You are on page 1of 35

16-QMP-05-3B

02 12.04.12 CLIENT COMMENTS INCORPORATED


AND REISSUED FOR USE
AKJ BPN TBY
01 29.03.12 CLIENT COMMENTS INCORPORATED
AND REISSUED FOR USE
AKJ ARUS TBY
00 21.02.12 ISSUED FOR USE AKJ ARUS TBY
Rev. Date Description Prpd. Chkd. Appd.

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR
HV VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 1 of 30












CHAPTER 4
TECHNICAL SPECIFICATION
FOR
HV VARIABLE FREQUENCY DRIVE
SYSTEM


























16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 2 of 35


1. Scope

The equipment listed below shall be supplied in accordance with the requirements specified in this
document, equipment data sheet, specification applicable codes and standards and other documents
attached/ referred herein.

Sl.
No.
Quantity STATION Description
1. 2 SET KHOPOLI
6.6kV, 3phase, minimum 18 pulse variable speed drive (VSD)
system suitable for 2 Nos. New Pump Motor of 2750kW
(Estimated rating) and 1 No. Existing 750kW (Refer Attach Motor
Data Sheet for Detail) including Dry type VSD transformer.

VSD Set/System shall be complete with the following as per
attached system configuration:
1. One No. Synchronous Panel.
2. One No. Common Drive Logic Panel.
3. One Set. of Down Stream Breakers Panel Board
(Consists of 9 Nos. of Breakers).
4. Interconnecting Power & Control Cables required for the
above VSD System.
5. 3 Nos. of Local Control panels.
6. Addition/ Modification of Existing 6.6kV Switchboard.
7. Any required change in control scheme.

Note:
Both VFDs shall have option for cross-selection of motor
according to the pump which is under operation as per attached
system configuration.
Same VFD shall be suitable for both rating of motor i.e. 2750kW &
750kW.

2
1 SET
For each
rating
-
Special Tools and Tackles required for the erection, testing,
commissioning, operation and maintenance of Complete System
at Khopoli.
3
1 SET
For each
rating
-
Recommended Commissioning Spare Parts for Complete System
at each location Khopoli.
4
1 SET
For each
rating
-
Mandatory Spares as per vendor recommendation for Complete
System at each location Khopoli.
5
1 SET
For each
rating
-
Recommended 2 year operation & maintenance Spare
(Vendor to submit unit rate separately for the same)
Notes:
1. Vendor to visit site (At Khopoli) before submitting offer and analyze required 6.6kV switchgear
modification/addition as per attached system configuration and indicate the same in their offer. All
the required modifications/additions due to addition of VFD system in the 6.6kV switchboard are in
the scope of vendor. Vendor to check and indicate interface requirement with UCP Panel and
Station PLC. All interface requirements and any changes in control scheme are in the scope of
vendor.
2. Vendors scope of work includes design, engineering, manufacturing, shop testing, inspection of
bought out items and supply of all electrical equipments.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 3 of 35

3. Pumps shall be fed from VSD system which includes input converter transformer. Protection and
Metering for VSD system shall be as per attached specifications for VSD system and referred codes
and standards.
4. VSD panel shall be located in the sub-station. Vendor to indicate requirement of Air-conditioned
room for the same (If any). However, equipment shall be suitable for operation even during failure of
Air-Condition.
5. With reference to limits of harmonics as per IEEE 519, the harmonics are to be controlled at 6.6kV
bus. The overall power factor of the drives at 100% load shall not be less than 0.99
6. Any other accessory, fixing hardware, switches etc. which shall be required for satisfactory operation
and completeness shall be provided by vendor.
7. Type test certificates and utility consumption list shall be submitted with the offer.
8. Inspection and Testing at works shall be as per VSD specification.

9. Final Documentation:
A. Vendor to furnish Hard Copy and electronic files of all the documents indicated for final
documentation in addition of hard copy.
B. Vendor to furnish all drawings and documents either in MS Word, MS Excel, Autocad, Microstation
stored in electronic media.
C. Final documentation shall be provided along with hard copies in compact disc compatible with
standard PC based application.
D. All operating and maintaining instructions in electronic media or in scanned images converted in
electronic media.

Final documentation shall be provided in CD with proper index along with hard copies.

ORDER OF PRECENDENCE:
1. Statutory Rules and Regulations
2. This Requisition
3. Equipment Data Sheet
4. Standard specification
5. Codes and Standards































16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 4 of 35

1.0 SCOPE
These specification covers design, manufacturing, testing at works, packing and
supply of High Voltage (6.6KV), AC Variable Frequency Drive system along with
bypass isolators. The VFD system shall be compatible with Squirrel Cage
Induction Motor as specified in specification no. 9579-02-TS-101 and complete
with converter, converter input transformer (if required), DC link reactor with
associated auxiliaries, harmonic filters (if required), isolators, field mounted local
control panel etc. as detailed below.
2.0 GENERAL
The Vendor shall be responsible for engineering and functioning of the complete
system, meeting the requirement of this specification and data sheets. This shall
include but not be limited to inverter sizing, input transformer sizing, transformer
impedance selection, vector group, input and output harmonic filter(if required)
design and sizing, output dv/dt filter sizing, isolator rating, motor cable selection/
sizing and motor sizing / selection.
3.0 SITE CONDITIONS
3.1 The VFD and all other associated equipments shall be suitable for operating
satisfactorily in humid and highly corrosive atmosphere prevailing in refineries
and other petroleum installations.
Ambient temperature: 5 to 50
0
C.
Humidity: 95%
Altitude: less than 1000m above MSL.
3.2 The AC drive (with or without in built converter transformer) & isolators shall be
installed indoors in a non-hazardous room, as specified in data sheet. Motor shall
be installed outdoors in hazardous area as specified in datasheet. The vendor
shall furnish the required clearances in VFD room including layout, earthing
requirement and the required capacity of AC, if any, for efficient and reliable
operation of the VFD.
3.3 VFD system shall be designed for continuous duty as per nameplate rating under
the specified ambient conditions.
4.0 APPLICABLE CODES AND STANDARDS
4.1 The equipment shall comply with the requirements of latest revision of following
standards issued by BIS (Bureau of Indian Standards), unless otherwise specified.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 5 of 35

The offered equipment shall comply with latest editions of following standards.
The vendor shall clearly bring out in the offer the applicable standard for every
feature of the offered component, if different from the following standards.
IS-3700 : Essential ratings and characteristic of semi-conductor devices
IS-3715 : Letter symbols for semi-conducting devices
IS-4411 : Code of designation of semi-conducting devices
IS-5001 : Guide for preparation of drawings for semi-conductor devices
IS-5469 : Code of practice for the use of semi-conductor junction devices
IS-6297 : Transformers and indicators for electronic equipment
IS-8789 : Performance parameters for motors
IS-12729 : Switchgear and control gear for voltages exceeding 1000V- General
requirements
IS-13408 : Code of practice for the selection, installation and maintenance of
electrical apparatus for use in potentially explosive atmospheres
IEC 146 : Semi Conductor converters
IEC 297 : Dimension of panels and racks
IEC 326 :General requirements and measuring methods for printed wiring
boards
IEC 352 : Solder less wrapped connection
IEEE 444 : Protection standards for converters
IEEE 519 : Harmonic control & reactive compensation of static power
converters
DIN 41488 : Electrical engineering dimensions
In case Indian standards are not available for any particular equipment,
standards issued by IEC/BS/VDE/ IEEE/NEMA/UL/FM/CE or equivalent agency
shall be applicable.
5.0 GENERAL REQUIREMENTS
5.1 The offered equipment shall be brand new with state of art technology and proven
field track record. No prototype equipment shall be offered.
5.2 The VFD model offered shall be from the existing VFD model series in the regular
manufacturing range of the manufacturer. Along with the offer the Vendor should
submit the supply record and satisfactory performance record for 8000 Hr
running of the VFD supplied in India or abroad in a hydrocarbon industry
(Preferably in a petroleum oil pipeline).
5.3 Vendor shall ensure availability of spare parts and maintenance support services
for the offered equipment for at least for 15 years from the date of supply. The
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 6 of 35

offered VFD manufacturer should have their maintenance service & spares supply
network in India to provide quick maintenance service & Spares supply support.
The vendor shall indicate the source for supply of spares & Maintenance service
location in India.
5.4 Vendor shall ensure proper coordination with the driven equipment supplier in
selection / sizing of offered variable frequency drive system.
6.0 TECHNICAL REQUIREMENT
6.1 Performance Requirement
6.1.1 The system shall be fully digital, Microprocessor based, energy efficient, and shall
provide very high reliability, high power factor, low harmonic distortion and low
vibration and wear and noise. It shall be easy to install in minimum time and
expense and no special tools shall be required for routine maintenance.
6.1.2 The system shall be designed to deliver the motor input current and torque for the
complete speed torque characteristics of the driven equipment, with maximum
input supply voltage variation of +10% and frequency variation of +3%. The
system shall be suitable for the load characteristics and the operational duty of
the driven equipment.
6.1.3 It shall be capable of withstanding the thermal and dynamic stresses and the
transient mechanical torque, resulting from short circuit. Any damage resulting
from such a short circuit or internal fault shall be limited to the component
concerned.
6.1.4 The drive system shall be designed to operate in one or more of the following
operating modes as to suit characteristics of the driven equipment or specified in
the data sheet:
a. Variable torque changing as a function of speed i.e. speed squared
b. Constant torque over a specific speed range.
c. Constant power over a specific speed range where the torque decreases when
speed increases.
d. Any other as specified in data-sheet
6.1.5 The drive controller shall be equipped with microprocessor based digital regulator
with programmable functions. The power control regulator logic shall provide for
an acceleration / deceleration current limit curve and shall be capable of field
adjustments without shutting the system down. Linear acceleration and
deceleration shall be separately programmable from 0.1 second to 20 second.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 7 of 35

6.1.6 The system shall be suitable for single quadrant operation and the speed variation
shall be within range 10-110% with speed set accuracy of +1% of rated maximum
speed and steady state regulation of +0.5% of rated speed.
The total harmonic distortion (THD) of the voltage and current at inverter output
shall be as per IEC 61800-4 and it shall be considered in the design of the motor.
6.1.7 Harmonics at the supply side of the drive system i.e. at primary of the main input
transformer shall be restricted within the maximum allowable levels of current
and voltage distortion as per recommendations in the latest edition of IEEE-519.
Harmonic studies shall be conducted with maximum and minimum system fault
level, cable capacitance, system equipment reactance etc. The studies shall
highlight but not be limited to maximum load current, expected resonant
frequencies, need of harmonic filters, sequence of switching of filters, voltage wave
form etc.
6.1.8 Unless otherwise specified, the overload capacity of the controller shall be 150% of
rated current of motor for one minute for constant torque applications, and 115 %
of rated current for one minute for variable torque applications at rated voltage. If
the motor load exceeds the limit, the drive shall automatically reduce the
frequency and voltage to the motor to guard against overload. If load demand
exceeds the current limit for more than 1 minute, the drive shall shut down to
prevent over heating of the motor and damage to the drive.
6.1.9 During operation, the system shall be capable of developing sufficient torque
under all load conditions to respond to a 20% alteration in speed set point within
a time limit up to 60 seconds.
6.1.10 The integrator action of the speed set point alteration shall be independently
adjustable for both an upward and a downward alteration. The minimum time
interval between set point adjustments by the distributed control system shall be
considered as 10 seconds.
6.1.11 The drive shall trip in case the speed exceeds 110% of the maximum operational
speed or reduces to 95% of the minimum operational speed for more than 10
seconds.
6.1.12 Maximum noise level from the drive at 1-meter distance, under rated load with all
normal cooling fans operating shall not exceed 85 dBA.
6.1.13 Variable frequency drive shall be arranged so that it can be operated in an open
circuit mode, disconnected from the motor for startup adjustments and
troubleshooting / maintenance.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 8 of 35

6.1.14 VFD should have by-pass system for running of motor on DOL in case of any
problem in VFD. By-pass system should be provided with 3 vacuum contactors of
6.6 KV voltage level & suitable current rating corresponding to Motor & VFD
rating. All the three contactors shall have Mechanical & Electrical interlocks. Also,
Contactors should have Electrical interlock with VFD. Vendor is to furnish the
detailed scheme, catalogue & datasheet of contactor, interlock details etc. with
VFD for owner approval.
6.1.15 Voltage at Motor Neutral shall be maintained at ground potential for the total
operating condition.
6.1.16 Motor space heater supply for approximate rating of 240 V, 400 Watts is to be
provided in VFD Panel interlocked with VFD Run command i.e. when Motor is
running, motor space heater shall be OFF and when Motor is stopped, motor
space heater shall be ON. In case of bypass mode operation of Motor, a contact
shall be taken from Bypass Mechanism so that logic for Space heater is ensured
i.e. heater is ON when Motor is stopped and vice-versa.
6.2 Control Requirement
6.2.1 The system shall operate on constant v/f supply with required boost capability in
low frequency mode of operation.
6.2.2 Short time voltage dips up to 20% of nominal voltage (e.g. in case of a large motor
start up connected to the same bus as VFD) shall not cause the control system to
stop functioning and shall not trip the drive system.
6.2.3 The system shall also be equipped with a facility which will restart the system in
case of voltage dip over 20% of power interruptions for min. 2 seconds, with
recovery of the voltage to its nominal value, with a facility to block the automatic
restart if required by the operator. Upon restart the converter shall be capable of
synchronizing onto a rotating motor and develop full acceleration torque within 10
seconds.
6.2.4 The system shall be suitable for number of starts as per the specifications of the
Motor in chapter-3.
6.2.5 The power controller shall be controlled to always start the motor in the forward
direction. Logic shall be provided to prevent the motor from being started in the
reverse direction.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 9 of 35

6.2.6 The drive motor shall be speed controlled corresponding to 4-20 mA or 0-10V
reference input signal, the drive shall automatically run at constant speed as at
80-110% of the last speed reference available prior to the loss of signal.
6.2.7 It shall be possible to vary the speed of the drive in either Local or Remote mode.
Local / Remote selection shall be from VFD panel unless otherwise specified.
a. With the selector switch in Local mode, the operator shall be able to set the
speed through keypad, mounted on front of the drive panel.
b. With the selector switch in Remote mode, speed of the motor shall be
controlled from a 4-20 mA signal, from owners PLC/SCADA system. The
relationship between the speed, torque and the reference signal (4-20mA)
within the operational speed shall be linear. Necessary equipment required for
interfacing with PLC/SCADA shall also be provided in the drive panel.
6.2.8 The required provision for the interface with remote PLC/SCADA located at control
room shall be through hardwiring of interface signals (DI/DO/AI/AO) with
potential free contacts and transducers. Also, provision for MODBUS
communication (RS 485) from VFD to Owners control panel shall be made
available. Vendor shall provide protocol details, mapping and addresses to be
taken by Owners panel.
6.3 Panel Construction
6.3.1 The drive shall be suitably housed in sheet steel panels fabricated with 2 mm
thick cold rolled sheet steel. The panel shall be suitable for indoor installation. The
panel shall be free standing, dust and vermin proof with degree of enclosure
protection as IP-4X. The maximum and minimum operating height shall be 1800
mm and 300 mm respectively.
6.3.2 The cable entry shall be from the bottom of the panel and bolted un-drilled gland
plate shall be provided. Clamp type terminals shall be used for connection of all
wire up to 10 mm
2
and terminal for higher sizes shall be bolted type suitable for
cable lugs. Minimum space for power cable termination shall be 600 mm clear
from bottom of the cable gland plate.
6.3.3 Bus bars shall be of electrolytic copper/aluminium, colour coded separately for AC
and DC system. All the live parts shall be sleeved / shrouded to ensure complete
safety to personnel intending to carry out routine inspection by opening the panel
doors. All the equipment inside the panel and on the doors shall be provided with
suitable nameplate.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 10 of 35

6.3.4 The panel shall include suitable semi conducting power devices (Diodes /
IGBT/IGCT/SGCT)

modules with protective devices, reactors (if required), filters (if
required), control circuit, control accessories, indication and annunciation etc. The
construction of the panel shall provide effective protection against electromagnetic
emissions and shall be the design requirement of integrated standards.
6.3.5 Upstream breaker ON/OFF/TRIP indications and remote breaker closing and trip
push button shall be provided on the front door.
6.3.6 Safety interlock shall be provided so that power cabinet cant be opened unless the
upstream breaker is disconnected, safety-grounding switch is closed and DC link
capacitor is discharged.
6.3.7 All the switches, component and accessories, which are essential for normal and
emergency operation, shall be mounted on the door and shall be operable
externally. All the analogue instruments, where provided, shall be switchboard
type, back connected, 96 mm x 96 mm. Scale shall have red mark indicating
maximum permissible operating rating.
6.3.8 Panels except power cell chamber shall be provided with illuminating lamp with
switch and fuse. 5/15A, 240V power socket with switch and fuse shall be
provided. Each panel shall have space heater with switch fuse/MCB and variable
setting thermostat.
6.3.9 Copper earth bus of minimum size 30 x 6 mm upto short circuit withstand
capacity of 31.5 KA and 50 x 6 mm for a short circuit withstand capacity above
31.5 KA shall be provided in the panel with provision for connection to Owners
plant earth grid. All the non-metallic components / parts shall be connected to the
main earth bus bar. Separate earth bus bar and stud for electronic control system
shall be provided.
6.3.10 All the metal parts shall be treated so as to ensure efficient anti-corrosive
protection. Hardwares shall be zinc passivated or electro-galvanized. Panel
enclosure and structure supports shall be thoroughly cleaned and degreased to
remove mill scale and rust etc. External surface shall be prepared for final
painting shade of RAL 7032 (Siemens grey) as per DIN.
6.3.11 All panels shall be of same height so as to form a uniform line-up, to give good
aesthetic appearance.
6.3.12 All the control wiring shall be enclosed in plastic / metal channel. Each wire shall
be identified at both ends by self-sticking wire marker tapes or PVC ferrules.
Power and control wiring inside the panel shall be done with BIS approved, PVC
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 11 of 35

insulated, fire retardant, copper conductor wire 1.5 mm
2
size wire shall normally
be used provided the control fuse rating is 10 Amps or less and 2.5 mm
2
size for
control fuse rating 16 A & above for electrical circuits and 0.5 mm
2
for electronic
circuits. All wires shall be ferruled and terminals shall be properly numbered,
minimum 20% spare terminal shall be provided.
6.3.13 All electronic modules and components shall be accessible from front of panel
only. Modular assemblies for both the system control electronic equipment and
power electronic equipments shall be used.
6.3.14 All low voltage compartment and cabling shall be electrically and physically
separated from the high voltage compartment.
6.3.15 Suitable removable type hooks shall be provided for lifting the panel.
6.3.16 Suitable transparent insulating material shall be used for covering live
components.
6.3.17 Drive keypad, operator control panel required for control, monitoring and
measurements shall be supplied and installed outside the panel on the front door.
It shall be accessible for operation without opening the front door and shall be
non-removable type.
6.3.18 All equipment shall be complete with cable glands, lugs etc. and cable glands shall
be double compression type.
6.3.19 DC link capacitor and pre-charging and discharging circuit shall preferably be
mounted in the rear of the panel.


6.4 Cooling
6.4.1 The drive panel shall be naturally air cooled as per manufacturers standards. If
unavoidable, forced type-cooling system shall be provided. Vendor shall ensure
that the panel dimensions and flow paths have been designed for continuous
running at the specified ambient without over hearting & suggest the cooling
system to be provided in VFD room considering heat generation in VFD & 50 deg
Cent ambient temp.
6.4.2 For fan cooled drives, redundant cooling fans (N+1) shall be provided. In case
the redundant fan is not possible to be mounted, same shall be supplied
loose.


6.4.3 Necessary starter shall be provided with in the VFD panels for the Ventilation fans
and any other auxiliary motors etc. The system provided shall be interfaced with
drive starting and shut down such that safety interlocks such as Start Permissive
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 12 of 35

from cooling system to drive and trip signal from cooling system to drive in case of
cooling system failure etc. shall be incorporated in the overall sequence logic.


6.5 Equipment / Component Specification
6.5.1 Motor
The motor shall be designed, constructed and tested in accordance with the
owners specification / data sheet (refer specification no. 9579-02-TS-101) for high
voltage induction motor, in addition to the following requirements:
a. The motor shall be suitable for operation with a solid state power supply
consisting of an adjustable frequency inverter for speed control and DOL.
b. The motor shall be suitable for the current waveforms produced by the power
supply including the harmonics generated by the drive.
c. The motor shall be designed to operate continuously at any speed over the
range (10-110%) of rated speed unless otherwise specified in data sheet.
d. The permitted voltage variation should take into account the steady state
voltage drop across the AC drive and all other system components upstream
of the motor.
e. The motor shall be constructed to withstand torque pulsations resulting from
harmonics generated by the solid-state power supply.
f. The motor insulation shall be designed to accept the applied voltage
waveform, within the Vpeak and dv/dt limits as per IEC-61800-4.
g. The drive manufacturer shall be solely responsible for proper selection of the
motor for the given load application and the output characteristics of the
drive.
For detailed motor specification and data sheet refer specification no. 9579-02-TS-
101.
6.5.2 Converter Transformer
a) The converter transformer, if provided, shall be copper wound dry type.
Insulation class of dry type transformer shall be H with temperature rise of
body limited to 75C. Dry type transformer shall preferably be mounted inside
the drive system panel. The impedances of converter input transformers with
more than one secondary winding for minimum 18 pulse systems shall be
selected to ensure equal load / current sharing between the secondary
windings, the converters and the motor windings under all operational
conditions including starting and restarting.
b) The transformation ratio, impedances, taps and secondary voltage shall be
chosen by the drive vendor to optimize system performance.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 13 of 35

c) The transformer shall be designed, manufactured and tested in accordance
with latest applicable Indian standards or equivalent international standards.
d) Transformer for operation with converters shall be suitable for operation with
non-sinusoidal wave shape and DC components under normal and abnormal
conditions of the system without exceeding the temperature.
6.5.3 Power Converter
a. The static power converter shall consist of a line side converter for operation as
a rectifier and a load side power converter for operation as a fully controller
inverter. Power converter shall be fast switching, most efficient and low loss
type.
b. The converter shall be co-ordinated with the transformers. The converter shall
be able to withstand a three phase short circuit current until interrupted by
normal breaker operation.
c. Adequate short circuit and over voltage protection shall be provided for the
converter and inverter system.
d. All power converter devices shall include protective devices, snubber networks
and dv/dt networks as required.
e. The current rating of the converters semi-conductor components shall not be
less than 120% of the nominal current flowing through the elements at full
load of the VFD through the whole speed range. If the parallel connection of
semi conductor is applied, the above current rating shall not be less than
140% of the above values.
f. All power diodes shall be of silicon type with minimum VBO rating at 2.5 times
the rated operating voltage.
g. The power converter circuit shall be designed so that motor can be powered at
its full nameplate rating continuously without exceeding its rated temperature
rise nor reducing its service factor due to harmonic currents generated by the
inverter operation.
h. The conversion devices and associated heat sinks shall be assembled such that
individual devices can be replaced without requiring the use of any special
precautions / tools.
i. The cooling system of the electronic components, if provided, shall be
monitored and necessary alarms shall be provided to prevent any
consequential damage to the power control devices.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 14 of 35

j. All power controller devices shall be protected with high speed semiconductor
grade fuse. I
2
t particulars of the power controller devices and the fuses shall be
supplied along with the calculations in support of the selection of fuses.
k. Offered system shall also take in account the distance between drive panel and
motor and system shall include all material and accessories to make system
suitable for a distance of 350 m unless otherwise specified in the data sheet.
6.5.4 Output filter
Vendor shall ensure that converter design is in such a way that both voltage and
current harmonics are within the limits as specified in IEEE-519. Output filter
shall be provided, if required. Output filter capacitors shall be provided with
discharge circuits to ensure that all residual stored charge is reduced to less than
50 V DC within 30 seconds after a loss of AC voltage. All capacitor shall be
maintenance free and self-healing type.
The VFD system shall inherently protect motor from high voltage dv/dt stress,
independent of cable length to motor. Output filter shall be an integral part of the
VFD system and included within the VFD enclosure.

6.5.5 DC Link Reactor (For CSI drive)
Smoothing reactors for the DC link shall be designed to sufficiently decouple the
rectifier and inverter portion of the converter and to limit fault currents in this
circuit.
Unless otherwise specified, the reactor shall be air-cooled or fan cooled typed
located within the panel.
Reactor shall be suitable for operation with the non-sinusoidal current wave
shapes and DC components under all operational conditions of the system without
exceeding its temperature limits.

6.6 PROTECTION, CONTROL METERING AND INDICATION / ANNUNCIATION
REQUIREMENTS
6.6.1 The manufacturer shall provide all the necessary system control, protection, alarm
equipment and metering for the entire drive system and its auxiliary equipment
and its description shall be furnished along with the offer including the details of
the system built-up.
6.6.2 Automatic sequence control shall include start-up of cooling system, auxiliary
system of the motor, interlock checking, automatic start and run-up of drive,
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 15 of 35

planned and emergency shutdown. The same shall be processed through
microprocessor based system.
6.6.3 All protection, metering, indication, alarm, annunciation and fault diagnostic as
required, shall be available at PLC over communication network (RS-485).
Necessary communication module shall be provided in VFD accordingly.
6.6.4 Operator Control Panel.
a. Each drive shall be equipped with a front mounted operator control panel
consisting of a backlit alphanumeric display and a keypad with keys for
parameterization and adjusting parameter which shall not be limited to start /
stop, local / remote, auto / manual, increase / decrease, menu navigation and
protection and measurement parameter selection etc. Display shall consist of
minimum 2 lines of 16 characters- LCD type.
b. All parameters names, fault messages, warnings and other information shall
be displayed in complete English words or Standard English abbreviations to
allow the user to understand what is being displayed without the use of a
manual or cross-reference table. This shall also be used for the modification of
all electrical values, configuration parameters, drive menu parameters,
application and activity function access, faults, local control, adjustment
storage, self test and diagnostics. Keypad shall be operable with password for
changing the protection setting, safety interlock etc. However the parameters
such as measurements, setting, mode of drive etc. shall be allowed to be
viewed without any password.
c. Operator console shall have facility / port to connect external hardware such
as Lap-Top etc. Console shall have facility for upload and download of all
parameter settings from one drive to another identical drive for start up and
operation.
d. Drive system control shall also have facility to receive tripping signal from
upstream breaker for tripping and also provision for closing upstream breaker
after all required process parameters are achieved.
e. User-friendly software for operation and fault diagnostic shall be loaded in the
drive system panel before commissioning.

6.6.5 Protective features
The system offered shall incorporate adequate protective features, properly
coordinated for the drive control and for motor but not limited to the following:
i) Converter transformer: short circuit, over current, earth fault & winding
temperature high
ii) Incoming and outgoing line surge protection with suitably designed surge
diverter.
iii) Under / over voltage protection
iv) Phase loss, phase reversal protection
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 16 of 35

v) Programmable over current protection and under load protection
vi) Inverter fault.
vii) Over frequency/speed operation.
viii) Ventilation loss.
ix) Over temperature of equipment
x) Specific motor protection, including motor winding, bearing temperatures,
over current, overload, negative phase sequence, locked rotor and earth
fault protections etc.
xi) System earth fault protection.
xii) Speed reference loss
6.6.6 Control
The following minimum controls shall be provided as a part of the Operator
Control Panel or through separate switches on the front panel door.
i) Start / stop(in local/remote mode)
ii) Speed control (Raise / lower)
iii) Acknowledge/Accept/ Test Push Button for annunciation
iv) Auto / Manual / Test Mode select
v) Emergency stop
vi) Trip-Remote Breaker
vii) Local Remote
viii) Sequential Switching of filters
6.6.7 Indications
Vendor shall provide indications as required for normal operation and for easy
maintenance, which shall not be limited to the following indications.
i) Motor running
ii) Motor stopped
iii) VFD System Fault
iv) System ready to start
v) Motor zero speed
vi) AC mains ON
vii) Motor over speed
viii) VFD ON
ix) Remote breaker trip
x) Owners speed reference fail
xi) Input Isolator ON
xii) Input Isolator OFF
xiii) Output Isolator ON
xiv) Output Isolator OFF
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 17 of 35

xv) Bypass Isolator ON
xvi) Bypass Isolator OFF
xvii) Motor Space heater ON
xviii) Motor Space heater OFF
xix) Rectifier output ON
xx) Motor Zero Speed

Above indications may be provided as a part of the operator control panel, i.e. door
mounted keypad or through indicating lamps / LEDS in VFD/Isolator Panel.
Potential free contacts of items i-iv shall be wired separately for remote indications
in Owners SCADA systems.
6.6.8 Metering
Digital display of the following parameters shall be as a part of the Operator
Control Panel, selectable by the operator.
i) Input AC voltage
ii) Input AC frequency
iii) Input AC Current
iv) Output voltage
v) Output current VFD
vi) Output frequency
vii) Motor speed
viii) Hour Run
ix) Necessary transducer shall be provided with 4-20mA output for indicating
motor speed and motor current in Owners SCADA system.
x) KW monitoring
xi) KWh monitoring
xii) Power factor
xiii) Drive Thermal State
6.6.9 Audio-visual annunciations
a. Audio-visual window annunciations shall be provided on the front of the panel.
All annunciations as required for normal and satisfactorily operation of the
drive system shall be included as per vendor standards. These annunciations
can be part of operator console panel.
b. Vendor shall include audio-visual alarm as required for normal operation and
maintenance of the system but not be limited to the following.
i) Rectifier fuse failure
ii) Main AC failure
iii) Inverter fuse failure
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 18 of 35

iv) Inverter overload
v) Inverter high temperature
vi) Cooling system failure
vii) Motor failed to start
viii) Transformer failure
ix) Communication and measurement system unhealthy
x) Motor Temperature High
xi) Harmonic Filters Monitoring
Common potential free contacts shall be provided for above annunciations and
these shall be wired up to terminal block for owners use for remote alarm and
monitoring.
Alarm accept / reset push button is to be provided on the front door of the panel.
6.7 Fault Diagnostic
Fault diagnostic shall be built into the system to supervise the operation and
failure of the system. The information regarding failure of any of the system
including shut down of the system shall be available for a period of minimum 7 4
days (96 hours) after a shut down even though no supply would be available to
the system. The system may be totally de-energized for maintenance or otherwise.
It shall be possible to retrieve the record of events prior to tripping of the system
or de-energization. Auxiliary supply to the system components or to the
electronics (firmware) for the diagnostics / display shall be taken care by the
manufacturer for this purpose.
6.8 External Power supply for auxiliary and Control Circuit
Auxiliary power supply for devices external to VFD module, space heater supply
for motor, VFD panel space heater, auxiliary power supply for transformers,
cubicle lamps etc. shall operate on 240 volts single phase AC provided by Owner.
All control circuit shall operate at 110V DC (Provided by owner).
Vendor shall include supply of all control transformers, protective devices,
required accessories etc. and any other control supply voltage as required for the
system shall be derived from the power supply made available by owner.
6.9 Reliability features
The expected lifetime of the drive system shall be 20 years. The system including
all individual components forming part of the system shall have an availability of
minimum 0.997 and a minimum MTBF of 40,000 Hours.
6.10 Maintenance features
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 19 of 35

The controller design shall incorporates the following maintenance features:
- Modular construction.
- All components shall be easily accessible.
- Standard diagnostics to aid maintenance personnel. These shall include LED
or alphanumeric displays, test or measurement points.
6.11 Painting
All metal surfaces shall be thoroughly cleaned and degreased. Fabricated
structure shall be pickled and then rinsed to remove any trace of acid. The under
surface shall be prepared by applying a coat of paint and coat of yellow zinc
chromate primer. After preparation of the under surface, the board shall be spray
painted with two coats of final paint. Colour shade shall be RAL 7032 (Siemens
grey) as per DIN.
The finished panels shall be dried in stoving ovens in dust free atmosphere. Panel
finish shall be free from imperfection like pin holes, orange peels, runoff paints
etc. All unpainted steel parts shall be cadmium plated or suitably treated to
prevent rust formation.
7.0 CDL PANEL AND SYNCHRONOUS PANEL
CDL or Common Drive Logic Panel functions as a common interface between
VFD1, VFD2, Upstream and Downstream Breakers, Unit Control Panel (UCP)-A,B
& C and Synchronous Panel.
Main Functions of the CDR Panel are:
Controls the VFD Start-up & Shutdown Sequence.
Receives Commands & Provides Feedback to UCP and Station PLC
Controls the downstream breaker line-up as per the VFD & Motor combination
selection.
Helps in Breaker Control during Synchronous change-over.
Synchronous panel takes voltage sample from downstream breaker of each VFD,
Upstream breaker of bypass and synchronize the VFD output with mains.
8.0 INSPECTION, TESTING AND ACCEPTANCE
8.1 All tests shall be carried out at the manufacturers works under his care and
expense. The tests shall be witnessed by an inspector of Owner or of an agency
authorized by the owner. Prior notice of minimum 4 weeks shall be given to the
inspector for witnessing the tests.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 20 of 35


8.2 The routine test shall be conducted on all the drive system. However type test
shall be performed on one system of each rating and type. For the purpose of
testing, drive system shall include input transformer, switchgears, converter,
filters etc. as defined in clause 1.0.
8.3 The Routine and Type tests to be performed on the drive system shall be as
follows:
8.3.1 Routine tests
a. Visual Inspection
It involves checking of the various equipments / components fault diagnostic
unit, wiring, terminals, earthing ratings etc. in line with the approved drawings
and visual inspection shall not be limited to the following:
i) Dimensions and door layout vis--vis the approved drawings.
ii) Degree of Protection of Cubicles.
iii) Simulation facility of control signals for testing purposes.
iv) Memory function of fault diagnostic.
v) Interface capability
vi) Voltage / current rating of power semi conductor elements.
vii) Cable termination size and number of terminals, cable supporting etc.
viii) Accessibility of components.
ix) External signals and indication / alarm signals on converter.
x) Earthing of cubicles and cubicle doors.
b. Insulation test
c. Checking of auxiliary devices
d. Checking the protective devices
e. Checking of control and functional requirements
f. Automatic restart / re-acceleration
g. Test capability to restart the system and resynchronize converter onto running
motor after a voltage interruption.
h. Light load and functional test
i. Load Duty test
8.3.2 Type Tests
a. Efficiency
b. Temperature rise
c. Torque pulsation
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 21 of 35

d. EM Immunity
e. EM Emission
f. Line side voltage and current distortion content
g. Power factor
h. Audible noise
i. High voltage test on transformer
j. Speed loop test capability to ride through voltage less than 80%.
k. Total Harmonic Distortion at input side
l. Allowable full load current Vs Speed
m. Dynamic Performance
n. Current limit and Current loop test
Type test certificate from Independent Testing Agency for similar equipment can
be accepted for a, b, c, d & e as mentioned above.
8.3.3 Additional tests on transformers/other auxiliaries shall be carried out as per the
applicable codes/standards.
9.0 CERTIFICATIONS
The Variable Frequency Drive shall have test certification from internationally
recognized test house i.e. CE/UL/FM/IEC/CSA/NEMA or equivalent. The VFD
and associated equipment shall have test certificates issued by recognized
independent test house (CIMFR/BASEEFA/LCIE/UL/FM or equivalent). All
indigenous motors shall conform to Indian Standards and shall be certified by
Indian testing agencies. All motors (indigenous and imported) shall also have valid
statutory approvals as applicable for the specified location.
10.0 PACKING AND DESPATCH
The equipment shall be divided into several shipping sections for protection and
ease of handling during transportation. The equipment shall be properly packed
for transportation by ship / rail or trailer. The equipment shall be wrapped in
polyethylene sheets before being placed in wooden crates / cases to prevent
damage to the finish. Crates / cases shall have skid bottoms for handling. Special
notations such as Fragile, The side up, Weight, Owners particulars, PO Nos.
etc. shall be clearly marked on the package together with other details as per
purchase order.
The equipment may be stored outdoors for long periods before installation. The
packing should also be suitable for outdoor storage areas with heavy rains / high
ambient temperature unless otherwise agreed.
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 22 of 35

11.0 Software of PLC of VFD
A copy of PLC software of the VFD along with any hardware / software key is to be
provided on DVD / CD on placement of purchase order as a backup for
maintenance of the VFD.
License software (both run time and works) to be supplied.

16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 23 of 35

13.0 DRAWINGS AND DOCUMENTATION
Following drawings and documents in English language shall be furnished as per
the schedule mentioned hereunder. It is mandatory for vendor to take approval of
all post PO documents/drawings before proceeding with manufacturing of VFD
and its By-pass system.
S.
N.
Drawing/ Document Time of submission No.
of
sets
1
Technical particulars/ catalogues for the
offered system and the detailed
description
To be submitted

Two
2 Block diagram of the system Along with the technical bid Two
3
Complete technical details of each
equipment / component
Along with the technical bid Two
4 GA layout showing overall dimensions Along with the technical bid Two
5
Single line diagram and control schematic
showing equipment rating
Along with the technical bid Two
6
The detailed scheme, catalogue &
datasheet of isolator, interlock details with
VFD
Along with the technical bid Two
7 List of spares for 2 years of maintenance Along with the technical bid Two
8
Reference list along with PO copies and
performance certificates from end user in
India only to whom such system (VFD of
same make & similar design for same or
higher rating) has been supplied.
Along with the technical bid Two
9
Detail of cooling system to be provided in
VFD room
Along with the technical bid Two
10
Copy of drive system certifications as per
clause no. 8.0
Along with the technical bid Two
11
Details of after sales (Service) network in
India with addresses, contact numbers,
manpower details and level of expertise (in
terms of drive rating etc.) available.
Along with the technical bid Two
12
BOM of cables in case converter
transformer is mounted outside VFD
Panel
Along with the technical bid Two
13
Block diagram of the system
On placement of purchase order
Two
14
Complete technical details of each
equipment / component
On placement of purchase order
Two
15
G.A. layout showing overall dimensions
On placement of purchase order
Two
16
Single line diagram and control schematic
showing equipment rating , interlocks,
control and power cable scheduling etc.
On placement of purchase order
Two
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 24 of 35

17
Protection co-ordination diagram
On placement of purchase order
Six
18
Torque / speed/ current / power factor of
the system
On placement of purchase order
Six
19
Foundation/mounting drawing of VFD,
Transformer, Bypass Isolator etc.
On placement of purchase order
Six
20
Special installation requirements for the
VFD system and cables
On placement of purchase order
Six
21
Operation and Maintenance manuals
On placement of purchase order
Three
22
Terminal details for wiring to external
station control panel including Potential
free contacts, DI, DO, AI & AOs
separately.
On placement of purchase order
Three
23
QAP for all independent equipments for
VFD system.
On placement of purchase order
Three
24
Detailed document on control philosophy

On placement of purchase order
Six

25
Detailed Single Line Diagram Along with the technical bid Two

26
Suggestive Sub-station Equipment Layout Along with the technical bid Two


16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 25 of 35

14.0 DATA SHEET FOR HV VARIABLES SPEED DRIVES
DATA FURNISHED BY OWNER
Sl.
no
FEATURES Description
1. BASIC REQUIREMENTS
i. Required rated output capacity : * (As per motor ratings / Pump
Load)
ii. Torque requirement : As per pump requirement
iii. Load/driven equipment details : Horizontal Centrifugal pumps
iv. Load torque details : Centrifugal pumps
v. Drive system : One drive for each pump
vi. Reacceleration of motor : As per Operational requirements of
Pump specifications
2. SITE CONDITIONS
a) Location : As per SOR
b) Design Ambient temperature : 5- 50
0
C
c) Altitude : Less than 1000m above mean sea
level
d) Humidity (max) : 95%(relative)
e) Location : Indoor
f) Installation area for VFD : Indoor
g) Installation area for motor &
LCP
: Hazardous zone-2, gas group-
IIA/IIB, Temperature class-T3,
Tropical, dusty, corrosive.
3 INPUT POWER SUPPLY
SYSTEM CONDITIONS

a) No. of phases : Three
b) AC input voltage : 6.6KV
c) Voltage fluctuation : 10%
d) Rated frequency : 50 Hz
e) Frequency fluctuation : 3%
f) System fault level : 25 KA (1 sec.)
4 SYSTEM REQUIREMENTS
a) Speed range required : As per Pump requirement
b) Speed reference signal : 4-20mA
c)
Operation in case of loss of
reference signal
: Last speed reference/ a set speed
lower than previous reference /
either of above as per manufactures
standard.
d) Acceleration time : As per clause 6.1.5
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 26 of 35

Sl.
no
FEATURES Description
e) Deceleration time : As per clause 6.1.5
f) Communication facility between
Owners control system and
drive
: Required
g) Harmonic study : Required
h) Braking : Flux braking/ DC injection
braking/ either of the above
i) Converter transformer :
Dry type
j) Output voltage of VFD system : 6.6KV, three phase (without using
any output transformer)
k) Type of converter/rectifier : Minimum 18 Pulse
l) Harmonic filters on supply bus : Vendor shall ensure that converter
design is in such a way that both
harmonics V&I harmonics are
within limits as specified in IEEE-
519
m) Power factor improvement
feature as part of harmonic
filters
: Vendor shall ensure that converter
design is in such a way, so that
minimum PF at input of each VFD
is 0.99 lag for the varying load of
10% to 110%
5 CONTROL LOCATION
a) Local/Remote operation : Required
b) Local/Remote selector switch
location
: At VFD panel
c) Speed raise/Lower signal : At VFD panel
d) Distance of VFD panel from
Motor
: 350m (maximum)
6 COMMUNICATION
On communication network
(compatible RS 485 port) the
following details shall be
available

a) Protection features : Yes
b) Indication : Yes
c) Metering : Yes
d) Annunciation : Yes
e) Diagnostic : Yes

16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 27 of 35


15.0 TECHNICAL DATA TO BE FURNISHED BY MANUFACTURER
(To be submitted separately for each location)
1. Make : Siemens / ABB / Rockwell / Yaskawa /
Hitachi
2. Model No. : *
3. Rating of drive panel
a) Output in amperes : * (to be provided)
b) Rating expressed at
(torque)
: *
c) Rating declared at
(temp.)
: 50 Deg C
d) Switching frequency at
declared rating
: * Hz
4. Applicable code / standards : CSA,UL,IEC,NEMA,ANSI,IEEE,CE/equivalent
5. Drive type : CSI/VSI
6. Speed range : 10% to 110% of rated motor speed
7. Speed reference signal type : 4-20mA
8. Input power supply ratings : 3 Phase 6.6Kv
9. Voltage : 6600 V + 10%
10. Frequency : 50 Hz + 3%
11. Output voltage at 10%
input voltage full speed, full
load
: 6600 v
12. Overload capability of
converter

a) 115% In( for variable
torque) for
: *
13. Overall efficiency of drive
(excl. motor) at

a) 100% load : *
b) 75% load : *
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 28 of 35

c) 50% load : *
14. Overall power factor of drive
(excl. motor) at
:
a) 100% load : *
b) 75% load : *
c) 50% load : *
15. AC Output :
a) Rated frequency range : *
b) Accuracy of frequency : *
16. Dynamic response :
a) Speed fluctuation band : *
b) Speed recovery time after
100% torque step
: *
17. Waveform distortion factor
(% harmonics) in output /
input waveform.
: *
(Number of harmonics and magnitude of each harmonic generated shall be
furnished)
18. Output short ckt. Capability
and duration
: *
19. Controls At Drive level
(Please answer as provided /
not provided

a) System start : *
b) System stop : *
c) Speed raise : *
d) Speed lower : *
e) Drive frequency setting : *
h) Remote bkr.trip : *
i)Electronic Ramp function : *
j) Speed and current
controller
: *
k) Drive ready to start signal : *
l) Ammeter : On digital operator or separate digital type
m) Speed indicator : On digital operator or separate digital type
20. a)Diodes / IGBT : *
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 29 of 35

/IGCT/SGCT configuration
Number and Ratings
b)Total No. of diodes / IGBT
/IGCT / SGCT
Number and Ratings
: *
21. Cooling system :
i) Type : Fan forced cooling
ii) Redundancy in cooling
units
: *
22. a)Type of feed-back for
speed control
: Open loop Vector
b)Speed control accuracy : *
23. List of controls provided at
the front of panel (As per
specification)
: Yes / No
24. List of status measuring
devices provided at the front
of panel (as per specification
: Yes / No
25. List of status indication and
annunciation provided (as
per specification)
: Yes / No
26. Type of electronic card
mounting arrangement
: *
27. DIMENSION
a) Length : *
b) Height : *
c) Depth : *
d) Weight of cubicle : *
(Dimensional details of all panels shall be furnished).
28. Degree of protection for
enclosure
: * (Minimum IP 4X)
29. Paint shade : As per specification
30. Heat output of Panel : *
31. Whether Air conditioning is
required for these panels
: *
32. Control supply voltage and
Aux. Power requirement
: 415 V, 3 phase, 4 Wire
33. Converter Transformer (If :
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 30 of 35

applicable)
a) Make : *
b) Type of transformer : Dry type
c) KVA Rating : *
d) Voltage ratio : *
e) Vector group : *
f) Taps : *
g) Insulation class : F (Min) for dry type transformer.
f) Impedance : *
g) Efficiency : > 98%
h) Weight : *
i) Winding RTDs /
Thermistors
: Minimum 1 per phase
g) Overall dimension
(L&BXH)
: *
h) Transformer accessories : *

* data to be filled up & furnished with the offer
Note:
1. If synchronous and de-synchronous transfers are required it shall be in "bumpless
close transition" only. Open transition is not acceptable.
2. Motor to be protected from all the electrical faults by VFD when it is in VFD mode and
by "DOL Feeder" when it is in DOL mode.










16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 31 of 35


16.0 COMPLIANCE / EXCEPTIONS AND DEVIATIONS FOR OFFERED VFD
NAME OF BIDDER:
Bidder to stipulate here exceptions and deviations to Bidding Document, if any,
separately for technical clauses in respect of the specifications.


Sl.
No.
Clause
No.
Accepted
(Tick one)
Deviation proposed by Bidder if No for column no. 3
1 2 3 4
1. 1.0 Yes / No
2. 2.0 Yes / No
3. 3.0 Yes / No
4. 4.0 Yes / No
5. 5.0 Yes / No
6. 6.0 Yes / No
7. 7.0 Yes / No
8. 8.0 Yes / No
9. 9.0 Yes / No
10. 10.0 Yes / No
11. 11.0 Yes / No
12. 12.0 Yes / No
13. 13.0 Yes / No
14. 14.0 Yes / No

Note:
1. If the space is not sufficient, separate sheets to be attached as per this format.
2. Bidder to note that clause no. 16.0 has been included in the Bidding document solely
for the convenience of the Bidder so as to facilitate them to list out the deviations /
exceptions both of technical and commercial nature from / to the bidding document.
Owner will not recognise any deviations / exception (s) in respect of the specifications
which is not listed at clause no. 16.0.
3. Offers without fully filled clause no. 16.0 may be summarily rejected.


(SIGNATURE OF BIDDER)
16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 32 of 35


15.0 List of the VFD Manufacturer or their Indian Representative

Sl No VFD Manufacturer

Indian Office / Representative
1(a)



1(b)
Siemens
Pittsberg
USA

Siemens
Nasik, India
Siemens Ltd.
IIADT
Post Box 85
Thane Belapur Road
Thane 400601
Maharashtra
2 Asea Brown Boveri
Turgi
Swizerland
Asea Brown Boveri Limited,
Drive Division
Kosbahalli road,
Nelemangla
Bangalore
Karnataka
3 Rockwell Automation
Cambridge
Canada
Rockwell Automation India Pvt Ltd
A-66, Sector-64
Noida-201301
UP
4 Yaskawa Electric Corporation
YUKUHASHI
Japan
Larsen & Toubro Ltd
Control & automation Business Unit
Automation campus
A-600, TTC Industrial Area
Shil-Mahape Road
Navi Mumbai - 400710

5 HITACHI

NOTE: Make of 6.6kV Downstream Breaker Panel, CDL Panel and Synchronization Panel
shall be Siemens/ABB/Schneider Electric/L&T.








16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 33 of 35














TECHNICAL DATA SHEET
FOR EXISTING
HT MOTOR AT KHOPOLI
































16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 34 of 35

PARAMETERS DESCRIPTION
Motor Condition Existing
Duty Centrifugal Pump
Output, kW 750
Volts, V 6600
Phases 3
Locked Rooter Torque 90% of F.L. torque
Enclosure TEFV
Frame XD40010
Poles 2
Speed, RPM 2988
Full Load Current, Amp 76.5
Frequency, Hz 50
Temperature Rise 75
O
C by resistance
Starting Current 636% of F.L. Current
Protection IPW55
Cooling Air-Cooled
Mounting Foot
Pull Out Torque 250% of Full Load Torque
Stator Winding Diamond Coils Star Connected
Net Weight, kg. 4875
Bearing (DE/NDE) Roller/Ball & Roller
Direction of Rotation Clock-Wise
Starting DOL
Lubrication Shell Alvania 3
Main Terminal Arrangement
No. of terminals 3 entry from below Peebles
flameproof containing Phase Segregated
type 15A
Connections (Terminals/Phase) U V W/L1 L2 L3
Space Heater Rating 240W, 240V, 1 Phase FLP terminal box
Stator Winding RTDs
Six platinum Resistors, wired to separate
terminal box
BASEEFA Certificate No. EX811075
Insulation Class F
Stator Connection Star
Power Factor 0.89




16-QMP-05-3B
W
o
r
d

Triune Energy Services Pvt. Ltd.
New Delhi
TECHNICAL SPECIFICATION FOR HV
VARIABLE FREQUENCY DRIVE
SYSTEM
Std. / Doc. Number Rev.
9579-02-TS-102 0
Sheet 35 of 35

SYSTEM CONFIGURATION:


Proposed
(2750KW)
Proposed
(2750KW)
Existing
(750KW)

You might also like