Product Catalogue

PVC Insulated Cables


BDS-900 and BS-6004
Type: BYA
Specification: BDS-900 and BS-6004
Voltage: 450/750 volts
1.

Copper Conductor

2.

PVC Insulation
Current Rating
Clipped to a
Bunched and Surface or on
Enclosed in
a Cable Tray
Approx
Weight of Conduits Two Bunched &
Cables Single Unenclosed 2
Cable
Phase at
Cables Single
35oC
Phase at 35oC

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Approx
Overall
Diameter

mm2

no./mm

ohm/km

mm

mm

kg/km

amp

amp

1.0 re
1.5 re
1.5 rm
2.5 re
2.5 rm
4.0 rm
6.0 rm
10 rm
16 rm
16 rm
25 rm
25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm
300 rm
400 rm
500 rm
630 rm

1/1.13
1/1.38
7/0.52
1/1.78
7/0.67
7/0.85
7/1.05
7/1.35
7/1.71
19/1.04
7/2.14
19/1.30
19/1.53
19/1.83
19/2.17
19/2.52
37/2.03
37/2.27
37/2.52
61/2.25
61/2.52
61/2.89
61/3.23
127/2.52

18.1
12.1
12.1
7.41
7.41
4.61
3.08
1.83
1.15
1.15
0.727
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

0.7
0.7
0.7
0.8
0.8
0.8
0.8
1.0
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8

2.8
3.3
3.5
3.9
4.2
4.8
5.4
6.8
8.0
8.1
9.8
9.9
11.0
13.0
15.0
17.0
19.0
21.0
23.5
26.5
29.5
33.5
37.0
41.0

17
22
23
35
36
55
75
115
178
180
275
280
375
530
720
1000
1225
1530
1890
2450
3060
4050
5000
6350

13
16
16
22
22
30
38
52
70
70
91
91
112
136
173
216
244
-

16
20
20
28
28
37
47
63
85
85
110
110
136
164
207
253
291
333
381
452
526
639
752
855

Type: BYFY
Specification: BDS-900 and BS-6004
Voltage: 300/500 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Nominal
Resistance of Nominal
Nominal
Thickness of Thickness
Diameter of Conductor at
Insulation
of Seath
Wires
20o C

Approx
Overall
Dimension

Current Rating
Clipped to a
Enclosed in
Surface or on
Approx
Conduits
a Cable Tray
Weight
Single
One Cable
of Cable
Phase at
Single Phase
o
35 C
at 35oC

mm2

no./mm

ohm/km

mm

mm

mm x mm

kg/km

amp

amp

1/1.13
1/1.38
1/1.78
7/0.85
7/1.05
1/1.13
1/1.38
1/1.78
7/0.85
7/1.05

18.1
12.1
7.41
4.61
3.08
18.1
12.1
7.41
4.61
3.08

0.6
0.7
0.8
0.8
0.8
0.6
0.7
0.8
0.8
0.8

0.9
0.9
1.0
1.0
1.1
0.9
0.9
1.0
1.1
1.1

6.8 x 4.4
7.7 x 4.8
9.2 x 5.7
10.8 x 6.5
12.1 x 7.3
9.2 x 4.4
10.6 x 4.8
12.6 x 5.7
15.2 x 6.7
17.0 x 7.5

55
70
100
155
205
80
100
150
235
310

13
16
22
30
37
11
15
20
28
35

15
18
26
33
43
12
16
22
33
40

2
2
2
2
2
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x

1.0
1.5
2.5
4.0
6.0
1.0
1.5
2.5
4.0
6.0

re
re
re
rm
rm
re
re
re
rm
rm

Type: BYFYE
Specification: BDS-900 and BS-6004
Voltage: 300/500 volts
1.

Copper Conductor

2.

PVC Insulation

3.

Earth Continuity Conductor

4.

PVC Sheath

Nominal
Cross
Sectional
Area of
Conductor

No. and
Nominal
Diameter
of Wires

Maximum
Nominal
Resistance Thickness
of Conductor of
Insulation
at 20o C

Current Rating
Clipped to
Enclosed a Surface
No. and
Approx
in
or on a
Nominal
Approx
Nominal
Weight
Conduits Cable Tray
Thickness Overall
Diameter
of Cable
Single
One Cable
of Seath
Dimension of Wires of
Phase at
Single
ECC
Phase at
35oC
35oC

no. x mm2

no./mm

Ohm/km

mm

mm

mm x mm

no./mm

kg/km

amp

amp

2
2
2
2
2

1/1.13
1/1.38
1/1.78
7/0.85
7/1.05

18.1
12.1
7.41
4.61
3.08

0.6
0.7
0.8
0.8
0.8

0.9
0.9
1.0
1.0
1.1

7.9 x 4.4
8.8 x 4.8
11.0 x 5.7
12.1 x 6.5
13.9 x 7.3

1/1.13
1/1.13
1/1.13
1/1.38
1/1.78

70
85
120
180
250

13
16
22
30
37

15
18
26
33
43

x
x
x
x
x

1.0 re
1.15 re
1.5 re
4.0 rm
6.0 rm

3 x 1.0 re
3 x 1.5 re
3 x 2.5 re

1/1.13
1/1.38
1/1.78

18.1
12.1
7.41

0.6
0.7
0.8

0.9
0.9
1.0

10.3 x 4.4 1/1.13


11.5 x 4.8 1/1.13
14.0 x 5.7 1/1.13

90
120
160

11
15
20

12
16
22

Type: BYFYE
Specification: BDS-900 and BS-6004
Voltage: 300/500 volts
1.

Copper Conductor

2.

PVC Insulation

3.

Earth Continuity Conductor

4.

PVC Sheath

Nominal
Cross
Sectional
Area of
Conductor

No. and
Nominal
Diameter
of Wires

Maximum
Nominal
Resistance Thickness
of Conductor of
Insulation
at 20o C

Current Rating
Clipped to
Enclosed a Surface
No. and
Approx
in
or on a
Nominal
Approx
Nominal
Weight
Conduits Cable Tray
Thickness Overall
Diameter
of Cable
Single
One Cable
of Seath
Dimension of Wires of
Phase at
Single
ECC
Phase at
35oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm x mm

no./mm

kg/km

amp

amp

2
2
2
2
2
3
3
3

1/1.13
1/1.38
1/1.78
7/0.85
7/1.05
1/1.13
1/1.38
1/1.78

18.1
12.1
7.41
4.61
3.08
18.1
12.1
7.41

0.6
0.7
0.8
0.8
0.8
0.6
0.7
0.8

0.9
0.9
1.0
1.0
1.1
0.9
0.9
1.0

7.9 x 4.4
8.8 x 4.8
11.0 x 5.7
12.1 x 6.5
13.9 x 7.3
10.3 x 4.4
11.5 x 4.8
14.0 x 5.7

1/1.13
1/1.13
1/1.13
1/1.38
1/1.78
1/1.13
1/1.13
1/1.13

70
85
120
180
250
90
120
160

13
16
22
30
37
11
15
20

15
18
26
33
43
12
16
22

x
x
x
x
x
x
x
x

1.0 re
1.15 re
1.5 re
4.0 rm
6.0 rm
1.0 re
1.5 re
2.5 re

Type: BYM
Specification: BDS-900 and BS-6004
Voltage: 300/500 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Maximum
No. and
Nominal Cross
Resistance of
Nominal
Sectional Area
Diameter of Conductor at
of Conductor
Wires
20o C

Nominal
Nominal
Thickness of Thickness
Insulation
of Seath

Approx
Overall
Diameter

Approx
Weight
of Cable

Current Rating
Clipped to a
In Conduit
Surface or on
Single
a Cable Tray
Phase at
Single Phase
35oC
at 35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

1 x 1.0 re
1 x 1.5 re

1/11.13
1/1.38

18.1
12.1

0.6
0.7

0.8
0.8

4.5
4.9

27
34

13
16

16
20

1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

2.5 re
4 rm
6 rm
10 rm
16 rm
16 rm
25 rm
25 rm
35 rm
1.0 re
1.5 re
2.5 re
4.0 rm
6.0 rm
10 rm
16 rm
25 rm
35 rm

1/1.78
7/0.85
7/1.05
7/1.35
7/1.71
19/1.04
7/2.14
19/1.30
19/1.53
1/1.13
1/1.38
1/1.78
7/0.85
7/1.05
7/1.35
7/1.71
7/2.14
19/1.53

7.41
4.61
3.08
1.83
1.15
1.15
0.727
0.727
0.524
18.1
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524

0.8
0.8
0.8
1.0
1.0
1.0
1.2
1.2
1.2
0.6
0.7
0.8
0.8
0.8
1.0
1.0
1.2
1.2

0.8
0.9
0.9
0.9
1.0
1.0
1.1
1.1
1.1
1.2
1.2
1.2
1.2
1.2
1.4
1.4
1.4
1.6

5.8
6.8
7.4
8.8
10.2
10.5
12.0
12.2
13.4
8.6
9.5
11.0
12.0
13.5
17.0
19.0
23.0
26.5

49
73
94
144
220
225
325
330
440
100
117
175
228
290
475
673
1000
1345

22
30
38
52
70
70
91
91
112
13
16
22
30
37
50
66
75
92

28
37
47
63
85
85
110
110
136
15
18
26
33
43
60
80
88
108

BDS-901 and VDE-0271/3.69


Type: NYY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1/1.38
1/1.78
7/0.85
7/1.05
7/1.35
7/1.71
7/2.14
19/1.53
19/1.83
19/2.17
19/2.52
37/2.03
37/2.27
37/2.52
61/2.25

12.1
7.41
4.61
3.08
1.83
1.15
0.727
.0524
0.387
0.268
0.193
0.153
.0124
0.0991
0.0754

0.8
0.9
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0

7.0
7.7
8.6
9.0
10.1
11.2
13.0
14.2
15.8
17.8
20.0
21.6
23.7
26.3
29.3

65
80
110
138
185
252
364
470
625
850
1110
1360
1710
2080
2710

27
36
47
59
78
100
130
155
185
225
270
310
350
390
450

22
30
39
50
69
94
125
160
195
245
300
350
405
460
555

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.5 re
2.5 re
4 rm
6 rm
10 rm
16 rm
25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm

1
1
1
1

x
x
x
x

300
400
500
630

rm
rm
rm
rm

61/2.52
61/2.89
61/3.23
127/2.2

0.0601
0.0470
0.0366
0.0283

2.4
2.6
3.0
3.0

2.0
2.2
2.2
2.2

32.2
35.6
40.3
44.2

3400
4400
5420
6750

515
585
680
800

640
770
900
1030

Type: NYY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/1.38
1-/1.78
7/0.85
7/1.05
7/1.35
7/1.71
7/2.14
19/1.53
1/1.38
1/1.78
7/0.85
7/1.05
7/1.35
7/1.71
7/2.14
Min 6 wire
Min 6 wire
Min 12 wire
Min 15 wire
Min 18 wire
Min 18 wire
Min 30 wire
Min 34 wire
Min 34 wire

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

0.8
0.9
1.0
1.0
1.0
1.0
1.2
1.2
0.8
0.9
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.6
2.6

11.9
13.1
15.1
16.3
18.1
20.2
24.5
27.4
12.3
13.6
15.8
17.0
19.0
21.4
25.8
23.5
27.0
30.0
34.5
37.0
41.0
44.5
50.5
56.0

170
230
310
380
512
690
1050
1350
200
266
365
460
620
925
1350
1340
1820
2460
3350
4100
5050
6200
7500
10100

25
34
44
55
74
97
125
150
22
30
38
48
64
83
110
130
155
190
225
260
295
330
385
524

19
27
35
45
62
84
110
140
16
23
32
41
56
75
98
120
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.5 re
2.5 re
4.0 rm
6.0 rm
10 rm
16 rm
25 rm
35 rm
1.5 re
2.5 re
4.0 rm
6.0 rm
10 rm
16 rm
25 rm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

Type: NYY-1
Specification: BDS-901 and VDE-0271/3.69
Voltage: 600/1000 volts

1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

5 x 1.5 re
7 x 1.5 re
10 x 1.5 re
12 x 1.5 re
16 x 1.5 re
21 x 1.5 re
24 x 1.5 re
30 x 1.5 re
5 x 2.5 re
7 x 2.5 re
10 x 2.5 re
12 x 2.5 re
16 x 2.5 re
21 x 2.5 re
24 x 2.5 re
30 x 2.5 re
5 x 4 rm
7 x 4 rm
10 x 4 rm
12 x 4 rm

1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
7/0.85
7/0.85
7/0.85
7/0.85

12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
4.61
4.61
4.61
4.61

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
1.0
1.0
1.0
1.0

1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
1.8
1.8
1.8
1.8

13.0
13.5
17.0
17.5
19.0
21.0
23.0
24.5
14.6
15.7
19.4
19.9
21.9
24.5
27.0
28.5
17.2
18.6
23.3
24.0

210
258
360
400
516
643
720
870
290
370
507
570
730
940
1060
1280
410
540
720
840

18
16
13
12
11
9
9
8
24
21
18
16
14
13
12
10
31
27
23
21

13
12
10
9
8
7
7
6
19
17
14
13
11
10
9
8
25
22
19
17

Type: NYCY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

Concentric Neutral:Copper

5.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

3 x 25 rm / 1 x 7 / 2.14
16 C
72 / 0.54
3 x 35 sm / 1 x Min 6 wire
16 C
72 / 0.54
3 x 50 sm / 1 x Min 6 wire
25C
50 / 0.8
3 x 70 sm / 1 x Min 12 wire
35 C
70 / 0.8
3 x 95 sm / 1 x Min 15 wire
35 C
59 / 1.05
3 x 120 sm / 1 Min 18 wire
x 70 C
71 / 1.13
3 x 150 sm / 1 Min 18 wire
x 70 C
71 / 1.13
3 x 185 sm / 1 Min 30 wire
x 95 C
67 / 1.53
3 x 240 sm / 1 Min 34 wire
x 120 C
67 / 1.53
3 x 300 sm / 1 Min 34 wire
x 150 C
1.63

ohm/km

0.727
0.15
0.524
1.15
0.387
0.727
0.268
0.524
0.193
0.387
0.153
0.268
0.124
0.268
0.0991
0.193
0.0754
0.153
0.0601
0.124

mm

mm

mm

kg/km

amp

amp

1.2

2.0

27.0

1550

110

98

1.2

2.0

24.0

1545

130

120

1.4

2.0

29.0

2145

155

150

1.4

2.0

31.0

2860

190

190

1.6

2.2

36.0

3900

225

230

1.6

2.2

38.6

4890

260

270

1.8

2.2

42.5

5830

295

305

2.0

2.6

47.5

7370

330

350

2.2

2.6

52.5

9380

385

410

2.4

3.0

58.0

11700

425

470

Type: NYFGbY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

Flat Galvanising steel with helical steel tape binder

5.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3
3

7/1.71
7/2.14
Min 6 wire
Min 6 wire
Min 12 wire
Min 15 wire
Min 18 wire
Min 18 wire
Min 30 wire
Min 34 wire
Min 34 wire

1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.601

1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

1.8
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.6
2.6
30.

24.0
28.0
25.0
28.0
31.0
36.0
38.6
42.5
47.0
52.5
58.0

1360
1890
1850
2410
3100
4370
5220
6340
7700
9950
12210

83
110
130
155
190
225
260
295
330
385
425

75
98
120
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x
x

16 rm
25 rm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

Type: NYFGbY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 3500/6000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

Flat galvanising steel with helical steel tape binder

5.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

7/2.14
Min 6 wire
Min 6 wire
Min 12 wire
Min 15 wire
Min 18 wire
Min 18 wire
Min 30 wire
Min 34 wire
Min 34 wire

.0727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

304
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.2
2.2
2.2
2.6
2.6
2.6
2.6
3.0
3.0
3.4

37.0
39.0
42.0
46.0
49.0
52.0
54.5
59.5
63.8
70.0

2900
3450
4150
5230
6080
7150
8250
10200
12000
15700

105
125
145
180
215
245
275
305
350
390

105
125
155
190
235
270
305
350
405
460

x
x
x
x
x
x
x
x
x
x

25 rm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

Type: NYSY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 3500/6000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

Metallic Shield with Copper

5.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

1 x25
1 x 35

7/2.14
19/1.53

0.727
0.524

3.4
3.4

1.8
1.8

18.0
19.5

645
770

131
156

120
150

1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

50
70
95
120
150
185
240
300
400
500
630
25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm
300 rm

19/1.83
19/2.17
19/2.52
37/2.03
37/2.27
37/2.52
61/2.25
61/2.52
61/2.89
61/3.23
127/2.52
7/2.14
19/1.53
19/1.83
19/2.52
19/2.17
37/2.03
37/2.27
37/2.52
61/2.25
61/2.52

0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.727
.0524
0.387
0.193
0.268
0.153
0.124
0.0991
0.0754
0.0601

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.2
2.4
2.4
2.2
2.2
2.2
2.6
2.6
2.6
3.0
3.0
3.4
3.4

20.5
22.5
24.5
26.0
27.5
29.5
32.1
34.5
38.0
41.5
45.5
36.2
38.8
42.0
51.0
47.0
54.5
59.0
63.0
69.0
74.5

860
1105
1410
1670
1980
2400
3010
3660
4570
5640
7140
1800
2300
3150
4500
3850
5750
6970
8400
10600
13200

183
223
268
300
335
380
450
490
570
645
730
105
125
145
215
180
245
275
305
350
390

180
230
280
325
365
420
500
580
690
775
900
105
125
155
235
190
270
305
350
405
460

Type: NYSEYFGbY
Specification: BDS-901 and VDE-0271/3.69
Voltage: 5800/10000 volts
1.

Copper Conductor

2.

Conducting Screen: Extruded Semiconductor

3.

PVC Insulation

4.

Insulating Screen: Extruded Semiconductor

5.

Copper Screen

6.

PVC Inner Sheath

7.

Flat glav. steel wire with helical ateel tape

8.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3

7/2.14
19/1.53
19/1.83
19/2.17
19/2.52
37/2.03
37/2.27

0.727
0.524
0.387
0.268
0.193
0.153
0.124

4.0
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.6
3.0
3.0
3.0
3.4
3.4

53.0
56.0
59.5
64.0
68.0
72.5
76.0

5000
5700
6500
7700
9100
10400
11900

100
120
140
170
200
230
260

100
120
145
180
220
250
290

x
x
x
x
x
x
x

25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm

3 x 185 rm
3 x 240 rm
3 x 300 rm

37/2.52
61/2.25
61/2.52

0.0991
0.0754
0.0601

4.0
4.0
4.0

3.8
308
4.2

81.0
88.0
95.0

13800
15000
18000

290
320
365

325
370
425

Type: NYA
Specification: VDE-0250/3.69
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

Nominal Cross
Sectional Area of
Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Nominal
Resistance of
Thickness of
o
Conductor at 20 C Insulation

Approx
Overall
Diameter

Approx
Weight of
Cable

Current Rating
In Air
In Conduit
at
o
at 35 C
35oC

no. x mm2

no./mm

ohm/km

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1

1/0.80
1/0.98
1/1.13
1/1.38
1/1.78
1/2.26
1/2.77
1/3.57
1/4.52

36.00
24.50
18.10
12.10
7.41
4.61
3.08
1.83
1.15

0.6
0.6
0.6
0.6
0.7
0.8
0.8
1.0
1.0

2.3
2.5
2.6
2.9
3.5
4.2
4.7
6.0
6.9

8
11
14
18
30
50
67
110
170

10
14
18
23
30
42
57

12
14
17
22
30
39
50
69
92

x
x
x
x
x
x
x
x
x

0.5 re
0.75 re
1.0 re
1.5 re
2.5 re
4.0 re
6.0 re
10 re
16 re

Type: NYIFY
Specification: VDE-0250/3.69
Voltage: 220/380 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Dimension

Current Rating
Approx
o
Weight of at 35 C
Ambient
Temp.
Cable
Under Plaster

no. x mm2

no./mm

ohm/km

mm

mm

mm x mm

kg/km

amp

2
2
2
3
3
3

1/1.38
1/1.78
1/2.26
1/1.38
1/1.78
1/2.26

12.1
7.41
4.61
12.1
7.41
4.61

0.4
0.5
0.6
0.4
0.5
06

0.8
0.9
0.9
0.8
0.9
0.9

4.4
5.2
6.0
4.4
5.2
6.0

70
105
146
105
160
225

17
23
31
17
23
31

x
x
x
x
x
x

1.5
2.5
4.0
1.5
2.5
4.0

re
re
re
re
re
re

x
x
x
x
x
x

12.0
13.5
15.5
19.0
21.5
25.0

Type: NYMT
Specification: VDE-0250/3.69
Voltage: 300/500 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

PVC Sheath

5.

Galvanised Steel Wire Rope

No. and Nominal


Nominal Cross Diameter of Wires
Sectional Area
Copper
Steel
of Conductor
Wire
Wire

Maximum
Resistance of
Conductor at
20o C

Nominal
Nominal
Maximum
Thickness of Thickness of Outer
Insulation
Seath
Diameter

Current
Approx
Rating at 35
Weight of o
C Ambient
Cable
Temp. in Air

no. x mm2

no./mm

no./mm

ohm/km

mm

mm

mm

kg/km

amp

2
2
2
2
3
3
3
3
4
4
4
4

1/1.38
1/1.78
1/2.26
1/2.77
1/1.38
1/1.78
1/2.26
1/2.77
1/ 1.38
1/1.78
1/2.26
1/2.77

19/0.6
18/0.6
19/0.6
19/0.6
19/0.6
19/0.6
19/06
19/0.6
19/0.6
19/0.6
19/0.6
19/0.6

12.1
7.41
4.61
3.08
12.1
7.41
4.61
3.08
12.1
7.41
4.61
3.08

0.6
0.7
0.8
0.8
0.6
0.7
0.8
0.8
0.6
0.7
0.8
0.8

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.6
1.4
1.4
1.6
1.6

9.8
11.0
12.5
13.5
10.5
11.5
13.0
15.0
11.0
12.5
14.5
16.5

205
250
330
400
225
280
176
507
250
320
460
590

17
23
31
41
17
23
31
41
17
23
31
41

x
x
x
x
x
x
x
x
x
x
x
x

1.5 re
2.5 re
4 re
6 re
1.5 re
2.5 re
4 re
6 re
1.5 re
2.5 re
4 re
6 re

BDS-833, BS-2004 & BS-6500


Type: IYAL
Specification: BS-2004
Voltage: 250/440 volts
1.

Copper Conductor

2.

PVC Insulation
Current Rating
Clipped to a
Bunched and Surface or on
Enclosed in
a Cable Tray
Conduits Two Bunched &
Cables Single Unenclosed 2
Phase at
Cables Single
35oC
Phase at 35oC

Nominal Cross
Sectional Area of
Conductor

No. and Nominal Nominal


Diameter of Wires Thickness of
Insulation

Approx
Overall
Diameter

Approx
Weight of
Cable

mm2

no./inch
no./mm

mm

mm

kg/km

amp

amp

0.89

2.03

18

13

16

0.89

3.48

24

16

20

1.0
1.3

1 / 0.044
1 / 1.12
3 / 0.029

3
3
3
7
7
7
7
7
7
7
7
7
7

1.9
2.9
4.5
6.5
9.5
14.5

/ 0.74
/ 0.036
/ 0.91
/ 0.029
/ 0.74
/ 0.036
/ 0.91
/ 0.044
/ 1.12
/ 0.052
/ 1.32
/ 0.064
/1.63

0.89

3.89

33

20

25

0.89

4.11

44

26

31

1.016

4.90

62

35

41

1.016

5.51

88

42

51

1.016

6.10

116

53

65

1.016

7.00

170

70

83

Type: IYAL
Specification: BS-2004
Voltage: 660/1100 volts
1.

Copper Conductor

2.

PVC Insulation
Current Rating
Clipped to a
Bunched and Surface or on
Enclosed in
a Cable Tray
Conduits Two Bunched &
Cables Single Unenclosed 2
Phase at
Cables Single
35oC
Phase at 35oC

Nominal Cross
Sectional Area of
Conductor

No. and Nominal Nominal


Diameter of Wires Thickness of
Insulation

Approx
Overall
Diameter

Approx
Weight of
Cable

mm2

no./inch
no./mm

mm

mm

kg/km

amp

amp

1.143

3.53

22

13

16

1.143

3.96

28

16

20

1.143

4.39

37

21

26

1.143

4.62

48

27

32

1.27

5.41

70

36

42

1.27

6.02

94

43

52

1.27

6.63

120

54

66

1.27

7.55

175

72

85

1.0
1.3
1.9
2.9
4.5
6.5
9.5
14.5

1
1
3
3
3
3
7
7
7
7
7
7
7
7
7
7

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

0.044
1.12
0.029
0.74
0.036
0.91
0.029
0.74
0.036
0.91
0.044
1.12
0.052
1.32
0.064
1.63

Type: IYYL
Specification: BS-2004
Voltage: 250/440 volts

1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

No. and
Nominal Cross
Nominal
Sectional Area of
Diameter of
Conductor
Wires

no./inch
no./mm

mm2

1
1
3
3
3
3
7
7
7
7
7
7
7
7
7
7

1.0
1.3
1.9
2.9
4.5
6.5
9.5
14.5

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

0.044
1.12
0.029
0.74
0.036
0.91
0.029
0.74
0.036
0.91
0.044
1.12
0.052
1.32
0.064
1.63

Current Rating
Clipped to a
Bunched and Surface or on
Enclosed in
a Cable Tray
Approx
Weight of Conduits Two Bunched &
Cables Single Unenclosed 2
Cable
Phase at
Cables Single
35oC
Phase at 35oC

Nominal
Thickness of
Insulation

Nominal
Thickness of
Sheath

Approx
Overall
Diameter

mm

mm

mm

kg/km

amp

amp

0.635

0.89

4.28

29

13

16

0.635

0.89

4.80

35

16

20

0.635

0.89

5.16

46

20

25

0.635

0.89

5.46

57

26

31

0.762

0.89

6.29

78

35

41

0.762

0.89

6.85

1.5

42

51

0.89

0.89

7.80

140

53

65

0.89

1.143

9.20

205

70

83

Type: IYFY
Specification: BS-2004
Voltage: 250/440 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Nominal
Thickness of
Insulation

Nominal
Thickness of
Sheath

Approx
Overall
Dimension

Current Rating
Clipped to a
Enclosed in
Surface or on
Approx
Conduits One
a Cable Tray 1
Weight of
Cable Single
Cable Single
Cable
Phase at
Phase at 35oC
35oC

mm2

no./inch
no./mm

mm

mm

mm x mm

kg/km

amp

amp

0.635

0.89

6.81 x 4.42

52

12

15

0.635

0.89

7.78 x 4.88

68

15

18

0.635

0.143

9.04 x 5.79

95

20

23

2 x 1.0
2 x 1.3
2 x 1.9

1
1
3
3
3

/
/
/
/
/

0.044
1.12
0.029
0.74
0.036

3
7
7
7
7
7
7
7
7
7
7
1
1
3
3
3
3
7
7
7
7
7
7

2 x 2.9
2 x 4.5
2 x 6.5
2 x 9.5
2 x 14.5
3 x 1.0
3 x 1.3
3 x 1.9
3 x 2.9
3 x 4.5
3 x 6.5

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

0.91
0.029
0.74
0.036
0.91
0.044
1.12
0.052
1.32
0.064
1.63
0.044
1.12
0.029
0.74
0.036
0.91
0.029
0.74
0.036
0.91
0.044
1.12

0.635

1.143

9.50 x 6.02

120

23

28

0.762

0.143

11.07 x 6.81 166

32

38

0.762

1.143

12.30 x 7.42 218

38

46

0.890

1.143

14.15 x 8.41 298

50

57

0.890

1.397

16.48 x 9.83 422

65

76

0.635

0.89

9.19 x 4.42

76

11

14

0.635

0.89

10.57 x 4.88 97

14

17

0.635

1.143

12.29 x 5.79 140

18

20

0.635

1.143

13.10 x 6.15 174

21

26

0.762

1.143

15.46 x 6.93 246

30

35

0.762

1.143

17.30 x 7.54 335

36

44

Type: Flexible Cords


Specification: BDS-899 and BS-6500
Voltage: 300/500 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Nominal
Resistance of Nominal
Nominal
Thickness of Thickness
Conductor
at
Diameter of
Insulation
of Sheath
Wires
20o C

Approx
Overall
Diameter

Current Rating
Approx
In
Weight In Conduit at Surface/Cable
o
35
C
of Cable
Tray at 35oC

mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

2
2
2
2
2
2
3
3
3
3
3
3
4
4
4

16/0.20
24/0.20
32/0.20
30 /0.25
50/0.25
56/0.30
16/0.20
24/0.20
32/0.20
30/0.25
50/0.25
56/0.30
16/0.20
24/ 0.20
32/0.20

39.00
26.00
19.50
13.30
9.98
4.95
39.00
26.00
19.50
13.30
7.98
4.95
39.00
26.00
19.50

0.6
0.6
0.6
0.6
0.7
0.8
0.6
0.6
0.6
0.6
0.7
0.8
0.6
0.6
0.6

0.8
0.8
0.8
0.8
1.0
1.0
0.8
0.8
0.8
0.9
1.1
1.1
0.8
0.9
0.9

6.5
7.0
7.5
8.0
9.5
11.5
7.0
8.0
8.5
9.8
11.0
13.0
8.0
9.0
9.5

50
65
70
95
150
220
60
75
90
120
180
270
70
90
110

3
6
10
15
20
25
3
6
10
15
20
25
3
6
10

4
7
11
16
21
26
4
7
11
16
21
26
4
7
11

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

0.5
0.75
1.0
1.5
2.5
4.0
0.5
0.75
1.0
1.5
2.5
4.0
0.5
0.75
1.0

4 x 1.5
4 x 2.5
4 x 4.0

30/.0.25
50/0.25
56/0.30

13.30
7.98
4.95

0.6
0.7
0.8

1.0
1.1
1.1

10.5
12.5
14.0

150
220
330

15
20
25

16
21
26

IEC-60502-1
Type: YY
Specification: IEC-60502-1
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1 / 1.38
1 / 1.78
7 / 0.85
7 / 1.05
7 / 1.35
7 / 1.71
7 / 2.14
19 / 1.53
19 / 1.83
19 / 2.17
19 / 2.52
37 / 2.03
37 / 2.27
37 / 2.52
61 / .25
61 / 2.52
61 / 2.89
61 / 3.23
127 / 2.52
127 / 2.85
127 / 3.20

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
.0153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
2.8
3.0

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.5

6.5
7.0
8.2
8.5
9.6
10.5
12.2
13.5
15.5
17.2
19.4
21.0
23.0
26.0
29.0
32.0
35.5
40.0
44.0
49.0
54.0

55
70
105
120
170
240
345
450
610
820
1100
1350
1680
2040
2675
3300
4300
5350
6600
8400
10500

27
36
47
59
78
100
130
155
185
225
270
310
350
390
450
515
585
640
800
945
1095

22.
30
39
50
69
94
125
160
195
245
300
350
405
460
555
640
770
900
1030
1160
1310

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.5 re
2.5 re
4 rm
6 rm
10 rm
16 rm
25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm
300 rm
400 rm
500 rm
630 rm
800 rm
1000 rm

Type: YY
Specification: IEC-60502-1
Voltage: 600/1000 volts

1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

PVC Oversheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1 / 1.38
1 / 1.78
7 / 1.05
7 / 1.05
7 / 1.35
7 / 1.71
7 / 2.14
19 / 1.53
1 / 1.38
1 / 1.78
7 / 0.85
7 / 1.05
7 / 1.35
7 / 1.71
Min 6 wire
Min 6 wire
Min 6 wire
Min 12 wire
Min 15 wire
Min 18 wire
Min 18 wire
Min 30 wire
Min34 wire
Min34 wire

12.1
7.41
3.08
3.08
1.83
1.15
0.727
0.524
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.1
2.2
2.3
2.5
2.7
2.9

11.9
13.0
16.3
16.3
18.1
20.2
24.5
27.0
12.3
13.6
15.8
17.0
19.0
21.4
22.5
23.5
26.5
30.0
35.0
37.0
41.2
45.5
51.0
56.5

170
228
380
380
512
690
1050
1340
200
266
365
460
620
925
1100
1340
1800
2460
3400
4100
5100
6250
8000
10300

25
34
55
55
74
97
125
150
22
30
38
48
64
83
110
130
155
190
225
260
295
330
385
425

19
27
45
45
62
84
110
140
16
23
32
41
56
75
98
120
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.5 re
2.5 re
4 rm
6 rm
10 rm
16 rm
25 rm
35 rm
1.5 re
2.5 re
4 rm
6 rm
10 rm
16 rm
25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

Type: YRaY
Specification: IEC-60502-1
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Round Galvanising Steel Wire Armoured

5.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
Wires
20o C

Nominal
Diameter of Nominal
Round
Thickness
Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1
1
1
1
1
1

19 / 1.53
19 / 1.83
19 / 2.17
19 / 2.52
37 / 2.03
37 / 2.27
37 / 2.52
61 / 2.25
61 / 2.52
61 / 2.89
61 / 3.23
127 / 2.52
127 / 2.85
127 / 3.20

0.524
0.387
0.268
1.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
2.8
3.0

1.25
1.25
1.25
1.25
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.5
2.5

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.2
2.3
2.5
2.6

17.0
19.0
20.5
23.0
25.5
28.0
30.0
33.0
36.5
41.0
44.5
48.5
55.0
60.0

600
755
975
1260
1560
1900
2300
2900
3600
4660
5700
7000
8900
11000

155
185
225
270
310
350
390
450
515
585
680
800
945
1095

160
195
245
300
350
405
460
555
640
770
900
1030
1160
1310

x
x
x
x
x
x
x
x
x
x
x
x
x
x

35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm
300 rm
400 rm
5000 rm
630 rm
800 rm
1000 rm

Type: YRGY
Specification: IEC-60502-1
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Round galvanising steel wires armouring

5.

Helical steel tape binder(Optional)

6.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
o
Wires
20 C

Nominal
Diameter of Nominal
Round
Thickness
Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

mm

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3
3

7 / 0.85
4.61
7 / 1.05
3.08
7 / 1.35
1.83
7 / 1.71
1.15
Min 6 wire 0.727
Min 6 wire 0.524
Min 6 wire 0.387
Min 12 wire 0.268
Min 15 wire 0.193
Min 18 wire 0.153
Min 18 wire 0.124

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8

1.25
1.25
1.25
1.25
1.6
1.6
1.6
2.0
2.0
2.0
2.5

1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.1
2.2
2.3
2.5

19.0
20.5
22.5
25.0
26.0
27.5
30.5
34.5
38.5
42.0
47.0

716
840
1050
1340
1750
2070
2650
3700
4760
5675
7250

38
48
64
83
110
130
155
190
225
260
295

32
41
56
75
98
120
150
190
230
270
305

x
x
x
x
x
x
x
x
x
x
x

4 rm
6 rm
10 rm
16 rm
25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm

ohm/km

3 x 185 sm
3 x 240 sm
3 x 330 sm

Min 30 wire 0.0991


Min 34 wire 0.0754
Min 34 wire 0.0601

2.0
2.2
2.4

2.5
2.5
2.5

2.7
2.9
3.1

51.0
57.0
61.0

8650
10800
13050

330
385
425

350
410
470

Type: YFGY
Specification: IEC-60502-1
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Round galvanising steel wires armouring

5.

Helical steel tape binder(Optional)

6.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
o
Wires
20 C

Nominal
Nominal
Diameter of
Thickness
Flat Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

mm

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
4

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.8
1.8
1.9
2.0
2.2
2.3
2.4
2.6
2.8
2.9
1.8
1.9
2.0
2.1
2.3
2.4
2.6
2.7
3.0
3.2

25.0
24.8
28.0
31.0
36.0
39.0
43.0
47.0
53.0
57.8
27.6
28.2
33.0
37.0
42.5
45.5
50.0
56.2
64.0
70.2

1600
1840
2410
3100
4370
5250
6400
7700
10000
12200
2000
2320
3300
4300
5650
7500
8220
10350
13000
15500

110
130
155
190
225
260
295
330
385
425
110
130
155
190
225
260
295
330
385
425

98
120
150
190
230
270
305
350
410
470
98
120
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
95 sm
70 sm
120 sm
150 sm
185 sm
240 sm
300 sm
25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

ohm/km

6 wire 0.727
6 wire 0.524
6 wire 0.387
12 wire 0.268
15 wire 0.193
18 wire 0.153
18 wire 0.124
30 wire 0.0991
34 wire 0.754
34 wire 0.0601
6 wire 0.727
6 wire 0.524
6 wire 0.387
12 wire 0.268
15 wire 0.193
18 wire 0.153
18 wire 0.124
30 wire 0.0991
34 wire 0.0754
34 wire 0.0601

Type: Control Cable(YY)


Specification: IEC-60502-1
Voltage: 600/1000 volts

1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

PVC Oversheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

5 x 1.5 re
7 x 1.5 re
10 x 1.5 re
12 x 1.5 re
19 x 1.5 re
37 x 1.5 re
5 x 2.5 re
7 x 2.5 re
10 x 2.5 re
12 x 2.5 re
19 x 2.5 re
37 x 2.5 re

1
1
1
1
1
1
1
1
1
1
1
1

12.1
12.1
12.1
12.1
12.1
12.1
7.41
7.41
7.41
7.41
7.41
7.41

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9

13.0
13.5
17.0
17.5
20.5
29.0
14.6
15.7
19.4
19.9
24.0
31.5

210
258
360
400
620
1100
290
370
507
570
900
1550

18
16
13
12
10
8
24
21
18
16
14
9

13
12
10
9
7
5
19
17
14
13
12
7

/
/
/
/
/
/
/
/
/
/
/
/

1.38
1.38
1.38
1.38
1.38
1.38
1.78
1.78
78
1.78
1.78
1.78

Type: Control Cable(YRGY)


Specification: IEC-60502-1
Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Round galvanising steel wires armouring

5.

Helical steel tape binder(Optional)

6.

PVC Sheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
Wires
20o C

Nominal
Nominal
Diameter of
Thickness
Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

mm

kg/km

amp

amp

5 x 1.5 re
7 x 1.5 re
10 x 1.5 re
12 x 1.5 re
19 x 1.5 re
37 x 1.5 re

1
1
1
1
1
1

12.1
12.1
12.1
12.1
12.1
12.1

0.8
0.8
0.8
0.8
0.8
0.8

1.25
1.25
1.25
1.25
1.6
1.6

1.8
1.8
1.8
1.8
1.8
1.9

16.5
17.5
20.5
21.5
25.0
32.0

500
575
750
840
1200
1850

18
16
13
12
10
8

13
12
10
9
7
5

/
/
/
/
/
/

1.38
1.38
1.38
1.38
1.38
1.38

5 x 2.5 re
7 x 2.5 re
10 x 2.5 re
12 x 2.5 re
19 x 2.5 re
37 x 2.5 re

1
1
1
1
1
1

/
/
/
/
/
/

1.78
1.78
1.78
1.78
1.78
1.78

7.41
7.41
7.41
7.41
7.41
7.41

0.8
0.8
0.8
0.8
0.8
0.8

1.25
1.25
1.25
1.25
1.60
1.60

1.8
1.8
1.8
1.8
1.8
2.0

17.5
18.5
22.5
23.0
27.0
35.0

590
675
900
980
1450
2350

24
21
18
16
14
9

19
17
14
13
12
7

Type: YSY
Specification: IEC-60502-1
Voltage: 1.8/3.0 KV
1.

Copper Conductor

2.

PVC Insulation

3.

Copper Screened

4.

PVC Oversheath

No. and
Nominal Cross
Nominal
Sectional Area
Diameter of
of Conductor
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at 35oC
Cable
30oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

7 / 2.14
19 / 1.53
19 / 1.83
19 / 2.17
19 / 2.52
37 / 2.03
37 / 2.27
37 / 2.52
61 / 2.25
61 / 2.52
61 / 2.89
61 / 2.23
127 / 2.52
127 / 2.85
127 / 3.20

0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.4
2.6
2.8
2.8
2.8
3.0

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.2
2.3
2.5

16.5
17.0
18.5
20.5
22.5
24.0
26.0
28.0
30.5
33.5
38.0
41.5
45.0
50.0
56.0

475
590
760
975
1230
1490
1800
2150
2700
3350
4350
5350
6650
8400
10500

130
155
185
225
270
310
350
390
450
515
585
680
800
945
1095

125
160
195
245
300
350
405
460
555
640
770
900
1030
11610
1310

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm
300 rm
400 rm
500 rm
630 rm
800 rm
1000 rm

Type: YSY
Specification: IEC-60502-1
Voltage: 3.6/6 KV
1.

Copper Conductor

2.

PVC Insulation

3.

Copper Screened

4.

PVC Oversheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

7 / 2.14
19 / 1.53
19 / 1.83
19 / 2.17
19 / 2.52
37 / 2.03
37 / 2.27
37 / 2.52
61 / 2.25
61 / 2.52
61 / 2.89
61 / 3.23
127 / 2.52
127 / 2.85
127 / 3.20

0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.283
0.0221
0.0176

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.2
2.4
2.5

18.0
19.5
20.5
22.5
24.5
26.0
27.5
29.2
32.0
34.3
37.8
41.0
45.3
51.0
56.0

645
770
860
1105
1410
1670
1980
2380
3000
3600
4550
5600
7100
8500
10500

131
156
183
223
268
300
335
380
450
490
570
645
730
910
1060

120
150
180
230
280
325
365
420
500
580
390
775
900
1035
1185

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
185 rm
240 rm
300 rm
400 rm
500 rm
630 rm
800 rm
1000 rm

Type: YSY
Specification: IEC-60502-1
Voltage: 1.8/3.0 KV
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Copper Screen

5.

PVC Oversheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.4

1.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.7
2.9

28.0
29.0
32.0
35.0
38.5
41.5
44.0
46.5
52.0
53.5

1380
1750
2190
2900
3770
4650
5550
6700
8600
10500

110
130
155
190
225
260
295
330
385
425

98
98
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

6 wire
6 wire
6 wire
12 wire
15 wire
18 wire
18 wire
30 wire
34 wire
34 wire

Type: YSY
Specification: IEC-60502-1
Voltage: 3.6/6 KV
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Copper Screen

5.

PVC Oversheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Seath
Diameter

Current Rating
Approx
Under
In Air
Weight of
Ground at at
Cable
30oC
35oC

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.601

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.0
2.1
2.1
2.3
2.4
2.5
2.6
2.7
2.9
3.0

34.0
35.0
37.5
41.0
44.5
48.0
50.5
53.0
58.0
61.5

1760
2130
2570
3350
4300
5200
6100
7350
9300
11200

105
125
145
180
215
245
275
305
350
390

105
125
155
190
235
270
305
350
405
460

x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

6 wire
6 wire
6 wire
12 wire
15 wire
18 wire
18 wire
30 wire
34 wire
34 wire

Type: YSYRGY
Specification: IEC-60502-1
Voltage: 1.8/3.5 KV
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Copper Screened

5.

PVC Separation Sheath

6.

Round galvanising steel wires armouring

7.

Helical steel tape binder(Optional)

8.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
o
Wires
20 C

Nominal
Diameter of Nominal
Round
Thickness
Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

mm

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.4

1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5

2.0
2.1
2.2
2.3
2.5
2.6
2.7
2.8
3.0
3.2

34.0
36.0
39.0
42.0
47.0
50.5
53.0
56.0
61.5
66.0

2400
3050
3600
4450
5880
6900
7950
9300
11450
13750

110
130
155
190
225
260
295
330
385
425

98
120
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

ohm/km

6 wire 0.727
6 wire 0.524
6 wire 0.387
12 wire 0.268
15 wire 0.193
18 wire 0.153
18 wire 0.124
30 wire 0.0991
34 wire 0.0754
34 wire 0.0601

Type: YSYRGY
Specification: IEC-60502-1
Voltage: 3.6/6 KV
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Copper Screened

5.

PVC Separation Sheath

6.

Round galvanising steel wires armouring

7.

Helical steel tape binder(Optional)

8.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
o
Wires
20 C

Nominal
Diameter of Nominal
Round
Thickness
Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

mm

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.15

2.2
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.2
3.4

41.0
42.0
46.0
49.0
53.0
56.0
59.0
61.5
67.0
72.0

3200
3630
4550
5480
6640
7700
8770
10200
12370
15300

105
125
145
180
215
245
275
305
350
390

105
125
155
190
235
270
305
350
405
460

x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

ohm/km

6 wire 0.727
6 wire 0.524
6 wire 0.387
12 wire 0.268
15 wire 0.193
18 wire 0.153
18 wire 0.124
30 wire 0.0991
34 wire 0.0754
34 wire 0.0601

Type: YSYFGY
Specification: IEC-60502-1
Voltage: 1.8/3.0 KV
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Copper Screened

5.

PVC Separation Sheath

6.

Flat galvanising steel wires armouring

7.

Helical steel tape binder(Optional)

8.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
o
Wires
20 C

Nominal
Nominal
Diameter of
Thickness
Flat Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

mm

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.4

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.9
2.0
2.1
2.2
2.3
2.4
2.6
2.7
2.9
3.1

32.5
33.5
36.0
39.5
43.5
46.5
50.0
52.5
57.0
60.0

2100
2500
3000
3800
4800
5700
6800
8000
10150
12000

110
130
155
190
225
260
295
330
385
425

98
120
150
190
230
270
305
350
410
470

x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

ohm/km

6 wire 0.727
6 wire 0.524
6 wire 0.387
12 wire 0.268
15 wire 0.193
18 wire 0.153
18 wire 0.124
30 wire 0.0991
34 wire 0.0754
34 wire 0.0601

Type: YSYFGY
Specification: IEC-60502-1
Voltage: 3.6/6 KV
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Inner Covering

4.

Copper Screened

5.

PVC Separation Sheath

6.

Flat galvanising steel wires armouring

7.

Helical steel tape binder(Optional)

8.

PVC Oversheath

Nominal
Cross
Sectional
Area of
Conductor

Maximum
No. and
Resistance of Nominal
Nominal
Thickness of
Diameter of Conductor at
Insulation
Wires
20o C

Nominal
Nominal
Diameter of
Thickness
Flat Armour
of Seath
Wire

Approx
Overall
Diameter

Current Rating
Approx Under
In Air
Weight Ground at
of Cable at 30oC 35oC

no. x mm2

no./mm

mm

mm

mm

mm

kg/km

amp

amp

3
3
3
3
3
3
3
3
3
3

Min
Min
Min
Min
Min
Min
Min
Min
Min
Min

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

2.1
2.2
2.3
2.4
2.5
2.7
2.8
2.9
3.1
3.2

38.0
39.5
43.0
46.0
50.0
53.5
56.0
59.0
64.0
98.0

2600
3100
3590
4450
5500
6500
7500
8800
10950
13200

105
125
145
180
215
245
275
305
350
390

105
125
155
190
235
270
305
350
405
460

x
x
x
x
x
x
x
x
x
x

25 sm
35 sm
50 sm
70 sm
95 sm
120 sm
150 sm
185 sm
240 sm
300 sm

ohm/km

6 wire 0.727
6 wire 0.524
6 wire 0.387
12 wire 0.268
15 wire 0.193
18 wire 0.153
18 wire 0.124
30 wire 0.0991
34 wire 0.0754
34 wire 0.0601

Other Cables
Type: NYAB
Voltage: 600/1000 volts
1.

Plain Annealed Flexible Copper Conductor

2.

PVC/Cotton Tape Binder

3.

PVC Insulation

Nominal Cross
Sectional Area of
Conductor

Maximum
No. and Nominal Resistance of
Nominal
Diameter of
o C Thickness of
Conductor
at
20
Wires
Insulation

Approx
Overall
Diameter

Approx
Weight of
Cable

Current Rating
at 350C Ambient
Temp.

no. x mm2

no./mm

ohm/km

mm

mm

kg/km

amp

1
1
1
1
1
1
1
1
1
1
1
1

7/0.40
19/0.53
19/0.65
49/0.55
49/0.63
84/0.62
133/0.59
133/0.70
189/0.70
259/0.70
336/0.68
392/0.70

24.50
4.470
2.920
1.770
1.120
0.708
0.514
0.379
0.262
0.189
.150
0.122

0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
1.8
2.0

2.5
4.7
5.3
7.2
8.1
10.5
12.0
14.5
16.5
19.0
20.5
23.0

14
50
75
125
185
285
396
560
760
1030
1260
1580

17
41
52
72
98
131
167
204
256
314
366
423

x
x
x
x
x
x
x
x
x
x
x
x

0.75 rm
4.0 rm
6.0 rm
10 rm
16 rm
25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm

Type: BYA
Flame Retardant Cables
Specification: BDS-900 and BS-2004
Voltage: 450/750 volts
1.

Copper Conductor

2.

FR-PVC Insulation
Current Rating
Clipped to a
Bunched and Surface or on
Enclosed in
a Cable Tray
Approx
Weight of Conduits Two Bunched &
Cables Single Unenclosed 2
Cable
Phase at
Cables Single
35oC
Phase at 35oC

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Approx
Overall
Diameter

no. x mm2

no./mm

ohm/km

mm

mm

kg/km

amp

amp

1
1
1
1
1
1
1
1
1
1
1
1
1
1

1/1.13
1/1.38
7/0.52
7/1.78
7/0.67
7/0.85
7/1.05
7/1.35
7/1.71
7/2.14
19/1.53
19/1.83
19/2.17
19/2.52

18.1
12.1
12.1
7.41
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193

0.7
0.7
0.7
0.8
0.8
0.8
0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6

2.8
3.3
3.5
3.9
4.2
4.8
5.4
6.8
8.0
9.8
11.0
12.5
14.5
17.0

17
22
23
35
36
55
75
115
178
275
375
530
720
1000

13
16
16
22
22
30
38
52
70
91
112
136
173
216

16
20
20
28
28
37
47
63
85
110
136
164
207
253

x
x
x
x
x
x
x
x
x
x
x
x
x
x

1.0 re
1.5 re
1.5 rm
2.5 re
2.5 rm
4.0 rm
6.0 rm
10 rm
16 rm
25 rm
35 rm
50 rm
70 rm
95 rm

Type: Service Drop Cables


Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

Maximum
Nominal Cross
Resistance of
Sectional Area No. and Nominal Diameter of Wires Conductor at
of Conductor
20o C

Nominal
Approx
Thickness of Overall
Insulation
Diameter

Current
Rating at
Approx
Weight of 350C
Cable
Ambient
Temp.

no. x mm2

no./mm

ohm/km

mm

mm

kg/km

amp

2.5 re / 2.5 re
4 rm / 4 re
4 rm / 6 rm
4 rm / 6 re
6 rm / 6 re
10 rm / 10 rm

1
7
7
7
7
7

7.41
4.61
4.61
4.61
3.08
1.83

1.6
1.6
1.6
1.6
1.6
1.6

10.0
11.7
12.0
12.0
12.3
14.5

90
135
165
160
180
270

27
35
35
35
45
62

x
x
x
x
x
x

1.78
0.85
0.85
0.85
1.05
1.35

/
/
/
/
/
/

1 x 1.78
1 x 2.26
7 x 1.05
1 x 2.77
1x 2.77
7 x 1.35

/
/
/
/
/
/

7.41
4.61
3.08
3.08
3.08
1.83

16 rm / 16 rm 7 x 1.71 / 7x 1.71
25 rm / 25 rm 7 x 2.14 / 7 x 2.14

1.15 /1.15
1.6
0.727 / 0.727 1.6

16.6
19.2

396
595

84
110

Type: Service Drop Cables


Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

Nominal Cross Sectional Area of


Conductor

Maximum
Resistance
No. and Nominal Diameter of of
Wires
Conductor
at 20o C

Nominal
Approx
Thickness
Overall
of
Diameter
Insulation

Current
Approx Rating at
Weight
350C
of
Cable Ambient
Temp.

no. x mm2

no./mm

mm

mm

kg/km

amp

3 x 4 rm / 4 re

7 x 0.85 / 1 x 2.26

1.6

15.0

275

32

3 x 4 rm / 6 re

7 x 0.85 / 1.2.77

1.6

15.5

290

32

3 x 6 rm / 6 rm

7 x 1.05 / 7 x 1.05

1.6

16.0

370

41

3 x 10 rm / 10 rm

7 x 1.35 / 7 x 1.35

1.6

18.5

538

56

3 x 16 rm x 16 rm

7 x 1.71 / 7 x 1.71

1.6

21.0

792

75

3 x 25 rm / 25 rm

7 x 2.14 / 7 x 2.14

1.6

24.5

1180

98

ohm/km

4.61 /
4.61
4.61 /
3.08
3.08 /
3.08
1.83 /
1.83
1.15 /
1.15
0.727 /
0.727

Type: Welding Cables


Voltage: 200 volts
1.

Copper Conductor

2.

PVC Insulation

Nominal Cross
Sectional Area of
Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Nominal
Resistance of
Thickness of
Conductor at 20o C Sheath

Approx
Overall
Diameter

Approx
Weight of
Cable

Current Rating at
Maximum Duty
Cycle of 60%

no. x mm2

no./mm

ohm/km

mm

mm

kg/km

amp

1
1
1
1
1
1

850 / 0.193
1196 / 0.193
1708 / 0.193
2392 / 0.193
3247 / 0.193
4101 / 0.193

0.780
0.554
0.386
0.272
0.206
0.161

2.1
2.1
2.1
2.2
2.2
2.2

12.0
13.2
15.0
17.0
19.0
23.0

320
430
590
790
950
1300

169
215
264
330
405
473

x
x
x
x
x
x

25 rm
35 rm
50 rm
70 rm
95 rm
120 rm

Type: NYYF (Co_Axial Cables)


Voltage: 600/1000 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Common Covering

4.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Maximum
Resistance of
Conductor at
20o C

Nominal
Thickness of
Insulation

Nominal
Approx
Thickness of Overall
Sheath
Diameter

Current
Approx
Rating at
Weight of
350C Ambient
Cable
Temp.

no. x mm2

no./mm

ohm/km

mm

mm

mm

kg/km

amp

1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4

19 / 0.53
19 / 0.65
49 / 0.53
49 / 0.65
84 / 0.62
133 / 0.59
133 / 0.70
189 / 0.70
259 / 0.70
336 / 0.68
392 / 0.70
7 / 0.53
7 / 0.69
19 / 0.53
19 / 0.65
49 / 0.53
49 / 0.65
84 / 0.62
133 / 059
7 / 0.53
7 / 0.69
19 / 0.53
19 / 0.65
49 / 0.53
49 / 0.65
84 / 0.62
133 / 0.59

4.470
2.920
1.770
1.120
0.708
0.514
0.379
0.262
0.189
0.150
0.122
12.10
7.28
4.56
3.03
1.81
1.44
0.722
0.524
12.10
7.28
4.56
3.03
1.81
1.44
0.722
0.524

1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
1.8
2.0
0.8
0.9
1.0
1.0
1.2
1.2
1.4
1.4
0.8
0.9
1.0
1.0
1.2
1.2
1.4
1.4

1.4
1.4
1.4
1.4
1.4
1.4
1.6
1.6
1.6
1.8
1.8
1.4
1.4
1.4
1.6
1.6
1.6
1.8
1.8
1.4
1.4
1.6
1.6
1.6
1.6
1.8
1.8

7.5
8.5
10.0
11.2
13.0
14.5
17.5
19.5
22.0
24.6
27.1
11.7
12.0
13.5
15.4
19.6
22.9
28.9
32.0
12.0
13.1
15.3
17.0
21.7
25.5
32.2
35.5

90
120
180
250
360
480
680
880
1164
1437
1840
175
220
270
408
637
955
1320
1900
200
270
340
500
780
1135
1640
2360

41
52
72
98
131
167
204
256
314
366
423
17
24
33
43
58
78
102
125
17
24
33
43
58
78
102
125

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

4 rm
6 rm
10 rm
16 rm
25 rm
35 rm
50 rm
70 rm
95 rm
120 rm
150 rm
1.5 rm
2.5 rm
4 rm
6 rm
10 rm
16 rm
25 rm
35 rm
1.5 rm
2.5 rm
4 rm
6 rm
10 rm
16 rm
25 rm
35 rm

Type: PVC Ins. Flexible Cable


Voltage: 250/440 volts
1.

Copper Conductor

2.

PVC Insulation

Nominal Cross
Sectional Area of
Conductor

No. and Nominal Nominal


Diameter of
Thickness of
Wires
Insulation

Approx Overall
Approx
Diameter of Each Weight of
Core
Cable

Current Rating
In Conduit at In Air at 35oC
35oC Ambient Ambient
Temp
Temp.

no. x mm2

no./inch

mm

mm

kg/km

amp

amp

1
1
1
1
2
2
2
2

14
23
40
70
14
23
40
70

0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635

2.26
2.57
2.84
3.43
2.26
2.57
2.84
2.26

9
13
17
25
19
27
35
51

2
5
11
16
2
5
11
16

3
6
13
18
3
6
13
18

x
x
x
x
x
x
x
x

0.4
0.65
1.1
2.0
0.4
0.65
2.0
2.0

/
/
/
/
/
/
/
/

0.0076
0.0076
0.0076
0.0076
0.0076
0.0076
0.0076
0.0076

Type: PVC Ins. Flexible Flat Cable


Voltage: 250/440 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

Nominal Cross
Sectional Area
of Conductor

No. and
Nominal
Diameter of
Wires

Nominal
Thickness of
Insulation

Nominal
Thickness of
Sheath

Approx
Overall
Dimension

Current Rating
Approx
In Conduit at In Air at 35oC
Weight of
35oC Ambient Ambient
Cable
Temp
Temp.

no. x mm2

no./inch

mm

mm

mm

kg/km

amp

amp

2 x 0.40
2 x 0.65

14 / 0.0076
23 / 0.0076

0.635
0.635

0.762
0.762

6.05 x 3.91
6.65 x 4.22

34
43

3
6

4
8

Type: PVC Ins. Flexible


Circular Cable
Voltage: 250/440 volts
1.

Copper Conductor

2.

PVC Insulation

3.

PVC Sheath

No. and
Nominal Cross
Nominal
Sectional Area of
Diameter of
Conductor
Wires

Nominal
Thickness of
Insulation

Nominal
Thickness of
Sheath

Approx
Overall
Diameter

Current Rating
Clipped to a
In Conduit
Surface or on
Approx
Single Phase a Cable Tray
Weight of
Single Phase
at 35oC
Cable
Ambient
at 35oC
Temp
Ambient
Temp.

no. x mm2

no./mm

mm

mm

mm

kg/km

amp

amp

2 x 0.4

14 / 0.0076

0.635

1.016

6.55

55

2
2
2
2
3
3
3
3
3
4
4
4
4
4

x
x
x
x
x
x
x
x
x
x
x
x
x
x

0.65
1.10
2.0
3.2
0.4
0.65
1.10
2.0
3.2
0.4
0.65
1.10
2.0
3.2

23 / 0.0076
40 / 0.0076
70 / 0.0076
110 / 0.0076
14 / 0.0076
23 / 0.0076
40 / 0.0076
70 / 0.0076
110 / 0.0076
14 / 0.0076
23 / 0.0076
40 / 0.0076
70 / 0.0076
110 / 0.0076

0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635
0.635

1.016
1.016
1.27
1.27
1.016
1.016
1.016
1.27
1.27
1.016
1.016
1.27
1.27
1.27

7.16
7.72
9.09
10.16
6.88
7.54
8.15
9.60
10.92
7.32
8.10
9.30
10.40
11.38

68
83
119
155
64
78
100
145
195
70
93
129
175
225

6
13
18
24
2
5
11
16
21
2
5
11
16
21

8
16
22
26
3
7
14
20
24
3
7
14
20
24