A fault condition may result in an electrical power transmission system from event such as lighting striking a power line, or downed trees, or utility poles shorting the power lines. The fault creates a surge of current through the electric power system that can cause serious damage to grid equipment. Conventional solutions to fault current over duty such as major substation upgrades, splitting existing substations buses or multiple circuit breakers upgrades could be very expensive.
A fault condition may result in an electrical power transmission system from event such as lighting striking a power line, or downed trees, or utility poles shorting the power lines. The fault creates a surge of current through the electric power system that can cause serious damage to grid equipment. Conventional solutions to fault current over duty such as major substation upgrades, splitting existing substations buses or multiple circuit breakers upgrades could be very expensive.
A fault condition may result in an electrical power transmission system from event such as lighting striking a power line, or downed trees, or utility poles shorting the power lines. The fault creates a surge of current through the electric power system that can cause serious damage to grid equipment. Conventional solutions to fault current over duty such as major substation upgrades, splitting existing substations buses or multiple circuit breakers upgrades could be very expensive.
Analysis of Positioning of Superconducting Fault Current Limiter in Smart Grid Application
S. Srilatha 1 , Dr.K. Venkata Reddy 2 1 PG-Student, Department of Electrical and Electronics Engg.JNT University, Kakinada, India 2 Assistant Professor, Department of Electrical and Electronics Engg, JNT University, Kakinada, India. 1 sreenitha.hve@gmail.com
2 kvr.jntu@gmail.com Abstract: The introduction of new generating facilities by independent power producers and increasing load demand can result in fault current over duty on existing transmission system protective equipment. Conventional solutions to fault current over duty such as major substation upgrades, splitting existing substations buses or multiple circuit breakers upgrades could be very expensive and require undesirable extended outages and result in lower power system reliability [8]. Due to the difficulty in power network reinforcement and the interconnection of more distributed generations, fault current level has become a serious problem in transmission and distribution system operations [10]. The utilization of fault current limiters (FCLs) in power system provides an effective way to suppress fault currents and result in considerable saving in the investment of high capacity circuit breakers. In this work a resistive superconducting fault current limiter designed. To reduce the fault current in the micro grid the designed SFCL placed in proposed system, which consists of a conventional power plant and 10MVA wind farm. The effect of SFCL on the micro grid, and optimal position for SFCL to get more reduction percentage of wind farm faults current. . Keywords: Faults currents, Smart Grids, Wind farm, Wind turbine Induction Generator.
1. Introduction A fault condition may result in an electrical power transmission system from event such as lighting striking a power line, or downed trees, or utility poles shorting the power lines to ground [6]. The fault creates a surge of current through the electric power system that can cause serious damage to grid equipment. With the increasing demand for power, electric power systems have become greater and are interconnected. Generation units of independent Power producers (IPPs) and renewable energy have been interconnected to power systems to support the rising demands [11]. As a result, faults in power networks incur large short-circuit currents flowing in the network and in some cases may exceed the ratings of existing circuit breakers (CB) and damage system equipment The problems of inadequate CB short-circuit ratings have become more serious than before since in many locations, the highest rating of the CB available in the market has been used. To deal with the problem, fault current limiters (FCLs) are often used in the situations where insufficient fault current interrupting capability exists [12]. Less expensive solutions such as current limiting reactors may have unwanted side effects, Such as increasing system losses, voltage regulation problems or possibly could compromise system stability. Smart grid is a modern electricity system. It uses sensors, monitoring, communications, automation and computers to improve the edibility, security, reliability, efficiency, and safety of the electricity system. Renewable energy technologies such as photovoltaic, solar thermal electricity, and wind turbine power are environmentally beneficial sources of electric power generation [3]. The integration of renewable energy sources into electric power distribution systems can provide additional economic benefits because of a reduction in the losses associated with transmission and distribution lines.
In this work a SFCL model is designed. SFCL is an innovative fault current limiter. It works on the principle of Superconducting Property. It is inactive e under normal condition. It is in active under fault condition; it inserts some resistance into the line to limit the fault current. It suppresses the fault current within first half cycle only. It operates better than Circuit breakers, Relays, because the Circuit breakers takes minimum 2-3 cycles before they getting activated. The effect of SFCL on micro grid fault current observed. The optimal place to SFCL is determined [11]. S. Srilatha et al. / IJAIR ISSN: 2278-7844 2012 IJAIR. ALL RIGHTS RESERVED 25
2. Proposed system
Fig.1. Proposed system model designed in Simulink/SimPowerSystem. Three phase to ground Fault and SFCL locations are indicated in the diagram.
The proposed system is composed of a 100 MVA, 20KV conventional power plant, composed of 3- phase synchronous machine, connected by 200 km long 154 KV distributed-parameters transmission line through a step-up transformer of 20/154KV( TR1). At the substation (TR2), the voltage is stepped down to 22.9 kV from 154KV. High power industrial loads of 6MW and 330MVAR loads are connected to the conventional source. The 10 MVA wind farms is composed of three fixed-speed induction-type wind turbines each having a rating of 3.33MVA. The wind farm is operating at 20KV, and is this voltage is stepped up to branch network voltages of 22.9KV through a 20KV/22.9KV transformer (TR3). The wind farm directly connects with the branch network (B1) through a transformer (TR3) and is providing power to the domestic loads. The 10MVA wind farm supplied to the customer loads at 400V, through distribution transformers of 22.9KV/400V. Three domestically loads are separated by each 5KM transmission line and at each end of 5KM transmission line a domestically load is connected through a distribution transformer, as shown in Fig.1. The most severe fault in the power system is three phase to ground fault, it results in very high current in the system. The designed fault current limiter is in such a way that it should reduce the fault current due to three phase to ground fault, then it can successfully reduces the fault current in micro grids for all remaining faults. Artificial faults are marked as Fault 1, Fault 2 and Fault 3, which represent three-phase- to-ground faults in distribution grid, customer grid and transmission line respectively as shown in the Fig.1.and for each and every fault the wind farm fault current observed. To reduce this wind farm fault current the designed superconducting fault current limiter is placed at three scenarios for three different faults in the power system. First, we assumed that single SFCL was located at Location 1 (Substation). Second, single SFCL was located at Location 2 (Branch Network). Third, single SFCL was located at Location 3 (Wind farm integration point with the grid). Finally, in order to clarify the usefulness of dual SFCL installed together for different locations, SFCLs were located at Location 1 (Substation) and Location 4 (Wind Farm) respectively. S. Srilatha et al. / IJAIR ISSN: 2278-7844 2012 IJAIR. ALL RIGHTS RESERVED 26
3. Superconducting fault current limiter
Superconducting Fault Current Limiter (SFCL) is innovative electric equipment which has the capability to reduce the fault current level within the first cycle of fault current [11]. The first-cycle suppression of fault current by a SFCL results in an increased transient stability of the power system carrying higher power with greater stability. The concept of using the superconductors to carry electric power and to limit peak currents has been around since the discovery of superconductors and the realization that they possess highly non-linear properties. More specifically, the current limiting behavior depends on their nonlinear response to temperature, current and magnetic field variations. Increasing any of these three parameters can cause a transition between the superconducting and the normal conducting regime. The current increase can cause a section of superconductor to become so resistive that the heat generated cannot be removed locally. This excess heat is transferred along the conductor, causing the temperature of adjacent sections to increase. The combined current and temperature can cause these regions to become normal and also generate heat. The term quench is commonly used to describe the propagation of the normal zone through a superconductor. Once initiated, the quench process is often rapid and uncontrolled. Though once initiated the quench process is uncontrolled, the extent of the normal region and the temperature rise in the materials can be predicted.
3.1. Simulation Model of SFCL
The resistive type SFCL was modeled considering four fundamental parameters of a resistive type SFCL. These parameters and their selected values are: 1) Transition or response time = 2m.sec 2) Minimum impedance = 0.01. Maximum impedance = 20 3) Triggering current and =550 A 4) Recovery time. = 10 msec. The SFCL working voltage is 22.9kV. The maximum impedance value can be varied from 20 ohms to 27 ohms. The SFCL model developed in Simulink/SimPower System is shown in Fig.3.1. The SFCL model works as follows. First, SFCL model calculates the RMS value of the passing current and then compares it with the characteristic table. Second, if a passing current is larger than the triggering current level, SFCLs resistance increases to maximum impedance level in a pre-defined response time. Finally, when the current level falls below the triggering current level the system waits until the Recovery time and then goes into normal state. The SFCL characteristic table shown in Fig.3.1 plays a main role which consists of standard parameter values of SFCL.
Fig.3.1 Simulink model of Single phase SFCL The current limiting resistance value is calculated and this value is implemented in the simulation model. The important parameter to be given in SFCL is the current limiting resistance value. It is stored in the SFCL characteristic table. In order to avoid harmonics caused by transients, filter is used. The SFCL model developed is tested in both single phase and three phase test systems and the current waveforms are recorded with the presence and absence of SFCL. The simulation model of a single phase test system with and without SFCL is shown in Fig.3.2 and Fig.3.3 respectively and the current waveforms are recorded. The fault current is induced in the source directly in order to reduce the complexity of the simulation model.
Fig.3.2.Simulation model of single phase system with SFCL The type of the fault induced in the model is single phase to ground fault where it is induced through the AC voltage source. An RMS block is needed in order to calculate the RMS value of the incoming current signal and to increase the impedance value according S. Srilatha et al. / IJAIR ISSN: 2278-7844 2012 IJAIR. ALL RIGHTS RESERVED 27
to the limited fault current value specified in the SFCL characteristic table.
Fig.3.3 Simulation model of single phase system without SFCL The SFCL subsystem can be implemented in various types of single phase test systems and the operation can be tested. The performance of the SFCL can also be tested in a power system generation and distribution systems using three phase SFCL for controlling the fault current for each phase. The subsystem specified in Fig.3.2 is the SFCL model designed for single phase system which is shown in Fig.3.3. Harmonics filtration is used in order to reduce the harmonics caused due to the abnormal fault current. A normal first order filter is used for reducing the harmonics. The type of the filter can be changed depending upon the application of the system. A controlled voltage source is connected in order to compensate the voltage sag caused due to the induced fault current which is caused due to both internal and external causes.
4. Results and Analysis
Four SFCLs possible locations were analyzed for three different fault occurring points in the power system depicted in Fig.1. First, we assumed that single SFCL was located at Location 1 (Substation). Second, single SFCL was located at Location 2 (Branch Network). Third, single SFCL was located at Location 3 (Wind farm integration point with the grid). Finally, in order to clarify the usefulness of dual SFCL installed together for different locations, SFCLs were located at Location 1 (Substation) and Location 4 (Wind Farm) respectively.
4.1. CASE I: Fault in Distribution Grid
This distribution grid fault is most frequent fault in the power system. Three phases to ground is applied at distributed grid for 0.4s - 0.41s as shown in Fig 4.1. The total current in the system is now forced to flow towards the fault point. The wind farm current direction and fault current direction is same in this fault case.
Fig 4.1. Wind farm fault current for distribution grid fault 4.1.1. SFCL at substation (Location1) In the case of SFCL located at Location 1 (Substation) fault current contribution from the wind farm increased to 1025A as shown in Fig4.2. The magnitude of fault current is higher than No FCL situation, and the percentage of increment of wind farm fault current is given by 28. These critical observations imply that the installation of SFCL in Location 1, instead of reducing, has increased the DG fault current. Fig 4.2 Wind farm fault current for SFCL at substation in distribution grid fault 4.1.2. SFCL at Branch network (Location2) The two locations of SFCLs dont show any difference on the effect of rising in wind farm fault current due to fault at distribution grid. The wind farm fault current is about 1025A and the percentage of increment of wind farm fault current is given by 28 as shown in the Fig 4.3. In this case also the placement of SFCL raises the wind farm fault current instead of reducing the wind farm fault current
Fig 4.3 Wind farm fault current for SFCL at branch network S. Srilatha et al. / IJAIR ISSN: 2278-7844 2012 IJAIR. ALL RIGHTS RESERVED 28
4.1.3. SFCL at Integration point (Location3) This location of SFCL reduces the fault current coming from two sources. SFCL is in direct path of fault current only. When SFCL is installed at the integration point of wind farm with the grid, marked as Location 3 in Fig4.4. The wind farm fault current has been successfully reduced to265A. SFCL gives 67% reduction of fault current from wind farm and also reduce the fault current coming from conventional power plant because SFCL located in the direct path of any fault current flowing towards Fault 1.
Fig 4.4 Wind farm fault current for SFCL at integration point 4.1.4. Dual SFCL at Substation and at Wind farm (Location4) With dual SFCL installed at Location 1 and Location 4, the wind farm fault current reduced to 380A and also,53% reduction in fault current from wind farm is also observed from Fig.4.5. However, even though two SFCLs were installed, wind farm fault current reduction is lower than what was achieved by the single SFCL installed at Location 3.
Fig 4.5 Wind farm fault current for dual SFCL at Substation and at Wind farm 4.2. CASE II: Fault in Customer Grid The wind farm fault current rises to 580A, due to customer grid fault as shown in Fig 4.6 There is no big difference in raise in wind farm fault current due to this fault. Because in this case just transformer secondary side impedance is added to the primary side impedance results in increased in impedance when compared to the fault1 case impedance ,so the wind farm fault current is reduced somewhat less than the first fault case.
Fig 4.6Wind farm fault current for customer grid fault
4.2.1 SFCL at Substation (Location1) In the case of SFCL located at Location 1 (Substation) fault current contribution from the wind farm was increased to 1050A and the magnitude of fault current is higher than No FCL situation and the percentage of increment of wind farm current is given by 81 as shown in the Fig4.7. These critical observations imply that the installation of SFCL in Location 1, instead of reducing, has increased the DG fault current. This sudden increase of fault current from the wind farm is caused by the abrupt change of power systems impedance.
Fig 4.7 wind farm fault current for SFCL at substation 4.2.2. SFCL at Branch network (Location2)
The two locations of SFCLs dont show any difference on the effect of raise in wind farm current due to fault at customer grid. The wind farm fault current is about 875A, and the percentage of increment of wind farm current is given by 51 as S. Srilatha et al. / IJAIR ISSN: 2278-7844 2012 IJAIR. ALL RIGHTS RESERVED 29
shown in the Fig 4.8. In this case also the placement of SFCL raises the wind farm fault current instead of reducing the raise in current due to fault.
Fig 4.8 Wind farm fault current for SFCL at branch network 4.2.3. SFCL at Integration point (Location3) This placement reduces the fault current coming from two sources. SFCL is in direct path of fault current only. When SFCL is installed at the integration point of wind farm with the grid, marked as Location 3 in Fig.4.9. In this case the fault current is same as that of NO SFCL case. SFCL at this location gives no negative effect on the wind farm fault current, because it reduces the fault current coming from conventional power plant as SFCL located in the direct path of any fault current flowing towards Fault 2.
Fig 4.9 Wind farm fault current for SFCL at integration point 4.2.4 Dual SFCL at Substation and at Wind farm (Locatio4) With dual SFCL installed at Location 1 and Location 4 the wind farm fault current reduced to 670A. 16% reduction in wind farm fault current is also observed as shown in Fig.4.10. However, even though two SFCLs were installed, wind farm fault current reduction is lower than what was achieved by the single SFCL installed at Location 3.
Fig 4.10 Wind farm fault current for dual SFCL at substation and at wind farm 4.3 CASE III: Fault in Transmission Line The wind farm current raises to 4400A due to transmission line fault as shown in Fig.4.11. The wind farm current in this fault case is very high when compared to the other fault cases because the transmission line impedance is very less when compared to the distribution grid and customer grid transformers, results in high fault current in the wind farm.
Fig 4.11 Wind farm fault current for transmission line fault 4.3.1 SFCL at Substation (Location1)
SFCL positioned at Location 1(Substation) reduces the wind farm fault current to 1540A, as shown in Fig4.12, and the percentage reduction of wind farm fault current is 65. This result comes from the fact that SFCL is installed directly in the path of reverse current being generated by the wind farm towards fault point. The currents directly coming from conventional fault are reduced in the SFCL only due to insertion of high resistance. So the wind farm S. Srilatha et al. / IJAIR ISSN: 2278-7844 2012 IJAIR. ALL RIGHTS RESERVED 30
current reduced due to this location for transmission line fault.
Fig 4.12 Wind farm fault current for SFCL at substation 4.3.2. SFCL at Branch network (Location2) SFCL positioned at Location 1(Substation) reduces the wind farm fault current to 1320A, as shown in Fig 4.13, and the percentage of reduction of wind farm fault current is 70. This result comes from the fact that SFCL is installed directly in the path of reverse current being generated by the wind farm towards fault point.
Fig 4.13Wind farm fault current for SFCL at branch network 4.3.2. SFCL at Integration point (Location3) When the SFCL was strategically located at the point of integration of the wind farm with the grid (Location 3), the highest fault current 4100A,as shown in Fig4.14,and the percentage of reduction of wind farm current is given by 7. SFCL injects current in same direction of currents coming from both conventional and wind farm currents.
Fig 4.14 Wind farm fault current for SFCL at integration point 4.3.4. Dual SFCL at Substation and at Wind farm (Location4) SFCL at location1 and at location4 are greatly reduce the wind farm fault current to 1000A, as shown in Fig4.15,and the percentage of reduction of wind farm fault current is given by 73, due to transmission line fault. Even though in this the wind farm fault current is reduced better when compared to other cases, but it is not economical and not feasible to use two SFCLs in the power system.
Fig 4.15 Wind farm fault current for dual SFCL at substation and at wind farm The Percentage change in wind farm fault current for all considered SFCL locations are tabulated below.
Table 4.1: Percentage change in wind farm fault current due to SFCL locations
Item Fault1 Distribution Grid Fault2 Customer Grid Fault3 Transmission Line Fault current 800A 580A 4400A SFCL Locatio n Fault Curren t(A)
The majority of faults in a power system might occur in the distribution grid and the SFCL designed to protect micro-grid should not be expected to cater for the transmission line faults (Fault 3). An important aspect to be noted here is that wind farms on distribution side can contribute fault currents to transmission line faults and this phenomenon must be considered while designing the protection schemes for the smart grid. The optimal location of SFCL is at integration point of two generating sources, for both distribution and customer grid faults. This location of SFCL in a power grid which limits all fault currents and has no negative effect on the DG source is the point of integration of the wind farm with the power grid for both distribution and customer grid faults. And SFCL should not be placed directly at the substation or the branch network feeder. This placement of SFCL results in abnormal fault current contribution from the wind farm in both distribution and customer grid faults. The optimal location of SFCL is at the substation or at branch network feeder for transmission line fault. And SFCL should not be placed directly at integration point of two sources. This placement of SFCL results in abnormal fault current contribution from the wind farm in transmission line faults. Even though multiple SFCLs in micro grid can reduce the wind farm current due to faults but dual SFCLs are inefficient both in performance and cost.
6. References
[1] S. Sugimoto, J. Kida, H. Arita, C. Fakui, and T. Yamagiwa, Principle and characteristics of a fault current limiter with series compensation, IEEE Trans. Power Delivery, vol. 11, no. 2, pp. 842847, Apr. 1996.
[2] B. C. Sung, D. K. Park, J. W. Park, and T. K. Ko, Study on a series resistive SFCL to improve power system transient stability: Modeling, simulation and experimental verification, IEEE Trans. Industrial Electron.,vol. 56, no. 7, pp. 24122419, Jul. 2009.
[3] Litos Strategic Communication, The Smart Gird: An Introduction,2008 [Online]. Available: http://www.oe.energy.gov/Smart ridIntroduction.htm, Prepared for U.S. Department of Energy.
[4] R. Strzelecki and G. Benysek, Power Electronics in Smart Electrical Energy Networks. London, U.K.: Springer-Verlag London Ltd.,2008, pp. 203213.
[5] J. Driesen, P. Vermeyen, and R. Belmans, Protection issues in microgrids with multiple distributed generation units, in Power Conversion Conf., Nagoya, April 2007, pp. 646653.
[6] W. Friedl, L. Fickert, E. Schmautzer, and C. Obkircher, Safety and reliability for smart-, micro-, and islanded grids, presented at the CIRED Seminar: SmartGrids for Distribution, Jun. 2008, Paper 107. [7] L. Dessaint, K. Al-Haddad, H. Le-Huy, G. Sybille, and P. Brunelle, A power system tool based on simulink, IEEE Trans. Industrial Electron., vol. 46, no. 6, pp. 12521254, Dec. 1999.
[8] K. Maki, S. Repo, and P. Jarventausta, Effect of wind power based distributed generation on protection of distribution network, in IEEE Developments in Power System Protection, Dec. 2004, vol. 1, pp.327330
[9] Leonard kovalsky, Xing Yuan, Kasegn Tekletsadik, Albert Keri, Joachim Bock, Frank Breuer. Applications of superconducting fault current limiters in electrical power transmission system [10] Power, A.J., An overview of transmission fault current limiters, Fault Current Limiters - A Look at Tomorrow, IEE Colloquium on 8 Jun 1995, pp. 1/1 - 1/5. [11] Kovalsky, L., Yuan, X., Tekletsadik, K., Keri, A., Bock, J. and Breuer, F., Applications of superconducting fault current limiters in electric power transmission systems, IEEE Trans. on Applied Superconductivity, Vol. 15, No. 2, June 2005.
[12] P. G. Slade, et al, "The Utility Requirements for A Distribution Fault Current Limiters", IEEE Transactions on Power Delivery, Vol. 7, No. 2 April 1992 507-515
[13] W. Paul, Makan Chen et al, "Superconducting Fault Current Limiter Applications, Technical & Economical Benefits and Simulations & Test Results", CIGRE, Session 13-201Paris, France, pp 1- 8
Power of Habit: The Ultimate Guide to Forming Positive Daily Habits, Learn How to Effectively Break Your Bad Habits For Good and Start Creating Good Ones