ROOF MOUNTED FANS

HCTB - HCTT Series, Axial Flow Fans


Description

AIR EXTRACTION

Applications

The HCTB-HCTT range of axial roof fans


incorporate a horizontal air discharge
configuration and are available in two versions
for either air extract or supply operation:
The HCTB-HCTT axial roof fan range is
supplied as standard suitable for air extract
operation. (On request models can be
provided as air supply fans).
The range comprises of 9 nominal fan sizes
with 52 model variations in total. Models are
available with 4 or 6 pole motors suiatble for
single or three-phase electrical supplies. All
three-phase motors can be operated with a
connection at 380-415V enabling the
possibility of two speed operation.
HCTB / - / B

HCTT / - / B

The HCTB-HCTT range are suitable for many


roof extract or supply ventilation applications
including: commercial office, shopping malls,
leisure facilities, kitchens and agricultural
buildings ventilation. The range incorporates the
following standard features and specifications:
Thermal Overload Protection (except model 800)
IP-65 Protection (except model 800 which is
IP-55)
Class F Motor Insulation.
Sealed For Life, ball bearings assemblies.
Motors suitable for speed control in single*
and three phase.
Three-phase motors can be operated in
connection with 380-415V 50 Hz electrical
supplies enabling to speeds of operation.
* Except models HCTB/4-560 and HCTB/4-630.

Technical characteristics Extract air configuration (type B)


"

Model Type

Speed

(r.p.m.)

Maximum
power
absorbed
(W)

Maximum current
absorbed
(A)
at 230 V

at 400 V

Maximum duty
(m3/h)
High
Low
speed
speed

Sound pressure*
level at 1,5 meters
(dB(A))
Inlet

Outlet

Weight

(kg)

SINGLE PHASE 4 POLE

HCTB/4-315-B
HCTB/4-355-B
HCTB/4-400-B
HCTB/4-450-B
HCTB/4-500-B
HCTB/4-560-B
HCTB/4-630-B

1300
1225
1290
1290
1290
1200
1290

100
200
340
480
650
980
1700

0,59
0,96
1,64
2,30
3,00
4,90
7,60

HCTB/6-450-B
HCTB/6-500-B
HCTB/6-560-B
HCTB/6-630-B

835
840
900
800

220
290
420
510

1,15
1,60
2,40
2,56

HCTT/4-315-B
HCTT/4-355-B
HCTT/4-400-B
HCTT/4-450-B
HCTT/4-500-B
HCTT/4-560-B
HCTT/4-630-B
HCTT/4-710-B
HCTT/4-800-B
HCTT/4-900-B
HCTT/4-1000-B

1300
1260
1350
1230
1350
1320
1290
1300
1400
1400
1450

150
200
300
500
660
1210
1600
2200
3 kW **
4 kW **
5,5 kW **

HCTT/6-450-B
HCTT/6-500-B
HCTT/6-560-B
HCTT/6-630-B
HCTT/6-710-B
HCTT/6-800-B
HCTT/6-900-B
HCTT/6-1000-B

835
830
850
810
900
930
930
930

190
250
410
600
1100
0,75 kW **
1,1 kW **
1,5 kW **

HCTT/8-710-B
HCTT/8-800-B
HCTT/8-900-B
HCTT/8-1000-B

670
700
700
700

370
370
550
750

1930
2680
3700
5600
7100
9820
13000

62
59
62
65
72
76
77

61
58
61
64
70
72
73

14,4
15,8
16,5
23,5
25,4
40,0
42,6

3900
4600
6850
8400

56
59
63
67

55
57
61
64

23,5
25,4
40,0
42,6

1930
2680
3700
5600
7100
9820
13000
18400
23800
30000
38500

1500
2000
2900
4500
5850
7600
9800

62
59
62
65
72
76
77
81
87
92
95

61
58
61
64
70
72
73
77
83
88
91

14,4
15,8
16,5
23,5
25,4
40,0
42,6
60,0
67,0
77,0
123,0

3900
4600
6850
8400
12700
15800
20000
24700

3000
3500
5400
6400

56
59
63
67
72
78
83
86

55
57
61
64
69
75
80
83

23,5
25,4
40,0
42,6
54,0
57,0
67,0
108,0

9500
11900
15000
18600

66
72
77
80

68
68
73
76

52,0
57,0
67,0
108,0

SINGLE PHASE 6 POLE

THREE PHASE 4 POLE

0,34
0,46
0,80
1,00
1,60
2,30
3,20
4,00
7,30
9,50
12,00
THREE PHASE 6 POLE

0,48
0,57
0,93
1,18
3,30
2,50
3,50
4,50
THREE PHASE 8 POLE

1,20
1,90
2,30
2,80

* Fan installed on a roof. ** Absorbed.

96

Construction

Specification data

Base
Manufactured from galvanised sheet steel.
Cowl
Manufactured from spun aluminium.
Impellers
The impellers for models 315 to 560 are manufactured from one piece injection moulded
plastic, reinforced with chemically anchored
fibreglass for additional strength. Models 630
to 800 incorporate separate plastic blades
locked within a die cast aluminium hub.

AIR SUPPLY

Roof Axial Extract or Supply Air Fans


Type: HCTB-HCTT
Models:
Extraction HCTT/-B (three-phase)
HCTB/-B (single-phase)
Supply Air HCTT/-A (three-phase)
HCTB/-A (single-phase)
Air stream temperature limits:
-40 C to +700 C
Motor: IP 65, Class F Insulation.

Motors
Asynchronous induction motors with squirrel
cage rotor in die-cast aluminium:
Single-phase 230 V 50 Hz
Three-phase 400 V 50 Hz

NEW
7 1 0 -1 0 0 0

HCTB / - / A

HCTT / - / A

Technical characteristics supply air configuration (type A)


"

Model Type

Speed

(r.p.m.)

Maximum
power
absorbed
(W)

Maximum current
absorbed
(A)
at 230 V

at 400 V

Maximum duty
(m3/h)
High
speed

Low
speed

2150
3250
4720
6670
8440
11400
15300

Sound pressure*
level at 1,5 meters
(dB(A))

Weight

Inlet

Outlet

(kg)

67
64
71
74
79
83
87

61
62
67
71
75
78
82

14,4
15,8
16,5
23,5
25,4
40,0
42,6

4400
5500
7900
9900

63
66
71
73

59
63
67
69

23,5
25,4
40,0
42,6

2150
3250
4720
6670
8440
11400
15300
20500
26600
35900
44900

1820
2520
3900
5250
7000
9800
12500

67
64
71
74
79
83
87
90
96
101
104

61
62
67
71
75
78
82
85
91
96
99

14,4
15,8
16,5
23,5
25,4
40,0
42,6
60,0
67,0
77,0
123,0

4400
5500
7900
9900
14200
17700
23800
28800

3600
4500
6700
7800

63
66
71
73
81
87
92
95

59
63
67
69
74
82
87
90

23,5
25,4
40,0
42,6
54,0
57,0
67,0
108,0

10600
13300
18000
21700

75
81
86
89

70
76
81
84

52,0
57,0
67,0
105,0

SINGLE PHASE 4 POLE

HCTB/4-315-A
HCTB/4-355-A
HCTB/4-400-A
HCTB/4-450-A
HCTB/4-500-A
HCTB/4-560-A
HCTB/4-630-A

1300
1225
1200
1290
1290
1250
1200

100
200
340
480
650
980
1700

0,54
0,96
1,64
2,30
3,10
4,90
7,60

HCTB/6-450-A
HCTB/6-500-A
HCTB/6-560-A
HCTB/6-630-A

835
840
900
900

220
290
420
510

1,10
1,50
2,30
2,50

HCTT/4-315-A
HCTT/4-355-A
HCTT/4-400-A
HCTT/4-450-A
HCTT/4-500-A
HCTT/4-560-A
HCTT/4-630-A
HCTT/4-710-A
HCTT/4-800-A
HCTT/4-900-A
HCTT/4-1000-A

1360
1350
1380
1350
1380
1380
1360
1300
1400
1400
1400

150
200
300
500
660
1210
1600
2200
3 kW **
4 kW **
5,5 kW **

HCTT/6-450-A
HCTT/6-500-A
HCTT/6-560-A
HCTT/6-630-A
HCTT/6-710-A
HCTT/6-800-A
HCTT/6-900-A
HCTT/6-1000-A

835
830
850
810
900
930
930
930

190
250
410
600
1100
0,75 kW**
1,1 kW**
1,5 kW**

HCTT/8-710-A
HCTT/8-800-A
HCTT/8-900-A
HCTT/8-1000-A

670
700
700
700

370
0,37 kW**
0,55 kW**
0,75 kW**

SINGLE PHASE 6 POLE

THREE PHASE 4 POLE

0,34
0,46
0,80
0,95
1,60
2,30
3,00
4,00
7,30
9,50
12,00
THREE PHASE 6 POLE

0,48
0,57
0,93
1,18
3,30
2,50
3,50
4,50
THREE PHASE 8 POLE

1,20
1,90
2,30
2,80

* Fan installed on a roof. ** Absorbed.

97

Performance curves Extract air configuration (type B)


Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

315-355 - 4 pole

400 - 4 pole

450 - 4 and 6 pole

500 - 4 and 6 pole

630 - 4 and 6 pole

560 - 4 and 6 pole

* Low speed: only for three-phase models.

98

Performance curves Extract air configuration (type B)


Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

710 - 4, 6 and 8 pole

1000 - 4, 6 and 8 pole

900 - 4, 6 and 8 pole

* Low speed: only for three-phase models.

Acoustic characteristics Extract air configuration (type B)


Sound power spectrum: To obtain the sound power level spectrum, subtract the correction value shown below from the value given in the
technical characteristics table:
Inlet
4-315
4-355
4-400
4-450
4-500
4-560

4-630

63
-21
-14
-12
-13
-17
-18
-14

125
-6
-3
-3
-5
-8
-11

250
-12
-3
-4
-5
-1
-1

500
10
1
3
2
2
6

1000
1
5
4
7
8
7

2000
1
7
7
6
6
6

4000
-4
4
5
4
1
0

8000
-12
-3
-3
-4
-7
-7

-6

-5

-4

Discharge
4-315
4-355
4-400
4-450
4-500
4-560

4-630

99

63
-20
-12
-10
-12
-14
-15
-11

125
-9
-2
-1
-2
-4
-3

250
-8
4
2
0
2
1

500
11
3
4
4
5
4

1000
1
5
4
6
6
6

2000
-1
6
5
5
5
6

4000
-5
3
5
3
2
2

8000
-11
-4
-4
-4
-6
-5

-1

-2

Performance curves Extract air configuration (type A)


Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

315-355 - 4 pole

400 - 4 pole

450 - 4 and 6 pole

500 - 4 and 6 pole

560 - 4 and 6 pole

630 - 4 and 6 pole

* Low speed: only for three-phase models.

100

Performance curves Supply air configuration (type A)


Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

710 - 4, 6 and 8 pole

800 - 4, 6 and 8 pole

900 - 4, 6 and 8 pole

1000- 4, 6 and 8 pole

Acoustic characteristiques Supply air configuration (type A)


Sound power spectrum: To obtain the sound power level spectrum, subtract the correction value shown below from the value given in the
technical characteristics table:
Discharge
4-315
4-355
4-400
4-450
4-500
4-560

4-630

63
-28
-24
-24
-24
-22
-24
-23

125
-6
-4
-3
-3
-4
2

250
-4
0
1
1
1
1

500
10
4
5
5
6
4

1000
2
7
7
8
8
7

2000
1
7
7
6
6
6

4000
-4
4
5
4
1
0

8000
-15
-9
-12
-11
-11
-11

Inlet
4-315
4-355
4-400
4-450
4-500
4-560

-13

4-630

101

63
-23
-23
-21
-24
-19
-21
-18

125
-1
-1
-1
-1
-1
-2

250
5
4
2
1
4
5

500
8
5
5
6
6
4

1000
4
7
7
7
7
6

2000
0
4
4
2
3
4

4000
-6
-2
-2
-4
-4
-4

8000
-11
-11
-13
-12
-10
-13

-1

-5

-14

Installation

or or

Type
of fan

Sealing
frame

Flat roof insulated


up-stand

Acoustic
up-stand

Accessory
adapter plate

Back draft
shutter

Flange with
spigot

Flexible
coupling

Circular
adapter

315

JMS-560

JBS-560

JAA-560

JPA-560

JCA-560

JBR-560

JAE-560

JCC-560

JMS-630

JBS-630

JAA-630

JPA-630

JCA-630

JBR-630

JAE-630

JCC-630

JMS-710

JBS-710

JAA-710

JPA-710

JCA-710

JBR-710

JAE-710

JMS-905

JBS-905

JAA-905

JPA-905

JCA-905

JBR-905

JAE-905

JMS-1100

JBS-1100

JAA-1100

JPA-1100

JCA-1100

JBR-1100

JAE-1100

355
400
450
500
560
630
710
800

 Mounting accessories
Sealing Frame JMS
For mounting a roof fan on an
up-stand or base
Supplied with screws and gasket
for a complete weatherproof
seal.

Back-Draft Shutter JAC


Prevents backdraught when the
fan is not in operation.
To be mounted at the fan inlet
with the JPA plate or fixed
directly to the fan base (rivets or
screws not supplied).

Flat Roof Up-Stand JBS


For mounting a fan on a flat roof
without up-stands
For use on horizontal roofs
Internal insulation to prevent
condensation
Supplied with screws and gasket
for a complete weather seal.

Flange JBR
For use when a circular
connection is required directly to
the fan or through a flexible
connection (by others)
To be mounted at the fan inlet
with the JPA plate or fixed
directly to the fan base (rivets or
screws not supplied).

Accessory Adapter Plate JPA


Used when mounting the
accessories (JCA, JBR, JAE)
The adapter plate allows the fan
to be disconnected from the upstand without having to remove
the duct.

Flexible Coupling JAE


Reduces the transmission of
vibrations when the duct is
connected directly to the fan
To be mounted at the fan inlet
with the JPA plate or fixed
directly to the fan base (rivets or
screws not supplied).

102

Adapter For Circular Duct JCC


For use when fitting the models
up to 400, directly to a spirally
wound circular duct.

Acoustic Up-Stand JAA


Reduces sound levels
For use when mounting a fan on
a flat roof without up-stands
Supplied with screws and
gasket for a complete weather
seal.

Attenuator pressure drops for JAA Up-Stand

Attenuation insertion loss dB at octave average frequencies


(for JAA Up-Stand)

Type

125

250

500

1000

2000

4000

8000

JAA-560

16

29

32

26

17

JAA-630

14

24

27

19

13

JAA-710

14

24

28

16

11

15

mm.
mmCEc.d.a.

10

300

435

560

630

710

905

1100

JAA-905

14

26

30

19

12

JAA-1100

16

27

32

20

13

500

1000

1500

2000

3000

4000

5000

10000

15000

20000

m3/h

 Electrical accessories
REB
Single-phase electronic speed
controllers.
For use with the single-phase roof fans

RMB / RMT
Auto-transformer speed controllers
For single-phase and three-phase
roof fans.

On/Off isolation switch IP55


Enables disconnection of electrical
supply at roof level when installed close
to the fan.
3 pole model for single speed operation
(with or without speed regulator)
6 pole model for operation in
connection.

Switch
Enables two speed commutattion for
supplied fans.

Type

B

C

315

640

560

450

315

12

40

70

341

355

760

630

535

355

12

40

80

361

400

760

630

535

400

12

40

80

361

450

895

710

590

450

14

40

110

410

500

895

710

590

500

14

40

110

410

560

1150

905

750

560

14

50

165

488

630

1150

905

750

630

14

50

165

488

710

1350

1100

840

710

14

50

200

551

800

1350

1100

840

800

14

50

200

732

900

1580

1250

950

900

14

50

200

756

1000

1580

1250

950

1000

14

50

200

756

 Dimensions (mm)

103

Recommendations for installing S&P roof extract or supply fans


The adjoining ducting should always be the same size (or larger) than the fan inlet section / diameter.

The base and ducting should be properly sealed to prevent air leakage and re-circulation.

Where possible, the roof fan should be installed to minimise the effects of strong cross winds. i.e. on a pitched roof at a point lower than the roof
top camber.

104