. See Detailed Procedures for more information on accessing the SECVT
UI.
UI Status Page
The SECVT UI Status page provides information that identifies the Converter, the
selected RS485 baud rate, and the SECVT firmware revision. The Status page also
provides a log of events.
There are two tabs on the SECVT Status page:
The About tab provides information about the SECVT identity on the network
and the firmware revision (Figure5).
SECVT Technical Bulletin 11
The Events tab provides a list of the 200 most recent SECVT reboots or power
losses. After 200 events are recorded, the oldest event is deleted when a new
event is added to the list.
The SECVT Reboot button is also found on the Status page (Figure5). Clicking
Reboot opens a reboot confirmation page. Confirming the reboot cycles the power
to the SECVT, which resets the Converter date and time to the default setting. You
must reenter the date and time values after rebooting the SECVT. See Setting the
SECVT Date and Time Values. A complete SECVT reboot takes less than 1 minute.
UI Configuration Page
Commission the SECVT for operation in your application by selecting or entering
the appropriate attribute values on the tabs on the Configuration page. Figure6
shows the RS485 tab (in edit mode) on the Configuration page.
There are four tabs on the SECVT Configuration page:
The RS485 tab establishes the RS485 and N2 Bus parameters.
The Network tab establishes the SECVT host name, IP address, and network
routing information for the Ethernet network.
The Administration tab establishes the logon passwords.
The Time tab establishes the SECVT time and date.
Figure 5: About Tab on the SECVT Status Page
Converter Reboot Button
VER_1_0
SECVT Technical Bulletin 12
Detailed Procedures
Commissioning an N2 Tunneling Application Overview
Commissioning an N2 Tunneling application begins with good planning and
design. Figure1 is a flowchart of steps for commissioning an SECVT and
supported NAE for N2 Tunneling applications.
An N2 Tunneling application requires very little bandwidth on the network, but
network firewalls, routers, switches, and other network devices may impede
N2messages and limit your tunneling application. See N2 Tunneling and Network
Performance.
Before installing the SECVT on WAN applications, we strongly recommend
testing the network route and determining the response time between the subnet on
which the supported NAE resides and the subnet on which any SECVTs are to
reside. See Determining Network Performance for procedures on testing your
network application.
To commission an N2 Tunneling application:
1. Obtain the required attribute values for commissioning the SECVT, the
supported NAE, and the N2 Tunneling application from your customers
network administrator or IT department.
Figure 6: RS485 Tab on the Configuration Page
SECVT Technical Bulletin 13
To gather the network information required for commissioning an SECVT and
N2 tunneling over Ethernet application, provide the Network Information
Worksheet for Commissioning the SECVT (LIT-12011170) to the customers
network administrator or IT department.
If you are using static IP addresses, see DNS Implementation Considerations.
Required attribute values include:
a unique IP address for each SECVT to be commissioned
the subnet mask and default gateway for each SECVT
the required UDP port address (if the default port addresses cannot be used)
the unique N2 device addresses for all N2 devices in the device cluster on
the SECVT N2 Bus
the N2 objects required to add the N2 devices to the Metasys site database
If you are using DHCP IP addresses, see DHCP Implementation
Considerations. Required attribute values include:
the host name of each SECVT to be commissioned
the default gateway for each SECVT
the required UDP port address (if the default port addresses cannot be used)
the unique N2 device addresses for all N2 devices in the device cluster on
the SECVT N2 Bus
the N2 objects required to add the N2 devices to the Metasys site database
Note: To use DHCP addressing, an NAE5512 or NAE5513 with Metasys
Release 3.1 software is required.
2. Obtain the SECVTs and supported NAEs for your application. Commission
each SECVT (one at a time) before installing it or connecting it to the network.
If you are using static IP addresses, record the new IP address for each SECVT
(on the labels provided) as you commission the devices. You can commission
and configure the supported NAE on the network or before you install the NAE
on the network.
3. Install the supported NAE and connect it to the network (if it is not already
installed and connected). Connect the SECVT at the appropriate location on
the network. Install the N2 devices, and connect them to the SECVT N2 Bus.
See Related Documentation for references to information on configuring
N2devices and an N2 Bus.
4. If your N2 application experiences N2 device offline conditions, determine the
network performance. See Determining Network Performance for performance
guidelines and procedures for testing the network.
SECVT Technical Bulletin 14
Guidelines for Commissioning an SECVT
Always commission the SECVT before installing it on the network.
All SECVTs are shipped with the same default IP address
(http://169.254.0.10). If you are commissioning more than one SECVT, apply
power to, connect to, and commission only one Converter at a time.
Clicking Save in the SECVT UI saves the changes on the displayed tab to
temporary (volatile) memory. Clicking Apply All Changes saves all
temporarily saved changes to nonvolatile memory and implements the
changes. See Navigating the SECVT UI for more information.
Do not click Apply All Changes on the Configuration page until all new
attribute values in all of the tabs are entered correctly. After you enter the new
Network tab values, clicking Apply All Changes changes the SECVT IP
address and breaks the Ethernet connection between your computer and the
SECVT. See Navigating the SECVT UI for more information.
If the connection between your computer and the SECVT is lost during
commissioning, and you cannot reestablish the connection, you can press the
Restore Defaults button to restore the original SECVT default values. Press
and hold the Restore Defaults button for at least 5 seconds. The red FAULT
LED should blink four times. Then the SECVT reboots and restores the
attributes to the original default values, including the default IP address you
used to connect.
Note: After restoring the default values, you have to reenter all of the values
you changed prior to pressing the Restore Defaults button.
The values entered into the Date and Time fields do not advance until you
Apply All Changes. To ensure that the date and time displayed on the SECVT
are synchronized with real time, you should set the date and time after
commissioning and installing the SECVT on the network.
Set the End-of-Line (EOL) switches to the proper position on the SECVT and
on any other N2 device on the N2 Bus. Refer to the SECVT Installation
Instructions (Part No. 24-10093-4) for information on setting the SECVT EOL
switches.
When an SECVT is applied to the network and powered on for the first time, it
may take up to 5 minutes for the network to locate the new SECVT and register
the new IP address and Media Access Control (MAC) address. The SECVT
does not operate as intended until these addresses are registered with the
appropriate devices on the network.
Connecting to, Accessing, and Navigating the SECVT UI
SECVT Technical Bulletin 15
Requirements
You need the following items to connect to an SECVT, access an SECVT Web UI,
and commission the SECVT for network operation:
an SECVT
a 24 VAC, 20 VA minimum, Class 2 power supply
a computer with an RJ 45 Ethernet port and Internet Explorer Version 6.0
an Ethernet cable (patch cable or crossover cable)
Note: The SECVT is designed to be connected directly to a computer
Ethernet port during the commissioning procedure. The SECVT detects
the cable polarity at the Ethernet port and automatically configures
itself to communicate with the computer via a patch cable or a
crossover cable. A hub or switch is not required.
DNS Implementation Considerations
The Domain Name Server (DNS) infrastructure must be configured to do the
following:
The Metasys server and/or Metasys engine and Metasys DHCP supported
devices (SWECVT, WRS-RTN Many-to-One Receivers) must be defined in
the same DNS domain.
The Metasys server and/or Metasys engine and Metasys DHCP supported
devices (SWECVT, WRS-RTN Many-to-One Receivers) require DNS servers
defined to resolve hosts in the domain which they are in.
We recommend that the Metasys server and/or engine and Metasys DHCP
supported devices (SWECVT, WRS-RTN Many-to-One Receivers) be in a
separate Virtual Local Area Network (VLAN) from all other devices at the
customers site.
If the DNS server and the Metasys server and/or Metasys engine are in
different networks (VLANs), routing must be available between networks.
DHCP Implementation Considerations
For Metasys devices to function properly in a DHCP implementation, the DHCP
servers must support dynamic DNS. The DHCP infrastructure must be configured
to do the following:
The DHCP server must create an A record in the defined DNS domain upon
handing a lease to a Metasys device. Optionally, you can configure the DHCP
server to update the PTR (pointer) record of the Metasys DHCP supported
device in the reverse zone DNS domain.
The domain for DNS updates must be included in the DHCP server
configuration. The Metasys DHCP supported device does not specify the
domain.
SECVT Technical Bulletin 16
The Metasys server and/or Metasys engine and the Metasys DHCP supported
devices (SECVT, WRS-RTN Many-to-One Receivers) all must be in the same
DNS domain.
We recommend that the Metasys server and/or Metasys engine and the
Metasys DHCP supported devices (SECVT, WRS-RTN Many-to-One
Receivers) be in a separate VLAN from all other devices at the customers site.
If the DNS server, Metasys server, Metasys engine, and/or Metasys DHCP
supported devices (SECVT, WRS-RTN Many-to-One Receivers) are in
different networks (VLANs), ensure that routing is available between networks
and that a proper router is passed in the DHCP lease.
If the DHCP server is not is the same VLAN as the Metasys devices, enable
DHCP forwarding to the proper DHCP server on the VLANs on which the
Metasys devices are located.
Metasys devices require that you configure the following DHCP options in the
DHCP server in addition to the IP address and subnet mask:
To gather the network information required for commissioning an SECVT and N2
tunneling over Ethernet application, provide the Network Information Worksheet
for Commissioning the SECVT (LIT-12011170) to the customers network
administrator or IT department.
Connecting to the SECVT and Accessing the UI
To connect to the SECVT and access the UI:
1. Turn on your computer, and connect the SECVT to the computer with an
Ethernet cable.
2. Power on the SECVT and allow it to go through its startup sequence.
Note: When the SECVT is powered On, it goes through a startup sequence.
See SECVT LED Test Sequence at Startup for more information.
3. In the Start menu on your computer, click Settings >Control Panel >Networks
and Dial Up to check the status and enable the local Ethernet network.
4. In the General menu dialog box, scroll to and click Internet Protocol
(TCP/IP) to highlight the text and click Properties. Ensure that a valid IP
address and subnet mask are assigned to the computer for the Ethernet network
connection to the SECVT. Valid IP addresses and subnet mask are:
IP Address =169.254.0.x (where x =any value between 2 and 255 other
than 10)
Subnet Mask =255.255.255.0
Table 3: DHCP Options
Option Description
Option 003 Router
Option 006 DNS Servers
Option 015 DNS Domain Name
SECVT Technical Bulletin 17
Note: Record the original network settings and IP address for your computer
before changing the setting values, so you can restore the original
values after you have commissioned the SECVT.
5. If necessary, enter a valid IP address and subnet mask in the Properties dialog
box.
6. Click OK.
7. With the network enabled, start Internet Explorer. Type the SECVT default IP
address (http://169.254.0.10) into the Address bar and press Enter. The
SECVT logon dialog box appears (Figure7).
8. In the logon dialog box, type the default User name (admin) and Password
(admin). An opening flash page (Figure8) appears for approximately
5seconds, and then the SECVT UI Home page opens (Figure9).
Note: The User name guest and the Password guest are available for SECVT
users who need to view the UI but do not need to edit any of the values
in the SECVT UI.
You should be logged on to the SECVT and ready to navigate the Web UI.
Figure 7: SECVT UI Logon Dialog Box
Default Password is admin
SECVT Technical Bulletin 18
Figure 8: SECVT UI Opening Flash Page
Figure 9: SECVT UI Home Page
SECVT Technical Bulletin 19
Navigating the SECVT UI
You navigate the SECVT UI just like a typical Web site.
Page links are on the left side of the page. From the Home page, the Page links go
to the Configuration and Status pages. Click a tab to open the associated property
sheet.
Figure10 shows a typical SECVT UI screen, the RS-485 tab (in edit mode).
Page Command buttons (Figure10) are above the Attribute and Value tables on
each of the Configuration tabs:
The Edit button opens an editable screen.
Note: All tabs and page links on the editable screen are disabled, and only the
Save, Reset, and Cancel page command buttons are active.
The Save button saves the edited attribute values on the screen to temporary
memory (Figure10).
Note: After you click Save, a command in red type appears just below the
tabs stating that you must click Apply All Changes to save the edited
values to permanent memory and implement the changes on the
SECVT (Figure11). Do not click Apply All Changes until you have
entered, saved, and reviewed all of the required attribute values on all
Configuration tabs in the SECVT UI.
Figure 10: RS485 Tab on the Configuration Page
SECVT UI
Page Links
Page Command Buttons
Active Tab
Editable Values: Select
the Required Value
SECVT Technical Bulletin 20
The Reset button resets the attribute values on the screen to the last saved
values (Figure10).
The Cancel button cancels all changes on the screen (Figure10).
Two Changes Command buttons are on the lower left of the Configuration page
(Figure11) whenever you are in a Tab screen:
The Apply All Changes button saves (to nonvolatile memory) all of the
temporary (volatile) changes that were saved on the various tabs and
implements the changes on the SECVT.
Note: Do not click Apply All Changes until after you have edited and
reviewed all required values in the SECVT UI. Clicking Apply All
Changes saves and implements the edited values on the SECVT,
including the new IP address. When the SECVT IP address is changed,
the network connection to your computer is broken.
The Cancel All Changes button cancels all of the temporary (volatile) values
that were changed and (temporarily) saved on the various tabs and reverts the
values to the previously saved (nonvolatile) values.
Figure 11: Network Tab on the Configuration Page
with the Apply All Changes Command (in Red)
Changes Command
Buttons
Apply All Changes Command
SECVT Technical Bulletin 21
Checking the SECVT Status
The SECVT UI has two tabs on the Status page that provide information about the
Converter. See UI Status Page for more information.
Note: You cannot edit any of the attribute values while on the Status page. Some
of the attribute values on the Status page can be changed on the
Configuration page. Some of the values (such as the MAC address) are
fixed. Some of the values (like the software version) can be changed by
updating the software. Any attribute value changes appear as new value in
the Status page tabs after you Apply All Changes.
To check the tabs on the Status page:
1. From anywhere in the SECVT UI, click the Status page link, and the Status
page About tab appears (Figure5).
2. Click the Events tab to go to the Events tab.
Commissioning an SECVT
Setting the Serial Network Attributes on the RS485 Tab
For the SECVT to communicate with the N2 field devices on its N2 Bus, you must
configure the RS485 serial network attributes on the Configuration page RS485
tab.
Note: Only the N2 Protocol value is available on the SECVT in this release.
Additional protocols will be available in future releases of the
Metasyssystem extended architecture.
To set the serial (N2) network attributes on the RS485 tab:
1. In the SECVT UI, click Configuration. The Configuration page appears.
Click the RS485 tab, and the RS485 tab opens.
SECVT Technical Bulletin 22
2. Click Edit (Figure12).
3. Select the appropriate values for the N2 field devices connected to the SECVT
according to Table4.
4. Review the new values and then click Save to save the new values to
temporary memory.
Table 4: RS485 Tab Attributes and Values
Attribute Attribute Description Default
Value
Valid Values
Protocol Select the appropriate protocol for the RS-485 field
bus.
Note: N2 is currently the only usable value for the
Protocol attribute.
N2 N2
Baud Rate Select the Protocol first, then select the
appropriate baud from the drop-down menu.
Note: 9600 is currently the only available value
for the Baud Rate attribute.
9600 N2 baud is 9600
(Do not select any other baud
for N2 protocol.)
Data Bits Select the data bits setting from the drop-down list. 8 7, 8
Parity Select the parity setting from the drop-down list. No No, Even, Odd
Stop Bits Select the stop bits setting from the drop-down list. 1 1, 2
Figure 12: RS485 Tab on the Configuration Page
SECVT Technical Bulletin 23
Note: Click Apply All Changes on the Configuration page to save all of the
edited values to nonvolatile memory. Clicking Apply All Changes may
break the Ethernet connection between your computer and the SECVT.
Do not click Apply All Changes until you have edited and reviewed all
the required values for the SECVT setup.
5. Open the next tab you need to edit.
Setting the Ethernet Network Attributes on the Network Tab
For the SECVT to communicate over the Ethernet network, enter the SECVT host
name and other network attributes on the Configuration page Network tab
(Figure13).
To gather the network information required for commissioning an SECVT and N2
tunneling over Ethernet application, provide the Network Information Worksheet
for Commissioning the SECVT (LIT-12011170) to the customers network
administrator or IT department.
To establish or change the Ethernet network attribute values on the Network tab:
1. In the SECVT UI, click Configuration. The Configuration Page appears. (By
default the Configuration page opens with the RS485 tab displayed.) Click the
Network tab and the Network tab opens.
2. Click Edit to open the Network tab (Figure13).
Figure 13: Network Tab
SECVT Technical Bulletin 24
3. Select or type the appropriate attribute values for the Ethernet network
according to Table5.
4. Review the new values, and then click Save to save the new values on the
Network tab to temporary memory.
Note: You must click Apply All Changes on the Configuration page to save
all of the edited values to nonvolatile memory, but do not click Apply
All Changes until you have edited and reviewed all the required values
for the SECVT setup. Clicking Apply All Changes breaks the Ethernet
connection between your computer and the SECVT.
5. If you are using static IP addresses, record the new IP address on the SECVT
label. If you are using DHCP addresses, record the host name on the SECVT
label.
Note: The host name may contain a maximum of 15 characters and may comprise
alphabet letters, numbers, and dashes.
6. Open the next tab you need to edit.
Changing the SECVT Logon Passwords
The SECVT has three User names for logging on to the UI. The User name value
cannot be changed. The three Password fields have default values. You can change
the default Password values and establish new Passwords for logging on to the
SECVTs in your application.
The UI logon feature also provides two levels of privilege when accessing the UI:
User privilege allows the user to check the SECVT status (only). There is one
User name for user privileges: guest.
Administrator privilege allows the user to check the SECVT status and
change all of the attribute values. There are two User names for administrator
privileges: admin and manager.
Table 5: Network Tab Attributes and Values
Attribute Attribute Description Default Value Valid Values
Host Name If you are using DHCP IP addresses, type the
host name of the SECVT.
Converter1 15 character maximum
comprising only
alphabet letters,
numbers, and dashes
DHCP Enabled Select Yes if you are using dynamic IP
addresses, select No to disable DHCP.
No Yes or No
IP Address
(Converter)
If you are using static IP addresses, type the
IP address assigned to the SECVT by your IT
department.
169.254.0.10 x.x.x.x (IP Version 4)
UDP Port
Number
Type the UDP Port number on the supported
NAE that the SECVT sent UDP packets to.
4096 1024 to 65535
Subnet Mask Type the subnet mask address that the SECVT
resides on.
255.255.255.0 x.x.x.x (IP Version 4)
Default
Gateway
Type the default gateway address. 169.254.0.1 x.x.x.x (IP Version 4)
SECVT Technical Bulletin 25
Table6 describes the attributes and values on the Administration tab.
To change the SECVT Password values:
1. Access the SECVT UI, go to the Configuration page, and click the
Administration tab. The Administration tab opens.
2. Click Change Password (Figure14).
3. Type the current password values where appropriate, and type your new
password in the New Password field. Then type your new password again in
the Reenter New Password field to confirm.
4. Click Save to save the new values to temporary memory.
Note: You must click Apply All Changes on the Configuration page to save all
of the temporarily save values to nonvolatile memory, but do not click
Apply All Changes until you have edited and reviewed all the required
values for the SECVT setup. Clicking Apply All Changes breaks Ethernet
connection between your computer and the SECVT.
5. Record the new Password values and store them in an appropriate place.
Table 6: Administration Tab Attributes and Values
Attribute Attribute Description Default Value
admin Logon password for administrative privileges (customer or on-site administrator). admin
manager Logon password for administrative privileges (J ohnson Controlsadministrator). manager
guest Logon password for user privileges (all other users). guest
Figure 14: Administration Tab on the Configuration Page
SECVT Technical Bulletin 26
Setting the SECVT Date and Time Values
The SECVT uses the date and time to log events to the Events Log.
Note: To ensure that the SECVT date and time are synchronized with real time,
you should set the date and time after the SECVT is commissioned and
installed on the production network.
The Time and Date values revert to the factory default settings
(01-01-1970, 12:00AM) whenever the SECVT loses power or is rebooted,
or whenever the Restore Defaults button is pressed.
To set Date and Time values for the SECVT:
1. Connect your computer to the network to which the SECVT is connected. Start
Internet Explorer on your computer. If you are using static IP addresses, type
the (new) SECVT IP address into the Address bar. If you are using DHCP IP
addresses, type the host name into the Address bar. Press Enter and log on to
the SECVT.
2. Access the SECVT UI, go to the Configuration page, and click the Time tab.
3. Click Edit (Figure15).
4. Enter the current date and time values.
5. Click Save to save the new values to temporary memory.
Figure 15: Time Tab on the Configuration Page
SECVT Technical Bulletin 27
6. Click Apply All Changes immediately to apply and implement the new date
and time values.
Note: The values entered into the Date and Time fields do not advance until
you Apply All Changes.
7. Close the SECVT UI and disconnect your computer from the network.
Configuring the NAE for N2 Tunneling over Ethernet
To apply N2 Tunneling over Ethernet to your Metasys network, a supported NAE
must be on the network. If you are using a static IP address, you must map the
SECVT IP address and the tunneled N2 devices to an N2 trunk on the supported
NAE. If you are using a DHCP IP address, enter a host name for the SECVT. The
host name may contain a maximum of 15 characters and may comprise alphabet
letters, numbers, and dashes.
Note: To use DHCP addressing, an NAE5512 or NAE5513 with Metasys Release
3.1 software is required.
Each of the N2 devices mapped to the NAE N2 Trunk (tunneled and hardwired)
must be assigned a unique N2 address so that the NAE can identify and
communicate with the individual N2 devices.
Install, commission, and configure the supported NAE per instructions. See
Related Documentation for references to information on installing,
commissioning, and configuring an NAE.
Note: You can configure the NAE online or offline using the System
Configuration Tool (SCT). We recommended that you configure the NAE
offline in SCT and download the configured archive database to the SCT.
See Related Documentation for references to information on creating,
editing, and downloading archive databases.
Requirements
You need the following items to configure a supported NAE to tunnel to
N2devices:
a computer with Internet Explorer Version 6.0 or later (and with SCT to
configure the supported NAE offline)
a commissioned and configured NAE that supports the N2 Tunneling feature.
See Supported NAEs. The NAE must have the Device objects for the tunneled
N2 devices configured in the NAE archive database.
Note: The NAE Auto-Discovery feature cannot find N2 devices that are
tunneled to the NAE. The NAE must contain a database with the device
objects for the N2 devices that are tunneled to the NAE.
a fully commissioned and installed SECVT with a 24 VAC, 20 VA minimum
Class2 power supply
SECVT Technical Bulletin 28
one or more N2 field devices wired in an N2 device cluster to the SECVT
N2Bus. (See Table2 for information on N2 device limits for N2 network
trunks on tunneling applications.) Each device mapped to an N2 trunk must
have a unique N2 Address.
Configuring the NAE to Communicate with Tunneled N2 Devices
To configure the supported NAE to communicate with tunneled N2 devices:
1. Log on to the supported NAE.
2. Drag and drop the target N2 Trunk into the Display panel. Click on the
N2Network Hardware tab.
3. Select the Advanced radio button, and then click Edit (Figure16).
Figure 16: N2 Network Advanced Hardware Tab
SECVT Technical Bulletin 29
4. Set the attribute values in the N2 Network Hardware Advanced tab according
to Table7.
5. Navigate to the N2 Device object for an N2 device that is connected to the
target SECVT N2 Bus and click the Hardware tab (Figure17).
Table 7: N2 Network Advanced Hardware Tab
Attribute Value
Trunk Number N2 trunk number 1 (=FC A port)
N2 trunk number 2 (=FC B port)
Select the N2 trunk you are tunneling N2
devices to. (Hardwire N2 to the FC port
associated with the N2 trunk.)
UDP Port Type in a UDP port number (between 1024 to
65535) to specify the UDP port where the NAE
receives tunneled N2 data. This number must
equal the port number entered on the Network
tab on the target SECVT.
4096 is the recommended UDP port number for
N2 trunk number 1 on the NAE.
4097 is the recommended UDP port number for
N2 trunk number 2 on the NAE.
Retries 5 (Range is 3 to 8)
Poll Delay 100 (Range is 100 to 1,000 ms)
Message Timeout 1750 (Range 250 to 3,000 ms)
See Determining Network Performance.
Diagnostic Messages False
Figure 17: An N2 Device Hardware Tab
SECVT IP Address for
Static addressing
Unique N2 Address
for N2 Field Device
SECVT host hame for DHCP addressing
SECVT Technical Bulletin 30
6. Click Edit to open the N2 Device Hardware tab. Set the attribute values
according to Table8.
7. Repeat Steps 4 and 5 for each N2 device on the SECVT N2 Bus.
8. Reboot the NAE.
The NAE should be ready to communicate with the remote N2 devices on the
SECVT N2 Bus at the designated IP address or host name.
Note: If the SECVT fails to come online after commissioning the device, see
Troubleshooting the SECVT.
Note: Your system must be commissioned before inserting an SECVT. The
device object must exist on the N2 trunk.
Table 8: N2 Device Hardware Tab Settings
Field Setting
Controller Type Set to N2 controller type you are using.
Net N2 Address Set to the N2 address of the N2 device. (N2 addresses are
typically set with a DIP switch on the N2 device.)
Host Name If using DHCP IP addresses, type in the host name of the
SECVT (to which the N2 device is connected).The host name
contains a maximum of 15 characters and may comprise
alphabet letters, numbers, and dashes.
IP Address If using static IP addresses, type in the IP address of the SECVT
(to which the N2 device is connected).
SECVT Technical Bulletin 31
Troubleshooting the SECVT
This section of this document provides information for troubleshooting an SECVT,
and troubleshooting SECVT communication with the supported NAE and the
N2devices. This section also provides information on how to determine network
performance related to N2 Tunneling. This section does not describe how to
troubleshoot NAEs, Ethernet networks, or N2 networks. See Related
Documentation for references to information about NAEs, Ethernet networks, and
N2 networks.
SECVT LED Status Indicators
The SECVT provides Light-Emitting Diode (LED) status indicators that are useful
for troubleshooting the SECVT.
The SECVT has six LEDs that provide status information.
SECVT LED Test Sequence at Startup
During startup, the SECVT automatically initiates an LED test sequence to verify
the operational status of the LEDs. Immediately after connecting supply power, the
following LED lighting sequence occurs:
1. The POWER LED lights, and then all of the remaining LEDs light.
2. The POWER LED remains lit while all other LEDs go to Normal operation as
indicated in Table9.
Note: If the LEDs do not go to normal operation, use Table9 to diagnose the
problem.
Table 9: SECVT LED Designations, Descriptions, and Indications
LED Label LED Color Normal Descriptions/Other Conditions
POWER Green On Steady On Steady =Power is on.
Off =Power is off.
FAULT Red Off Off Steady =No Faults
On Steady =Device Fault
Blink =Ethernet Network Fault
N2 BUS Green Flicker Flicker =Normal communications; N2 port is transmitting and
receiving data. Flickers are generally in sync with data transmission
but should not be used to indicate specific transmission times.
Off Steady =No N2 traffic on the SECVT N2 Bus.
10 Link
1
1. Only one LINK LED is on at a time.
Green -- On Steady =Ethernet connection is established at 10 Mbps.
100 Link
1
Green -- On Steady =Ethernet connection is established at 100 Mbps.
Ethernet Green Flicker Flicker =Data is transferring on the Ethernet connection. Ethernet
traffic is general traffic (may not be for the SECVT).
Off Steady =No Ethernet traffic, probably indicates a dead Ethernet
network or bad Ethernet connection.
SECVT Technical Bulletin 32
Determining Network Performance
Network performance determines the viability of your N2 Tunneling application.
See N2 Tunneling and Network Performance for more information. The following
tests help to determine your networks performance.
These tests should be performed prior to installation on all WAN applications.
These tests should also be performed after changes are made to your network or
whenever your N2 application exhibits an increase in N2 device offline conditions.
Refer to the Microsoft WindowsHelp system on your computer for more
information about and examples of these tests.
Determining the N2 Message Path Using the Trace Routing Test
Use the trace routing test to determine the devices or nodes that tunneled N2 data
must traverse between the subnet on which the supported NAE is to reside and the
subnets on which any associated SECVTs are to reside. The trace routing test also
determines the time (in milliseconds) for a message to pass between devices along
the route. The test can be used to determine which network devices are impeding
the tunneled messages. Search for tracert command in Windows Help for more
information.
Note: Do not use the trace route test result times to determine network
performance in Table10. Use the PATHPING test result times to determine
network performance.
To perform this test, you need to know the IP address (or host name) of a device on
the target subnet.
To perform the trace routing test:
1. Connect your computer with an Ethernet cable to either the subnet on which
the NAE is to reside or the subnet on which the SECVT are to reside.
2. Click Start > Run... to open the Run... dialog box.
3. Type cmd in the Run... dialog box and click OK to open a DOS window.
4. Type tracert (after C:\>) followed by a space and then the IP address of the
target device on the target subnet.
5. Press Enter.
The trace route test sends several test messages from your computer to the target IP
address and provides a tabulation of the resulting message delays between devices.
Refer to Windows Help for more information on deciphering the trace route test
results.
Determining the NAE Message Timeout Using the PATHPING Test
Use the PATHPING test to verify that a device on the network can communicate
with other devices on the network and to determine the message delay between the
various devices that the message traverses on the network. Search for pathping
command in Windows Help for more information.
SECVT Technical Bulletin 33
Use the average total PATHPING time to determine the total message cycle time
between an SECVT and the supported NAE. See Table10.
To perform the PATHPING test, your computer must be configured to use
Transfer Control Protocol/Internet Protocol (TCP/IP) protocol and at least one
device (with an IP address) must be connected to the target subnet.
To perform the PATHPING test:
1. Connect your computer with an Ethernet cable to the subnet on which the NAE
is to reside.
2. Click Start > Run... to open the Run... dialog box.
3. Type cmd in the Run... dialog box and click OK to open a DOS window.
4. Type pathping (after C:\>) followed by a space and then the IP address (or
host name) of the target device on the subnet on which the SECVT is to reside.
5. Press Enter.
If you get a reply and test result times, your computer and the target device are
communicating on the network.
If you do not get a reply, try to PATHPING your own computer IP address.
If you can PATHPING your computers IP address, but not any other IP
addresses, check the TCP/IP properties of the Ethernet connection on your
computer and make sure the IP address is set to the same subnet as the NAE.
If you do not get a reply from your computers IP address, make sure that any
wireless connection is disabled and the Ethernet connection is enabled on your
computer.
Table 10: Estimated N2 Tunneling Performance Based on PATHPING Test
Average Total
PATHPING
Time (ms)
Total Message
Cycle Time
(ms)
N2 Tunneling Application Performance
<25 <50 Excellent, no noticeable difference from a hardwired N2
Bus.
25-50 <100 Good, slight delays may be noticed on devices that
display a user interface.
50-150 100-300 Acceptable, but recommended for N2 devices or
N2 applications that can operate independently of the
NAE and Metasys system.
150-500 300-1000 Application specific, recommended only for specialized
N2 applications that can run independently of the NAE and
Metasys system.
>500 >1000 Unacceptable, delays are too long, hardwire the N2
device or N2 application, or find a faster Ethernet route.
SECVT Technical Bulletin 34
The test result times generated by the PATHPING test are representative of the
network performance when the test is performed. The results are also for only one
PATHPING test attempt. We suggest testing at different times (especially during
peak network usage) and using the -q parameter to provide results that include a
number of test attempts. Refer to Windows Help for more information on using the
-q parameter.
See Table10 to determine your networks performance and what Message Timeout
and N2 Retries values to set on the supported NAE.
Determining N2 Device Status Using HVAC PRO in Pass Through
Mode
If you have HVAC PRO on your computer, you may be able to connect your
computer to the supported NAE and view remote tunneled N2 devices in Pass
Through mode.
Refer to the HVAC PRO Users Guide (LIT-63750402) for information on using
HVAC PRO. Refer to Chapter 17 Using HVAC PRO Software in Pass Through
Mode for information on using Pass Through mode.
SECVT Troubleshooting Guide
Table 11: Troubleshooting the SECVT (Part 1 of 3)
Problem or Symptom Cause
Action
SECVT Inoperable;
None of the LEDs are lit.
No 24 VAC power (or bad power) to SECVT.
Check power supply and power connections. (Refer to the SECVT Installation
Instructions [Part No. 24-10093-4] for power supply and wiring information.)
Damaged SECVT.
Check power supply and power connections.
SECVT Inoperable;
Red Fault light is On.
SECVT in Fault condition (Fault LED On steady =Device Fault).
Determine source of the device fault. Cycle 24 VAC power to SECVT to reboot.
SECVT in Fault condition (Fault LED Blinking =Ethernet Network Fault).
Check Ethernet network for possible problems and resolve any Ethernet network
problems. Cycle 24 VAC power to SECVT to reboot.
Cannot establish direct
connection between
computer and SECVT;
Both the 10 LINK and 100
LINK LEDs are Off.
Bad physical connection between computer and SECVT.
Check Ethernet cable and port connections. Replace Ethernet cable.
Note: The SECVT is designed to connect directly to a computer Ethernet port
during the commissioning procedure. The SECVT detects the cable polarity
at the Ethernet port and automatically configures itself to communicate with
the computer via a patch cable or a crossover cable. A hub or switch is not
required.
Cannot establish direct
connection between
computer and SECVT;
Status LEDs Normal and
either the 10LINK or 100LINK
LED is On.
Computer Internet Protocol (IP) address incorrect or Ethernet network disabled.
Check/reset computer IP address. Make sure the Ethernet network used to connect
to SECVT is Enabled.
(See Connecting to, Accessing, and Navigating the SECVT UI.)
Computer may be attempting to connect to another network connection that is
enabled. Disable all network connections (wired and wireless) on the computer
except for the direct connection to the SECVT and retry the direct connection.
SECVT IP address incorrect.
Press Restore Defaults button on SECVT to reestablish factory default IP address.
(See Guidelines for Commissioning an SECVT.)
SECVT Technical Bulletin 35
No serial communication
between all N2 devices on
SECVT cluster and the NAE;
10 LINK or 100 LINK LED is
On, ETHERNET LED is
flashing, and N2 BUS LED is
Off.
N2 Bus on SECVT wired incorrectly or too many N2 devices on the SECVT N2
device cluster.
Check all N2 wiring to ensure proper connections and polarity. Limit the number of
N2 devices on the SECVT N2 Bus to 32 or less. (See Related Documentation for
references to installation and N2 network wiring.)
EOL Switches set incorrectly.
Check N2 device cluster on SECVT N2 Bus and set EOL Switches according to
SECVT position on N2 Bus. (Refer to the SECVT Installation Instructions [Part No.
24-10093-4] for information about setting EOL switches.)
No serial communication
between all N2 devices on
SECVT cluster and the NAE;
10 LINK or 100 LINK LED is
On, ETHERNET LED is
flashing, and N2 BUS LED is
Off.
NAE is not a supported model.
See Supported NAEs for more information.
If you are using static IP addresses, the SECVT IP address or UDP Port value does
not match the IP address or UDP Port value entered into NAE N2 device Hardware
tab on NAE UI.
Check SECVT IP address and ensure that IP addresses on the Hardware tabs for
the tunneled N2 device objects match the SECVT IP address.
The subnet mask and default gateway values entered into the Network tab on the
SECVT do not match the subnet mask and default gateway for the supported NAE.
If you are using static IP addresses, two or more SECVTs (reporting to a supported
NAE) have the same IP address.
Ensure that each SECVT reporting to the supported NAE has a unique IP address.
No communication between
NAE and one or more
N2 devices on SECVT
cluster. 10 LINK or 100 LINK
LED is On, ETHERNET LED is
flashing, and N2 BUS LED is
flashing.
If you are using static IP addresses, the IP address entered on the NAE N2 Device
object Hardware tab for one or more N2 devices does not match the SECVT IP
address.
Check SECVT IP address and ensure that IP addresses on the Hardware tabs for
the tunneled N2 device objects match the SECVT IP address. Reset the NAE and
the SECVT after making any changes in the UIs.
N2 device object for one or more of the tunneled N2 devices does not reside (or is
improperly entered) into NAE archive database.
Check NAE archive database to ensure that all of the required N2 device objects for
the tunneled N2 devices reside in the database and are entered correctly. (Refer to
the SCT Technical Bulletin [LIT-1201534] for information on checking and restoring
NAE archive databases.) Reset the NAE and the SECVT after making any changes
in the UIs.
N2 Net Address (entered into NAE N2 device Hardware tab on NAE UI) for one or
more of the tunneled devices does not match the N2 address setting on the N2 field
device.
Check the N2 address setting on any noncommunicating N2 device and ensure that
it matches the N2 Net Address value on the Hardware tab of the corresponding N2
device object. Reset the NAE and the SECVT after making any changes in the UIs.
Some or all of the N2 devices
on an SECVT N2 Bus go
temporarily offline.
The NAE N2 Network values are not set properly. Ensure that the Retries value is
set to 5 and the Message Timeout value is set to 1750 ms on the N2 Network
Advanced Hardware tab. See Configuring the NAE to Communicate with Tunneled
N2 Devices on page 28 for more information.
Network performance problems may be preventing Ethernet communication
between the NAE and SECVT. Changes to the network may change the response
time between the NAE and SECVT.
Perform a PATHPING test between the subnets on which the NAE and the SECVT
reside. See Determining Network Performance for information on performing a
PATHPING test.
Table 11: Troubleshooting the SECVT (Part 2 of 3)
Problem or Symptom Cause
Action
SECVT Technical Bulletin 36
All of the N2 devices on an
SECVT N2 Bus go
permanently offline.
The network may use NATs to communicate across the Internet, and the NATs are
set to provide dynamic IP addresses, but the NAEs and SECVTs are set to require
static IP addresses.
Configure the NATs to provide static internal and external IP addresses. If you are
using DHCP to assign addresses to SECVTs that communicate across networks that
use NAT, your DHCP server should be configured to always allocate the exact same
IP address to the SECVT's MAC addresses. This configuration makes these
SECVTs behave as if they have static IP addresses, although they have DHCP
addresses.
The NAE shows the SECVT
temporarily offline.
The SECVT obtained a different IP address, which can occur when using DHCP IP
addressing. Offline does not occur if the SECVT obtains the same IP address.
An N2 device does not come
online after approximately
15 minutes.
An invalid IP address may be entered for the SECVT.
Browse to the devices hardware tab and verify that the IP address is valid. The IP
address should not be 0.0.0.0.
The SECVT may not have reported to a Domain Name Server (DNS) server. Open a
Remote Desktop Connection to the NAE and PING the host name that was used for
the device. If the PING command fails to make a connection, contact your IT
department for assistance. It may be necessary to specify the Completion Domains
or DNS Server IP Addresses in the configuration of the NAE. It is also possible that
unused host name/IP address assignments need to be cleared from the DNS.
The NAE can not resolve the
SECVTs host name.
An SECVT using DHCP addressing was powered down for an extended period of
time, causing the SECVT to obtain a different IP address. The NAE does not find the
SECVT because the SECVT came back online with a different IP address.
Delete the SECVT's existing host name and hit save in the NAE. Reenter the
SECVT's host name and hit save in the NAE. If communication issues continue, try
using static addressing instead of DHCP addressing on the SECVT.
The SECVT does not come
online to the NAE after the
device is enabled for DHCP.
The DNS server may contain duplicate entries or may contain no entries.
Perform an nslookup command on the hostname. Only one entry should appear for
the hostname.
If multiple entries exist (the DNS server is resolving a host name to two different IP
addresses), the customers IT department should manually update the DNS records.
This is done by manually scavenging the DNS table to clear old records.
If no entries exist, The customers IT department should check the DNS Servers
security credentials, and configure the DNS Server to allow dynamic updates for the
requested zone. The client should then be able to register in the requested zone.
Table 11: Troubleshooting the SECVT (Part 3 of 3)
Problem or Symptom Cause
Action
SECVT Technical Bulletin 37
Technical Specifications
Serial to Ethernet Converter (SECVT)
Product Code MS-SECVT-0
Power Requirement 20-30 VAC, 50/60 Hz, 4.5 VA, Class 2 power supply (North America) or a current
limited power supply complying with IEC 60950
Power Consumption 4.5 VA Maximum
Power Supply Interface One 3-Position, Screw-Terminal Plug Block
Ambient Operating
Temperature
0 to 50C (32 to 122F)
Ambient Operating Humidity <90% RH, Noncondensing, 85% Maximum Dewpoint
Ambient Storage Temperature -40 to 70C (-40 to 158F)
Ambient Storage Humidity <95% RH, Noncondensing
Transmission Speed Ethernet Communication
10 or 100 Mbps
Serial Communication (RS-485 bus, N2 Protocol)
9600 Baud
Bandwidth Usage Not more than 0.5% of the usable bandwidth on a 10 Mbps Ethernet network
Network and Serial Interfaces One 8-Pin, RJ -45 connector for 10/100 Mbps Ethernet port
One 4-Position, Screw-Terminal Plug Block for the N2 Bus
Dimensions 180 x 128 x 58 mm (7.1 x 5.0 x 2.3 in.)
Housing Gray Plastic Housing with UL94-5VB Flammability Rating
Mounting On flat surface with screws on three mounting clips or on DIN rail
Shipping Weight 0.51 kg (1.13 lb)
Compliance United States Intended for connection to an NEC Class 2 power supply
Listed to UL 916, Energy Management Equipment (PAZX),
File E107041 (Pending)
UL94-5VB Flammability Rating (Receiver Housing is Plenum Rated
per UL 1995, Heating and Cooling Equipment)
FCC compliant to CFR 47, Part 15, Subpart B, Class B
Canada Intended for connection to an CEC Class 2 power supply
Listed to CAN/CSA C22.2 No. 205-M1983, Signal Equipment
(PAZX7), File E107041 (Pending)
UL94-5VB Flammability Rating (Receiver Housing is Plenum Rated
per CSA C22.2 No. 236, Heating and Cooling Equipment)
Industry Canada (IC) compliant to Canadian ICES-003 Class A
limits
Europe CE-Mark - EMC Directive 89/336/EEC
Australia and
New Zealand
Australia/New Zealand emissions (C-tick mark) ACN: 002 968 103
C-tick dependent on CE compliance per EMC
Directive 89/336/EEC
AS/NZS CISPR 22, Class B
Product Warranty 1-year warranty against defects in material and workmanship
Published in U.S.A. www.johnsoncontrols.com
SECVT Technical Bulletin 38
Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. 2008 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond
these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting
from misapplication or misuse of its products.
Limited Warranty
Johnson Controls, Inc. (JCI) warrants the Serial to Ethernet Converter (SECVT) to be free from defects in material and
workmanship for a period of up to one (1) year from the date of sale. The date of sale must be established by a receipt showing the
purchase date, seller and product sold. If the date of sale cannot be determined, the warranty shall be determined by the date of
manufacture.
This warranty does not extend to goods subjected to misuse, neglect, accident or improper installation, or to products which have
been altered or repaired by anyone except Seller. Buyer, or any person receiving such a product during the duration of the
warranty, shall contact the nearest Johnson Controls Product Provider or Johnson Controls, Inc. Customer Service at 1-800-275-
5676 as soon as any defect becomes known, for instructions on returned goods procedures.
Credit to be allowed will be based on then current prices. THIS REMEDY IS SOLE AND EXCLUSIVE. No other remedy will be
allowed, whether in contract or tort, including strict liability and negligence. Seller shall not be liable for any direct or
consequential damages arising from any defective product.
THIS WARRANTY IS OFFERED IN LIEU OF ANY OTHER WARRANTY, EXPRESS OR IMPLIED, INCLUDING (WITHOUT
LIMITATION) THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

You might also like