Professional Documents
Culture Documents
n
; which is generally a weak function
of temperature. When nE0:5; C
0
T; n is very close to 1. Thus TRC becomes
identical to RTI, which is a sprinkler property describing the thermal sensitivity.
Like the RTI, the TRC is an index showing the sensitivity of a heat detector. The
TRC can be a function of (1) the shape of a heat detectors sensing element and (2)
unlike the RTI, the choice of reference temperature. In order to reduce any potential
inuence of n and C
0
T; n on the determination of the TRC of each detector,
the reference temperature should be close to the median point of the detectors
operating temperature range. The TRC values of the heat detectors can be obtained
in a manner similar to the way in which the RTI values are obtained for the
sprinklers [2].
3. Plunge-tunnel tests to obtain TRC
3.1. Test sample preparation
Various types of xed temperature heat detectors were chosen for test samples.
Figs. 1a and b show the photos of the 11 types of the test samples mounted on the
test plates. They are denoted as Types AK. Among them, seven types, Types AG,
ARTICLE IN PRESS
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 193
were restorable, the rest were non-restorable detectors. The rating temperatures of
the detectors are given in parentheses as follows: A (57
C); B (77
C); C (57
C); D
(93
C); E (88
C); F (71
C); G (88
C); H (57
C); I (90
C); J (57
C); K (93
C).
In order to minimize the possible heat conduction effects to each detector sample
through the plates, marinite was chosen as the test plate material. Each mounted
detector sample was plunged into the tunnel, which is shown in Fig. 2, until the
sample activated.
ARTICLE IN PRESS
Fig. 1. (a) Detector samples Type A through Type F used in the tests. (b) Detector samples Type GType
K used in the tests.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 194
3.2. Test conditions
In order for the TRC values to be acceptable for practical applications, the
following characteristics are desirable:
(1) The measured TRC values should be applicable to a wide range of conditions
that can be imposed by re. Thus, tests under various temperatures and
ARTICLE IN PRESS
Fig. 1 (continued).
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 195
velocities should be conducted and the TRC values obtained through these
conditions should be reasonably consistent.
(2) Once condition (1) is met, one test condition should be picked as a
representative of all the test conditions. The ideal qualications for the newly
picked condition are: (1) the TRC value measured under the condition should be
close to the average of the TRC values measured across the various test
conditions, and (2) the reproducibility of the tests under the condition should be
excellent.
(3) Different test samples from an identical model should provide reasonably
consistent TRC values. This condition (3), however, is more relevant with a
quality control issue at a manufacturers production site than with the validity
of a test method.
A multiple series of plunge tests were carried out to see if the test results would
satisfy all the above requirements. In order to check item (1) mentioned above, eight
different plunge test conditions were used as shown in Table 1. In order to minimize
the ratio of the radiational heat loss by a test sample to tunnel walls to the convective
heat gain by the test sample through the air ow in the tunnel, the air temperatures
were set high, 197
C and 291
C)/
air velocity (m/s)
Condition
number
Air temperature (
C)/
air velocity (m/s)
1 197/0.51 5 291/0.49
2 197/0.91 6 291/0.91
3 197/1.55 7 291/1.57
4 197/2.56 8 291/2.54
Table 2
Effects of n to the average of the TRC values across the eight plunge test conditions
Detector ID n=0.4 n=0.5 n=0.6
% x s s= % x % x s s= % x % x s s= % x
A 118 12.8 0.11 124 9.2 0.08 130 11.0 0.09
B 110 7.9 0.07 114 4.6 0.04 119 9.2 0.08
C 34 6.5 0.19 36 9.0 0.25 39 11.6 0.30
D 25 2.0 0.08 26 3.3 0.13 27 5.1 0.19
E 18 2.1 0.12 18 1.5 0.08 19 1.5 0.08
F 23 2.5 0.11 24 1.4 0.06 25 1.2 0.05
G 25 2.9 0.12 26 2.2 0.08 26 1.9 0.07
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 197
(3) The degree of the scattering of the TRC values is substantially higher for
detectors E, F, and G when n=0.4 is used, compared with the degree of the
scattering of the TRC values with n=0.5 or n=0.6.
(4) Although the degree of the scattering of the TRC values is lower for detectors E,
F, and G with n=0.6 than the degree of the scattering of the TRC values with
n=0.5, the difference in the degrees of the scatterings at each detector sample is
insignicant.
Thus, it was decided that the computation of the TRC values for all the detectors
to be conducted with n=0.5. Once n=0.5 was chosen for all the detector samples,
Eq. (4) could be further simplied by assuming that C
0
T; n 1:0 . Then TRC
values are the same as RTI values. Thus, the term RTI was used hereafter as a
thermal sensitivity index of heat detectors.
Figs. 39 show the average RTI value with error bars at each test condition and
the average RTI value across all the test conditions of test sample AG. The error
bars correspond to the highest and the lowest RTI values measured under each test
condition. The gures indicate that the average of the RTI values of each detector
sample across all the test conditions seemed to be an acceptable representation of the
detector samples RTI value. The normalized standard deviations of all the test
samples, except detector samples C and D, were not greater than 8%. The RTI
values of detectors C and D under the higher temperature with high velocities (i.e.,
conditions 7 and 8) were considerably higher than their corresponding average RTI
ARTICLE IN PRESS
0 1 2 3 4 5 6 7 8 9
0
20
40
60
80
100
120
140
R
T
I
(
m
.
s
)
1
/
2
Test Condition Number
Average RTI at the given test condition
Average RTI over all the test conditions
Fig. 3. Average RTI values of detector sample A.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 198
ARTICLE IN PRESS
0 1 2 3 4 5 6 7 8 9
0
20
40
60
80
100
120
140
Test Condition Number
Average RTI at the given test condition
Average RTI ovel all the test conditions
R
T
I
(
m
.
s
)
1
/
2
Fig. 4. Average RTI values of detector sample B.
0 1 2 3 4 5 6 7 8 9
0
10
20
30
40
50
60
Test Condition Number
Average RTI at the given Test Condition
Average RTI over all the Test Conditions
R
T
I
(
m
.
s
)
1
/
2
Fig. 5. Average RTI values of detector sample C.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 199
ARTICLE IN PRESS
0 1 2 3 4 5 6 7 8 9
0
10
20
30
40
Test Condition Number
Average RTI at the given test condition
Average RTI over all the test conditions
R
T
I
(
m
.
s
)
1
/
2
Fig. 6. Average RTI values of detector sample D.
0 1 2 3 4 5 6 7 8 9
0
10
20
30
Test Condition Number
Average RTI at the given test condition
Average RTI over all the test conditions
R
T
I
(
m
.
s
)
1
/
2
Fig. 7. Average RTI values of detector sample E.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 200
ARTICLE IN PRESS
0 1 2 3 4 5 6 7 8 9
0
10
20
30
Test Condition Number
Average RTI at the given test condition
Average RTI over all the test conditions
R
T
I
(
m
.
s
)
1
/
2
Fig. 8. Average RTI values of detector sample F.
0 1 2 3 4 5 6 7 8 9
0
10
20
30
40
Test Condition Number
Average RTI at the given test condition
Average RTI over all the test conditions
R
T
I
(
m
.
s
)
1
/
2
Fig. 9. Average RTI values of detector sample G.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 201
values, which resulted in noticeably higher normalized standard deviations than
those of the other detector samples. Although the case of detectors C and D calls for
more study to nd out the cause of the large deviation of RTI values under condition
7 and 8, the overall average RTI values of detectors C and D were also deemed
acceptable. The detectors are likely to respond well before the surrounding
environments ever reach the conditions resembling condition 7 or 8, should a re
break out.
The next step is nding a test condition among the eight conditions that would
serve as the standard test condition. The RTI values of detector samples will be
measured only under this condition and the average RTI value will be assigned as the
RTI value of the given detector type. The ideal qualities of the condition are: (1) the
RTI value measured under the condition should be close to the average of the RTI
values measured under all the eight test conditions, and (2) the measured RTI values
obtained through multiple tests under the condition should exhibit a low degree of
uctuations, i.e., a good reproducibility of tests.
The test data showed that the best test condition that meets the above
qualications varies depending on the test samples. Although there is no outstanding
test condition that can be equally applicable to all the samples, either condition 3 or
4 seemed to be an equally acceptable choice. The test condition 3 was chosen for the
standard test condition for future tests because the detector response time under the
condition would be longer than that under condition 4. That would reduce the
magnitude of a potential error associated with the time required to plunge the test
samples into the tunnel.
3.4. RTI measurements of multiple samples of the same model
For any practical usefulness, the RTI values should be reasonably consistent
among detectors of the same model. In order to assess the consistency of the RTI
values among the detectors of the same model, seven sets of restorable detectors
(Types AG) and four sets of non-restorable detectors (Types HK) were tested
under test condition 3. For the restorable detectors, 10 series of tests were conducted.
Figs. 1016 show the average RTI value of each sample and the average RTI value
obtained through all the ve samples for each restorable detector type, Types AG.
The average RTI value of each sample is the average of 10 RTI values measured
through the 10 tests and the overall average of the ve samples is thus the average of
50 RTI values.
The gures show that the normalized standard deviations associated with the
different samples of the same model are reasonably low except the samples from
Types D and E. As this is an issue more relevant to quality control of the products
than to the concept associated with RTI, the high degree of deviation seemed to
warrant more caution when we need to test these products. Overall, the normalized
standard deviations associated with the different samples of the same model are
within the boundary established by the normalized standard deviations associated
with a sample of the same model under the different test conditions. Thus, assigning
ARTICLE IN PRESS
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 202
ARTICLE IN PRESS
0 1 2 3 4 5 6
0
20
40
60
80
100
120
140
Sample ID Number
Average RTI of each sample
Average RTI of all five samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 10. Average RTI values of detector samples A1A5.
0 1 2 3 4 5 6
0
20
40
60
80
100
120
140
Sample ID Number
Average RTI of each sample
Average RTI of all five samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 11. Average RTI values of detector samples B1B5.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 203
ARTICLE IN PRESS
0 1 2 3 4 5 6
0
10
20
30
Sample ID Number
Average RTI of each sample
Average RTI of all five samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 12. Average RTI values of detector samples C1C5.
0 1 2 3 4 5 6
0
10
20
30
Sample ID Number
Average RTI of each sample
Average RTI of all five samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 13. Average RTI values of detector samples D1D5.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 204
ARTICLE IN PRESS
0 1 2 3 4 5 6
0
10
20
30
Sample ID Number
Average RTI of each sample
Average RTI of all five samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 14. Average RTI values of detector samples E1E5.
0 1 2 3 4 5 6
0
10
20
30
Average RTI of each sample
Average RTI of all five samples
Sample ID Number
R
T
I
(
m
.
s
)
1
/
2
Fig. 15. Average RTI values of detector samples F1F5.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 205
a RTI value to a detector based on the measurements with a number of selected
samples under one test condition was deemed acceptable.
Multiple samples of non-restorable detectors were also tested under condition 3.
Twenty samples each from Types HK were mounted to the plates and plunged into
the tunnel. Some data points obtained with the samples of Types J and K were
deemed unreliablethe timer either did not trip at all or did take unreasonably a
long time before it tripped. In order to prevent the rest of data from being
contaminated, those data points were discarded. Eighteen data points for Type J
detectors and 17 data points for Type K were used in the analysis. Figs. 1720 show
the RTI value of each sample of the non-restorable detectors used in the test
program and the average RTI value of all the test samples per type. The gures show
that detector Types H and K have quite higher degrees of the standard deviations
compared with those of Types I and J.
4. Full-scale re tests to measure detector response times
4.1. Test description
In order to make a comparison between the detector-response times estimated by
using the RTI values obtained through the bench-scale tests and the real response
times, full-scale re tests were conducted. The detectors used in the tests were the
ARTICLE IN PRESS
0 1 2 3 4 5 6
0
10
20
30
Sample ID Number
Average RTI of each sample
Average RTI of all the samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 16. Average RTI values of detector samples G1G5.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 206
ARTICLE IN PRESS
0 5 10 15 20
0
10
20
30
40
50
Sample ID Number
RTI of each sample
Average RTI of all the samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 17. RTI values of detector samples H1H20.
0 5 10 15 20
0
10
20
30
Sample ID Number
RTI of each sample
Average RTI of all the samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 18. Average RTI values of detector samples I1I20.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 207
ARTICLE IN PRESS
0 5 10 15 20
0
20
40
60
80
100
120
140
Sample ID Number
RTI of each sample
Average RTI of all the samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 19. Average RTI values of detector samples J1J18.
0 2 4 6 8 10 12 14 16 18
0
20
40
60
80
100
120
140
160
180
200
Sample ID Number
RTI of each sample
Average RTI of all the samples
R
T
I
(
m
.
s
)
1
/
2
Fig. 20. Average RTI values of detector samples K1K17.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 208
same types of the detectors used in the plunge tests described earlier. The response
time of each detector was estimated by solving Eq. (4). The TRC value in the
equation was substituted with a RTI value, C
0
T; n 1 , and n=0.5 were used in the
computations.
Seven restorable detectors and a sprinkler were mounted on the ceiling. They were
arranged in such a way that each detector could maintain an approximately 3.4-m
radial distance from the center-axis of the plume that was generated by a 0.76-m-
diameter-heptane-pan re, as shown in Fig. 21. The dimensions of the test room were
18.3 m by 12.2 m by 4.6 m high. The detectors and the instruments attached on the
ceiling were: velocity probe 1, detectors AG, velocity probe 2, and a sprinkler,
respectively, from left to right in the gure, approximately 0.15 m apart each other.
The pan was placed on a 1.6-m high platform, so that the ceiling clearance from the
pan was 3.0 m. Temperatures and velocities of the ceiling jet ows from the re
plume were measured by the two velocity probes, which were equipped with pressure
transducers and thermocouples. Fig. 22 shows a comparison of the measured and the
computed response time of each detector and the sprinkler, which is represented as
Type S in the gure. The comparison of the detector response times showed the
following:
(1) In general, the matches between the computed and the measured response times
of the detectors were excellent.
(2) The discrepancies between the measured and the computed response times were
more pronounced with the high temperature rating detectors, i.e., detector types
D, E, and G, than the discrepancies with the low-temperature rating ones.
ARTICLE IN PRESS
Fig. 21. The pan-re and the detectors used in the full-scale tests.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 209
(3) Detectors D and E took substantially longer times to activate than the times
estimated by the computations. Detector G, however, activated sooner than the
computation indicated; it responded even before the ceiling jet temperature
reached the xed rating temperature of the detector.
Additional tests with the identical settings also conrmed the same trend
mentioned above, i.e., excellent matches except the cases with detectors D, E, and G.
Detectors F and G were rate compensated xed temperature detectors. They
respond at a pre-set xed temperature when the surrounding temperature rises
relatively slowly. However, when the surrounding temperature rises fast, they tend to
activate sooner than the surrounding temperature reaches the pre-set xed
temperature. The temperature measurement indicated that detector F might have
activated at the pre-set temperature. But it was clear that detector G was activated by
the rate of temperature rise rather than by the xed temperature, which made the
estimated time using the RTI based on a xed temperature rating irrelevant.
In order to see the behavior of the high-temperature rating detectors more closely,
the re source was moved closer to the detectors. In the following tests, the center of
the pan was located 3.0 m away in the radial direction and 3.0 m away in the vertical
direction from the detectors. Figs. 23 and 24 show, respectively, the ceiling jet
temperatures and the ceiling jet velocities measured at velocity probes 1 and 2.
Fig. 25 shows a comparison of the measured and the computed response time of each
detector.
ARTICLE IN PRESS
A B C D E F G S
0
20
40
60
80
100
120
140
R
e
s
p
o
n
s
e
T
i
m
e
(
s
)
Detector Type
Measured
Computed
Fig. 22. Comparison of the measured and the computed detector response times where the test re was
3.4 m away.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 210
ARTICLE IN PRESS
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
20
30
40
50
60
70
80
90
100
110
120
130
C
e
i
l
i
n
g
J
e
t
T
e
m
p
e
r
a
t
u
r
e
(
C
)
Velocity Probe 1
Velocity Probe 2
Time (s)
Fig. 23. Ceiling jet temperatures measured at velocity probes 1 and 2 (R=3.0 m).
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
C
e
i
l
i
n
g
J
e
t
V
e
l
o
c
i
t
y
(
m
/
s
)
Time (s)
Velocity Probe 1
Velocity Probe 2
Fig. 24. Ceiling jet velocities measured at velocity probes 1 and 2 (R=3.0 m).
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 211
The comparison showed the following:
(1) In general, the matches between the computed and the measured response times
of the detectors were excellent.
(2) Compared with the previous tests where the radial distance of the re source was
3.4 m away from the detectors, the match between the measured and the
computed response time of detector D was exceptionally good. The match in
detector E was also much improved compared with that in the previous tests.
detector G again activated much sooner than the estimate indicated.
(3) Detector Gs activation long before the surrounding temperature reached the
xed rating temperature invalidated the time estimate based on the RTI that was
assigned for a xed temperature rating detector.
Additional tests under the identical settings conrmed the same trend mentioned
above.
5. Summary and conclusions
A method to quantify heat detectors thermal response sensitivities that would
enable re safety engineers to estimate the response times of heat detectors with
reliable accuracy was established by this work. Multiple samples from 11 detector
ARTICLE IN PRESS
A B C D E F G S
0
20
40
60
80
100
120
140
R
e
s
p
o
n
s
e
T
i
m
e
(
s
)
Detector Type
Measured
Computed
Fig. 25. Comparison of the measured and the computed detector response times where the test re was
3.0 m away.
S. Nam et al. / Fire Safety Journal 39 (2004) 191215 212
types, all xed temperature rating ones, were used in the study. The project was
carried out with two subtasks: bench-scale tests measuring thermal response
sensitivities of the samples and full-scale tests validating the methodology developed
in the rst task.
A plunge-tunnel similar to what has been used to measure response time index
(RTI) of automatic sprinklers was utilized in the bench-scale tests. As a true thermal
response sensitivity index of a detector should be independent of surrounding
conditions that can be caused by different sets of res, eight different plunge test
conditions were used to measure the detector response times. The eight conditions
consisted of two set temperatures, 197
C and 291