DESCRIPTION
The FireNET Plus 1127 series control panel is an
analog addressable fire alarm panel with build options
containing 1 or 2 SLC loops, a Digital Alarm
Communicator/ Transmitter (DACT), and an RS-485
bus for network communication. Each SLC loop
supports 127 devices of any combination (sensors or
modules), and 127 analog sounder bases, for a
possible total of 254 points per loop. Communication
between devices is accomplished by use of standard
cable (shielded or twisted pair is not required). Each
panel includes a 4-amp power supply and has 2 onboard NAC circuits. The RS-485 bus provides
communication to the panel network while another
RS-485 bus provides communication for peripheral
devices. The RS-232 interface allows the convenience
of programming via a PC. The system will support a
variety of Hochiki devices; photo, ion and heat
sensors, which contain a unique, patented sensor
design incorporating automatic drift compensation and
day/night sensitivity modes. Additional devices
include contact monitors, relay controllers, supervised
auxiliary output and short circuit isolator modules. In
addition, interfaces to conventional detection systems
can be established by using a conventional zonemonitoring module. The Loop Explorer Windows
Software interface provides the installer with fingertip
access to installation programming and diagnostic
tools. An Auto Learn feature offers the convenience
for quick start applications. Add to this a reputation
for high quality and dedicated service which makes
this an exceptional product both in performance and
value.
PRODUCT LISTINGS
S6468
3038713
Continued on back.
Find latest revision at www.hochiki.com
F0087
03/2010
SPECIFICATIONS
Primary AC
Output DC
Power Supply
Charger Current
Dimensions
Weight
Color
Material
Display
Network
Zones
SLC loops
Devices per loop
Addresses per panel
NAC Outputs
Relay Outputs
Aux. Power
PC Port / Printer
DACT Formats
DESCRIPTION
CONTROL PANEL EXPANDERS
FNP-1127-SLC
FN-4127-NIC
FN-4127-IO
FN-LCD-S
FNP-LED
ALG-V, ALK-V
AIE-EA
ATG-EA
NSA-6
NSA-4
ASB
DH-98A
DH-98AR
MS-RA, MS-RA/R,
MS-KA/R
FRCME-S
FRCME-P
FRCME-4
FRCMA, FRCMA-I
DIMM
CZM
R2M
R2ML/H Series
SOM
SOM-A, SOM-AI
SCI
AMS Series
TCH-B100
FN-ACC
FNP-ETR
Hochiki America Corporation FireNET Plus ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL
DESCRIPTION
The FireNET 4127 control panel is an analog addressable fire alarm panel containing 2 or 4 SLC loops with
each loop supporting 127 devices of any combination
(sensors or modules), and 127 analog sounder bases,
for a possible total of 254 points. Communication
between devices is transferred through standard cable
(shielded or twisted pair is not required). Each panel
includes a 5.25 amp power supply and has 4 on board
NAC circuits. An RS-485 bus provides communication to
the panel network, while the RS-232 interface allows the
convenience of programming via a PC. The system will
support a variety of Hochiki devices: photo, ion and heat
sensors, which contain a unique, patented sensor
design incorporating automatic drift compensation and
day/night sensitivity mode. Additional devices include
contact monitors, relay controllers, supervised auxiliary
output and short circuit isolator modules. In addition,
interfaces to conventional detection systems can be
established by using a conventional zone-monitoring
module. The Loop Explorer Windows Software
interface provides the installer with fingertip access to
installation programming and diagnostic tools. An
Auto-learn feature offers the convenience for quick start
applications. Add to this a reputation for high quality and
dedicated service makes this an exceptional product
both in performance and value.
PRODUCT LISTINGS
UL 864, Local Signaling Unit.
Types: Automatic, manual,
waterflow, sprinkler supervisory,
California
S8255 Remote Station and Central
Station Service (DACT)
State Fire
Non-coded signaling.
Marshal
NFPA 70, 72 &13 Compliant 7165-0410:159
3033817
F0068
03/2011
SPECIFICATIONS
Primary AC
Output DC
Power Supply
Charger Current
Dimensions
Weight
Color
Material
Display
Network
Zones
SLC loops
Devices per loop
Addresses per panel
NAC Outputs
Relay Outputs
Voltage Outputs
Aux. Power
Aux. Inputs
PC Port
Printer Port
DESCRIPTION
CONTROL PANEL EXPANDERS
FN-4127-SLC
FN-4127-NIC
FN-4127-IO
FN-DAC
FN-CTM
FN-LCD-N
FN-LCD-S
ALG-V
ALK-V & ALK-V2
ACA-V
AIE-EA
ATG-EA
NSA-6
NSA-4
ASB
DH-98A
DH-98AR
MS-RA, MS-RA/R, MS-KA/R
FRCME-M
FRCME-P
FRCME-4
FRCMA, FRCMA-I
DIMM
CZM
R2M
SOM
SOM-A, SOM-AI
SOM-R
SCI
AMS Series
TCH-B100
FN-ACC
FN-ETR
ANNUNCIATORS
ACCESSORIES
Hochiki America Corporation FireNET ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL
DESCRIPTION
This alternate build of the FireNET 4127 control panel
is equipped with a Plexiglass window to meet the
requirements of major cities including the City of
Denver. Access level 2 is enabled as soon as the outer
door of the enclosure is opened (CAT 30 Key).
The FireNET 4127 control panel is an analog addressable fire alarm panel containing 2 or 4 SLC loops with
each loop supporting 127 devices of any combination
(sensors or modules), and 127 analog sounder bases,
for a possible total of 254 points. Communication
between devices is transferred through standard cable
(shielded or twisted pair is not required). Each panel
includes a 5.25 amp power supply and has 4 on board
NAC circuits. An RS-485 bus provides communication to
the panel network, while the RS-232 interface allows the
convenience of programming via a PC. The system will
support a variety of Hochiki devices: photo, ion and heat
sensors, which contain a unique, patented sensor
design incorporating automatic drift compensation and
day/night sensitivity mode. Additional devices include
contact monitors, relay controllers, supervised auxiliary
output and short circuit isolator modules. In addition,
interfaces to conventional detection systems can be
established by using a conventional zone-monitoring
module. The Loop Explorer Windows Software
interface provides the installer with fingertip access to
installation programming and diagnostic tools. An
Auto-learn feature offers the convenience for quick start
applications. Add to this a reputation for high quality and
dedicated service makes this an exceptional product
both in performance and value.
Specifications subject to change without notice.
Continued on back.
PRODUCT LISTINGS
UL 864, Local Signaling Unit.
Types: Automatic, manual, waterflow,
sprinkler supervisory, Auxiliary
Service(local energy), and Central
Station Service, Remote Station
Service and Proprietary Service
S8255 (DACT) Non-coded signaling.
NFPA 70, 72 &13 Compliant
California
State Fire
Marshal
7165-0410:159
F0093
07/2009
SPECIFICATIONS
Primary AC
Output DC
Power Supply
Charger Current
Dimensions
Weight
Color
Material
Display
Network
Zones
SLC loops
Devices per loop
Addresses per panel
NAC Outputs
Relay Outputs
Voltage Outputs
Aux. Power
Aux. Inputs
PC Port
Printer Port
DESCRIPTION
CONTROL PANEL EXPANDERS
FN-4127-SLC
FN-4127-NIC
FN-4127-IO
FN-DAC
FN-CTM
FN-LCD-N
FN-LCD-S
ALG-V
ALK-V & ALK-V2
AIE-EA
ATG-EA
NSA-6
NSA-4
ASB
DH-98A
DH-98AR
MS-RA, MS-RA/R,
MS-KA/R
FRCME-S
FRCME-P
FRCME-4
DIMM
CZM
R2M
SOM
SOM-A, SOM-AI
SCI
AMS Series
TCH-B100
FN-ACC
FN-ETR
ANNUNCIATORS
ACCESSORIES
Hochiki America Corporation FireNET ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL
STANDARD FEATURES
PRODUCT OVERVIEW
Continued on back.
F0084
02/2010
SYSTEM REQUIREMENTS
CD ROM Drive
1Ghz Pentium or equivalent processor
Windows XP
256MB RAM memory (recommended 1GB)
10GB Hard Drive (20GB recommended if many
maps are to be used)
32MB or better graphics card
Any sound card
Monitor must support 1024 x 768 graphics driver
Mouse
Printer (optional)
One RS232 serial port per network
FEATURES
Ability to import Loop Explorer configuration file to
FireNET graphix file
Drag and drop from device tree to maps
Real time Graph of device analog values
Connectivity of additional workstations over
network. (Number of additional workstations
depends on license)
FireNET graphix systems available in the following
packages;
1 to 4 node package (GUS1-4)
5 to 8 node package (GUS5-8)
9 to 16 node package (GUS9-16)
17 to 32 node package (GUS17-32)
33+ node package (GUS33+)
System upgrade packages available, call for more
information.
To add additional workstations, use one of the
following part numbers;
1 workstation (GUSR2001)
2 workstations (GUSR2002)
3 workstations (GUSR2003)
4 workstations (GUSR2004)
5 workstations (GUSR2005)
6 workstations (GUSR2006)
7 workstations (GUSR2007)
8 workstations (GUSR2008)
SPECIFICATIONS
Operating Voltage
21- 30VDC
Maximum Current
360mA
Wire Size
12AWG to 22AWG
Communication Method
RS485
3900ft. (1200m)
Avalible Dimensions
DESCRIPTION
The FNP-LED system uses flexible, optic light guides
to illuminate areas on a floor plan, laid over a high
resolution grid. This unique system dispenses
completely with wiring and enables indicators to be
moved, removed or added onsite without the need for
any wiring. All indicators can be configured to operate
upon any event type and at point, zone or group level
via the powerful and intuitive Loop Explorer
configuartion tool. FNP-LED can be supplied with or
without optional LED's and controls. Optional LED's
indicate Power On, Fire, Trouble and Disablements
and optional controls are for Alarm Silence, Buzzer
Silence, Lamp Test, and Reset. Housed in an
attractive, slimline enclosure to match FireNET Plus
Fire Alarm Panels. High quality, full color floor plans
provide a clear and geographical indication of event
activation, which enables fast identification of the Fire
Alarm source.
Red or Charcoal
Material
ABS/Steel Enclosure
Max. LED's
AM2: 40 LEDs
AM3: 72 LEDs
AM4: 88 LEDs
Operation Temperature
CAT 30 Key
PRODUCT LISTINGS
S5694
California
State Fire
Marshal
7120-0410:181
3038713
Continued on back.
Find latest revision at www.hochiki.com
F0102
12/2010
CURRENT RATINGS
Standby Current
Red LED Driver Board
Alarm Current
Red LED Driver Board
DESCRIPTION
The FN-LCD-N type LCD network annunciator is
designed to be used with the FireNET analog
addressable system. It allows for remote access,
monitoring & control of the FireNET system throughout
the building.
The FN-LCD-N is a true network annunciator that can
access, monitor & control any or all FireNET panels in
the network. Each FN-LCD-N is completely
independent. The highly intuitive user interface and
320 character LCD display of the FN-LCD-N is exactly
the same as the FireNET panel. In addition to routing
any panel in the network to the FN-LCD-N, every event
category within each panel can also be individually
routed, as well as routing of all remote control functions
(reset, alarm silence, re-sound alarm) from individual
panels. The FN-LCD-N supports the same RS485
expansion port as the FireNET panel, allowing for
FireNET expansion boards and accessories to be
connected to the network annunciator.
The FN-LCD-N also has (4) output relays for fire,
supervisory, trouble & auxiliary. The relays are
programmable (except supervisory).
Security is established by the use of a password or
firefighters enable key. Designed to be aesthetically
pleasing, the FN-LCD-N is available in charcoal grey
or red and can be surface or flush mounted using a
standard trim ring kit.
PRODUCT LISTINGS
UL 864, NFPA 70 & 72:
Signaling Device
S8255 Vol. 2
California
State Fire
Marshal
7120-0410:165
Continued on back.
Find latest revision at www.hochiki.com
F0071
06/2009
SPECIFICATIONS
Input DC
Aux. Output DC
Dimensions
Weight
Color
Material
Display
Network
Relay Outputs
PC Port
Printer Port
Expansion Port
ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the network annunciator model FN-LCD-N.
The FN-LCD-N shall connect to the FireNET fire alarm control panel (FACP) network. The network annunciator
shall be capable of annunciating on its 320 character display and local buzzer, the condition of any FireNET FACP
or network annunciator on the network. Up to 64 FN-LCD-N network annunciators or FireNET FACP's may be
connected together on the network. The FN-LCD-N shall be UL listed, and have surface or flush mount capability.
WIRING DIAGRAM
DESCRIPTION
The FN-LCD-S serial annunciator provides a
convenient and cost effective remote annunciator
solution. Up to 15 FN-LCD-S annunciators can be
connected to the slave RS-485 port of the FireNET
control panel or network annunciator. The FN-LCD-Ss
large 320 character display and navigation buttons are
a complete mimic of the FireNET control panel
display. The use of a common interface allows the
user to easily operate the FN-LCD-S as if he were
operating the FireNET control panel directly.
Security is established by the use of a password or
firefighters enable key. Designed to be aesthetically
pleasing, the FN-LCD-S is available in charcoal grey
or red enclosures. The FN-LCD-S can be surface or
flush mounted without the need for a trim ring.
PRODUCT LISTINGS
SPECIFICATIONS
Current Draw
Standby:
Alarm:
Dimensions
FN-LCD-S
Back Box
Weight
20mA @ 24VDC
110mA @ 24VDC
10.88" W x 8.00" H x 1.38" D
10.38" W x 7.38" H x 1.25" D
3.5 lbs
California
State Fire
Marshal
7120-0410:165
Color
Material
Display
ABS/steel enclosure
8 line x 40 character LCD
(320 characters total)
Network
RS485 port
Continued on back.
Find latest revision at www.hochiki.com
F0070
09/2007
ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the serial remote annunciator model
FN-LCD-S. The FN-LCD-S shall connect to the FireNET fire alarm control panel (FACP) or network
annunciator (FN-LCD-N) RS485 slave bus. The serial remote annunciator shall annunciate on its 320
character display and local buzzer, the condition of its master FireNET FACP. Up to 15 FN-LCD-S serial
annunciators may be connected together on a single RS-485 FireNET slave bus. The FN-LCD-S shall be
UL listed and compatible with the Hochiki FireNET control panel, and have surface or flush mount
capability.
WIRING DIAGRAM
1522RO @
ADDRESS
COMM1
COMM2
+24V
K S
2
ON
1
0V
RESET
RESET W / DOG
FIT JUMPER
FOR END OF LINE
COMM1 COMM2
COMMS
ACTIVE
Reset
Switch
Not Used
Not Used
DIP Switch used to set
the FN-LCD-S address
between 1 -15
7. PR2
COMMS
l +
8. PR3
ADDITIONAL
I/O BOARDS
( +)
NETWORK
IN
l +
24 VDC
(- )
(+)
l +
AUX
24X
NETWORK
OUT
RS-485
l +
(- )
To next
serial
FN-LCDS or
other
RS485
Buss
Device
STANDARD FEATURES
Contact ID and SIA reporting formats
UL 864 9th Edition listed
Programmable from FireNET control panel or by
using Loop Explorer
Zone or Address (Point) reporting
SPECIFICATIONS
Power Requirements
24VDC @ 20mA
Operating Temperature
0-49 C @ 93% RH
Dimensions
FireNET Firmware Required
5.48" x 7.48"
3.8 or higher
PRODUCT LISTINGS
UL 864, NFPA 72:
Central Station, Remote
Station & Proprietary
S8255
California
State Fire
7170-0410:170
Continued on back.
F0073
01/2008
ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the FN-DAC Digital Alarm Communicator. The
FN-DAC shall connect to the FireNET 4127 fire alarm control panel RS-232 port. The communicator shall be
programmable by using the front panel controls or by using Loop Explorer software. The FN-DAC shall allow the
use of a computer and modem to remotely access the FireNET network to perform remote diagnostics and system
configuration. The FN-DAC shall be programmable to report events by zone or by address, and shall be capable of
reporting using Contact ID or SIA format.
WIRING DIAGRAM
Telephone line
connections
24 VDC
Input Power
To J5 connector
on FireNET panel
MODEL DESCRIPTION
DCP-AMS
DCP-AMS-KL
DCP-AMS
DCP-AMS-LP
DCP-AMS-KL
DCP-AMS-KL-LP
DESCRIPTION
The DCP-AMS are the Hochiki America series of
addressable manual pull stations that provide a fast and
practical means of manually initiating a fire alarm signal.
Both single action and dual action manual pull stations
are available. Resetting of the pull station requires either
a Cat 30 key or a 1/8" hex key (depending upon the
model used).
DCP-AMS-LP
DCP-AMS-KL-LP
STANDARD FEATURES
PRODUCT LISTINGS
California State
Fire Marshal
S6512
3033215
7150-0410:169
Continued on back.
F0066
07/2010
ENGINEERING SPECIFICATIONS
Manual pull stations shall be Hochiki addressable AMS-series single or dual action models, DCP-AMS, DCP-AMSKL, DCP-AMS-LP, or DCP-AMS-KL-LP. Models shall be made of 14 AWG CRS and painted with Red enamel. The
words Fire Alarm shall be in a contrasting color and be embossed text 1/2" tall. The electronics shall be fully
integrated into the manual pull station requiring only connection to the SLC loop of the control panel. Programming of
the manual pull station address must be possible with the manual pull station fully installed.
Manual pull stations shall be Underwriters Laboratories Inc. Listed, CSFM Approved, and be installed within the limits
defined in the Americans With Disabilities Act.
WIRING DIAGRAMS
Hochiki America Corporation
DCP-AMS
OUT TO
NEXT
MODULE
SC-
Ser. No.
S+
SC-
S+
S6512
NON-CODED ALARM BOX
36CC
UL
Listed
+ S
Hochiki
DCP
- SC
Compatible
Panel
TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED
TO A COMPATIBLE LISTED CONTROL PANEL
Class B (Style 4)
Hochiki America Corporation
DCP-AMS
Ser. No.
Ser. No.
Ser. No.
S+
SC-
S+
+ S
UL
Listed
- SC
Hochiki
DCP
+ S
Compatible
Panel
- SC
SC-
S+
SC-
S6512
S6512
S6512
NON-CODED ALARM BOX
36CC
(OUT) S
(OUT) SC
S6512
DCP-SCI
SC-
S+
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
(IN) SC
(IN) S
S5694
DCP-SCI
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
(OUT) S
(OUT) SC
S5694
DCP-SCI
(IN) SC
S6512
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
SC-
(OUT) S
(OUT) SC
S+
S5694
(IN) SC
(IN) S
Ser. No.
(IN) S
DCP-SCI
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
UL
Listed
Hochiki
DCP
Compatible
Panel - SC
S5694
S
SC
Ser. No.
(IN) S
(IN) SC
(OUT) S
(OUT) SC
2 SLC (Class A or B)
Loops per
expander
System Capacity
Loop Current
STANDARD FEATURES
24 - 40VDC
127 sensors/modules +
127 analog sounder bases, 254 total
Loop Load
impedance
Size
6.3" L x 4.5" W
DESCRIPTION
The model FN-4127-SLC Dual SLC Loop Expander is
a two loop expander board that increases the
standard FireNET loop capacity from 2 to 4 loops.
The FN-4127-SLC can be added at the factory or
installed in the field, and mounts within the main
control board location as a piggy-back board. By
adding the FN-4127-SLC, the FireNET capacity is
increased from 254+254 to 508+508 analog
addressable points within the overall 800 address/
sub-address limit. The FN-4127-SLC has the same
functionality as the built-in SLC loops. The FN-4127SLC utilizes Hochikis robust DCP loop protocol for
highly reliable and fast alarm reporting without the
need for shielded or twisted pair wiring for the SLC
loops.
PRODUCT LISTINGS
S8255
Vol. 1
Sec. 2
California
State Fire
Marshal
7170-0410:170
F0062
04/2010
24 VDC Nominal
20mA
Cable Length
4,000ft Max.
Cable Type
Protocol
Address Setting
32F~120F
90%RH
DESCRIPTION
STANDARD FEATURES
Dipswitch
Operating Temperature
Operating Humidity
RS-485
ENGINEERING SPECIFICATIONS
PRODUCT LISTINGS
S8255
UL 864 Category
UOJZ CNN:
Signal System Control
Unit Sub-Assembly
NFPA72 compliant
California
State Fire
Marshal
7170-0410:170
F0063
06/2010
24 VDC Nominal
Channels
STANDARD FEATURES
PRODUCT LISTINGS
S8255
Vol. 1
Sec. 2
California
State Fire
Marshal
7170-0410:170
1A max.
Communications
Max Distance from
panel
Cable Capacity
Indicators
Size
7.5" L x 2.4" W
DESCRIPTION
The FireNET FN-4127-IO is a 16 channel Input/Output
board that provides powerful input/output expansion &
addition to the FireNET system allowing up to thirty two I/O
boards to be connected to each FireNET panel within the
FireNET network. Every I/O board connected to any panel
is available to the entire network, which allows for network
wide input/output mapping. Typical uses include graphical
LED map displays/annunciators, tabular LED zone display/
annunciators, input/output logic to & from the fire system
for secondary use (I/O board points cannot be used for
primary fire initiation inputs or notification outputs) such as
access control, burglar, CCTV, intercom, voice, or other 3rd
party systems. Each channel can be configured to produce
a variety of input actions or respond to a variety of output
categories or logic. All channels can trigger, or react from,
network wide cause and effect logic depending on their
configuration. The flexibility of these boards is further
enhanced by the fact that each of the channels is
configurable as either an input or an output. Connection
can be achieved through a simple two wire RS485
communications protocol and two wire power input. I/O
boards can be mounted locally in the control panel or
distributed on a bus up to 4,000ft from the panel when
using the FN-ACC accessory enclosure.
F0061
04/2010
SPECIFICATIONS
Operating Voltage
Average Current Consumption
Alarm Current
Ambient Temperature
Maximum Humidity
Dimensions
Weight
Mounting
12 ~ 30 VDC
0mA (Standby)
1A for 0.5 seconds
DESCRIPTION
STANDARD FEATURES
PRODUCT LISTINGS
UL 864, NFPA 70 & 72:
Signaling Device
S8255 Vol. 2
California
State Fire
Marshal
7170-0410:170
Continued on back.
F0064
01/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki America FN-CTM City Tie Module.
The module terminal blocks shall be capable of accepting up to 14 AWG wire. The FN-CTM shall be configured
such that the Fire Alarm Control Panels EOL (end of line) device connects directly with the FN-CTM to ensure
supervision of the interface wiring. The module shall fit into a standard 4" electrical back box. The FN-CTM shall
be Underwriters Laboratories Listed for the intended purpose.
FN-CTM
Local Energy
City Tie
Trip Coil
City Tie
EOL
S8255
NAC Input
E.O.L. DEVICE
NAC Circuit
U.L. LISTED
E.O.L. DEVICE
FOR FireNET
PART NUMBER
0400-01046
10K OHM 1/4W
Signaling Devices
ISSUE NO. BF-8887
Hochiki FireNET
or
Compatible UL Listed
Fire Alarm Control Panel
NAC Circuit
Wiring Polarity Shown in
Alarm Condition.
SPECIFICATIONS
Models
Max. Battery Capacity
Max. I/O Board Capacity
Dimension
Colors
Material
FN-ACC-R / FN-ACC-C
2 x 33Ah
6 x FN-4127-IO
17.80"W x 14.85"H x 5.77"D
Red or Charcoal
ABS/steel enclosure
DESCRIPTION
The FN-ACC is designed to provide a method to properly
store backup batteries for the FireNET and FireNET Plus
panels. The enclosure can also be used to mount 16
Channel I/O Boards. The battery enclosure comes in
two colors Red (FN-ACC-R) & Charcoal (FN-ACC-C) and
comes with a keylock.
DIMENSION
F0116
04/2011
OPERATION
STANDARD FEATURES
SPECIFICATIONS
Operating Voltage
Standby Current
Alarm Current
Transmission Method
17-41 VDC
390A
800A
DCP - Digital
Communication Protocol
Maximum Humidity
95% RH Non-Condensing
UL Ambient Installation 32F to 100 F
Temperature Range
(0 C to 37.8 C)
Operating Temperature
14F to 122 F
Range
(-10 C to 50 C)
Sensitivity Range
0.5 - 3.8%/FT@300FPM
0.5 - 2.74%/FT@2000FPM
0.5 - 2.68%/FT@4000FPM
Air Velocity Range
0-4000 fpm
Color & Case Material Bone PC, Black / ABS Blend
Weight
3.4oz (5.1 oz. with 4" base)
Bases
4"
YBN-NSA-4
6"
HSB-NSA-6 & ASB
Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, photoelectric sensors HOCHIKI
America Model ALK-V. The combination sensor
head and twist lock base shall be UL listed compatible with a UL listed fire alarm control panel.
PRODUCT LISTINGS
3034568
California
State Fire
Marshal
7272-0410:173
S1383
Continued on back.
Find latest revision at www.hochiki.com
F0076
04/2011
BASES
The HOCHIKI America except for ASB both YBN-NSA-4 and the HSB-NSA-6 mounting bases are electronics free and are
a simple rugged design with screw terminals for wiring connections. A common mounting base allows sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided
which is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using
a small diameter screw driver.
(+)
(-)
U.L.
LISTED
POWER
LIMITED
SUPPLY
(+)
*
* - OPTIONAL WIRING CONFIGURATIONS FOR REMOTE OUTPUT
(+)
U.L.
LISTED
COMPATIBILE
CONTROL
PANEL
(-)
U.L.
LISTED
POWER
LIMITED
SUPPLY
UL LISTED
COMPATIBLE
CONTROL
PANEL
(+)
NEXT DEVICE
8mA Max.
LOOP OUT
NEXT DEVICE
(Aux.)
FIGURE A
(+)
TOP VIEW
8mA MAX.
OUTPUT
NOTE: Class A style 7 wire configuration requires the installation of short circuit isolators (SCI).
DO NOT CONNECT FOR CLASS B (STYLE 4)
LOOP IN
CO
ICA B
ER V.
RE
I AM 7 B
-06 AS
C HIK-08
HO HA
CO
ICA B
ER V.
RE
I AM 7 B
-06 AS
C HIK-08
HO HA
.
RP
.
RP
SC
SC
G
3
TP
3
TP
TS
C
1
TP
DE
TS
1
TP
DE
2
TP
2
TP
AUX POWER
S5
S5
RED
RED
BLACK
1.4 ohms
2.4 ohms
3.0 ohms
3.6 ohms
6.1 ohms
9.1 ohms
12.2 ohms
18.3 ohms
BLACK
FIGURE B
BOTTOM VIEW
2
C-0 03
21
RED
RED
BLK
BLK
RED
2
C-0 03
21
RED
BLK
BLK
RED
BLACK
127
75
60
50
30
20
15
10
OPERATION
Shown without base
STANDARD FEATURES.
Low Profile - Only 2.22" high, including base
Simple and reliable device addressing method
Automatic compensation for sensor
contamination
Built in fire test feature
Uses the noise immune Digital Communication
Protocol (DCP), which utilizes interrupts for fast
response to fires
SPECIFICATIONS
Operating Voltage
Standby Current
Alarm Current
Transmission Method
17-41 VDC
350A
460A
DCP - Digital
Communication Protocol
Maximum Humidity
95% RH Non Condensing
UL Ambient Installation 32F to 100F
Temperature Range
(0C to 37.8C)
Operating Temperature
14F to 122F
Range
(-10C to 50C)
Radiation Source
Americium 241 (0.98Ci)
Color & Case Material Bone PC / ABS Blend
Weight
4.2oz (5.9 oz. w/ 4" base)
Base
4" YBN-NSA-4
6" HSB-NSA-6
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated
on the plans, dual-chamber, ionization smoke sensor
HOCHIKI America AIE-EA. The combination sensor head
and twist-lock base shall be UL listed compatible with a
UL listed fire alarm control panel.
PRODUCT LISTINGS
3022559
MEA
S1383
Specifications subject to change without notice.
NYC Department
of Building
284-91-E Vol. 4
California
State Fire
Marshal
7272-0410:148
Continued on back.
F0022
04/2011
BASES
The HOCHIKI America HSB-NSA-6 and the YBN-NSA-4 mounting bases are electronics free and are a
simple rugged design with screw terminals for wiring connections. A common mounting base allows
sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head
locking system is provided which is enabled by removing a small plastic tab on the back of the sensor.
Once locked, the head can be removed using a small diameter screw driver.
HSB-NSA-6 Base
YBN-NSA-4 Base
NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V and ATG-EA, bases and modules), to be used concurrently in a system's signal conditioning loop.
Hochiki America Corporation AIE-EA
OPERATION
STANDARD FEATURES
Low Profile - Only 2.0" high, including base
Simple and reliable device addressing method
Uses the noise immune Digital Communication
Protocol (DCP), which utilizes interrupts for fast
response to fires
Adjustable threshold temperature 135F - 150F
(determined by panel)
SPECIFICATIONS
Operating Voltage
Standby Current
Alarm Current
Transmission Method
17-41 VDC
350A
500A
DCP - Digital
Communication Protocol
Maximum Humidity
95% RH Non-Condensing
UL Ambient Installation 32F to 115 F
Temperature Range
(0 C to 47 C)
Operating Temperature 135F to 150 F
Range
(57.2 C to 65.6 C)
Color & Case Material Bone PC / ABS blend
Weight
3.2oz
(4.9 oz. with 4" base)
Bases
4"
YBN-NSA-4
6"
HSB-NSA-6
ENGINEERING SPECIFICATIONS
Heat sensors are installed in accordance with NFPA
(National Fire Protection Association) 72, the UL Listed
Spacing Requirements and the rules and regulations set
forth by the local authorities having
PRODUCT LISTINGS
3022559
MEA
S2966
Specifications subject to change without notice.
NYC Department
of Building
284-91-E Vol. 4
California
State Fire
Marshal
7270-0410:147
Continued on back.
F0023
03/2011
BASES
The HOCHIKI America HSB-NSA-6 and the YBN-NSA-4 mounting bases are electronic free and are a simple rugged
design with screw terminals for wiring connections. A common mounting base allows sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided which is
enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using a
small diameter screw driver.
(DIAGRAM OF 2 BASES HERE)
HSB-NSA-6 Base
YBN-NSA-4 Base
NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V and ATG-EA, bases and modules), to be used concurrently in a system's signal conditioning loop.
Hochiki America Corporation ATG-EA
OPERATION
STANDARD FEATURES
SPECIFICATIONS
Operating Voltage
Standby Current
Alarm Current
Transmission Method
Operating Temperature
UL Temperature Range
Storage Temperature
Range
Maximum Humidity
Color & Case Material
Weight
Dimensions
Bases
17-41 VDC
450A
540A
DCP - Digital
Communication Protocol
14F (-10C) - 122F (50C)
135F (57C) - 150F (65C)
-4F (-20C) - 140F (60C)
95% RH Non-Condensing
Ivory
4.2 oz (5.9 oz. with 4" base)
3.9"W x 1.8"H
4"
YBN-NSA-4
6"
HSB-NSA-6
6"
ASB
PRODUCT LISTINGS
California
State Fire
Marshal
S1383
7272-0410:0182
Continued on back.
F0099
04/2011
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Multi-Criteria sensor HOCHIKI America Model ACAV. The combination sensor head and twist lock base shall be UL listed compatible with the UL listed fire alarm control
panel.
The base shall permit direct interchange with the HOCHIKI America ALG-V Photoelectric type smoke sensor, ALK-V/
ALK-V2 Photoelectric type sensor, AIE-EA ionization type smoke sensor, and the ATG-EA heat sensor.
The sensitivity of the sensor shall be capable of being measured by the control panel.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.
BASES
The HOCHIKI America YBN-NSA-4 and the HSB-NSA-6 mounting bases are electronics free and are a simple rugged
design with screw terminals for wiring connections. A common mounting base allows sensor interchange and maintains
loop continuity when sensors are removed. A simple anti-tamper head locking system is provided which is enabled by
removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using a small diameter
screw driver.
YBN-NSA-4 Base
HSB-NSA-6 Base
NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA, ALG-V, ACA-V
ALK-V and ATG-EA, bases and modules), to be used concurrently in a system's SLC (Signaling Line Circuit).
Hochiki America Corporation ACA-V Multi-Criteria Sensor
Plastic Tamper-lock
Bone PC / ABS Blend
HSB-NSA-6: 6 inches
YBN-NSA-4: 4 inches
ALG-V, ALK-V, ALK-D, AIE-EA,
ATG-EA, ACA-V
APPLICATION
YBN-NSA-4
The HOCHIKI America YBN-NSA-4 and the HSB-NSA6 mounting bases are electronics free and contain a
simple rugged design with screw terminals for wiring
connections. A common mounting base allows sensor
interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head locking
system is provided which is enabled by removing a small
plastic tab on the back of the sensor. Once locked, the
head can only be removed using a small diameter screw
driver.
OPERATION
HSB-NSA-6
The YBN-NSA-4 and HSB-NSA-6 are designed specifically for use with the Hochiki NS Analog models AIEEA, ALG-V, ALK-V, ALK-D, ATG-EA, and ACA-V.
STANDARD FEATURES
PRODUCT LISTINGS
CS463
California
State Fire
Marshal
7300-0410:132
S1383
MEA
284-91-E Vol. IV
3022559
Continued on back.
F0013
07/2010
ENGINEERING SPECIFICATIONS
The base shall permit direct interchange with the HOCHIKI America AIE-EA Ionization type Smoke Sensor, ALG-V,
ALK-V Photoelectric Smoke Sensor, ALK-D Photoelectric Smoke Sensor for in-duct use, ATG-EA Heat Sensor, and
the ACA-V Multi-criteria Sensor.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.
YBN-NSA-4
(+)
UL LISTED
COMPATIBLE
DCP LOOP
UL LISTED
POWER LIMITED
SUPPLY
(+)
8mA MAX.
OUTPUT
HSB-NSA-6
(+)
UL LISTED
COMPATIBLE
DCP LOOP
UL LISTED
POWER LIMITED
SUPPLY
(-)
(+)
8mA MAX.
OUTPUT
8mA MAX.
OUTPUT
NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V, ALK-V, ALK-D, ACA-V and ATG-EA, bases and modules), to be used concurrently in a system's signaling line circuit.
Hochiki America Corporation Analog Sensor Bases
STANDARD FEATURES
Programmable evacuation codes - Continuous,
March, ANSI Temporal patterns
Operating Voltage
SLC Current
Consumption
Auxiliary Supply Voltage
Auxiliary Current
Consumption
Sound Pressure Level
at 10ft.
Max. Quantity Per Loop
UL Ambient Installation
Temperature Range
Operating Temperature
Range
Dimensions (without
sensor)
Weight
Relative Humidity
Compatible Detectors
PRODUCT LISTINGS
California
State Fire
Marshal
S1383
7300-0410:161
17 ~ 41 VDC
110A (Typical)
110A (Alarm)
16 ~ 31 VDC
550A (Typical)
18mA (Alarm)
85dB
127
32F (0C) ~ 100F (38C)
32F (0C) ~ 122F (50C)
1.34H x 5.94D
0.455 lb
93% RH Non-Condensing
ALG-V, ALK-V, AIE-EA, ATG-EA,
ACA-V
DESCRIPTION
The ASB Analog Sounder Base is designed for use
with Hochiki analog sensors ALG-V, ALK-V, ACA-V,
AIE-EA, and ATG-EA. Each addressable base is to
be connected to a Hochiki America Corporation DCP
Signaling Line Circuit (SLC). The ASB provides an
audible alarm in the immediate vicinity. Typical
applications are hotels, apartments, and hospitals.
The ASB has a highly configurable programming
algorithm that allows the user to set up groups of
bases for synchronization of modulation tones. Each
device has 16 states that are programmed with the
desired output pattern to be used (e.g., Temporal or
March) for each state.
3036551
Continued on back.
F0056
07/2010
WIRING DIAGRAM
FIRE ALARM
CONTROL
PANEL
NEXT DEVICE
8mA Max.
LOOP OUT
NEXT DEVICE
(Aux.)
FIGURE A
(+)
TOP VIEW
8mA MAX.
OUTPUT
NOTE: Class A style 7 wire configuration requires the installation of short circuit isolators (SCI).
DO NOT CONNECT FOR CLASS B (STYLE 4)
LOOP IN
RP
CO
IC A . B
M ER R EV
I A 67 B
H IK08-0 AS
HOC H A-
P.
C OR
CA B
ERI V.
AM RE
KI -067 AS B
C HI 08
HO H A-
.
SC
SC
G
TP
TP
TP
SC
DET
TP1
C
TS
DE
TP
TP
AUX POWER
S 56
2
C-01 03
2
2
C-01 03
2
RED
RE
D
BLK
BLK
6
S5
RE
D
RE D
BLK
BLK
RED
BLACK
RED
RED
BLACK
BLACK
FIGURE B
BOTTOM VIEW
1.4 ohm
75
60
50
30
20
15
10
2.4 ohm
3.0 ohm
3.6 ohm
6.1 ohm
9.1 ohm
12.2 ohm
18.3 ohm
alarm systems
Installs quickly and easily
No screens or filters to clean
Rugged gray steel back box with clear cover
Accessories - Remote LED alarm
indication capability (DH-98-AR only)
Meets UL 268A Requirements
APPLICATION
Duct housing with an ALG-DH analog
photoelectric sensor.
SPECIFICATIONS
D uct Detector Model #
DH-98-AR
DH-98-A
ALG-DH
Analog Photoelectric
Communication
Input Voltage
Standby Current
2mA AVG
10mA
8mA
Alarm Current
Alarm Contacts
55mA
2 form C rated at
10A@250V AC
N/A
Control Panel
N/A
Power,Alarm,
Horn/Piezo
Test
Air Velocity
Ambient Temperature
Humidity
Housing Material
Grey Paint
Dimensions
PRODUCT DESCRIPTION
Finish
3022559
3lbs.
Sampling Tubes
PRODUCT LISTINGS
MEA
S1383
Specifications subject to change without notice.
NYC Department
of Building
284-91-E Vol. 4
California
State Fire
Marshal
7272-0410:149
Continued on back.
F0036
04/2010
PRODUCT DESCRIPTION,
continued
Mounting the duct smoke unit is accomplished by the use of a template and 4 sheet metal screws, which are
provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture
screws.
The compact DH-98-AR contains 2 sets of form "C" contacts rated at 10 amps.
The pilot and alarm visual indicators, provided on the front of the DH-98-AR duct unit, signal the operating
status of the device. A manual test/ reset switch is located along side the visual indicators.
ENGINEERING SPECIFICATIONS
Air duct smoke detectors shall be HOCHIKI AMERICA DH-98 Series. The detectors shall be listed by Underwriters
Laboratories per UL 268A. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet per
minute.
The duct detector housings shall be of metal construction and complete mechanical installation may be
performed without removal of the detector cover. The duct detector shall not require additional filters or screens
which must be maintained. The housing shall contain a base which will accept an analog photoelectric sensor
head. Terminal connections shall be of the screw type and be a minimum of #6 screw. For installations
requiring relay functions, terminals shall be provided for remote pilot, remote alarm indication, strobe/ horn and
remote key switch. For installation not requiring relay functions, visual indication of alarm and power must be
provided on detector front. A manual reset switch shall be located on the front of the device (DH-98-AR only).
All wiring must comply with local codes and regulations.
WIRING DIAGRAMS
LOOP INTERFACE
UL LISTED
CONTROL PANEL
S (+)
TO NEXT
SENSOR
SC (-)
FAN SHUT DOWN EXAMPLE
DH-98-AR
OBSERVE POLARITY
INPUT VOLTAGE
24 V.D.C.
10 mA Standby
55mA Alarm
4
-
REMOTE
ALARM
LED
+
5
6
+
REMOTE
PILOT LED
UL LISTED
CONTROL PANEL
FAN
SUPPLY VOLTAGE
ADDRESSABLE
LOOP
LOOP INTERFACE
Note
DH-98-A
ALG-DH ANALOG
SENSOR
8
NC
9
NO
ALARM CONTACTS
10.0A @ 250VAC
11
10
NC
12
NO
ALARM CONTACTS
10.0A @ 250VAC
REMOTE TEST
SWITCH
S (+)
ANALOG ADDRESSABLE
FIELD LOOP WIRING
SC (-)
TO NEXT SENSOR
OR RETURN
TO CONTROL PANEL
SPECIFICATIONS
Power Requirements
Alarm LED
Pilot LED
Horn
Sound Pressure
Horn
Dimensions
Single Gang
Double Gang
ALARM
MS-RA
Functions:
Remote Alarm LED (red)
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
DH-98-A, DH-98-AR
ALARM
PILOT
TEST/RESET
ALARM
TEST/RESET
ALARM
PILOT
MS-KA/R
Functions:
Remote Alarm LED (red)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
DH-98-AR
MS-RA/P
Functions:
Remote Alarm LED (red)
Pilot LED (green)
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
ALARM
TEST/RESET
ALARM
PILOT
TEST/RESET
15 mA
15 mA
20 mA @ 24 VDC
78 db @ 10 feet
2.75" (69.85mm) W
4.5" (114.3mm) H
4.5" (114.3mm) W
4.5" (114.3mm) H
MS-KA/P/R
Functions:
Remote Alarm LED (red)
Pilot LED (green)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
MS-RA/R
Functions:
Remote Alarm LED (red)
Push-button Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
DH-98-AR
MS-RA/P/R
Functions:
Remote Alarm LED (red)
Pilot LED (green)
Push-button Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
04/2010
MS-RH/KA/P/R
Functions:
Remote Alarm Horn
Remote Alarm LED (red)
Pilot LED (green)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
ALARM
PILOT
TEST/RESET
WIRING DIAGRAM
RED
RED
RED
24VDC
ALARM
ALARM
GREEN
24VDC
HORN
PILOT
LED
LED
BLACK
BLACK
ALARM
PILOT
BLACK
KEY OR
24VDC
PUSH BUTTON
"TEST/RESET"
SWITCH
BLACK
TEST/RESET
PRODUCT SPECIFICATIONS
PUSH
KEY
PILOT ALARM BUTTON OPERATED
TEST/
TEST/
LED
LED
RESET
RESET
(GREEN) (RED)
HORN
SINGLE
GANG
DOUBLE
GANG
MODEL #
MS-RA
MS-RA/P
MS-RA/R
MS-RA/P/R
MS-KA/R
MS-KA/P/R
MS-RH/KA/P/R
Hochiki America Corporation DH-98 Duct Detector Remote Accessories
25.3 ~ 39 VDC
24 VDC
154A (Typical)
161A (Maximum)
Typical 1.15mA
2A @ 24 VDC Power Limited
10K ohms Resistor
127
4.2W x 4.7H x 1.4D
32F (0C) ~ 120F (49C)
4 square electrical box
90% RH Non-Condensing
STANDARD FEATURES
CS943
S5694
MEA
284-91-E Vol. IV
3022559
DESCRIPTION
The Supervised Output Module (DCP-SOM), has been
designed to provide application flexibility and quick
response to emergency conditions. Flexibility is
provided by a wide range of operating modes, including
supporting multi-zone operations, and/or functions, up
to 16 different modulation patterns and multi-state
programming. The operating parameters for the DCPSOM are maintained by the module and do not require
individual communication with the control system
during emergency conditions to operate. The control
panel simply broadcasts system conditions on the
Signaling Line Circuit (SLC) and the DCP-SOMs do
the rest based upon the custom configuration. Each
DCP-SOM provides a Class B Individual Circuit rated
for 2.0 Amps @ 24 VDC. Each DCP-SOM also
requires a 24 Volt power source in addition to the SLC.
Provide software controlled LED indication: blinks
green or red when polled, or can be latched on.
California
State Fire
Marshal
7300-0410:150
Continued on back.
F0057
03/2011
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable Supervised Output Module (DCPSOM). The modules shall be UL listed and compatible with Hochiki Digital Communications Protocol (DCP)
supporting control panel loops. The device address shall be electrically programmable and stored in EEPROM. A
bi-colored LED shall indicate device status.The DCP-SOM shall be supplied with a plastic cover and shall be
suitable for mounting to a 4" square or double gang electrical back box. The DCP-SOM shall provide a monitor LED
that is visible from outside the cover plate.
E.O.L.
DEVICE
0400-01046
WIRING DIAGRAM
HOCHIKI AMERICA CORP.
E.O.L. DEVICE
PART NUMBER
0400-01046
OUTPUT TO
COMPATIBLE
U.L. LISTED
DEVICES FOR
FIRE
PROTECTION
SIGNALING
SERVICE
Note: SLC circuit is in reference to S, and SC
DCP-SOM
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
OUT TO
NEXT
SC
GND
S
For Dry Indoor Use Only
24+
TB1
TB2
OUT+
MODULE
WARNING!!!
25.3 ~ 39 VDC
24 VDC
12 volts (Typical)
10mA (Typical)
127
STANDARD FEATURES
Dimensions
Ambient Temperature
Mounting
PRODUCT LISTINGS
S5694
California
State Fire
Marshal
3036830
7300-0410:150
90% RH Non-condensing
DESCRIPTION
The Class A Supervised Output Modules (DCP-SOM-A &
SOM-AI) have been designed to provide application
flexibility and quick response to emergency conditions.
Flexibility is provided by a wide range of operating
modes, including supporting multi-zone operations, and/
or functions, up to 16 different modulation patterns and
multi-state programming. The operating parameters for
the DCP-SOM-A & -AI are maintained by the module
and do not require individual communication with the
control system during emergency conditions to operate.
The control panel simply broadcasts system conditions
on the Signaling Line Circuit (SLC) and the DCP-SOM-A
& -AI modules do the rest based upon the custom
configuration. Each DCP-SOM-A & -AI provides a single
Class B or Class A circuit rated for 2.0 Amps @ 24
VDC. Each DCP-SOM-A & -AI also requires a 24 VDC
power source in addition to the SLC.
F0091
05/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable Class A Supervised Output Modules
(DCP-SOM-A & -AI). The modules shall be UL listed and compatible with the fire alarm control panel. The device
address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall flash to indicate normal
system communication .
The DCP-SOM-A & -AI shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or
double gang electrical back box. The DCP-SOM-A & -AI shall provide a monitor LED that is visible from outside the
cover plate.
WIRING DIAGRAM
U.L. LISTED 1481 24VDC
REGULATED, POWER
LIMITED SUPPLY FOR FIRE
PROTECTION SIGNALING
SERVICE FOR AUDIBLE
DEVICES. REFER TO
CONTROL PANEL
MANUFACTURER'S
INSTALLATION
INSTRUCTIONS.
OUT TO NEXT
INTERFACE MODULE
S+
SC-
DCP-SOM-A
TB1
24V +
24V -
HOCHIKI
24V+
24V-
IN S+
S+
OUT+
IN SC-
SC-
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
OUTIN+
TB3
INCLASS-B CLASS-A
CLASS-B
CLASS-A
!
SELECT CLASS-A WIRING
BY SETTING THIS JUMPER
OUT TO NEXT
INTERFACE MODULE
S+
SC-
TB1
24V +
DCP-SOM-AI
24V+
24V -
IN S+
24VOUT+
For Proper Installation
See HA-06-138 Rev 06/09
S+
IN SC-
SC-
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
OUT S+
OUT-
HOCHIKI
IN+
OUT SCTB3
INCLASS-B CLASS-A
CLASS-B
U.L. LISTED SIGNALING DEVICES
+
-
!
SELECT CLASS-B WIRING
BY SETTING THIS JUMPER
E.O.L. DEVICE
PART NUMBER
0400-01046
CLASS-A
E.O.L. DEVICE
PART NUMBER
0400-01046
25 . 3 ~ 39 V D C
24 VD C
15 4 A ( Ty p ica l)
M a x im u m : 6m A (R ed A la rm
LE D O n )
C ur re nt C on s um p tio n on
A uxiliar y Po w er L ine s
M a xim u m Ou tpu t C u rre n t
S ole n oid C u r ren t
C on s um p tio n
C om p at ib le S o le n oid s
T yp ica l 1.1 5m A
E OL D e v ic e
S O M -R D im e nsio ns
O pe ra tin g T e m p e ra t u re
M o u n tin g
R ela t ive H u m idit y
STANDARD FEATURES
AS C O : 82 1 0G 2 07
Pa r ke r/ Sk in ne r:
73 2 18 B N 4 U M L VN O C 1 11 C 2
10 K o h m s R e sist o r & 1 N 5 8 17
D io de
4. 2 W x 4 . 7 H x 1 .4 D
32 F (0 C ) ~ 1 2 0F (4 9 C )
4 squ a r e e lect rica l bo x
90 % R H N o n-C on d en sing
DESCRIPTION
S5694
2A @ 2 4 V D C P o w er L im it ed
M a x im u m : 44 3 m A
California
State Fire
Marshal
7300-0410:150
F0111
08/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable Supervised Output Module (DCPSOM-R). The modules shall be UL listed and compatible with FireNET 4127 Fire Alarm Control Panel. The device
address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device
status.The DCP-SOM-R shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or
double gang electrical back box. The DCP-SOM-R shall provide a monitor LED that is visible from outside the cover
plate. DCP-SOM-R is provided with a disable switch (SOM-R-DS), which shall be suitable for mounting to a single
gang electrical back box.
WIRING DIAGRAM
SOLENOID
Hochiki America Corporation
DCP-SOM-R
TB2
24+
TB1
SC
GND
S
For Dry Indoor Use Only
BLACK
OUT+
RED
SOM-R
RED
IN
OUT
IN
OUTPUT TO
COMPATIBLE
U.L. LISTED
SOLENOID
VALVE
OUT
YELLOW
YELLOW
U.L. LISTED
FireNET 4127
FIRE CONTROL
PANEL
10KOhms EOL
SOM-R-DS
Disable Key Switch
IN-B
IN-A
SC-
S+
DCP-FRCME-4
AH-9755
S5694
FRCME
25.3 ~ 39 VDC
339A (Typical)
358A (Alarm)
1 Monitoring Inputs
10K Ohms Resistor
127
1.75"W x 2.37"H x 0.5"D
32F (0C) 120F (49C)
2" electrical box
90% RH Non-Condsensing
DESCRIPTION
STANDARD FEATURES
UL 864 9th Edition Listed
Single input contact monitor
Fast, reliable contact monitoring utilizing the
PRODUCT LISTINGS
California
State Fire
Marshal
7300-0410:150
S5694
Continued on back.
Find latest revision at www.hochiki.com
F0113
04/2011
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules
Hochiki DCP-FRCME-M. The modules shall be UL listed and compatible with the Hochiki Digital Communication
Protocol (DCP) supporting control panel. The device address shall be electrically programmable and stored in
EEPROM.
The DCP-FRCME-M shall be suitable for mounting to a single gang electrical back box.
WIRING DIAGRAM
OUTPUT TO NEXT INTERFACE
MODULE ON THE SLC LOOP
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
E.O.L. DEVICE
PART NUMBER
0400-01046
25.3 ~ 39 VDC
550A (Typical)
660A (Alarm)
Monitoring Inputs
10K ohms Resistor
127
4.2W x 4.7H x 1.4D
32F (0C) ~ 120F (49C)
4 square electrical box
90% RH Non-Condensing
DESCRIPTION
STANDARD FEATURES
UL 864 9th Edition Listed
Single input contact monitor
Fast, reliable contact monitoring utilizing the
PRODUCT LISTINGS
CS943
California
State Fire
Marshal
7300-0410:150
S5694
MEA
284-91-E Vol. IV
3022559
Continued on back.
Find latest revision at www.hochiki.com
F0002
07/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules
Hochiki DCP-FRCME-4. The modules shall be UL listed and compatible with the Hochiki Digital Communication
Protocol (DCP) supporting control panel. The device address shall be electrically programmable and stored in
EEPROM.
The DCP-FRCME-4 shall be supplied with a plastic face plate and shall be suitable for mounting to a 4" square or
double gang electrical back box. The DCP-FRCME-4 shall provide a monitor LED that is visible through the face
plate.
OUT TO
NEXT
MODULE
1S80
SC
U.L. LISTED
COMPATIBLE
CONTROL
PANEL
IN-B
DCP-FRCME-4
IN-A
SC-
S5694
S+
E.O.L. DEVICE
PART NUMBER
0400-01046
25.3 ~ 39 VDC
550A (Typical)
660A (Alarm)
Monitoring Inputs
10K ohms Resistor
127
3.0W x 1.9H x 0.5D
32F (0C) ~ 120F (49C)
Single gang electrical box
90% RH Non-Condensing
DESCRIPTION
STANDARD FEATURES
UL 864 9th Edition Listed
Single input contact monitor
Fast, reliable contact monitoring utilizing the
PRODUCT LISTINGS
California
State Fire
Marshal
7300-0410:150
S5694
MEA
284-91-E Vol. IV
3022559
Continued on back.
Find latest revision at www.hochiki.com
F0123
04/2011
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules
Hochiki DCP-FRCME-P. The modules shall be UL listed and compatible with the Hochiki Digital Communication
Protocol (DCP) supporting control panel. The device address shall be electrically programmable and stored in
EEPROM.
The DCP-FRCME-P shall fit inside a single gang electrical back box.
WIRING DIAGRAM
POWER LIMITED
S U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046
COMPATIBLE
SC CONTROL
PANEL
Wht
1S80
SC
IN-B
IN-A
DCP-FRCME-P
Blk
SC (IN)
Red
SC (OUT)
S5694
S (OUT)
S (IN)
OUT TO
NEXT
MODULE
U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046
25.3 ~ 39 VDC
630A (Typical)
6.3A (Alarm)
SCI On Resistance
40m ohm Max. (Normal Condition)
SCI Fault Detection Threshold
12 volts (Typical)
10mA (Typical)
127
Dimensions
Ambient Temperature
Mounting
(Both Models)
Yellow LED indicates a short circuit condition
(FRCMA-I only)
Can be programmed to monitor Normally Open
(NO) or Normally Closed (NC) contacts in Class B
Operates on Class A or Class B SLC loop
Accepts up to 14 AWG wire
UL 864 Listed
PRODUCT LISTINGS
S5694
California
State Fire
Marshal
3036830
7300-0410:150
Relative Humidity
STANDARD FEATURES
Single input contact monitor
Fast, reliable contact monitoring utilizing the
DESCRIPTION
The Hochiki FRCMA/-I Fast Response Contact Monitoring
Modules are designed to be used with pull stations, water
flow switches, and other applications requiring the monitoring of dry contact alarm initiating devices. The interrupt
driven Digital Communications Protocol (DCP) combines
maximum communication reliability and fast response to
emergency conditions. Two different mounting configurations are provided to meet a wide range of applications.
The FRCMA/-I contact monitoring module does not require
a separate 24 VDC power source.
Each addressable contact monitoring module is
programmed with its own unique Signaling Line Circuit
(SLC) loop address. The device address is electrically
programmable and stored on onboard EEPROM. Up to
127 devices can be placed on the Hochiki DCP SLC loop.
The module supervises the wiring to the contact with an
End Of Line (EOL) resistor in Class B mode. It can be
programmed to monitor Normally Open (NO) or Normally
Closed (NC) contacts. If a fault condition occurs in the
wiring, the module sends a trouble status signal to the fire
alarm control panel. When a change of status (contact
changes state) is sensed by the FRCMA/-I, it sends an
interrupt to the Fire Alarm Control Panel indicating that an
alarm has occurred. FRCMA-I version has built-in integrated
SCI circuitry. In the event of a short on the S-SC line, the
SCI circuit will activate and its yellow LED indicator will be
turned on steady and the module will report the short circuit
condition to the Fire Control Panel.
Continued on back.
Find latest revision at www.hochiki.com
F098
05/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules Hochiki
DCP-FRCMA/-I. The modules shall be UL listed and compatible with the Fire alarm control panel. The device address
shall be electrically programmable and stored in EEPROM.
The FRCMA/-I shall be supplied with a plastic face plate and shall be suitable for mounting to a 4" square or double
gang electrical back box. The FRCMA/-I shall provide a monitor LED that is visible through the face plate. FRCMA-I
shall provide a SCI LED that is visible through the face plate.
WIRING DIAGRAM
FRCMA/-I:
WIRING DIAGRAMS FOR CLASS A (STYLE D) WIRING
TB1
TB2
FIGURE 2A.
TB1
TB2
FIGURE 2B
TB2
E.O.L. DEVICE
PART NUMBER
0400-01046
FIGURE 2C
TB1 AND TB2 SHOWN IS SUPERVISED
AND INHERENTLY POWER LIMITED
STANDARD FEATURES
Can be placed at any location on SLC loop
Checks the line for short circuit at power up. If the
SPECIFICATIONS
Absolute Max. Applied Voltage S, SC: 41 VDC
Supply Voltage Norminal
S, SC: 33 VDC
Normal Current Consumption
270 A (Typical)
Active Current Consumption
10 mA (Typical)
(Short Circuit Condition)
Dimensions
4.2"W x 4.7"H x 1.4"D
Weight
1.4 oz
Visual Indicator (Yellow Status LED)
- No indication in normal condition.
- On steady in active (short) condition.
Operation Temperature Range
0C (32F)~ 49C (120F) Non-condensing
Allowable Ambient Humidity
90% Non-condensing
WIRING:
Note: All wiring must conform to local codes, ordinances and regulations.
1. Install module wiring in accordance with job drawings and appropriate wiring diagram.
2. Secure the module to an approved electrical box
(supplied by installer).
MOUNTING REQUIREMENTS: 4" SQ Electrical box
or double gang.
PRODUCT LISTINGS
CS943
S5694
MEA
California
State Fire
Marshal
7300-0410:150
284-91-E Vol. IV
Specifications subject to change without notice.
Continued on back.
Find latest revision at www.hochiki.com
F0008
06/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-SCI short circuit isolator. The
modules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP) supporting control panel
loops. The isolator module must be suitable for mounting in a standard 4" square electrical box or double gang. The
isolator module must provide a yellow LED for indication of status.
TB1
UL LISTED
COMPATIBLE
CONTROL
PANEL
(IN) S
(IN) SC
(OUT) S
(OUT) SC
LISTED
DCP-SCI
S5694
(IN) S
(IN) SC
(OUT) S
(OUT) SC
(OUT) SC
(IN) S
(IN) SC
(OUT) S
TB1
++ +
SIGNALING DE VICE
IS SUE NO. AH-9774
DCP-SCI
SE R. NO. XXXXXXXXX
S5694
WIRING DIAGRAM
DCP-SCI
SIGNALING DEVICE
ISSUE NO. AH-9774
S5694
LISTED
25.3 ~ 39 VDC
390A (Typical)
400A (Alarm)
2 Independently Controlled Form C
1Amp @ 30VDC or
0.5Amp @ 120 VAC
127
4.2W x 4.7H x 1.4D
32F (0C) ~ 120F (49C)
4 square electrical box
90% RH Non-Condensing
DESCRIPTION
STANDARD FEATURES
UL 864 9th Edition Listed
Provides two independently configurable Form C
PRODUCT LISTINGS
CS943
S5694
MEA
284-91-E Vol. IV
3022559
California
State Fire
Marshal
7300-0410:150
Continued on back.
Find latest revision at www.hochiki.com
F0058
07/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-R2M addressable relay
module. The modules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP) supporting
control panel loops. The relay module must provide two Form C dry contacts rated at 1Amp @ 30 VDC or 0.5Amp
@ 125 VAC. The relay module must be suitable for mounting in a standard 4" square electrical box or double gang.
The relay module must provide a bi-colored LED for indication of status.
WIRING DIAGRAM
WIRING TO BOTH SETS
OF FORM "C" CONTACTS
MUST BE EITHER POWER
LIMITED OR NON-POWER
LIMITED. DO NOT MIX
POWER LIMITED WIRING
WITH NON-POWER
LIMITED WIRING ON TB2.
ALL WIRING SHOWN ON
TB2 IS NOT SUPERVISED.
CONTACTS ARE SHOWN IN
STANDBY MODE - REFER
TO CONTROL PANEL'S
OPERATION MANUAL FOR
PROPER RELAY OPERATION
AND CONFIGURATION.
DCP-R2M
S, SC WIRING
POWER LIMITED
POWER
LIMITED
SC -
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
1
NC1
NON
POWER
LIMITED
S +
HOCHIKI
SET 1
COM1
TB1
NO1
S5694
NO2
CROSS OUT
TYPE NOT
USED
SET 2
COM2
NC2
25.3 ~ 39 VDC
350A (Typical)
405A (Alarm)
Contacts
12 volts (Typical)
10mA (Typical)
127
Dimensions
Ambient Temperature
PRODUCT LISTINGS
S5694
California
State Fire
Marshal
3036830
7300-0410:150
Relative Humidity
Mounting
STANDARD FEATURES
90% RH Non-condensing
DESCRIPTION
The Dual Relay Modules (R2ML/H Series) have been
designed to provide flexibile and quick response to
emergency conditions. The R2ML/H Series allows
independent control of two form C contacts for a variety of
normally open and normally closed contact applications
such as fan operation, elevator recall, door closure, and
auxiliary notification.
Each R2ML/H Series module provides independent control
of two Form C contacts while utilizing one SLC (Signaling
Line Circuit) address. The R2ML/H Series modules have a
highly configurable programming algorithm that allows the
user to set up groups of devices (zoning) for simultaneous
operation of multiple R2ML/H modules. Each module has
16 priority states that are programmed. The operating
parameters are maintained by the module and do not require
individual communication with the control panel during the
emergency condition to operate. The control panel
broadcasts the control command on the SLC loop and the
R2ML/H Series modules do the rest based on their custom
configuration. Since mechanically latching relays are used
within the R2ML/H Series modules, a separate 24VDC
power source is not required.
Continued on back.
F097
05/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-R2ML/H Series addressable
relay modules. The modules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP)
supporting control panel loops. The relay module must provide two Form C dry contacts rated as follows: R2ML - 2A
@ 30 VDC or 0.5A @ 120 VAC and R2MH - 8A @ 30VDC or 4.8A @ 250 VAC. The relay module must be suitable
for mounting in a standard 4" square electrical box. The relay module must provide a bi-colored LED for indication of
status. R2M-LI/-HI shall provide an SCI LED that is visible through the face plate.
WIRING DIAGRAM
SCI VERSION
TB2
DCP-R2MH-I
S, SC WIRING
POWER LIMITED
SET 1
COM1
OUT_SC-
POWER
LIMITED
OUT_S+
NON
POWER
LIMITED
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
NO1
NO2
IN_ SCIN_S+
NC1
CROSS OUT
TYPE NOT
USED
SET 2
COM2
NC2
B
FIGURE 1.
WIRING DIAGRAM
NON-SCI VERSION
TB2
DCP-R2MH
S, SC WIRING
POWER LIMITED
SET 1
COM1
POWER
LIMITED
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
NO1
NC1
NON
POWER
LIMITED
S +
NO2
SC CROSS OUT
TYPE NOT
USED
SET 2
COM2
NC2
FIGURE 2.
WIRING DIAGRAM
25.3 ~ 39 VDC
600A (Typical)
720A (Alarm)
2 Independent Monitoring Inputs
22K ohms Resistor
127
4.2W x 4.7H x 1.4D
32F (0C) ~ 120F (49C)
4 square electrical box
90% RH Non-Condensing
DESCRIPTION
STANDARD FEATURES
The Hochiki Dual Input Monitor Module (DIMM) is designed for use on a UL listed Fire Alarm Control Panel.
It provides two independent contact monitoring circuits while only utilizing one address on the SLC loop.
Up to 127 devices can be placed on a single SLC
loop. The device address is uniquely stored on an
onboard EEPROM. The module can be programmed
to monitor Normally Open (NO) or Normally Closed
(NC) contact fire alarm and supervisory devices. The
interrupt driven Digital Communication Protocol (DCP)
combines maximum communication reliability and
fast response to emergency conditions. The module
has a single bi-colored LED to indicate device status. It fits into a standard 4" square or double gang
electrical back box.
PRODUCT LISTINGS
S5694
California
State Fire
Marshal
3033215
7300-0410:150
Continued on back.
Find latest revision at www.hochiki.com
F0003
07/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki DCP-DIMM addressable contact
monitoring modules. The modules shall be UL listed and compatible with the Hochiki Digital Communications
Protocol (DCP) supporting control panel loops. The device address shall be electrically programmable and stored in
EEPROM. The contact module must be suitable for mounting in a standard 4" square electrical box or double gang.
The contact module must provide a bi-colored LED to indicate device status.
DCP-DIMM
TB1
Input A
S
U.L. LISTED
SC
COMPATIBLE
FIRE CONTROL
PANEL
Input B
STANDARD FEATURES
PRODUCT LISTINGS
S5694
California
State Fire
Marshal
3033215
7300-0410:150
25.3 ~ 39 VDC
18.8 ~ 27.2 VDC
670A
1mA Max.
60mA Max.
4.7K ohms Resistor
127
<1.5K ohms
>2.5K ohms & <6K ohms
>10K ohms
50 ohms (total wire length)
4.2W x 4.7H x 1.4D
32F (0C) ~ 120F (49C)
4 square electrical box
90% RH Non-Condensing
DESCRIPTION
The Hochiki Conventional Zone Module (DCP-CZM) is
designed for use on an analog addressable Fire Alarm
system. Up to 127 devices can be placed on a single
SLC loop. The device address is uniquely stored on an
onboard EEPROM. The module allows the panel to
interface and monitor two-wire conventional detectors
or pull stations. Each DCP-CZM transmits the status
on one zone of devices (25 maximum per zone) back
to the panel. It supervises the power supply as well
as the entire zone of devices. Status conditions are
reported as normal, open or alarm. All 2-wire smoke
detectors must be UL listed as compatible to be
interfaced with the DCP-CZM. The interrupt driven
Digital Communication Protocol (DCP) combines
maximum communication reliability and fast response
to emergency conditions. The module has a single bicolored LED to indicate device status. It fits into a
standard 4" square or double gang electrical back box.
Continued on back.
Find latest revision at www.hochiki.com
F0004
05/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Conventional Zone Module (DCP-CZM). The
modules shall be UL listed and compatible with the Hochiki America Analog Control Panel Protocol. The device
address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device status.
The DCP-CZM shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or double gang
electrical back box. The DCP-CZM shall provide a monitor LED that is visible from outside the cover plate.
LIST OF COMPATIBLE DEVICES
Detector Model
Detector
Identifier
Detector Type
Base Model
Max
Base
Indetifier Detectors
SLK-24F
HD-3
Photoelectric
HSB-224
HB-53
25
SIH-24F
HD-3
Ionization
HSB-224
HB-53
25
SLR-24H
HD-3
NS4-224, NS6-224
HB-5
SLR-24V
HD-3
Photoelectric
NS4-224, NS6-224
HB-5
25
25
SLR-835/-835W
HD-3
Photoelectric (8-35V)
18
HD-5
NS4-224, NS6-224
NS4-224W, NS6-224W
NS4-224, NS6-224
NS4-224W, NS6-224W
HB-5
SLR-835H/-835HW
Photoelectric (8-35V)
w/thermal
HB-5
18
18
Photoelectric w/heat
SLR-835B-2/-2W
HD-6
N/A
N/A
SLR-835BH-2/-2W
HD-6
Photoelectric (8-35V)
w/thermal (baseless)
N/A
N/A
18
SIJ-24
HD-3
NS4-224, NS6-224
HB-5
25
DCD-135/-190
HD-3
NS4-224, NS6-224
HB-5
25
DFE-135/-190
N/A
HSC-224L
HB-62
25
SLV-24/-24N/-24V
HD-3
Photoelectric
NS4-224, NS6-224
NS4-224W, NS6-224W
HB-5
25
Ionization
Heat Fixed Temp/Rate of Rise
EXPLODED VIEW
3-4: CLASS A
OPTIONAL BRANCH CIRCUIT TO
NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
S
SC
U.L. LISTED
COMPATIBLE SC
FIRE CONTROL S
PANEL
CLASS A
DCP-CZM
TB1
IN+
IN-
S
24V-
OUT+
24V+
TB2
SC
UL LISTED
+
1481 24VDC
REGULATED
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP.
JP2
OUT-
MAX. 25 CONVENTIONAL
DETECTORS
24-
24V+
CONVENTIONAL
ZONE MODULE
NEXT DEVICE
EXPLODED VIEW
1-2: CLASS B
SC
U.L. LISTED
COMPATIBLE SC
FIRE CONTROL
S
PANEL
UL LISTED
+
1481 24VDC
REGULATED
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP.
CLASS B
DCP-CZM
TB1
TB2
SC
S
INOUT+
24V+
OUT-
MAX. 25 CONVENTIONAL
DETECTORS
24-
24V+
NEXT DEVICE
IN+
24V-
JP2
CONVENTIONAL
ZONE MODULE
EB
Features:
True Multiplex 6 Channel Distributed Audio
Integrated Fire Phone, Area of Rescue
and Fan & Damper Control capability
Modular System - components added as needed
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Fast RS-485 Communication Protocol
Fully Supervised
Easy Installation and Operation
Natural Sound Voice Recordings
Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Works with Analog/Addressable and
Microprocessor based Fire Alarm Panels.
3 Minute Message Restart on Microphone Key
Made in the USA.
VoiceNET
High Rise Voice
Evacuation System
SYSTEM
RESET
PAGE
ALL-CALL
FAULT
SILENCE
PAGING
CONTROL
277-96-E
6911-1446:103
Description:
LISTED
#S5661
System Configuration:
714.522.2246
www.hochiki.com
FNV-DP
Distributed Panel
Voice Evacuation
Speaker Circuits
#18 AWG
F
I
R
E
F
I
R
E
Hochiki VoiceNET
True-Multiplex
System
Capabilities
F
I
R
E
F
I
R
E
TB1
TB2
TB1
TB2
TB3
TB3
FNV-25/50/100
FNV-25/50/100
Fire
Phone
Phone
NetComm Loop:
-Twisted Pair, Category 5
-4,000 Feet between panels
-50,000 Feet Total System Loop
-Data and 6 Audio Channels Simultaneously
-High Speed RS-485 Communications
-Style 4 or Style 7 Field Selectable
FNV-DP
Distributed Panel
Voice Evacuation
Speaker Circuits
F
I
R
E
F
I
R
E
FNV-MP
Master Panel
F
I
R
E
PAGING
CONTROL
F
I
R
E
TB1
TB2
TB3
TB1
TB2
TB3
Fire Phone
Fire
FNV-25/50/100
FNV-25/50/100
Fire
Phone
Phone
Hochiki VoiceNET
High Rise Multiplex
11 Floor Typical Riser Diagram
S
11th Floor
S
P
10th Floor
AR
S
P
CM
9th Floor
FNV-DP
AR
S
P
8th Floor
AR
S
P
7th Floor
AR
S
P
6th Floor
AR
S
P
5th Floor
CM
FNV-DP
S
P
4th Floor
AR
AR
S
P
3rd Floor
AR
S
P
RS 485
DATA LOOP
2nd Floor
AR
S
P
FNV-MP
1st Floor
FNV-DP
S
P
Basement
AR
S
P
Speaker, Speaker/Strobe
AR
Engineering Specifications
Hochiki VoiceNET High Rise
The voice evacuation system shall be Hochiki Series VoiceNET FNV High Rise or approved
equal.
The VoiceNET FNV system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a highspeed communication bus and have the capacity for 6 channels of audio and data on a single
pair of wires. The field wiring for the communication bus may be configured for either Style "4"
or Style "7" supervision. The system shall have the capacity for Fire Fighters Phone, Area-ofRescue communication and also have the capacity for Fan & Damper control with monitored
feedback. The system shall have a minimum capacity of 2028 monitor and control points.
The Master Panel shall contain an integral microphone, dual channel digital message repeater,
(DMR) and digital tone generator, 120 VAC power supply, and battery charger. The system
shall be modular in design, and shall be expandable such that additional system control points
may be configured. The system shall include integral self-diagnostic routines that shall
continually monitor system status, and shall indicate the precise type of trouble conditions
should they occur in the system. A trouble condition within the system shall cause a trouble
indication to be transmitted to the FACP.
Distributed panels shall provide a minimum of 4 Class "B" speaker circuits, expandable to
sixteen total. Alternately, panel may be configured for 4 Class "A" speaker circuits, up to 8 total.
Panel may be configured for 1 to 8 amplifiers. Panel must provide up to 6 simultaneous audio
channels, up to 8 Fire Phone circuits, up to 4 Area of Refuge circuits and up to two
Control/Monitor loops. Amplifiers will contain their own power supplies, battery chargers and
provide auxiliary power for other components. Speaker circuits shall be supervised for short
and open circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.
System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of an
alarm signal and evacuation message to the appropriate area. Non-Alarm areas may receive
alert tones and messages as required or activated by the FACP.
The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.
To prevent unauthorized tampering, the voice evacuation system shall disable the microphone
if the microphone is keyed continuously for 3 minutes or more. Systems that do not have this
feature shall not be acceptable.
Features:
True Multiplex 6 Channel Distributed Audio
Integrated Fire Phone, Area of Rescue
and Fan & Damper Control capability
Modular System - components added as needed
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Fast RS-485 Communication Protocol
Fully Supervised
Easy Installation and Operation
Natural Sound Voice Recordings
Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Works with Analog/Addressable and
Microprocessor based Fire Alarm Panels.
3 Minute Message Restart on Microphone Key
Made in the USA.
FNV-MP
High Rise Voice Evacuation System
Master Panel
SYSTEM
RESET
PAGE
ALL-CALL
FAULT
SILENCE
PAGING
CONTROL
Description:
The Hochiki FNV High Rise Evacuation System
operates in conjunction with the Fire Alarm Control
Panel (FACP) in a building to provide automatic
response to life safety emergencies.
The Hochiki FNV includes all necessary features
to provide an effective voice evacuation system.
The Hochiki FNV can be custom configured to
satisfy the needs of any high rise application.
Fire department authorities can easily take
command of evacuation or relocation procedures
and emergencies. Building management and fire
brigades can monitor and control emergency
response even before the professionals arrive
The FNV system includes capacity for 6 channels
of simultaneous audio. This provides for
evacuation, stay-in-place, or other public address
announcements and automatic messages.
Fire Fighter Phones or Warden Stations may be
included as required. Area-of-Rescue stations can
reassure handicapped occupants that help is on
the way. Smoke control, stair pressurization, and
HVAC shutdown can be completely automatic,
unless controlled manually by management or fire
authorities.
System Configuration:
Basic System Includes:
Master Panel (FNV-MP)
Master Mic Control
16 Switch Control points
Dual Channel DMR
High Speed communication loop
Optional
Integrated Master Fire Phone
Area-of-Rescue
Fan and Damper system control
Maximum System Configuration
Up to 1000 monitor and control points
LISTED
714.522.2246
www.hochiki.com
FNV MP64/P
Master Panel
Ribbon Cable Connection Detail
MMC
20 Pin Ribbon
1
2
3
J1
TB1
MFP
SLC
2
TB1
TB2
P3
P4
SLC
1
P2
P5
P5
P2
DCC
ASC
34 Pin Ribbon
P1
P2
SLC
4
SLC
3
10 Pin Ribbon
P1
34 Pin Ribbon
34 Pin Ribbon
1 2 3
TB2
TB3
TB4
TB5
P3
SSC
1
2
TB3
M
F
I
PWR-2A
TB1
TB2
I/O
Card
TB1
1 2 3
IOI
Components mounted to
back plate inside of cabinet.
Components mounted on hinged front panel.
Connectors shown are on the back of the
components.
In the Master Panel system components are mounted to a removable back plate. The door and front panel are
removable. This enables field wiring to be installed cleanly.
Connections to the User Interface components ( Switch/LED banks, Mic/System control and Master Fire Phone)
is accomplished with ribbon cables. The front panel mounts separately on a continuous hinge so once installed
the access for system programming is easily accommodated.
NetCom Bus
(Supervised)
*A - Optional wiring for
Style 7 supervision
1
2
3
P3
1 2 3 4
TB1
P5
TB4
ASC
P5
P4
P1
TB1
TB2
P3
P2
TB6
1 2 3 4
DCC
J1
TB5
1 2 3 4
P2
1
2
3
1 2 3 4
TB3
1 2 3 4
P2
MFP
1 2 3 4
TB2
TB1
TB2
P3
P1
1 2 3 4
TB1
P4
J1
LED1
TB7
DCC
P4
P2
MBR
LED1 LED2 LED3
P1
TB3
TB4
TB5
P1
TB9
P3
TB3
TB4
TB5
DISTRIBUTED PANEL
MASTER PANEL
1
2
3
P3
TB1
P5
TB4
ASC
P4
P5
P1
J1
TB1
TB2
P3
TB5
P2
TB6
1 2 3 4
DCC
1
2
3
1 2 3 4
TB3
1 2 3 4
P2
MFP
1 2 3 4
TB2
1 2 3 4
P2
1 2 3 4
TB1
TB1
TB2
P3
P1
1 2 3 4
P4
J1
LED1
TB7
DCC
P4
P2
MBR
LED1 LED2 LED3
P1
MASTER PANEL
TB3
TB4
TB5
TB9
P3
DISTRIBUTED PANEL
P1
TB3
TB4
TB5
FNV-MP16/P
FNV-MP32/P
FNV-MP48/P
FNV-MP64/P
FNV-MP80/P
FNV-MP96/P
Technical Characteristics:
Primary Power: 120 VAC
24 VDC Battery Power
Electrical Ratings:All Circuits @ 24VDC.
Master Panel
DCC
ASC
MFP
SSC
SLC
MMC
IOI
Standby
80 mA
30 mA
10 mA
25 mA
6 mA
45 mA
20 mA
Alarm
80 mA
30 mA
10 mA
25 mA
6 mA
45 mA
20 mA
14.5 x 27 x 4 whd
Charcoal Greystandard
Redoptional
Features:
FNV-DP
High Rise Voice Evacuation System
Distributed Panel
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
TB1
TB2
TB3
TB4
1
2
3
J1
TB1
TB2
1 2 3 4
TB5
P3
1 2 3 4
P2
TB6
DCC
DCC
1 2 3 4
P4
TB7
8 B
AMI
1
MBK
MBR
P1
TB8
4 A
TB1
TB1
1
TB2 11
J1
1 TB3
2
3
4
YEL
5
6
7 GRN
8
RED
MESSAGE
GAIN
Description:
J2
FAULT
1 2 3
NORMAL
10
9
8
7
6
5
4
3
2
1
ALARM
P2
MIC
GAIN
MESSAGE
GAIN
FNV-25E
J2
FAULT
1 2 3
NORMAL
10
9
8
7
6
5
4
3
2
1
ALARM
P2
MIC
GAIN
FNV-25E
SN1
TB2 11
J1
1 TB3
2
3
4
YEL
5
6
7 GRN
8
RED
SN1
S1
S1
System Configuration:
Fire department authorities can easily take
command of evacuation or relocation procedures
and emergencies. Building management and fire
brigades can monitor and control emergency
response even before the professionals arrive
The FNV system includes capacity for 6 channels
of simultaneous audio. This provides for
evacuation, stay-in-place, or other public address
announcements and automatic messages.
Fire Fighter Phones or Warden Stations may be
included as required. Area-of-Rescue stations can
reassure handicapped occupants that help is on
the way. Smoke control, stair pressurization, and
HVAC shutdown can be completely automatic,
unless controlled manually by management or fire
authorities.
LISTED
714.522.2246
www.hochiki.com
FNV
Distributed Panel
Connection Detail
Speaker Circuits
10K
EOLR
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
FPI
P3
1 2 3 4
10K
EOLR
AMI
MBK
1 2 3 4
P10
P2
P14
P15
P1
DCC
MBR
TB3
1234
P1
TB8
TB9
TB11
Set EOLR
TB1
TB1
1
TB2 11
J1
1 TB3
2
3
4
5
YEL
6
7 GRN
8
RED
MESSAGE
GAIN
J2
FAULT
1 2 3
NORMAL
10
9
8
7
6
5
4
3
2
1
ALARM
P2
MIC
GAIN
1 TB3
2
3
4
5
YEL
6
7 GRN
8
RED
MESSAGE
GAIN
J2
FAULT
1 2 3
NORMAL
P2
MIC
GAIN
10 PIN RIBBON
SN1
S1
10
9
8
7
6
5
4
3
2
1
ALARM
FNV-25E
SN1
S1
TB2 11
J1
FNV-25E
10 PIN RIBBON
10 PIN RIBBON
10 PIN RIBBONS
TO MBR J7
MBR J7
FPI
AMI
Each FNV-DP panel may
have up to 4 FPI cards for
a max. of 16 phone circuits.
F
I
R
E
F
I
R
E
E
O
L
F
I
R
E
1 2 3 4
TB1
1 2 3 4
TB2
1 2 3 4
TB3
F
I
R
E
F
I
R
E
F
I
R
E
EOLR
E
O
L
EOLR
EOLR
1 2 3 4
TB4
1 2 3 4
1 2 3 4
F
I
R
E
F
I
R
E
1 2 3 4
F
I
R
E
F
I
R
E
TB5
TB6
1 2 3 4
TB7
MBR
EOL
1 2 3 4
TB1
1 2 3 4
TB8
AMI
MBK#1
MBK#2
TB5
1 2 3 4
TB2
1 2 3 4
TB3
EOL
1 2 3 4
TB4
FNV-DPS25/P
FNV-DPS50/P
FNV-DPS100/P
FNV-DP25
FNV-DP50
FNV-DP100
FNV-DP25/P
FNV-DP50/P
FNV-DP100/P
Included with basic panel, additional cards give the ability to control
multiple modules or accommodate full 3 channel operation
Technical Characteristics:
Primary Power: 120 VAC
24 VDC Battery Power
Electrical Ratings: All Circuits @ 24VDC.
Distributed Panel
Standby
55 mA
DCC
10 mA
MBR
10 mA
AMI
13 mA
FPI
Alarm
55 mA
55 mA
10 mA
13 mA
14.5 x 27 x 4 whd
Charcoal Greystd Redoptional
Description:
VoiceNet
Fire Phone Equipment
FNV-FJ
Ordering Information:
Model Number
FNV-FJ
Description
Telephone Jack
FNV-FH
FNV-FH
Portable Handset
Color - Red
(6 mount in FNV-TC cabinet)
FNV-TC
Telephone Cabinet
Holds 6 FNV-FH Portable Handset
Cabinet: Charcoal Gray - std. -R Red
(Surface/Semi-Flush Mount / Key Lock
27 x 14-1/2 x 4 h-w-d)
FNV-FS
FNV-WS
FNV-TC
FNV-FS
FNV-WS
Warden Station
Armored cable / Thumb Turn Latch
Cabinet: Red
(Surface/Semi-Flush Mount
12-3/4 x 7-1/4 x 3-3/4 h-w-d)
LISTED
714.522.2246
www.hochiki.com
10K 1/2W
EOLR
Fire Phone
Handset
Jack
Fire Phone
Handset
Jack
10K 1/2W
EOLR
Fire Phone
Handset
Jack
Fire Phone
Handset
Jack
10K 1/2W
EOLR
Fire Phone
Handset
Jack
Fire Phone
Handset
Jack
10K 1/2W
EOLR
Fire Phone
Handset
Jack
Fire Phone
Handset
Jack
10K 1/2W
EOLR
To Additional
Fire Phone Circuits
(not shown)
Fire Phone
Handset
Jack
Fire Phone
Handset
Jack
1 2 3 4
1 2 3 4
1 2 3 4
TB1
TB2
TB3
1 2 3 4
TB6
1 2 3 4
Fire
Phone
Loops
TB
TB5
1 2 3 4
FPO
1 2
TB7
(Supervised)
MBR
/
10 Pin Ribbon Cable
FPI
Cards plug into slots
available on MBR
First FPI allows 4 Fire Phone
Circuits off of MBR. Adding 2nd
FPI and an FPO allows 4
additional Fire Phone Circuits
(16 circuits max. in any FNV-DP)
Features:
True Multiplex 6 Channel Distributed Audio
Integrated Fire Phone, Area of Rescue
and Fan & Damper Control capability
Modular System - components added as needed
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Fast RS-485 Communication Protocol
Fully Supervised
Easy Installation and Operation
Natural Sound Voice Recordings
Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Works with Analog/Addressable and
Microprocessor based Fire Alarm Panels.
3 Minute Message Restart on Microphone Key
Made in the USA.
VoiceNET
High Rise Voice
Evacuation System
SYSTEM
RESET
PAGE
ALL-CALL
FAULT
SILENCE
PAGING
CONTROL
277-96-E
6911-1446:103
Description:
LISTED
#S5661
System Configuration:
714.522.2246
www.hochiki.com
FNV-DP
Distributed Panel
Voice Evacuation
Speaker Circuits
#18 AWG
F
I
R
E
F
I
R
E
Hochiki VoiceNET
True-Multiplex
System
Capabilities
F
I
R
E
F
I
R
E
TB1
TB2
TB1
TB2
TB3
TB3
FNV-25/50/100
FNV-25/50/100
Fire
Phone
Phone
NetComm Loop:
-Twisted Pair, Category 5
-4,000 Feet between panels
-50,000 Feet Total System Loop
-Data and 6 Audio Channels Simultaneously
-High Speed RS-485 Communications
-Style 4 or Style 7 Field Selectable
FNV-DP
Distributed Panel
Voice Evacuation
Speaker Circuits
F
I
R
E
F
I
R
E
FNV-MP
Master Panel
F
I
R
E
PAGING
CONTROL
F
I
R
E
TB1
TB2
TB3
TB1
TB2
TB3
Fire Phone
Fire
FNV-25/50/100
FNV-25/50/100
Fire
Phone
Phone
Hochiki VoiceNET
High Rise Multiplex
11 Floor Typical Riser Diagram
S
11th Floor
S
P
10th Floor
AR
S
P
CM
9th Floor
FNV-DP
AR
S
P
8th Floor
AR
S
P
7th Floor
AR
S
P
6th Floor
AR
S
P
5th Floor
CM
FNV-DP
S
P
4th Floor
AR
AR
S
P
3rd Floor
AR
S
P
RS 485
DATA LOOP
2nd Floor
AR
S
P
FNV-MP
1st Floor
FNV-DP
S
P
Basement
AR
S
P
Speaker, Speaker/Strobe
AR
Engineering Specifications
Hochiki VoiceNET High Rise
The voice evacuation system shall be Hochiki Series VoiceNET FNV High Rise or approved
equal.
The VoiceNET FNV system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a highspeed communication bus and have the capacity for 6 channels of audio and data on a single
pair of wires. The field wiring for the communication bus may be configured for either Style "4"
or Style "7" supervision. The system shall have the capacity for Fire Fighters Phone, Area-ofRescue communication and also have the capacity for Fan & Damper control with monitored
feedback. The system shall have a minimum capacity of 2028 monitor and control points.
The Master Panel shall contain an integral microphone, dual channel digital message repeater,
(DMR) and digital tone generator, 120 VAC power supply, and battery charger. The system
shall be modular in design, and shall be expandable such that additional system control points
may be configured. The system shall include integral self-diagnostic routines that shall
continually monitor system status, and shall indicate the precise type of trouble conditions
should they occur in the system. A trouble condition within the system shall cause a trouble
indication to be transmitted to the FACP.
Distributed panels shall provide a minimum of 4 Class "B" speaker circuits, expandable to
sixteen total. Alternately, panel may be configured for 4 Class "A" speaker circuits, up to 8 total.
Panel may be configured for 1 to 8 amplifiers. Panel must provide up to 6 simultaneous audio
channels, up to 8 Fire Phone circuits, up to 4 Area of Refuge circuits and up to two
Control/Monitor loops. Amplifiers will contain their own power supplies, battery chargers and
provide auxiliary power for other components. Speaker circuits shall be supervised for short
and open circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.
System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of an
alarm signal and evacuation message to the appropriate area. Non-Alarm areas may receive
alert tones and messages as required or activated by the FACP.
The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.
To prevent unauthorized tampering, the voice evacuation system shall disable the microphone
if the microphone is keyed continuously for 3 minutes or more. Systems that do not have this
feature shall not be acceptable.
ADDRESS SETTING:
1. Install sensor onto programmer, ensuring that
sensor protrusions align with programmer grooves.
2. Press the left gray button to switch programmer on.
A battery check message will appear followed by
the device's address (Unprogrammed sensors will
read address 127).
STANDARD FEATURES
Compact unit
Easy to use
Provides address setting and reading
Can be used on both sensors and modules
Has the diagnostic ability to display the
analog value
SPECIFICATIONS
Rated Voltage:
9 VDC
Battery:
9 VDC
Weight:
0.34 lbs
Length:
6 1/4"
Color:
White
PRODUCT PARTS
9 Volt Battery
Remote Programming Cables
Continued on back
9/2003
Remote Programming
Jack
Programming Buttons
Display
PROGRAMMING BUTTONS:
LEFT GRAY BUTTON
RIGHT GRAY BUTTON
RED BUTTON
TESTING A SENSOR
Note: Ionization sensors require a 30 second stabilization period before analog value reading should be taken.
1. Install the sensor and power up programmer as previously described on page 1
2. Press the Red button. An A will appear on the display followed by the analog value. The
value will be continuously updated for three minutes
3. The ALG photoelectric sensor should have a value displayed of between 56-63. The AIE
ionization sensor should have a value displayed of between 52-73.
Values out of these ranges indicate that the sensor chamber has become contaminated. Refer to technical
bulletin HA-96 for proper servicing instructions or return sensor to factory for servicing.
DISPLAY MESSAGES:
bAt- On upon power up (battery check). Also on when battery is low. Low battery good for up to 3,000
address setting operation.
E0 - Attempting to set an address beyond 127.
E1 - Attempting to program an address with no device connected.
E2 - Can not find device after power up.
E3 - Invalid sensor response.
E4 - Can not find the device program.
E5 - Device read error.
E6 - Fail during Analog value reading
Hochiki America Corporation TCH-B100 Hand-Held Programmer
OPERATION
STANDARD FEATURES
Preparation
1. Remove the TSE-A100 from its carrying case.
2. Unscrew the combustion chamber from the
bottom of the TSE-A100.
3. Unscrew the punk stick holder retainer from
the combustion chamber.
4. Insert a punk stick into the punk stick holder in
the combustion chamber.
5. Light the punk stick with a flame.
6. Reassemble the combustion chamber.
7. Screw the combustion chamber back into the
bottom of the TSE-A100
8. Extend the telescopic pole of the TSE-A100 to
a length which enables you to reach the
detector you wish to test.
Testing a Detector
Once you have prepared the TSE-A100, follow the steps
in this section to test smoke detectors.
SPECIFICATIONS
Continued on back
Rated Voltage
Battery
Combustion Material
Weight
Length
Color
3 VDC
2 - "D" Batteries
Punk Stick
(7 mm diameter, 150 mm long)
5 Lbs.
5.25 to 14.1 feet
Brown
PRODUCT PARTS
TSE-A100 Self-Contained Smoke Generator
Punk Stick (Part No. TSE-P100)
01/2002
OPERATION,
continued
NOTE
1. Use only the filter and combustion material
specified.
2. Check battery capacity before use to assure
efficient operation.
3. Remove batteries before long-period storage.
Telescopic Pole
Combustion Chamber
Punk Stick
Instruction Label
NSRT / NSTT
SMOKE DETECTOR REMOVAL TOOL / TESTER
STANDARD FEATURES
NSRT
Combination removal tool/outer cover removal tool
for AIE, ALG, SIJ, and SLR-24/-835 series sensors/
detectors.
Choose either a Hand held or 15 stainless steel
extension pole with easy grip black handle.
NSTT
NSRT HEAD
SPECIFICATIONS
Detector Tester/Removal Tool
Dimensions
NSRT HEAD: 4.0" D x 2.0" H
NSTT HEAD: 4.0" D x 1.5" H
Material
Highly durable PVC
molded plastic
Color
Black - provides visible contrast
Alignment
NSRT HEAD:
One side for arrow labels for
easy visibility, one side for
removal from base.
NSTT HEAD:
One side for sensitivity testing.
NSTT HEAD
Extension Pole
Dimensions
Material
NSTT-A100 WITH 15' POLE
(COMPLETE)
F044
02/2005
APPLICATION
NSRT-A100
The Hochiki America NSRT-A100 will enable the user to easily remove and replace the ALG, AIE, SLR, and SIJ series
sensors/ detectors from their mounting bases. Also, the NSRT-A100 is designed to remove the outer covers of the
ALG, AIE and SLR series sensors/detectors
NSTT-A100
The SIJ-24 and SLR-24/-835 series detectors, manufactured with magnetically activated dual reed switches for sensitivity
testing, can be sensitivity tested with the NSTT-A100. This meets the requirements of a UL listed calibrated test
without the use of combustion materials.
The NSTT-A100 is in compliance with the test requirements outlined in the NFPA 72 Inspection, Testing and Maintenance,
Chapter 10.
APPLICATION
X187 and S187 are used to program the FireNET family
of panels.
SPECIFICATIONS
X187/S187:
10 feet (3 meters)
Left Connector:
Right Connector:
FN-V187 VoiceNET Serial Interface Cable is used to
interconnect a FireNET Panel with a VoiceNET Master
Panel.
Cable Length:
FN-P187 Printer Interface cable is used to connect a
serial printer to the FireNET family of panels.
Cable Type:
X187:
Non-Jacketed Version
S187:
Jacketed Version
Continued on back
F092
02/2010
SPECIFICATIONS
SPECIFICATIONS
FN-V187:
FN-P187:
Cable Type:
Cable Type:
Cable Length:
10 feet (3 meters)
Cable Length:
10 feet (3 meters)
Left Connector:
Right Connector:
WIRING DIAGRAMS:
PROGRAMMING INTERFACE:
DESCRIPTION
PRODUCT LISTINGS
Continued on back.
Find latest revision at www.hochiki.com
F0117
04/2011
SPECIFICATIONS
Supply Voltage
Power Supply DC Rating
Number of Zones
NAC Outputs
Relay Outputs
Display
Charger Current
Battery
Operating Temperature
Operating Humidity
Color
Dimension
Weight
DESCRIPTION
DETECTORS
SLV-24V
SLV-24N
SLR-24H
DSC-EA
DCD-135
DCD-190
20
20
20
20
20
20
NS6-224
NS4-224
NS6-100
NS4-100
HPS-SAK/HPS-DAH
HPS-SAH/HPS-DAK
BASES
20
20
20
20
PULL STATION
25
RELEASING ACCESORY
0400-02590
HCA-RC
3001000
131-035
Hochiki America Corporation HCA Series CONVENTIONAL FIRE ALARM CONTROL PANEL
1
1
1
1
DESCRIPTION
Continued on back.
Specifications subject to change without notice.
F0094
04/2010
SPECIFICATIONS
Supply Voltage
Power Supply DC Rating
Mains Supply Fuse
Dimensions
Weight
Color
Material
Max. Battery Size
Fault Contact Rating
Local Fire Contact Rating
Fire Contact Rating
NAC Output Rating
Detection Zone Current
Detection Zone
End of line resistor
Sounder Output
Stand by Current
Alarm Current
End of line resistor
Cable Capacity
Operating Humidity
Operating Temperature
DESCRIPTION
DETECTORS
SLR-24V/-24VN
SLR-24H
SLR-835H/ -835HW
SLR-835/-835W
SLR-835-BH-2W
SIJ-24
DFE-135
DFE-190
DCD-135
DCD-190
DSC-EA
SLV-24/-24N
25
25
25
25
25
25
25
25
25
25
25
25
NS6-224
NS4-224
NS4-100
NS6-100
HPS-SAK/HPS-DAH
HPS-SAH/HPS-DAK
PPE-2(JE)
32
Call Point
32
BASES
25
25
25
25
PULL STATION
BEAM DETECTORS
SPC-24
SRA-24
Beam detector
Reflective beam detector
8
5
NOTIFICATION DEVICES
GENTEX
GES24-1575WR
GEC3-24WR
WGEC-2475WR
AMSECO/POTTER
SH24W-153075R
SH24-75110R
SL24W-153075R
MBA-6
HOCHIKI
FBB-1501
Horn/Strobe
Horn/Strobe
Horn/Strobe
8
8
10
Horn/Strobe
Horn/Strobe
Horn/Strobe
6" Motor Driven Bell, 24VDC
8
8
8
4
STANDARD FEATURES
SPECIFICATIONS
Primary Input Power 120 volts, 60 Hz, 1 Amps
(Optional 220 - 240VAC)
Indicating Current
24VDC unfiltered, 5Amps
Standby Power
24VDC standby batteries
Charging Capability 10 24 AH batteries
Dimensions
26"H x 14 1/2"W x 4 1/2" D
Specifications subject to change without notice.
PRODUCT LISTINGS
S6468
California
State Fire
Marshal
7165-0410:154
Continued on back.
Find latest revision at www.hochiki.com
F0067
08/2007
ORDERING INFORMATION
Model
Description
Fire Alarm Control Panel
HCP-1008E
HCP-1008ES
HFA-1024TR
HRTI-1
Adder Modules
HDM-1008
HSGM-1004
Four Class A/B (Style Z/Y) Indicating Circuit Module (Rated at 1.7 Amps per circuit).
HRM-1008
Eight Relay Circuit Module comes with eight Form C relays (Rated for 28 VDC @ 1 Amp.
max. per relay)
Auxiliary Modules
HDACT-100U
HDACT-100
HPR-100
Remote Annunciator
HRAM-1032
Main Annunciator Chassis comes with common control features, indicators and 32
bi-colored LEDs
HBB-1001
HDM-204
FOUR INITIATING CIRCUIT & TWO INDICATING
CIRCUIT MODULE
The HDM-204 Module provides the HCP-204E Fire Alarm
Control Panel with up to 4 Class B (Style B) or 2 Class
A (Style D) Initiating Circuits. In addition it provides up
to 2 Class A/B (Style Z/Y) Indicating Circuits which are
rated for 1.7 Amps each. Each of the indicating circuits
can be configured for silenceable or non silenceable. In
addition each circuit comes with an individual trouble
indicator. All circuits are power limited for use with limited
energy cable. The HDM-204 consists of a PC board
which mounts at the bottom of the chassis. The PC
board is connected via cables to the board on the main
chassis.
HRM-204
AUXILIARY QUAD RELAY MODULE
The HRM-204 Auxiliary Relay Module provides the HCP200 Series with four configurable auxiliary relays. The
relays can be configured for either relay per zone,
Common Alarm relay(s) or Common Supervisory relay(s).
Each relay is rated for 28 VDC @ 1 Amp max. The
module is mounted on the top of any detection module,
with hardware provided for the module. Requires one
HCH-429 Accessory Mounting Plate when HRM-204 is
mounted in the HCP-202 or HCP-204.
PRODUCT LISTINGS
California
State Fire
Marshal
7165-0410:152
S6468
Specifications subject to change without notice.
Continued on back.
Find latest revision at www.hochiki.com
F0054
04/2010
HRM-208
EIGHT RELAY MODULE
The HRM-208 Auxiliary Relay Module provides the HCP200 Series with eight configurable auxiliary relays. The
relays can be configured for either relay per zone,
Common Alarm relay(s) or Common Supervisory relay(s).
Each relay is rated for 28 VDC @ 1 Amp max. The
module is mounted on the top of any detection module,
with hardware provided for the module. Requires one
HCH-429 Accessory Mounting Plate when an HRM-208
is mounted in the HCP-202 or HCP-204.
HPR-100
POLARITY REVERSAL & CITY TIE MODULE
The HPR-100 Polarity Reversal & City Tie Module allows
connection to two different types of monitoring systems.
The City Tie provides an output of 24 VDC at 210 mA
max. The module supervises the City Tie connection
and will provide a system trouble if not connected. A
terminating resistor is supplied with the module. The
Polarity Reversal provides a 24 VDC output for normal
condition and a polarity reverse 24 VDC output for alarm.
The module is also capable of transmitting a system
trouble Zero Volts. This option is jumper selectable.
The output current is limited to 8 mA.
HDACT-100
DIGITAL ALARM COMMUNICATOR TRANSMITTER/
DIALER MODULE
The HDACT-100 Digital Alarm Communicator Transmitter/
Dialer Module allows the HCP-200 Fire Alarm Control
Panels to use one or two phone lines to call a Central
Station and report a local Alarm, Trouble or Supervisory
condition. Requiring two supervised telephone lines, the
HDACT-100 can be programmed to use the Security
Industry Association (SIA) Digital Communication
Standard (DCS) and Ademco Contact ID protocols. The
HDACT-100 is powered by the HCP-200 Fire Alarm
Control Panels and communicates with them via an RS485 Interface. The HCFG-100 Configuration and
Diagnostics Tool is required to program the HDACT-100.
STANDARD FEATURES
PRODUCT LISTINGS
California
State Fire
Marshal
7120-0410:153
S5694
Continued on back.
F0048
04/2010
INSTALLATION DIAGRAM
Standard Electrical
Box
Secure
with
#6-32
Screws
Paper Label
Wall
Clear Lexan
Std
Elec.
Box
Wall
Surface Mount
Std
Elec.
Box
Flush Mount
24 VDC
OUTPUT
24 VDC
INPUT
RS-485
OUTPUT
24 VDC POWER TO
NEXT ANNUNCIATOR
RS-485
INPUT
+
NOTE: ALL CIRCUITS ARE POWER LIMITED AND
MUST USE TYPE FPL, FPLR, OR FPLP POWER
LIMITED CABLE.
HRAM-1032
HRAX-1048
STANDARD FEATURES
SPECIFICATIONS
HBB-1001 Enclosure
HBB-1002 Enclosure
HBB-1003 Enclosure
PRODUCT LISTINGS
9H x 13W x 1D
16H x 13W x 1D
23H x 13W x 1D
06/2003
HEIGHT
H (IN.)
MOUNTING
A(IN.)
B(IN.)
BACKBOX
HBB-1001
9.0"
9.95"
7.5"
HBB-1002
16.0"
9.95"
14.5"
HBB-1003
23.0"
9.95"
WALL
21.5"
DOOR
A
1.2"
#6-32
HEXNUTS
BB-1001 BACKBOX IS SHOWN
ANNUNCIATOR CHASSIS
ORDERING INFORMATION
Model
Modules
HRAM-1032
Description
HRAX-1048
Main Annunciator Chassis comes with Common Control Features, Indicators and 32 Bi-Colored
LEDs
Adder Annunciator Chassis comes with 48 Bi-Colored LEDs
Backboxes
HBB-1001
HBB-1002
HBB-1003
STANDARD FEATURES
Low profile, 2.0" high (with base)
2 or 4 wire base compatibility, relay bases available
Highly stable operation, RF/Transient protection
Low standby current, 45A at 24VDC
Two built-in power/alarm LEDs
Non-directional smoke chamber
Vandal resistant security locking feature
Built-in magnetic go/no go detector test feature
Removable smoke labyrinth for cleaning or
replacement
Compatible with SIJ-24 ionization detectors
Backwards compatible with Hochiki SLK/SLR-24
and SIH detectors
Highly resistant to false alarms caused by steam
SPECIFICATIONS
Light Source
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Air Velocity Range
Ambient Temperature
Color & Case Material
Sensitivity Range
Mounting
GaAlAs Infrared
Emitting Diode
17.7 - 30.0 VDC
15.0 - 33.0 VDC
42 VDC
45A @ 24 VDC
160A max. @ 24VDC
150mA max. @ 24 VDC
0-300 fpm
32F to 120F (0C to 49C)
Bone PC/ABS Blend
0.5 - 3.8%/ft
Refer to NS Conventional
Detector Base Data Sheet
OPERATION
The SLV-24 photoelectric smoke detector utilizes two
bicolored LEDs for indication of status. In a normal
standby condition the LEDs flash Green every 3
seconds. When the detector senses smoke and goes
into alarm the status LEDs will latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke
chamber. In a normal standby condition, the receiving
element receives no light from the pulsing LED light
source. In the event of a fire, smoke enters the detector
smoke chamber and light is reflected from the smoke
particles to the receiving element. The light received is
converted into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the
reference level are received within a specified period of
time, the time delay circuit triggers the SCR switch to
activate the alarm signal. The status LEDs light
continuously during the alarm period.
PRODUCT LISTINGS
3033131
California
State Fire
Marshal
7272-0410:174
S1383
Continued on back.
Find latest revision at www.hochiki.com
F0075
10/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLV-24 photoelectric
smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed
fire alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24H combination photoelectric/heat detector,
SIJ-24 ionization type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base
shall be appropriate twist-lock base NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or
complete retrofit, the SLV-24 may be used in conjunction with, or as a replacement for, Hochiki America detectors
(SLK-24, SLK-24FH and the SIH-24) on most HSB and HSC base applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby
condition the LEDs will flash Green. When the detector is actuated, the flashing LEDs will latch on Red. The detector
may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed in the detector to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
LISTED
END OF LINE
DEVICE
Resistor shown is for
example only. Not all
annunciators have in
line resistance.
NEGATIVE
NS4 SERIES
NS6 SERIES
LISTED
END OF LINE
DEVICE
COM
N/C
N/O
HSC-RELAY SERIES
N/O
N/C
COM
4-WIRE OPERATION
INITIATING
CIRCUIT
6
5
4
3
2
1
LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC
LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24
HSC-4R
HSC-4R
STANDARD FEATURES
Low profile, 2.0" high (with base)
2 or 4 wire base compatibility, relay bases available
Highly stable operation, RF/Transient protection
Low standby current, 45A at 24VDC
Two built-in power/alarm LEDs
Non-directional smoke chamber
Vandal resistant security locking feature
Built-in magnetic go/no go detector test feature
Removable smoke labyrinth for cleaning or
replacement
Compatible with SIJ-24 ionization detectors
Backwards compatible with Hochiki SLK/SLR-24V
and SIH detectors
Highly resistant to false alarms caused by steam
SPECIFICATIONS
Light Source
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Air Velocity Range
Ambient Temperature
Color & Case Material
Sensitivity Range
Mounting
GaAlAs Infrared
Emitting Diode
17.7 - 30.0 VDC
15.0 - 33.0 VDC
42 VDC
45A @ 24 VDC
160A max. @ 24VDC
150mA max. @ 24 VDC
0-4000 fpm
32F to 120F (0C to 49C)
Bone PC/ABS Blend
0.5 - 2.68%/ft
Refer to NS Conventional
Detector Base Data Sheet
OPERATION
The SLV-24V photoelectric smoke detector utilizes two
bicolored LEDs for indication of status. In a normal
standby condition the LEDs flash Green every 3
seconds. When the detector senses smoke and goes
into alarm the status LEDs will latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke
chamber. In a normal standby condition, the receiving
element receives no light from the pulsing LED light
source. In the event of a fire, smoke enters the detector
smoke chamber and light is reflected from the smoke
particles to the receiving element. The light received is
converted into an electronic signal.
Signals are processed and compared to a reference
level, and when two consecutive signals exceeding the
reference level are received within a specified period of
time, the time delay circuit triggers the SCR switch to
activate the alarm signal. The status LEDs light
continuously during the alarm period.
PRODUCT LISTINGS
3033131
California
State Fire
Marshal
7272-0410:174
S1383
Continued on back.
F0076
03/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLV-24V photoelectric
smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire
alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24H combination photoelectric/heat detector,
SIJ-24 ionization type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base
shall be appropriate twist-lock base NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or
complete retrofit, the SLV-24V may be used in conjunction with, or as a replacement for, Hochiki America detectors
(SLK-24, SLK-24FH and the SIH-24) on most HSB and HSC base applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby
condition the LEDs will flash Green. When the detector is actuated, the flashing LEDs will latch on Red. The detector
may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed in the detector to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
LISTED
END OF LINE
DEVICE
Resistor shown is for
example only. Not all
annunciators have in
line resistance.
NEGATIVE
NS4 SERIES
NS6 SERIES
LISTED
END OF LINE
DEVICE
COM
N/C
N/O
HSC-RELAY SERIES
N/O
N/C
4-WIRE OPERATION
COM
INITIATING
CIRCUIT
6
5
4
3
2
1
LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC
LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24
HSC-4R
HSC-4R
OPERATION
STANDARD FEATURES
Low profile, 2.0" high (with base)
Highly stable operation, RF/Transient protection
Low standby current, 45A at 24VDC
Two built-in power/alarm LEDs
Non-directional smoke chamber
Built-in magnetic go/no go detector test feature
Removable smoke labyrinth for cleaning or
replacement
Highly resistant to false alarms caused by steam
SPECIFICATIONS
Light Source
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Air Velocity Range
Ambient Temperature
Color & Case Material
Sensitivity Range
Mounting
GaAlAs Infrared
Light Emitting Diode
17.7 - 30.0 VDC
15.0 - 33.0 VDC
42 VDC
45A @ 24 VDC
160A max. @ 24VDC
150mA max. @ 24 VDC
0-4000 fpm
32F to 120F (0C to 49C)
Bone PC/ABS Blend
0.5 - 2.68%/ft
Refer to NS Conventional
Detector Base Data Sheet
PRODUCT LISTINGS
California
State Fire
Marshal
7272-0410:174
S1383
Continued on back.
F0083
05/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLV-24M marine photoelectric smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL
listed fire alarm panel.
The base shall be appropriate twist-lock base NS4-220 (Marine Type) and NS6-220 (Marine Type).
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby
condition the LEDs will flash Green. When the detector is actuated, the flashing LEDs will latch on Red. The detector
may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured.
To facilitate installation, the detector shall be non-polarized. Voltage and RF/transient suppression techniques shall be
employed in the detector to minimize false alarm potential.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.
WIRING DIAGRAM
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
LISTED
END OF LINE
DEVICE
Resistor shown is for
example only. Not all
annunciators have in
line resistance.
NEGATIVE
NS4-220
NS6-220
STANDARD FEATURES
Low profile, 1.8" high (with base)
2 or 4 wire base compatibility, relay bases available
Highly stable operation, RF/Transient protection
Low standby current, 45A at 24VDC
Two built-in power/sensitivity supervision/alarm LEDs
Non-directional smoke chamber
Vandal resistant security locking feature
Built-in magnetic go/no go detector test feature
Removable smoke labyrinth for cleaning or
replacement
SPECIFICATIONS
Light Source
GaAlAs Infrared
Emitting Diode
Rated Voltage
17.7 - 30.0 VDC
Working Voltage
15.0 - 33.0 VDC
Maximum Voltage
42 VDC
Supervisory Current
45A @ 24 VDC
Surge Current
160A max. @ 24VDC
Alarm Current
150mA max. @ 24 VDC
Air Velocity Range
0-4000 fpm
Ambient Temperature
32F to 120F (0C to 49C)
Color & Case Material Bone PC/ABS Blend
Sensitivity Test Feature Automatic Sensitivity
window verification test
Mounting
Refer to NS Conventional
Detector Base Data Sheet
Specifications subject to change without notice.
OPERATION
The SLR-24V photoelectric smoke detector utilizes two
bicolored LEDs for indication of status. In a normal
standby condition the LEDs flash Green every 3 seconds. When the detector senses that its sensitivity has
drifted outside the UL listed sensitivity window the LEDs
will flash Red every 3 seconds. When the detector
senses smoke and goes into alarm the status LEDs will
latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke chamber. In a normal standby condition, the receiving element receives no light from the pulsing LED light source.
In the event of a fire, smoke enters the detector smoke
chamber and light is reflected from the smoke particles
to the receiving element. The light received is converted
into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the reference level are received within a specified period of time,
the time delay circuit triggers the SCR switch to activate
the alarm signal. The status LEDs light continuously
during the alarm period.
PRODUCT LISTINGS
1D5A1.AY
California
State Fire
Marshal
7272-0410:107
S1383
Continued on back.
Find latest revision at www.hochiki.com
F0017
10/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLR-24V photoelectric smoke detectors.
The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24H combination photoelectric/heat detector, SIJ-24 ionization
type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twist-lock base
NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLR-24V maybe used in conjunction
with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-24FH and the SIH-24) on most HSB and HSC base applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the LEDs
will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When the detector is
actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector
without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify that
it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to
minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
LISTED
END OF LINE
DEVICE
Resistor shown is for
example only. Not all
annunciators have in
line resistance.
NEGATIVE
NS4 SERIES
NS6 SERIES
LISTED
END OF LINE
DEVICE
COM
N/C
N/O
HSC-RELAY SERIES
N/O
N/C
4-WIRE OPERATION
COM
INITIATING
CIRCUIT
6
5
4
3
2
1
LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC
LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24
HSC-4R
Hochiki America Corporation SLR-24V
HSC-4R
Specifications subject to change without notice.
STANDARD FEATURES
SPECIFICATIONS
Light Source
Heat Sensor
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature
Color & Case Material
Sensitivity Test Feature
Mounting
GaAlAs Infrared
Emitting Diode
135F
17.7 - 30.0 VDC
15.0 - 33.0 VDC
42 VDC
45A @ 24 VDC
160A max. @ 24 VDC
150mA max. @ 24 VDC
32F to 120F
(0C to 49C)
Bone PC/ABS Blend
Automatic Sensitivity
window verification test
Refer to NS Conventional
Detector Base Data Sheet
OPERATION
The SLR-24H photoelectric smoke detector utilizes two
bicolored LED's for indication of status. In a normal
standby condition the LED's flash Green every 3
seconds. When the detector senses that its sensitivity
has drifted outside the UL listed sensitivity window the
LED's will flash Red every 3 seconds. When the detector
senses smoke and goes into alarm the status LED's will
latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke
chamber. In a normal standby condition, the receiving
element receives no light from the pulsing LED light
source. In the event of a fire, smoke enters the detector
smoke chamber and light is reflected from the smoke
particles to the receiving element. The light received is
converted into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the
reference level are received within a specified period of
time, the time delay circuit triggers the SCR switch to
activate the alarm signal. The status LED's light
continuously during the alarm period.
PRODUCT LISTINGS
3006185
California
State Fire
Marshal
7272-0410:107
S1383
Continued on back.
F0015
10/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLR-24H photoelectric
smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire
alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24V photoelectric detector, SIJ-24 ionization type
smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twistlock base NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLR-24
maybe used in conjunction with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-24FH and the SIH24) on most HSB and HSC base applications.
The smoke detector shall have two flashing status LED's for visual supervision. When the detector is in standby
condition the LED's will flash Green. When the detector is outside the UL listed sensitivity window the LED's will flash
Red. When the detector is actuated, the flashing LED's will latch on Red. The detector may be reset by actuating the
control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.
4-WIRE OPERATION
(+)
INITIATING
CIRCUIT
LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
(-)
H1
H2
YEL
ORN
PUR
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC
(+)
LISTED
END OF LINE
RELAY
(-)
HSC-4R
HSC-4R
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL
(+)
LISTED
END OF LINE
DEVICE
(-)
PANEL
POWER
SUPPLY
(-)
NEGATIVE
NS4 SERIES
NS6
SLR-835
STANDARD FEATURES
SPECIFICATIONS
Light Source
Operating Voltage
Working Voltage
Wave Form
Heat Sensor
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature
Compatibility Identifier
Color & Case Material
Sensitivity Test Feature
Ordering Codes
White
Bone
Dimensions
Mounting
SLR-835H
APPLICATION
The HOCHIKI America SLR-835/-835H can be used in all
areas where photoelectric smoke detectors are required. It is
suited for fires ranging from smoldering to flaming fires.
NS4 Series, NS6 Series, HSC-4R or HSC-(X)R Style bases
may be used with the SLR-835/-835H.
OPERATION
The SLR-835/-835H Photoelectric Smoke Detector utilizes
two bicolored LEDs for indication of status. In a normal
standby condition the LEDs flash green every 3 seconds.
When the detector senses that its sensitivity has drifted
outside the UL listed sensitivity window the LEDs will flash
Red every 3 seconds. When the detector senses smoke
and goes into alarm the status LEDs will latch on Red.
The detector utilizes an infrared LED light source and silicon
photo diode receiving element in the smoke chamber. In a
normal standby condition, the receiving element receives
no light from the pulsing LED light source. In the event of a
fire, smoke enters the detector smoke chamber and light is
reflected from the smoke particles to the receiving element.
The light received is converted into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the reference
level are received within a specified period of time, the time
delay circuit triggers the SCR switch to activate the alarm
signal. The status LEDs light continuously during the alarm
period.
PRODUCT LISTINGS
3007144
California
State Fire
Marshal
7272-0410:107
S1383
Continued on back.
F0024
10/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLR-835 Photoelectric smoke
detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
When the supply power is 24VDC, the base shall permit direct interchange with Hochiki America SLR-24H combination
photoelectric/heat detector, SLR-24 photoelectric smoke detector, SIJ-24 ionization type smoke detector and DCD-135/190heat
detector.
The base shall be the appropriate twist-lock base NS4 Series, NS6 Series, HSC-4R, or HSC-(X)R Series. In the event of partial
or complete retrofit, the SLR-835, SLR-835H may be used in conjunction with, or as a replacement for, Hochiki America
detectors ( SLK-835H, SLK-24F, SLK-24FH and the SIH-24F) on most HSB and HSC base application.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the
LEDs will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When the detector
is actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector
without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify
that it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated on the drawing. The
locking feature shall be field removable when not required.
4-WIRE OPERATION
INITIATING
CIRCUIT
LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR
UL LISTED
POWER
SUPPLY
24VDC
LISTED
END OF LINE
RELAY
HA-EOLR-24
HSC-4R
HSC-4R
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
NEGATIVE
LISTED
END OF LINE
DEVICE
Resistor shown is for example
only. Not all annunciators have
in line resistance.
NS4 SERIES
NS6 SERIES
LISTED
END OF LINE
DEVICE
TERMINAL BLOCK USED ON
COM
N/C
N/O
HSC-RELAY SERIES
N/O
N/C
COM
6
5
4
3
2
1
HSC-(XXX)R (2-WIRE)
GRY
BLU
GRN
YEL
ORN
PUR
APPLICATION
SPECIFICATIONS
Light Source
Operating Voltage
Working Voltage
OPERATION
PRODUCT LISTINGS
3007144
Specifications subject to change without notice.
California
State Fire
Marshal
7272-0410:107
S1383
Continued on back.
F0026 10/2010
OPERATION, continued
in the comparator, and when two consecutive signals exceeding the basic level are received within a specific period of
time, the time delay circuit triggers the SCR switch to activate the alarm signal. The status LED lights continuously
during alarm period.
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans HOCHIKI America SLR-835B direct-wire photoelectric
smoke detectors. The detector shall be UL listed compatible (2-wire model) with a UL listed fire alarm panel.
The smoke detector shall have green flashing status LED's for visual supervision. When the detector is actuated, the
flashing LED's will turn red and latch on steady. The detector may be reset by actuating the control panel reset switch.
The detector shall have a sensitivity window verification feature. If the sensitivity of the detector drifts outside its
approved window the LED's will flash red to indicate an out of sensitivity condition.
The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field selectable.
It shall be possible to perform a functional test of the detector without the need of generating smoke. The method shall
simulate effects of products of combustion in the chamber to ensure testing of detector circuits.
Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.
WIRING DIAGRAMS
2-Wire Wiring Diagram
U.L. Listed
Compatible
Control
Panel
Listed
End-of-Line
Device
Listed
End-of-Line
Device
U.L. Listed
Control
Panel
U.L. Listed
Power
Supply
*24VDC
Listed
End-of-Line
Relay
12 or 24VDC
U.L. Listed
Power
Supply
*12VDC
DESCRIPTION
SPECIFICATIONS
Light Source
Voltage
Nominal
Working
Wave Form
Alarm Current
Surge Current
Average Stand-By
Current
Ambient Temperature
Sensitivity Test Feature
Automatic Sensitivity Window Verification Test
Compatibility Identifier HD-6
Heat Sensor
135 F
Order Codes
2-Wire Detector & Trim Ring
White
Bone
4-Wire Detector & Trim Ring
White
Bone
PRODUCT LISTINGS
SLR-835BH-2W
SLR-835BH-2
SLR-835BH-4W
SLR-835BH-4
3012444
California
State Fire
Marshal
7272-0410:107
S1383
Specifications subject to change without notice.
Continued on back.
Find latest revision at www.hochiki.com
F0019
10/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans HOCHIKI America SLR-835BH baseless photoelectric
smoke detectors. The combination detector head shall be UL listed compatible with an UL listed fire alarm panel.
The smoke detector shall have flashing status LED for visual supervision. When the detector is actuated, the flashing
LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch.
The detector shall have a sensitivity window verification feature.
The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field selectable.
It shall be possible to perform a functional test of the detector without the need of generating smoke. The method shall
simulate effects of products of combustion in the chamber to ensure testing of detector circuits.
Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.
WIRING DIAGRAMS
2-Wire Wiring Diagram
U.L. Listed
Compatible
Control
Panel
Listed
End-of-Line
Device
U.L. Listed
Control
Panel
U.L. Listed
Power
Supply
*24VDC
24VDC 12VDC
NO
24VDC 12VDC
NO
Listed
End-of-Line
Relay
12 or 24VDC
U.L. Listed
Power
Supply
*12VDC
STANDARD FEATURES
Choice of fixed temperature/rate-of-rise
Response
SPECIFICATIONS
Temperature
135 7.5F
Temperature
190 7.5F
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature
Contact Rating
Color & Case Material
Mounting
OPERATION
The DCD-135/-190 fixed temperature/rate-of-rise heat
detectors are suited to detect in the presence of slow or
fast rising temperatures due to burning combustibles.
The construction of these models incorporate a
thermistor heat element protected from damage by the
built-in, durable plastic guard. These electronic heat
detectors incorporate two power/alarm LED's for 360
indication of status. In standby condition the power LED's
flash Green. In an alarm condition the LED's latch on
Red. The DCD-135/-190 electronic heat detection
circuitry performs the same function as a Mechanical
Device but with Electronic Precision. If the heat rise is
less than 12/minute the DCD will not alarm until it
reaches its alarm temperature (135 or 190 7.5F). If
the heat rise is greater than 12/minute the DCD will
alarm immediately giving an early warning signal and
latching the Red alarm LED's on.
PRODUCT LISTINGS
MEA
284-91E Vol. IV
S2966
1D5A1.AY
California
State Fire
Marshal
7270-0410:151
Continued on back.
Find latest revision at www.hochiki.com
F0016
04/2010
ENGINEERING SPECIFICATIONS
Automatic heat detectors where ambient temperatures do not exceed 120F shall be the DCD-135 fixed temperature/
rate-of-rise heat detector rated at 135F. For areas where ambient temperatures exceed 120F, but not 160F, the
DCD-190 fixed temperature/rate-of-rise heat detector rated at 190F shall be used. Electrical contacts shall be
normally open, rated at 150mA @ 24VDC.
Heat detectors shall be installed in accordance with National Fire Protection Association Standard 72, the spacing
assigned by Underwriters Laboratories and in accordance with the rules and regulations set forth by the local authorities
having jurisdiction. Automatic heat detectors shall be Underwriters Laboratories listed.
4-WIRE OPERATION
(+)
INITIATING
CIRCUIT
LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
(-)
H1
H2
YEL
ORN
PUR
UL LISTED
POWER
SUPPLY
24VDC
(+)
LISTED
END OF LINE
RELAY
HA-EOLR-24
(-)
HSC-4R
HSC-4R
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL
(+)
LISTED
END OF LINE
DEVICE
(-)
PANEL
POWER
SUPPLY
(-)
NEGATIVE
NS4 SERIES
NS6 SERIES
LISTED
END OF LINE
DEVICE
TERMINAL BLOCK USED ON
HSC-224RA/RST VERSION ONLY
HSC-(XXX)R (2-WIRE)
(-)
COM
N/C
5
4
3
N/O
HSC-RELAY SERIES
N/O
N/C
COM
2
1
GRY
BLU
GRN
YEL
ORN
PUR
OPERATION
STANDARD FEATURES
Self-Restoring
Heat element protected by a built-in guard
Contact Rating of 100 mA
Highly Dependable
ENGINEERING SPECIFICATIONS
SPECIFICATIONS
Temperature
135 7.5F
Temperature
190 7.5F
Contact Rating
N/O Contacts
100mA @ 60 V
Color & Case Material
Ivory ACS
Mounting
Refer to back of this sheet
Response
PRODUCT LISTINGS
MEA
California
State Fire
284-91E Vol. II
Marshal
7270-0410:119
S2966
Specifications subject to change without notice.
Continued on back.
Find latest revision at www.hochiki.com
10/2010
COMPATIBLE BASES
HSC-(XXX)L HEAT DETECTOR BASE
The HSC-xxx L Series is a 6" base featuring a current limiting resistor, latching annunciator output
and a latching circuit so the alarm LED will remain lit until the control panel has been reset. Heat
detectors are not recognized as proper detection for life safety protection, therefore they should
be utilized only for the protection of property.
COMPATIBLE
(+)
UL LISTED
LISTED
END OF LINE
DEVICE
3.9K 1/2W
CONTROL
PANEL
(-)
PANEL
POWER
SUPPLY
(-)
HSC-(XXX)L SERIES
NEGATIVE
24mA
38mA
HSC-221L
HSC-220L
41mA
73mA
(+)
COMPATIBLE
UL LISTED
CONTROL
PANEL
LISTED
DEVICE
(-)
6
NS6-100
Non polarized, not current limited. No annunciator output.
We try to keep our product information up-to-date and accurate. However, we cannot cover
all specifications or anticipate all requirements. For additional information contact
your local distributor or call or write Hochiki America Corporation.
Hochiki America Corporation DFE-135/190
STANDARD FEATURES
Microprocessor based for reliability
Simple setup & alignment with signal strength LED's
Provides 60 feet on center linear protection at a
SPECIFICATIONS
Rated Voltage
Supply Voltage
Supervisory Current
Alarm Current
Trouble Current
Operating Temperature
Range
UL Installation
Temperature Range
Sensitivity Test Feature
Allowable misalignment
angle (MAX)
Dimensions
Mounting
Maximum Humidity
24VDC
19VDC - 33VDC
Emitter 50A @ 24VDC
Receiver 200A @24VDC
20mA @ 24DC
20mA @ 24VDC
14 F - 122 F
32 F - 100 F
Hochiki test filters
Emitter +/- 0.5
Reciever +/-1.0
3.2"W x 5.5"H x 4.0"D
Wall mount or Single Gang Box
95% R.H. non-condensing
gymnasiums
theatres
factories
tunnels
stables
warehouses
high air velocity areas
OPERATION
The near infrared pulsed beam generated by the
emitter is sensed by the photodiode of the receiver,
where it is converted into an electrical signal. This
signal is then amplified and applied, via an analog to
digital converter, to a microprocessor. The normal
state signal (the initial beam data) once stored in the
microprocessor is used as reference for comparison
with subsequent beam signals.
When there is a difference between actual beam
strength and stored reference data that exceeds the
programmed alarm obscuration reference level, a fire
signal is produced. A trouble signal is generated if the
beam is more that 90% obstructed (as opposed to
partially obscured by smoke).
PRODUCT LISTINGS
S1383
California
State Fire
Marshal
7260-0410:172
Continued on back.
Find latest revision at www.hochiki.com
F0072
06/2010
OPERATION, continued
The microprocessor also provides compensation for a change in received signal value, with time, caused by contamination
of the optics. Since such a change with time appears as a slow change in the beam signal, the microprocessor compensates in such a manner that the signal moves closer to the reference data at a rate approximately +1% per hour. When
this compensating capability reaches a limit, the SPC-24 automatically generates a trouble signal.
A calibrated test filter is available upon request to test and verify the sensitivity setting of the SPC-24 projected beam
smoke detectors.
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install, where indicated on the plans, Hochiki America SPC-24 Projected Beam Smoke
Detector. The projected beam smoke detector shall have a range of 32.8 feet to 328 feet. The projected beam smoke
detector shall be field adjustable to one of the three obscuration settings of 25%, 50% or 70% per span. These settings
shall be capable of being verified with calibrated filters. Side to side spacing shall be a maximum of 60 feet on center.
The projected beam smoke detector shall possess circuitry that automatically compensates for normal ambient changes
in the intensity of the emitted beam strength. The microprocessor shall provide compensation for a change in received
signal value, with time, caused by contamination of the optics. Since such a change with time appears as a slow change
in the beam signal, the microprocessor shall compensate in such a manner that the signal moves closer to the reference
data at a rate of approximately +1% per hour. When this compensating capability reaches a limit, the microprocessor
shall automatically generate a trouble signal.
The projected beam smoke detector(s) shall also signal a trouble condition if the beam has a blockage of 90% or more for
more than 20 seconds and automatically resets to normal when blockage is removed.
The projected beam smoke detector(s) shall be UL listed for these applications. Voltage and RF transient protection shall
be integral to the internal circuitry of the projected beam smoke detector so as to minimize false alarm potential.
To facilitate easy installation and setup, the projected beam smoke detectors shall employ signal strength indicating
LED's. Alignment shall be facilitated by turning an alignment adjustment wheel and monitoring the relative signal strength
based upon which LED's are illuminated.
The detectors shall also illuminate a red LED, which is visible externally, when an alarm condition is indicated.
The projected beam smoke detector shall provide a Form "A" dry contact for alarm and Form "B" dry contact for trouble.
INSTALLATION
The HOCHIKI America SPC-24 Projected Beam Smoke Detector shall be installed in accordance with the Installation
Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional guidance on spacing,
irregular ceiling surfaces and other design considerations.
E1
E2
E1
Emitter
E2
E1
E1
E2
E2
Emitter
EOL-24
Receiver
Receiver
24V +
24V Zone +
Zone -
24V
0V
F1
F2
T1
24V
0V
F1
F2
T2
24V
0V
F1
F2
T1
24V
0V
F1
F2
T2
End of Line
Resistor
Control
Panel
GENERAL DESCRIPTION
STANDARD FEATURES
Detector spacing from 25ft-100ft.
Pulsed beam to reduce overall consumption and
improve the noise rejection characteristics.
Small flat reflector.
Automatic drift compensation.
Fire detection sensitivity can be set to 20% or
30% obscuration.
SPECIFICATIONS
Operating Voltage
Stand-by Current
Max Current In Alarm
Operating Range
Sensitivity
Compensation
Reflector mounting
angle
Operating Temp. Range
Storage Temp. Range
Maximum Humidity
Color & Case Material
Size: SRA-24
Reflector
Weight: SRA-24
Reflector
15-33Vdc
350A at 24Vdc
50mA at 24Vdc
25ft - 100ft
20% or 30%
1% per Hr. 50%
10%
32F to +100F
-22F to +158F
95%RH - Non condensing
(at 104F)
Ivory ABS
6" x 4.8" x 3.1"
7.5" x 7.5" x.1"
1.9 lbs (Including termination module)
1.6 oz.
PRODUCT LISTINGS
Underwriters Laboratories: S1383
Factory Mutual:
CSFM #: 7260-0410:158
Continued on back.
12/2003
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install, where indicated on the plans, HOCHIKI America SRA-24 Reflective
Beam Detector. The detector shall have a range of 25 feet to 100 feet. The beam smoke detector shall be
field adjustable to one of the two obscuration settings of 20%, or 30% per span. These settings shall be
capable of being verified with calibrated filters. Side to side spacing shall be a maximum of 60 feet on
center.
The reflective beam detector shall posses circuitry that automatically compensates for normal ambient
changes in the intensity of the emitted beam strength. The microprocessor shall provide compensation for
a change in received signal value, with time, caused by contamination of the optics. Since such a change
with time appears as a slow change in the beam signal, the microcomputer compensates in such a manner
that the signal moves closer to the reference data at a rate of approximately +1% per hour. When this
compensating capability reaches a limit, the microcomputer automatically generates a trouble signal.
The reflective beam detector(s) shall also signal a trouble condition if the beam has a blockage of 90% for
more than 20 seconds and automatically resets to normal when blockage is removed.
The reflective beam detector(s) shall be UL listed for these applications. Voltage and RF transient protection shall be integral to the internal circuitry of the reflective beam detector so as to minimize false alarm
potential.
To facilitate easy installation and setup, the reflective beam detectors shall employ signal strength indicating LED's. Alignment shall be facilitated by turning an alignment adjustment screws and monitoring the
relative signal strength based upon which LEDs are illuminated.
The detectors shall also illuminate a red LED, which is visible externally, when an alarm condition is indicated.
The reflective beam detector shall provide a Form "A" dry contact for alarm and Form "B" dry contact for
trouble.
INSTALLATION
The HOCHIKI America SRA-24 Reflective Beam Detector shall be installed in accordance with the Installation Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional
guidance on spacing, irregular ceiling surfaces and other design considerations.
TYPICAL WIRING
Reflector
Reflector
24V
24V
Zone
Zone
+
+
-
24V
0V
F1
F2
T1
Control
Panel
24V
0V
F1
F2
T2
24V
0V
F1
F2
T1
24V
0V
F1
F2
T2
End of Line
Resistor
NOTE: End of line relay and trouble contacts are closed when power is applied.
STANDARD FEATURES
SPECIFICATIONS
Rated Voltage:
Working Voltage:
Normal Current:
Alarm Current:
Response to Ultraviolet:
OPERATION
The HF-24 uses an ultraviolet detector tube which absorbs
very weak ultraviolet light such as that emitted from a
flame. This is detected as a train of discharge pulses
creating a current. The electronic circuitry in the detector
body translates this action as an alarm signal. There is
a counter circuit which prevents the alarm from occurring
from one-shot ultraviolet light such as lightning or cosmic
flares. Additionally there are circuit refinements which
limit the detection of only wave lengths from 1850 to 3000
angstroms thus ignoring visible and infrared light.
Ambient Temperature:
14 to 122 Fahrenheit (-10 C to +50 C)
Mounting:
Color:
Continued on back.
Find latest revision at www.hochiki.com
F0011
09/2004
DETECTION RANGE
Ceiling
120
#1
2m
Ceiling Height
3m
#2
4m
5m
6m
7m
8m
Floor
# 1: Flame from a candle or lighter
# 2: Flame from a wad or newspaper, burning flame
WIRING DIAGRAMS
NS Series and HSC Series Base
HSC SERIES
(+)
NS6 SERIES
COMPATIBLE
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
NS4 SERIES
LISTED
END OF LINE
DEVICE
(-)
HSB-2 Wire
UL LISTED
CONTROL
PANEL
(+)
LISTED
END OF LINE
DEVICE
3.9K 1/2W
(-)
PANEL
POWER
SUPPLY
NEGATIVE
16mA MAX.
OUTPUT
(-)
16mA MAX.
OUTPUT
SPECIFICATIONS
DH-98-P
Operating Voltage
DH-98-HVP
115V AC,
24V AC/DC
230V AC,
24V AC/DC
SLR-24DH
SLR-24DH
Conventional
Photoelectric
Conventional
Photoelectric
Power Requirements
Standby
8mA
230 VAC
14mA
115 VAC
24 VAC
Power Requirements
Alarm
20mA
20mA
24 VDC
13mA
13mA
230 VAC
15mA
115 VAC
28mA
24 VAC
95mA
24 VDC
60mA
60mA
Alarm Contacts
1 Form A (1A)
Self Diagnostic
Test
Self Diagnostic
Test
Power, Alarm,
Horn/Piezo,
Test
Power, Alarm,
Horn/Piezo,
Test
DESCRIPTION
The HOCHIKI AMERICA DH-98 Duct Smoke Detector
provides early detection of smoke and products of
combustion present in air moving through HVAC ducts in
Commercial, Industrial and Residential applications. The
DH-98 is designed to prevent the recirculation of smoke in
areas by the air handling systems, fans and blowers.
Complete systems may be shut down in the event of smoke
detection. The HOCHIKI AMERICA DH-98-P operate on
115 VAC, 24 VAC and 24 VDC and the DH-98-HVP operate
on 230 VAC, 24 VAC and 24 VDC.
1 Form A (1A)
Detection Loop
Trouble Contacts
95mA
Ambient Temperature
Humidity
Housing Material
Finish
Grey Paint
Dimensions
Radioactive Element
California
State Fire
Marshal
3005751
3240-0410:155
3 lbs.
Sampling Tubes
PRODUCT LISTINGS
S1383
Continued on back.
F0038
03/2011
PRODUCT DESCRIPTION,
continued
Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7.5")
is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake
sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths 2.5 ft., 5 ft. and 10 ft. and cut
to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 4 sheet metal
screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4
capture screws.
The compact DH-98 contains 3 sets of alarm contacts; 1 set of form C contacts rated at 10 amps, 1 set of form A
contacts rated at 10 amps and 1 set of form A contacts rated at 1 amp. There is also 1 set of form C 10 amp trouble
contacts for monitoring detector head removal, and the failure of the input supply voltage.
The pilot and alarm visual indicators provided on the front of the DH-98 duct unit signal the operating status of the
device. A manual test/reset switch is located along side the visual indicators.
ENGINEERING SPECIFICATIONS
Air duct smoke detectors shall be HOCHIKI AMERICA DH-98 Series. The detectors shall be listed by Underwriters
Laboratories per UL 268A. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet per minute.
The detectors shall have the ability to interconnect up to 30 units using the same independent power supply.
The duct detector housings shall be of metal construction and complete mechanical installation may be performed
without removal of the detector cover. Visual indication of alarm and power must be provided on detector front. A manual
reset switch shall be located on the front of the device. Detector heads shall not require additional filters or screens
which must be maintained. The housing shall contain a detector base which will accept photoelectric or ionization
detector heads. Terminal connections shall be of the screw type and be a minimum of # 6 screw. Terminals shall be
provided for remote pilot, remote alarm indication, strobe/horn and remote key switch. All wiring must comply with local
codes and regulations.
WIRING DIAGRAMS
A LA R M
CONTACTS
1 0 .0 A @ 1 1 5 V A C
S ee
P ower
C o n n e c tio n s
A LA R M
CO NTACTS
1A @ 24V DC
10
11
12
*T R O U B L E
CO NTACTS
10.0A @ 11 5V A C
13
14
REMO TE
A C C E S S O R IE S
15
16
17
18
19
* T ro u b le c o n tac ts a re sh o w n in n o n -e n e rg ize d
c o n d itio n . T ro u b le c o n tac ts m o n ito r p o w e r
c o n n e c te d a n d h e a d re m o v ed .
D H -9 8 D U C T S M O K E D E T E C T O R
24V A C , 60H z
@ 0 .1 A M P M A X .(D e te c to r o n ly ).
U P T O 1 . 9 A M P S F O R A U X IL IA R Y
O U T P U T S (H O R N S /S T R O B E S ).
24V D C
@ 0 .1 A M P M A X .(D e te c to r o n ly ).
U P T O 1 .9 A M P S F O R A U X IL I A R Y
O U T P U T S (H O R N S /S T R O B E S ).
20
D H -9 8 -I
-P
D H -9 8 -P
- 98
2 4 V .A . C . O P E R A T IO N
2 4 V .D .C . O P E R A T I O N
1 1 5 V A C 6 0 H z IN P U T
@ 0 .1 A M P M A X .
2 3 0 V A C 6 0 H z IN P U T
@ 0 .1 A M P M A X .
D H -9 8 -I
-P
D H -9 8 -H V I
P
1 1 5 V .A .C . O P E R A T IO N
2 3 0 V . A . C . O P E R A T IO N
INPUT
POWER
DUCT UNIT #2
DUCT UNIT #3
P
P
16
16
18
16
18
18
SPECIFICATIONS
Power Requirements
Alarm LED
Pilot LED
Horn
Sound Pressure
Horn
Dimensions
Single Gang
Double Gang
ALARM
MS-RA
Functions:
Remote Alarm LED (red)
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
DH-98-A, DH-98-AR
ALARM
PILOT
TEST/RESET
ALARM
TEST/RESET
ALARM
PILOT
MS-KA/R
Functions:
Remote Alarm LED (red)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
DH-98-AR
MS-RA/P
Functions:
Remote Alarm LED (red)
Pilot LED (green)
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
ALARM
TEST/RESET
ALARM
PILOT
TEST/RESET
15 mA
15 mA
20 mA @ 24 VDC
78 db @ 10 feet
2.75" (69.85mm) W
4.5" (114.3mm) H
4.5" (114.3mm) W
4.5" (114.3mm) H
MS-KA/P/R
Functions:
Remote Alarm LED (red)
Pilot LED (green)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
MS-RA/R
Functions:
Remote Alarm LED (red)
Push-button Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
DH-98-AR
MS-RA/P/R
Functions:
Remote Alarm LED (red)
Pilot LED (green)
Push-button Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
04/2010
MS-RH/KA/P/R
Functions:
Remote Alarm Horn
Remote Alarm LED (red)
Pilot LED (green)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP
ALARM
PILOT
TEST/RESET
WIRING DIAGRAM
RED
RED
RED
24VDC
ALARM
ALARM
GREEN
24VDC
HORN
PILOT
LED
LED
BLACK
BLACK
ALARM
PILOT
BLACK
KEY OR
24VDC
PUSH BUTTON
"TEST/RESET"
SWITCH
BLACK
TEST/RESET
PRODUCT SPECIFICATIONS
PUSH
KEY
PILOT ALARM BUTTON OPERATED
TEST/
TEST/
LED
LED
RESET
RESET
(GREEN) (RED)
HORN
SINGLE
GANG
DOUBLE
GANG
MODEL #
MS-RA
MS-RA/P
MS-RA/R
MS-RA/P/R
MS-KA/R
MS-KA/P/R
MS-RH/KA/P/R
Hochiki America Corporation DH-98 Duct Detector Remote Accessories
NS Series Bases
ID
NS6-224 O R N S4-224
HB-5
NS6-220 O R N S4-220
HB-3
NS6-221 O R N S4-221
HB-4
NS6-100* O R NS4-100*
The NS6 and NS4 Series is designed specifically for use with
HOCHIKI Conventional Models SIJ-24 Ionization Smoke Detector,
SLR-24V Photoelectric Smoke Detector, SLV-24, SLV-24N, SLV-24V
Photoelectric Smoke Detectors, SLR-24H Photoelectric with Heat
Smoke Detector, SLR-835 Photoelectric Smoke Detector, SLR-835H
Photelectric Smoke Detector w/heat, or DCD-135/190 Fixed
Temperature/Rate-of-Rise Heat Detector. The Base is an electronics
free 6" base featuring a plastic tamper-lock lug. Each base is
equipped with a resistor. Refer to the chart (left) for additional
specifications. The NS4 base is a 4" version of the NS6 base.
HB-55
ID
HSC-224R
HB-73
HSC-220R
HB-72
HB-71
HSC-221R
4 Wire Base
ID
HSC-4R
N/A
HSC-4R12
N/A
2 Wir e Latchi ng
ID
HSC-224L
HB-62
67-80mA @ 24V
HB-64
HSC-220L
The HSC-L Base Series is designed specifically for use with the
HOCHIKI Fixed Temperature Heat Detectors Models
DFE-135/ 190.
The HSC-L Series is a 6" base featuring a current limiting
resistor, latching annunciator output and a latching circuit so the
alarm LED will remain lit until the control panel has been reset.
HB-63
We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or
anticipate all requirements. For additional information contact your local distributor or Hochiki America Corporation.
F0014
04/2010
LISTED
END OF LINE
DEVICE
Resistor shown is for example
only. Not all annunciators
have in line resistance.
NEGATIVE
NS4 SERIES
NS6 SERIES
LISTED
END OF LINE
DEVICE
GRY
BLU
GRN
YEL
ORN
PUR
PIGTAIL AUXILLIARY
CONTACTS
TWO FORM "C"
4-WIRE OPERATION
LISTED
END OF LINE
DEVICE
INITIATING
CIRCUIT
LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC
H1
H2
H1,H2 - TERMINAL
PIGTAIL AUXILLIARY CONTACTS
ONE FORM "C"
YEL
ORN
PUR
HSC-4R OR HSC-4R12
PANEL
POWER
SUPPLY
NEGATIVE
HSC-(X) L SERIES
LISTED
END OF LINE
DEVICE
NS6 SERIES
We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or anticipate all
requirements. For additional information contact your local distributor or Hochiki America Corporation.
Hochiki America Corporation Conventional Detector Bases
ID
NS6-220
HA #0300-04840
NS4-220
HA #0300-04830
Alarm Current
93mA (150mA @ 24.0V MAX)
HB-3
HB-3
DESCRIPTION
PRODUCT LISTINGS
California
State Fire
Marshal
7272-0410:174
S1383
LISTED
END OF LINE
DEVICE
Resistor shown is for example
only. Not all annunciators
have in line resistance.
NS4 SERIES
NS6 SERIES
We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or
anticipate all requirements. For additional information contact your local distributor or Hochiki America Corporation.
F0112
09/2010
STANDARD FEATURES
Wide operating voltage
Selectable Evacuation Codes: continuous or temporal
Three different configurations: individual, group, and
global modes
High sound pressure level (85 dB at 10 ft)
Can be configured to satisfy a wide variety of
applications
Available with or without relay, 2 and 4 wire
configurations, and bone or white color
SPECIFICATIONS
Model
SBC-2, 2W
8.7-30VDC
26mA@8.7VDC
35mA@12VDC
65mA@24VDC
19-30VDC
53mA@19VDC
65mA@24VDC
GROUP/
GLOBAL MODE
30mA@19VDC
40mA@24VDC
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
1
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654321
10987654324321098765432109876543243210987654321
1
4
4
10987654321321098765432109876543213210987654321
10987654321
4
1
1
4
1
10987654321321098765432109876543213210987654321
4
109876543243210987654321
4
1
10987654321321098765432109876543213210987654321
10987654321
109876543243210987654321
4
10987654321
109876543213210987654321
10987654321
109876543213210987654321
4
4
10987654321321098765432109876543213210987654321
0987654324321098765432109876543243210987654321
4
13210987654321
1
4
1
10987654321321098765432109876543213210987654321
1
4
4
Rated Voltage
12mA@8.7VDC
18mA@12VDC
45mA@24VDC
1A@28VDC
OR
0.5A@120VAC
93%RH(non-condensing)
93%RH(non-condensing)
85 dB
32F (0C) to
100F (38C)
5.94 x 1.34
10-18VDC
18-30VDC
75mA@12VDC
65mA@24VDC
24VDC
12VDC
2A@30VDC OR 0.5A@120VAC
2A@30VDC OR 0.5A@120VAC
93%RH(non-condensing)
85 dB
32F (0C) to
100F (38C)
5.94 x 1.34
0.365 lb
PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7300-0410:160
Specifications subject to change without notice.
0.455 lb
SBC-4/24, 4/24W
SBC-4/12, 4/12W
SBC-2R, 2RW
GROUP/
GLOBAL MODE
85 dB
32F( 0C ) to 100F (38C)
5.94 x 1.34
0.455 lb
SLR-835/-835W
SLR-24V, SLR835H/-835HW
Continued on back.
F0012
11/2005
EOL
RESISTOR
INITIATING
LOOP
UL
LISTED
CONTROL
PANEL
NEXT DEVICE
TOP VIEW
OR
P57
1
20
EOL
RELAY
+12
+12
-12
-12
NEXT
NEXT
J2
J2
J4
J4
S1
8
G
AL
05
8
J3
S1
CO
8
G
AL
J3
VLT
GRY
BRN
05
8
CO
ON
GRN
YEL
ORG
RED
BLK
WHT
BRN
VLT
GRY
GRN
YEL
ORG
RED
BLK
WHT
ON
12V/24V
AUX
20
P57
BOTTOM VIEW
CONVENTIONAL SOUNDER BASE 24V WITH RELAY (2 WIRE) SBC-2R
1
20
P 57
20
P57
1
NC
NO
COM
+ 12
J2
J2
24V ONLY
AUX
NC
NO
COM
+ 12
NEXT
J4
J4
NEXT
S1
J3
8S
CO
DS
05
7
6
AL
05
S
GD
4
3
CO
AL
2
1
1
ON
ON
GRY
VLT
BRN
GRN
YEL
ORG
RED
BLK
WHT
VLT
GRY
BRN
GRN
YEL
ORG
RED
BLK
WHT
S1
J3
8S
EOL
RELAY
- 12
- 12
NOTES: FOR ADDITIONAL SOUNDER WIRING DIAGRAM SBC-2, AND SBC-2R INFORMATION, PLEASE REFER TO
INSTALLATION INSTRUCTION HA-06-085.
UL LISTED
12V/24V
EOL
RELAY
POWER
SUPPLY
12V: SBC-4/12
24V: SBC-4/24
NEXT DEVICE
TOP VIEW
P5
03
7203
P572
J2
NEXT
J4
NEXT
J3
J3
ON
4
3
2
1
1
RED
BLK
RED
BLK
GRN
YEL
ORG
RED
BLK
WHT
S1
S1
RE D
BLK
RE
D
BLK
GRN
YEL
ORG
RE
D
BLK
WH
T
ON
J4
RED
BLACK
NC
NO
COM
+ 12
- 12
J2
UL
LISTED
CONTROL
PANEL
NC
NO
COM
+ 12
- 12
INITIATING
LOOP
RED
RED
BLACK
BLACK
EOL
RESISTOR
BOTTOM VIEW
NOTES: FOR ADDITIONAL SOUNDER WIRING DIAGRAM SBC-4 INFORMATION, PLEASE REFER TO INSTALLATION
INSTRUCTION HA-06-086.
Hochiki America Corporation Conventional Sounder Base
SPECIFICATIONS
STANDARD FEATURES
Power Supply
24 VDC 10% 0.5A or less
Current Output
4-20mA DC output (Receiving resistance: 100 ohm or less)
Contact Output
Alarm 1 output, Alarm 2 output , Alarm 3 output,
& System Fault output
Contact Capacity
24 VDC, 0.5A or less (each contact output)
Contact Output Logic
NO (form A) or NC (form B) selectable
by a jumper pin
AC Power Supply Monitoring Input
NO (form A) or NC (form B) selectable
by system setting
Internal Wiring
Heat-resistance shielded wires
Materials
Body & panel: Steel plate of 0.8 mm thick, baked painting
Display operating panel: Steel plate of 1.0 mm thick
Colors
Body & panel:
Munsell 2.5Y9/1 or equivalent
Display operating panel: Munsell 5Y6/0.5 or equivalent
Weight
Approximately 8.2 lbs. (3.7kg.)
Dimensions
12.48" W x 8.86" H x 4.00" D
317mm x 225mm x 102mm
PRODUCT LISTINGS
Installation
Accessory
Indoor (Non-condensing)
Dedicated flexible pipe
3026973
Specifications subject to change without notice.
Continued on back.
Find latest revision at www.hochiki.com
F0069
01/2007
OPERATION
An aspirating smoke detection system continuously draws air from the monitored area into the sampling pipes. The
air is drawn from the sampling pipes into the main sampling unit. In the main sampling unit, the air is analyzed by
very sensitive laser detection components. The laser detection components constantly monitor for the presence of
smoke particles.
If smoke particles are detected, the unit will activate the alarm output relays in accordance with the sensitivity
selected and the alarm level reached. The SZA-NA(FM) High Sensitivity Smoke Detector is between 20 and 1000
times more sensitive than spot-type smoke detectors. The SZA-NA(FM) has three alarm stages. Alarm 1 is the
lowest obscuration alarm (high sensitivity), activating when very small amounts of smoke are detected. The Orange
Alarm 1 LED will light, and the Alarm 1 relay will activate. As the smoke density reaches alarm level 2, the Red
Alarm 2 LED will light and Alarm 2 relay will activate. As the smoke density reaches alarm level 3, the Red Alarm 3
LED will flash and the Alarm 3 relay will activate.
The SZA-NA(FM) is ideal for use in areas such as computer server rooms, clean rooms, telecommunication
equipment rooms, medical equipment/operating rooms, power generation plants, and many other applications. By
continuously sampling the area, the SZA-NA(FM) can provide the earliest warning of the presence of smoke, even
before the smoke is visible to the human eye.
1
2
3
1 Relay Connections 2 Jumpers (N/O or N/C)
4 Fan Unit
5 Laser Unit and Air Flow Sensor
TERMINAL BLOCK
4
3 Programming Display
6 24 VDC Fuse
MOUNTING
STANDARD FEATURES
Metal Construction
Enclosed switch with glass rod (included)
10 Amps @ 120 VAC
Available in: Single Action, Dual Action and
Dual Action in Spanish (HPS-DAH/S)
UL, CSFM Listed
Made in USA
HPS-SAH
HPS-SAK
DESCRIPTION
Hochiki Americas Models HPS series pull stations
are available in six models:
HPS-DAH
HPS-DAH/S
PRODUCT LISTINGS
California
State Fire
Marshal
S6512
HPS-DAK
7150-0410:162
HPS-DAK/S
Continued on back.
F0033
03/2010
Rear View
Front View
PULL DOWN
SPECIFICATION
ELECTRICAL WIRING
Hochiki America Corporation Series HPS-SAH, HPS-SAK, HPS-DAH, HPS-DAH/S, HPS-DAK, HPS-DAK/S
STANDARD FEATURES
Manual Station
SPECIFICATIONS
Contact Current Rating 10A @ 120 VAC
PRODUCT LISTINGS
California
State Fire
Marshal
S6512
To Fire Alarm
Control/Communicator
zone or point
1
N/O
Switch
7150-0410:162
Wire Connections
F0035
03/2010
STANDARD FEATURES
Corrosion-resistant construction
KEY reset
Lift and Latching pull-down lever
Enclosed switch with glass rod (Included)
Screw terminal connections
SPECIFICATIONS
Model
Contact
Contact Rating
HPS-DAK-WP
(1) Form A
Manual Station
To Fire Alarm
Control/Communicator
zone or point
N/O
Switch
Wire Connections
Specifications subject to change without notice
F0086
06/2010
Normally Open
DESCRIPTION
Hochiki America Models HPS-CP series pull stations
are available in two models:
HPS-CP call point/break glass
HPS-CP/S call point/break glass (Spanish)
HPS-CP
WIRING DIAGRAM
TOP REAR VIEW
L1
IN INITIATING
L2
CIRCUIT
L2 OUT
L1
HPS-CP/S
STANDARD FEATURES
Actuating switch, a heavy duty plunger type
Glass plate (2.5" x 2.5"), a Factrolite single
strength (obscured) type.
Steel rod attached
Mounts in a standard electrical outlet box
Available in English & Spanish
UL listed
Made in USA
PRODUCT LISTINGS
California
State Fire
Marshal
S6512
7150-0410:164
F0059
03/2010
STANDARD FEATURES
Compatible with all Hochiki Control Panels
Rugged die-cast housing
Rated class I group B (hydrogen) C&D, class II
groups E,F,G, class III, 4X outdoor
Weather Proof
Corrosion-resistant construction
Latching alarm levers
Screw Terminals 12-22 AWG
Key-locked reset
Optional glass break rod
DPDT Contacts
SPECIFICATIONS
Contacts
The unit is a high quality manual fire alarm box constructed entirely of a high strength metal die-cast alloy
with a low profile and rounded edges to fit most design
applications. All components are prepainted or have
plated surfaces to inhibit corrosion. Non-corroding
screw terminals are provided for wire connections to
the HPS-SA-EX/WP.
The HPS-SA-EX/WP is manufactured in conformance
with the standards set forth in the Americans with
Disabilities Act (ADA).
The HPS-SA-EX/WP has a white pull down lever in its
center. Pulling down the lever latches it into place.
The HPS-SA-EX/WP's normally open contact switch is
shorted causing an alarm on the fire initiating loop.
The pull down lever can not be reset unless the correct
key is inserted into the manual fire alarm box lock and
the unit is opened. The latching lever can then be
restored to its normal position.
When the HPS-SA-EX/WP is being reset and has a
glass break rod installed, all debris must be removed
prior to installing another rod to ensure the unit will
close and lock securely.
PRODUCT LISTINGS
California
State Fire
E236171
7151-0410:163
F0034
04/2010
OPERATION
STANDARD FEATURES
Preparation
1. Remove the TSE-A100 from its carrying case.
2. Unscrew the combustion chamber from the
bottom of the TSE-A100.
3. Unscrew the punk stick holder retainer from
the combustion chamber.
4. Insert a punk stick into the punk stick holder in
the combustion chamber.
5. Light the punk stick with a flame.
6. Reassemble the combustion chamber.
7. Screw the combustion chamber back into the
bottom of the TSE-A100
8. Extend the telescopic pole of the TSE-A100 to
a length which enables you to reach the
detector you wish to test.
Testing a Detector
Once you have prepared the TSE-A100, follow the steps
in this section to test smoke detectors.
SPECIFICATIONS
Continued on back
Rated Voltage
Battery
Combustion Material
Weight
Length
Color
3 VDC
2 - "D" Batteries
Punk Stick
(7 mm diameter, 150 mm long)
5 Lbs.
5.25 to 14.1 feet
Brown
PRODUCT PARTS
TSE-A100 Self-Contained Smoke Generator
Punk Stick (Part No. TSE-P100)
01/2002
OPERATION,
continued
NOTE
1. Use only the filter and combustion material
specified.
2. Check battery capacity before use to assure
efficient operation.
3. Remove batteries before long-period storage.
Telescopic Pole
Combustion Chamber
Punk Stick
Instruction Label
NSRT / NSTT
SMOKE DETECTOR REMOVAL TOOL / TESTER
STANDARD FEATURES
NSRT
Combination removal tool/outer cover removal tool
for AIE, ALG, SIJ, and SLR-24/-835 series sensors/
detectors.
Choose either a Hand held or 15 stainless steel
extension pole with easy grip black handle.
NSTT
NSRT HEAD
SPECIFICATIONS
Detector Tester/Removal Tool
Dimensions
NSRT HEAD: 4.0" D x 2.0" H
NSTT HEAD: 4.0" D x 1.5" H
Material
Highly durable PVC
molded plastic
Color
Black - provides visible contrast
Alignment
NSRT HEAD:
One side for arrow labels for
easy visibility, one side for
removal from base.
NSTT HEAD:
One side for sensitivity testing.
NSTT HEAD
Extension Pole
Dimensions
Material
NSTT-A100 WITH 15' POLE
(COMPLETE)
F044
02/2005
APPLICATION
NSRT-A100
The Hochiki America NSRT-A100 will enable the user to easily remove and replace the ALG, AIE, SLR, and SIJ series
sensors/ detectors from their mounting bases. Also, the NSRT-A100 is designed to remove the outer covers of the
ALG, AIE and SLR series sensors/detectors
NSTT-A100
The SIJ-24 and SLR-24/-835 series detectors, manufactured with magnetically activated dual reed switches for sensitivity
testing, can be sensitivity tested with the NSTT-A100. This meets the requirements of a UL listed calibrated test
without the use of combustion materials.
The NSTT-A100 is in compliance with the test requirements outlined in the NFPA 72 Inspection, Testing and Maintenance,
Chapter 10.
OPERATION
Test Procedure
STANDARD FEATURES
Combination tester/removal.
Tests Hochiki America smoke detectors with a
dual reed switch.
Choose either a Hand held or 15' stainless steel
extension pole with easy grip black handle.
No combustion material needed.
No meter, batteries, or screwdriver required.
UL listed.
Meets outlined requirements in the NFPA 72
Inspection, Testing and Maintenance, Chapter 7.
SPECIFICATIONS
Detector Tester/Removal Tool
Dimensions
3.4" D x 2.4" H
Material
Highly durable PVC
molded plastic
Color
Gray-provides visible contrast
Alignment
One side for test, one side
for removal. Color-coded
labels for easy visibility
Tester/Removal Tool Handle
Options
Hand Held or Extension Pole
Dimensions
Pole extends to 15'
Material
Stainless steel with
easy grip black handle
PRODUCT LISTINGS
Underwriters Laboratories: S1316
MEA Report #: 284-91-E Vol. II
12/2003
OPERATION, continued
3. If the detector does alarm when the removal/test tool is placed in this position, the detector is not within specified
sensitivity limits and may require service.
4. Rotate the TRT-A100 one-half circle (180). Align white arrow shown on tester tool with tamper resistant set
screw.
5. Wait six to eight seconds. Detector SHOULD alarm and the indicator LED should remain lit.
6. If detector does not alarm when the TRT-A100 is positioned correctly, may not within specified sensitivity limits
and may require service. See Technical Bulletin HA-88 (November '96) for more information.
Removal Procedure
This section explains how to use the HOCHIKI America TRT-A100 Tester/Removal Tool to remove smoke detectors
from their bases.
1.
2.
3.
4.
Flip the TRT-A100 so the five small arrows located beneath the white orange arrows are point upward.
Fit the TRT-A100 to the detector and lock into place.
To remove a detector, rotate the TRT-A100 to the left (counterclockwise).
To install a detector, rotate the TRT-A100 to the right (clockwise).
H E AT D E T E C T O R T E S T E R S
fast
efficient
convenient
innovative
safe
patented
30ft reach
CAT
SOLO 409
HEAT TESTER
The SOLO 409 is a professional and robust tool for testing heat
detectors fitted at heights up to 30ft. Unlike the SOLO 461, it
does require a power cord lead but, conversely, does not require any
special energy saving features.
q Designed for use on fixed temperature, rate of rise and
combination detectors.
q Suitable for any model of spot type heat detector fitted at heights of
up to 30ft.
q Large clear cup fits over detector enabling a clear view of the
detector LED.
q Tests detectors up to 194F operating temperature.
q Thermal cut-out for added protection.
What is CAT ?
The revolutionary and patented CAT (Cross Air Technology) system applies
the stimulus directly to the sensor in the most efficient way possible - horizontally.
For tests on combination rate of rise / non-restorable detectors, a silicon baffle is supplied
to ensure correct airflow.
energy efficient
The SOLO 461 incorporates a 'reference platform', which ensures that the 'beam' of heated
air is lined up correctly with the sensor, whatever size and shape of detector.
Under the control of a microprocessor, blown air is heated by the element
just before exiting the duct. The narrow opening focuses the heat into a 'beam'.
Because the hot 'beam' of air is targeted directly at the sensor, substantial amounts of energy
and time are saved. This design allows many more tests per Battery Baton than ever before.
Specifications
SOLO 461 (CATTM Cordless)
Suitable detector types :
Maximum detector size :
Number of test:
Maximum height:
Approvals:
Safety Features:
Operating features:
Environment:
range includes:
Solo 460:
Solo 720:
Solo 724:
Dimensions
Inside diameter 4in approx
Diameter 1.15in, Length 19.3in
3in (w) X 5.3in (l) X 2.6in(h)
Spot type, Rate of Rise, Fixed Temperature and Combination up to 90C / 194F
Up to 30ft using SOLO extension poles
110 / 120V AC
600W approx
50 / 60 Hz
20in nominal
CEE 17 Industrial
1lb 14oz
Inside diameter 4.5in approx, working depth 3in approx
Thermal cut out, electrically fused, double insulated
Ordering Information
Part No
Solo 409:
Description
110 / 120V AC Corded Heat Detector Tester
Solo 460:
Solo 461:
Solo 720:
Solo 724:
HEC3/HES3
12/24VDC SERIES
APPLICATIONS
The Commander3 Series is a low profile strobe and
horn/strobe combination that offers dependable
audible and visual alarms and the lowest current
available.
The HE3 Series 24VDC offers tamperproof field
selectable candela options of 15, 30, 60, 75, and 110
candela.
The 12VDC offers tamperproof field selectable candela
options of 15, 30, 60, and 75 candela. The Commander3 Series horn offers a continuous or synchable
temporal three in 2400Hz and mechanical tone, a
chime and whoop tone. All tones are easy for the
professional to change in the field by using switches.
The HE3 Series has a minimal operation current and
has a minimum flash rate of 1Hz regardless of input
voltage.
The Commander3 Series is shipped with the standard
4" metal mounting plate which incorporates the
popular Super-Slide feature that allows the installer to
easily test for supervision. The product also features a
locking mechanism which secures the product to the
bracket without any screws showing.
The Commander3 also features the Checkmate Instant Voltage Verification feature which allows the
installer to check the voltage drop draw and match it
to the blueprint.
The HE3 Series appliances are UL 464 and UL 1971,
listed for use with fire protective systems and are
warranted for three years from date of purchase.
Specifications subject to change without notice.
PRODUCT LISTINGS
California State
Fire Marshal
F0103
05/2010
Part Number
HEH12-R
HEH12-W
HEH24-R
HEH24-W
Nominal
Voltage
12VDC
12VDC
24VDC
24VDC
0500-04920
0500-04940
0500-04800
0500-04820
Reverberant dBA
@ 10ft., per UL 464
62-82
62-82
62-82
62-82
In Anechoic Room
dBA @10ft.
100
100
100
100
Part
Number
0500-04880
0500-04900
0500-04890
0500-04910
0500-05020
0500-05000
0500-05030
0500-05010
Nominal
Voltage
12 VDC
12 VDC
12 VDC
12 VDC
24 VDC
24 VDC
24 VDC
24 VDC
Candela
(UL 1971)
15, 30, 60, 75
15, 30, 60, 75
15, 30, 60, 75
15, 30, 60, 75
15, 30, 60, 75, 110
15, 30, 60, 75, 110
15, 30, 60, 75, 110
15, 30, 60, 75, 110
Model Designations:
W = Wall mount R = Red faceplateW = Off-white
faceplateP = Plain (no lettering)
ALERT bezel available
AGENT bezel available.
21
Part
Number
0500-04840
0500-04860
0500-04850
0500-04870
0500-04980
0500-04960
0500-04990
0500-04970
Nominal
Voltage
12 VDC
12 VDC
12 VDC
12 VDC
24 VDC
24 VDC
24 VDC
24 VDC
Candela
(UL 1971)
15, 30, 60, 75
15, 30, 60, 75
15, 30, 60, 75
15, 30, 60, 75
15, 30, 60, 75,
15, 30, 60, 75,
15, 30, 60, 75,
15, 30, 60, 75,
30cd
131mA
212mA
60cd
186mA
331mA
75cd
237m
436mA
110
110
110
110
Reverberant dba @
10ft., per UL 464
62-82
62-82
62-82
62-82
62-82
62-82
62-82
62-82
15cd 30cd
55mA 63mA
78mA 96mA
Minimum dBA
@ 10ft., per
UL 464 (HIGH)
Temp 3 2400Hz
76
Temp 3 Mechanical
75
Temp 3 Chime
62*
Continuous 2400Hz
79
Continuous Mechanical
78
Continuous Chime
63*
Whoop
78
Minimum dBA
@ 10ft., per
UL 464 (LOW)
69*
68*
60*
74*
72*
61*
71*
Regulated 12VDC
Max. Operating @
High Setting (mA)
29
26
13
29
26
13
55
Temp 3 2400Hz
Temp 3 Mechanical
Temp 3 Chime
Continuous 2400Hz
Continuous Mechanical
Continuous Chime
Minimum dBA
@ 10ft., per
UL 464 (HIGH)
78
76
70*
81
80
70*
Minimum dBA
@ 10ft., per
UL 464 (LOW)
71*
70*
66*
74*
72*
66*
In Anechoic Room
dBA @ 10ft.
100
100
100
100
100
100
100
100
Regulated 24VDC
Max. Operating @
High Setting (mA)
28
25
15
28
25
15
60cd
75cd
110cd
88mA 112mA 136mA
137mA 180mA 224mA
NOTES:
To obtain the horn/strobe current draw,
add the strobe current draw and the horn
current draw.
Operating temperature: 32to 120F (0
to 49 C). The HE3 Series is not listed for
outdoor use.
The sound output for the temporal 3
tone is rated lower since the time the horn
is off is averaged into the sound output
rating. While the horn is producing a tone
in the temporal 3 mode its sound pressure
is the same as the continuous mode.
For nominal and peak current across UL
regulated voltage range for filtered DC
power and unfiltered (FWR [Full Wave
Rectified]) power, see installation manual.
12VDC models are DC only.
Hochiki does not recommend using a
coded or pulsing signaling circuit with any
of our strobe products (see Technical
Bulletin 014).
*Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level
required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use.
Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always
private mode).
1
RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the
listed voltage range (16-33VDC for 24VDC units) (8-17VDC for 12VDC units). For strobes the UL max current is
usually at the minimum listed voltage (16VDC for 24VDC units) (8VDC for 12VDC units). For audibles the max current is
usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual.
Hochiki America Corporation Commander3 Series Selectable Candela Evacuation Sginals
Engineering Specifications:
The Audible alarm indicating appliance shall be AMSECO model H24W or equivalent device. The horn shall be listed under UL 464
standard for Audible Signaling Appliance and shall be approved for fire protective service. The sound output shall be field selectable.
The Horn shall provide two different field selectable tones a High and Low field selectable sound output setting. The signaling Select-AHorn Horn shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The Horn shall be
capable of WALL mounting to a universal backbox. The H24W shall be installed as per plans and specifications.
H24W Horn
Select -A- Horn
TM
Series
Description:
PC3
Pattern
P
C
3
P
C
2
P
C
1
1
1
1
1
0
0
0
0
PC1
Volume
PC2
Tone
1
1
0
0
1
1
0
0
1
0
1
Average Current
( mA )
DC
Sound Output
( dBA @ DC )
FWR
16V
NON-TEMP
TE
FIR
E MAR
SH
ST
LL
TE
STI N
OF CA L IFO
NI
ST
A
LI
Horn
UL
C
RV I C
MEA
TEMPORAL
Low
High
Low
Low
High
Electro
Mechanical
3000 Hz
Features:
Application:
Low
High
3000 Hz
UL
High
Electro
Mechanical
33V
16V
24V
33V
16V
24V
33V
35
22
35
22
52
39
52
39
36
23
36
23
45
30
45
30
64
39
64
39
85
75
85
75
87
78
88
78
88
81
88
81
27
15
27
35
22
35
52
39
52
36
23
36
45
30
45
64
39
64
81
71
80
83
75
83
84
77
84
15
0
1
0
1
0
24V
27
15
27
15
22
39
23
30
39
71
75
77
Sync Module
F.A.C.P.
Signal
Circuit_
Sync Module
SMS1-3A
_
H+H
IN_
To Next Device or
End-Of Line-Resistor
OUT
_
F.A.C.P.
Strobe Signal
Circuit
F.A.C.P.
Horn Signal
Circuit
+ _
SMS1-3A
_
H+H
IN
To Next Device or
End-Of Line-Resistor
OUT
_
Dimensions:
Inches (mm)
5 (127)
3-3/8 (85.7)
1-13/16 (46)
1-17/32 (39)
5 (127)
To Next Device or
End-Of Line-Resistor
+ _
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
WARNING:
Conductor Size (AWG), Length and capacity should be taken into consideration
prior to design and installation of these products, particularly in retrofit
installations.
3-9/32 (83.5)
Control
Panel
3-3/8 (85.7)
Jumper
3-9/32 (83.5)
Mounting Options:
Mounting to a single gang box.
Surface mount.
Ordering Information:
Model
Number
H24WR
H24WW
Input
Voltage
( VDC )
24
24
Sync w/
SMS1-3A
Module
Universal
Mounting
Wall
Mount
Ceiling
Mount
Color
Red
Color
White
06/2003
Horn
4BX-1
Surface Mount
back box
4 x 4 x 1-1/2
backbox
4 x 4 x 1-1/2
backbox
2 backbox
Horn
Horn
4SP-M
Mounting Plate
Engineering Specifications:
The Audible alarm indicating appliance shall be AMSECO model H24W or equivalent device. The horn shall be listed under UL 464
standard for Audible Signaling Appliance and shall be approved for fire protective service. The sound output shall be field selectable.
The Horn shall provide two different field selectable tones a High and Low field selectable sound output setting. The signaling Select-AHorn Horn shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The Horn shall be
capable of WALL mounting to a universal backbox. The H24W shall be installed as per plans and specifications.
H24W Horn
Select -A- Horn
TM
Series
Description:
PC3
Pattern
P
C
3
P
C
2
P
C
1
1
1
1
1
0
0
0
0
PC1
Volume
PC2
Tone
1
1
0
0
1
1
0
0
1
0
1
Average Current
( mA )
DC
Sound Output
( dBA @ DC )
FWR
16V
NON-TEMP
TE
FIR
E MAR
SH
ST
LL
TE
STI N
OF CA L IFO
NI
ST
A
LI
Horn
UL
C
RV I C
MEA
TEMPORAL
Low
High
Low
Low
High
Electro
Mechanical
3000 Hz
Features:
Application:
Low
High
3000 Hz
UL
High
Electro
Mechanical
33V
16V
24V
33V
16V
24V
33V
35
22
35
22
52
39
52
39
36
23
36
23
45
30
45
30
64
39
64
39
85
75
85
75
87
78
88
78
88
81
88
81
27
15
27
35
22
35
52
39
52
36
23
36
45
30
45
64
39
64
81
71
80
83
75
83
84
77
84
15
0
1
0
1
0
24V
27
15
27
15
22
39
23
30
39
71
75
77
Sync Module
F.A.C.P.
Signal
Circuit_
Sync Module
SMS1-3A
_
H+H
IN_
To Next Device or
End-Of Line-Resistor
OUT
_
F.A.C.P.
Strobe Signal
Circuit
F.A.C.P.
Horn Signal
Circuit
+ _
SMS1-3A
_
H+H
IN
To Next Device or
End-Of Line-Resistor
OUT
_
Dimensions:
Inches (mm)
5 (127)
3-3/8 (85.7)
1-13/16 (46)
1-17/32 (39)
5 (127)
To Next Device or
End-Of Line-Resistor
+ _
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
WARNING:
Conductor Size (AWG), Length and capacity should be taken into consideration
prior to design and installation of these products, particularly in retrofit
installations.
3-9/32 (83.5)
Control
Panel
3-3/8 (85.7)
Jumper
3-9/32 (83.5)
Mounting Options:
Mounting to a single gang box.
Surface mount.
Ordering Information:
Model
Number
H24WR
H24WW
Input
Voltage
( VDC )
24
24
Sync w/
SMS1-3A
Module
Universal
Mounting
Wall
Mount
Ceiling
Mount
Color
Red
Color
White
06/2003
Horn
4BX-1
Surface Mount
back box
4 x 4 x 1-1/2
backbox
4 x 4 x 1-1/2
backbox
2 backbox
Horn
Horn
4SP-M
Mounting Plate
HP-24 / HP-24T
Piezo Alert Mini Horn
Description:
AMSECOs Series mini horns are designed for alarm signaling
in individual rooms, apartments, hotels, offices, etc. where
dependable high performance alarm signaling is required.The
mini horns produce a high sound output with a minimum
current draw of just 15mA at 24VDC.
The mini horn is clearly labeled with FIRE lettering and is
polarized for connecting to supervised fire alarm circuits.
The mini horn is available with terminals or 4-wires, in red or
white housing 24VDC models.
L
LL
ST
A
OF C A L IFO
R
TE
FIR
E MA R
SH
ST
APPROVED
RVI C
MEA
A DA
Features:
* Designed to meet or exceed NFPA/ANSI Standards
and UL 464 Audible Signal Appliance.
* Screw terminals capacity up to 12 AWG.
* 4-wires for easy field wiring.
* Polarized with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Mounts to a single gang box.
* Available in red or white housing.
Engineering Specifications:
The Audible alarm indicating appliance shall be AMSECO
model HP-24 or equivalent device. The horn shall be listed
under UL 464 standard for Audible Signaling Appliance and
shall be approved for fire protective service. The sound output
shall be 82 dB at 10 ft. The signaling mini Horn shall operate on
24VDC from a non-coded regulated DC supply or full-wave
rectified, unfiltered supply. The Horn shall be capable of WALL
mounting to a single gang box. The HP-24 shall be installed as
per plans and specifications.
Dimensions:
FM
A
NI
UL ULC
TI
IS N
Application:
Control
Panel
_ +
Inches (mm)
To Next Device or
End-of Line-Resistor
_ +
Mounting:
FIR
0.16 (4)
1.42
(36)
2.73
(69.2)
1.42
(36)
Specifications:
Model
Number
Rated
Voltage
( VDC )
Wiring
Type
Operating
Range
(VDC)
UL
dB @ 10ft.
( dBA )
Average
Current
( Amps)
Plate
Color
HP-24R
24
4-wire
19.2 ~ 26.4
82
97
0.015
Red
HP-24W
24
4-wire
19.2 ~ 26.4
82
97
0.015
White
HP-24TR
24
Terminal
HP-24TW
24
Terminal
19.2 ~ 26.4
82
97
0.015
Red
19.2 ~ 26.4
82
97
0.015
White
Indoor
dB @ 10ft
( dBA)
Temperature
Operating
Range
-4F ~ 140 F
(-20C ~ 60C)
06/2003
Single gang
back box
Engineering Specifications:
Octagon
back box
The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be
designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync
protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4 x 4x 1-1/2 back box. Signaling devices shall be
installed in all sleeping and non-sleeping areas as per plans and specifications.
4 square
back box
SH24C-177
SPC-1
SPC-1
SPC-1
Horn /Strobe
Ceiling and Wall Mount Combination
Description:
Mounting
Back Box
Color
24
4"x4"x1-1/2"
Red
SMD10-3A
24
4"x4"x1-1/2"
Red
The total current draw from all devices connected to the sync module should not exceed
3.0A, and should only be connected to circuits that provide continuously applied voltage.
06/2003
90
G
IN
IL
E
FI
45
45
90
I
F RE
90
90
45
45
TEMPORAL
3000 Hz
20 X 20
30 X 30
40 X 40
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
NA
15 cd.
30 cd.
60 cd.
135 cd.
185 cd.
240 cd.
305 cd.
375 cd.
455 cd.
540 cd.
635 cd.
95 cd.
95 cd.
135 cd.
185 cd.
240 cd.
240 cd.
305 cd.
375 cd.
Four Strobes
per Room
NA
NA
15 cd.
30 cd.
30 cd.
60 cd.
60 cd.
95 cd.
95 cd.
135 cd.
135 cd.
185 cd.
FI
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
Strobe Signal
Circuit
To Next Device or
End-Of Line-Resistor
Horn
33V
235
220
235
220
235
220
235
220
16V
511
497
511
497
511
497
511
497
24V
379
366
379
366
379
366
379
366
33V
312
301
312
301
312
301
312
301
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
=0
P
C
3
1
1
1
1
0
0
0
0
P
C
2
1
1
0
0
1
1
0
0
Average Current
P
C
1 16V
1 34
0 17
1 34
0 17
1 34
0 17
1 34
0 17
( mA )
DC
24V
44
25
44
25
44
25
44
25
Sound Output
( dBA@DC)
FWR
33V
49
34
49
34
49
34
49
34
16V
33
19
33
19
33
19
33
19
24V
40
27
40
27
40
27
40
27
33V
45
34
45
34
45
34
45
34
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
DC
Current ( mA )
Average
Strobe only
@ 177cd.
Peak
F.A.C.P.
Horn Signal
Circuit
SMD10-3A
_
H+H
FI
INPUT OUTPUT
_
_
16V
390
596
460
24V
255
438
476
FWR
33V
191
386
508
16V
483
859
788
24V
344
816
828
33V
272
708
716
To Next Device
or End-Of LineResistor
+ _
Dimensions:
Inches (mm)
+
_
To Next Device or
End-Of Line-Resistor
+
Horn
Signal
Circuit
24V
294
275
294
275
294
275
294
275
FI
Strobe
F.A.C.P.
Strobe
Signal
Circuit
419
402
419
402
419
402
419
402
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
To Next Device or
End-Of LineResistor
In-Rush
15 cd.
30 cd.
60 cd.
95 cd.
20X 20
30X 30
40X 40
50X 50
60X 60
70X 70
80X 80
90X 90
100X 100
110X 110
120X 120
130X 130
H+H
OUT
+ _
177cd.
177cd.
110cd.
IN
+ _
50 X 50
30
20
10
SMD10-3A
F.A.C.P.
Signal
Circuit
To Next Device
or End-Of LineResistor
FI
FI
FI
1
0
1
0
1
0
1
0
3-3/8 (85.7)
Ordering Information:
Maximum
Ceiling
Height (ft.)
F.A.C.P.
Signal
Circuit
FI
ST
A
C
FI
FI
LL
A
90
SMS1-3A
ELECTRO
MECHANICAL
Sync Module
I
F RE
Red
White
3000 Hz
Horn
only
I
F RE
60
60
PC1
Volume
NON-TEMP.
Compound
I
F RE
Selectable
Selectable
90
1
1
0
0
1
1
0
0
Sound Output
( dBA@DC)
FWR
FI R E
90
I
F RE
Compound
Model
Number
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
PC2
Tone
ELECTRO
MECHANICAL
Ceiling/Wall
Ceiling/Wall
Housing
Color
RBX-1
SMD10-3A
SMD10-3A
Flash
Rate
(Times/min.)
FI
177
177
Horn
Sound
Output
PC3
Pattern
90
24
24
Mounting
Type
ELECTRO
MECHANICAL
TEMPORAL
3000 Hz
1
1
1
1
0
0
0
0
=1
45
SH24C-177R
SH24C-177W
Sync
Module
RBX-1
ELECTRO
MECHANICAL
NON-TEMP.
3000 Hz
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
DC
Model
Number
Strobe
Output
(Candela)
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Input
Voltage
(VDC)
RBX-1
Ordering Information:
RBX-1
Wiring Terminals:
45
P P P
PC1
C C C
Volume 3 2 1 16V
PC2
Tone
( mA )
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
FI
SPC-1
I
F RE
Features:
SPC-1
90
SPC-1
FI
MEA
FI
SH
Horn
&
Strobe
@
177cd.
Average Current
E MAR
RV I C
PC3
Pattern
=0
FIR
=1
Compound
90
Compound
Octagon
back box
4 square
back box
STI N
A
OF C L IFOR
TE
WA
LL
LI
UL
C
ST
UL
Double gang
back box
Single gang
back box
Horn/Strobe 177cd.
A
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate
NI
Application:
+
_
WARNING:
* The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
1-13/32 (35)
6-7/8 (174)
2-25/32 (70)
3-3/8 (85.7)
Single gang
back box
Engineering Specifications:
Octagon
back box
The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be
designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync
protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4 x 4x 1-1/2 back box. Signaling devices shall be
installed in all sleeping and non-sleeping areas as per plans and specifications.
4 square
back box
SH24C-177
SPC-1
SPC-1
SPC-1
Horn /Strobe
Ceiling and Wall Mount Combination
Description:
Mounting
Back Box
Color
24
4"x4"x1-1/2"
Red
SMD10-3A
24
4"x4"x1-1/2"
Red
The total current draw from all devices connected to the sync module should not exceed
3.0A, and should only be connected to circuits that provide continuously applied voltage.
06/2003
90
G
IN
IL
E
FI
45
45
90
I
F RE
90
90
45
45
TEMPORAL
3000 Hz
20 X 20
30 X 30
40 X 40
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
NA
15 cd.
30 cd.
60 cd.
135 cd.
185 cd.
240 cd.
305 cd.
375 cd.
455 cd.
540 cd.
635 cd.
95 cd.
95 cd.
135 cd.
185 cd.
240 cd.
240 cd.
305 cd.
375 cd.
Four Strobes
per Room
NA
NA
15 cd.
30 cd.
30 cd.
60 cd.
60 cd.
95 cd.
95 cd.
135 cd.
135 cd.
185 cd.
FI
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
Strobe Signal
Circuit
To Next Device or
End-Of Line-Resistor
Horn
33V
235
220
235
220
235
220
235
220
16V
511
497
511
497
511
497
511
497
24V
379
366
379
366
379
366
379
366
33V
312
301
312
301
312
301
312
301
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
=0
P
C
3
1
1
1
1
0
0
0
0
P
C
2
1
1
0
0
1
1
0
0
Average Current
P
C
1 16V
1 34
0 17
1 34
0 17
1 34
0 17
1 34
0 17
( mA )
DC
24V
44
25
44
25
44
25
44
25
Sound Output
( dBA@DC)
FWR
33V
49
34
49
34
49
34
49
34
16V
33
19
33
19
33
19
33
19
24V
40
27
40
27
40
27
40
27
33V
45
34
45
34
45
34
45
34
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
DC
Current ( mA )
Average
Strobe only
@ 177cd.
Peak
F.A.C.P.
Horn Signal
Circuit
SMD10-3A
_
H+H
FI
INPUT OUTPUT
_
_
16V
390
596
460
24V
255
438
476
FWR
33V
191
386
508
16V
483
859
788
24V
344
816
828
33V
272
708
716
To Next Device
or End-Of LineResistor
+ _
Dimensions:
Inches (mm)
+
_
To Next Device or
End-Of Line-Resistor
+
Horn
Signal
Circuit
24V
294
275
294
275
294
275
294
275
FI
Strobe
F.A.C.P.
Strobe
Signal
Circuit
419
402
419
402
419
402
419
402
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
To Next Device or
End-Of LineResistor
In-Rush
15 cd.
30 cd.
60 cd.
95 cd.
20X 20
30X 30
40X 40
50X 50
60X 60
70X 70
80X 80
90X 90
100X 100
110X 110
120X 120
130X 130
H+H
OUT
+ _
177cd.
177cd.
110cd.
IN
+ _
50 X 50
30
20
10
SMD10-3A
F.A.C.P.
Signal
Circuit
To Next Device
or End-Of LineResistor
FI
FI
FI
1
0
1
0
1
0
1
0
3-3/8 (85.7)
Ordering Information:
Maximum
Ceiling
Height (ft.)
F.A.C.P.
Signal
Circuit
FI
ST
A
C
FI
FI
LL
A
90
SMS1-3A
ELECTRO
MECHANICAL
Sync Module
I
F RE
Red
White
3000 Hz
Horn
only
I
F RE
60
60
PC1
Volume
NON-TEMP.
Compound
I
F RE
Selectable
Selectable
90
1
1
0
0
1
1
0
0
Sound Output
( dBA@DC)
FWR
FI R E
90
I
F RE
Compound
Model
Number
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
PC2
Tone
ELECTRO
MECHANICAL
Ceiling/Wall
Ceiling/Wall
Housing
Color
RBX-1
SMD10-3A
SMD10-3A
Flash
Rate
(Times/min.)
FI
177
177
Horn
Sound
Output
PC3
Pattern
90
24
24
Mounting
Type
ELECTRO
MECHANICAL
TEMPORAL
3000 Hz
1
1
1
1
0
0
0
0
=1
45
SH24C-177R
SH24C-177W
Sync
Module
RBX-1
ELECTRO
MECHANICAL
NON-TEMP.
3000 Hz
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
DC
Model
Number
Strobe
Output
(Candela)
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Input
Voltage
(VDC)
RBX-1
Ordering Information:
RBX-1
Wiring Terminals:
45
P P P
PC1
C C C
Volume 3 2 1 16V
PC2
Tone
( mA )
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
FI
SPC-1
I
F RE
Features:
SPC-1
90
SPC-1
FI
MEA
FI
SH
Horn
&
Strobe
@
177cd.
Average Current
E MAR
RV I C
PC3
Pattern
=0
FIR
=1
Compound
90
Compound
Octagon
back box
4 square
back box
STI N
A
OF C L IFOR
TE
WA
LL
LI
UL
C
ST
UL
Double gang
back box
Single gang
back box
Horn/Strobe 177cd.
A
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate
NI
Application:
+
_
WARNING:
* The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
1-13/32 (35)
6-7/8 (174)
2-25/32 (70)
3-3/8 (85.7)
Single gang
back box
Engineering Specifications:
Octagon
back box
The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be
designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync
protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4 x 4x 1-1/2 back box. Signaling devices shall be
installed in all sleeping and non-sleeping areas as per plans and specifications.
4 square
back box
SH24C-177
SPC-1
SPC-1
SPC-1
Horn /Strobe
Ceiling and Wall Mount Combination
Description:
Mounting
Back Box
Color
24
4"x4"x1-1/2"
Red
SMD10-3A
24
4"x4"x1-1/2"
Red
The total current draw from all devices connected to the sync module should not exceed
3.0A, and should only be connected to circuits that provide continuously applied voltage.
06/2003
90
G
IN
IL
E
FI
45
45
90
I
F RE
90
90
45
45
TEMPORAL
3000 Hz
20 X 20
30 X 30
40 X 40
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
NA
15 cd.
30 cd.
60 cd.
135 cd.
185 cd.
240 cd.
305 cd.
375 cd.
455 cd.
540 cd.
635 cd.
95 cd.
95 cd.
135 cd.
185 cd.
240 cd.
240 cd.
305 cd.
375 cd.
Four Strobes
per Room
NA
NA
15 cd.
30 cd.
30 cd.
60 cd.
60 cd.
95 cd.
95 cd.
135 cd.
135 cd.
185 cd.
FI
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
Strobe Signal
Circuit
To Next Device or
End-Of Line-Resistor
Horn
33V
235
220
235
220
235
220
235
220
16V
511
497
511
497
511
497
511
497
24V
379
366
379
366
379
366
379
366
33V
312
301
312
301
312
301
312
301
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
=0
P
C
3
1
1
1
1
0
0
0
0
P
C
2
1
1
0
0
1
1
0
0
Average Current
P
C
1 16V
1 34
0 17
1 34
0 17
1 34
0 17
1 34
0 17
( mA )
DC
24V
44
25
44
25
44
25
44
25
Sound Output
( dBA@DC)
FWR
33V
49
34
49
34
49
34
49
34
16V
33
19
33
19
33
19
33
19
24V
40
27
40
27
40
27
40
27
33V
45
34
45
34
45
34
45
34
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
DC
Current ( mA )
Average
Strobe only
@ 177cd.
Peak
F.A.C.P.
Horn Signal
Circuit
SMD10-3A
_
H+H
FI
INPUT OUTPUT
_
_
16V
390
596
460
24V
255
438
476
FWR
33V
191
386
508
16V
483
859
788
24V
344
816
828
33V
272
708
716
To Next Device
or End-Of LineResistor
+ _
Dimensions:
Inches (mm)
+
_
To Next Device or
End-Of Line-Resistor
+
Horn
Signal
Circuit
24V
294
275
294
275
294
275
294
275
FI
Strobe
F.A.C.P.
Strobe
Signal
Circuit
419
402
419
402
419
402
419
402
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
To Next Device or
End-Of LineResistor
In-Rush
15 cd.
30 cd.
60 cd.
95 cd.
20X 20
30X 30
40X 40
50X 50
60X 60
70X 70
80X 80
90X 90
100X 100
110X 110
120X 120
130X 130
H+H
OUT
+ _
177cd.
177cd.
110cd.
IN
+ _
50 X 50
30
20
10
SMD10-3A
F.A.C.P.
Signal
Circuit
To Next Device
or End-Of LineResistor
FI
FI
FI
1
0
1
0
1
0
1
0
3-3/8 (85.7)
Ordering Information:
Maximum
Ceiling
Height (ft.)
F.A.C.P.
Signal
Circuit
FI
ST
A
C
FI
FI
LL
A
90
SMS1-3A
ELECTRO
MECHANICAL
Sync Module
I
F RE
Red
White
3000 Hz
Horn
only
I
F RE
60
60
PC1
Volume
NON-TEMP.
Compound
I
F RE
Selectable
Selectable
90
1
1
0
0
1
1
0
0
Sound Output
( dBA@DC)
FWR
FI R E
90
I
F RE
Compound
Model
Number
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
PC2
Tone
ELECTRO
MECHANICAL
Ceiling/Wall
Ceiling/Wall
Housing
Color
RBX-1
SMD10-3A
SMD10-3A
Flash
Rate
(Times/min.)
FI
177
177
Horn
Sound
Output
PC3
Pattern
90
24
24
Mounting
Type
ELECTRO
MECHANICAL
TEMPORAL
3000 Hz
1
1
1
1
0
0
0
0
=1
45
SH24C-177R
SH24C-177W
Sync
Module
RBX-1
ELECTRO
MECHANICAL
NON-TEMP.
3000 Hz
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
DC
Model
Number
Strobe
Output
(Candela)
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Input
Voltage
(VDC)
RBX-1
Ordering Information:
RBX-1
Wiring Terminals:
45
P P P
PC1
C C C
Volume 3 2 1 16V
PC2
Tone
( mA )
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
FI
SPC-1
I
F RE
Features:
SPC-1
90
SPC-1
FI
MEA
FI
SH
Horn
&
Strobe
@
177cd.
Average Current
E MAR
RV I C
PC3
Pattern
=0
FIR
=1
Compound
90
Compound
Octagon
back box
4 square
back box
STI N
A
OF C L IFOR
TE
WA
LL
LI
UL
C
ST
UL
Double gang
back box
Single gang
back box
Horn/Strobe 177cd.
A
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate
NI
Application:
+
_
WARNING:
* The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
1-13/32 (35)
6-7/8 (174)
2-25/32 (70)
3-3/8 (85.7)
Single gang
back box
Engineering Specifications:
Octagon
back box
The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be
designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync
protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4 x 4x 1-1/2 back box. Signaling devices shall be
installed in all sleeping and non-sleeping areas as per plans and specifications.
4 square
back box
SH24C-177
SPC-1
SPC-1
SPC-1
Horn /Strobe
Ceiling and Wall Mount Combination
Description:
Mounting
Back Box
Color
24
4"x4"x1-1/2"
Red
SMD10-3A
24
4"x4"x1-1/2"
Red
The total current draw from all devices connected to the sync module should not exceed
3.0A, and should only be connected to circuits that provide continuously applied voltage.
06/2003
90
G
IN
IL
E
FI
45
45
90
I
F RE
90
90
45
45
TEMPORAL
3000 Hz
20 X 20
30 X 30
40 X 40
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
NA
15 cd.
30 cd.
60 cd.
135 cd.
185 cd.
240 cd.
305 cd.
375 cd.
455 cd.
540 cd.
635 cd.
95 cd.
95 cd.
135 cd.
185 cd.
240 cd.
240 cd.
305 cd.
375 cd.
Four Strobes
per Room
NA
NA
15 cd.
30 cd.
30 cd.
60 cd.
60 cd.
95 cd.
95 cd.
135 cd.
135 cd.
185 cd.
FI
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
Strobe Signal
Circuit
To Next Device or
End-Of Line-Resistor
Horn
33V
235
220
235
220
235
220
235
220
16V
511
497
511
497
511
497
511
497
24V
379
366
379
366
379
366
379
366
33V
312
301
312
301
312
301
312
301
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
=0
P
C
3
1
1
1
1
0
0
0
0
P
C
2
1
1
0
0
1
1
0
0
Average Current
P
C
1 16V
1 34
0 17
1 34
0 17
1 34
0 17
1 34
0 17
( mA )
DC
24V
44
25
44
25
44
25
44
25
Sound Output
( dBA@DC)
FWR
33V
49
34
49
34
49
34
49
34
16V
33
19
33
19
33
19
33
19
24V
40
27
40
27
40
27
40
27
33V
45
34
45
34
45
34
45
34
16V
86
76
87
77
80
*1
73
82
*2
74
24V
88
80
88
81
84
76
84
77
33V
88
83
88
83
84
79
84
79
DC
Current ( mA )
Average
Strobe only
@ 177cd.
Peak
F.A.C.P.
Horn Signal
Circuit
SMD10-3A
_
H+H
FI
INPUT OUTPUT
_
_
16V
390
596
460
24V
255
438
476
FWR
33V
191
386
508
16V
483
859
788
24V
344
816
828
33V
272
708
716
To Next Device
or End-Of LineResistor
+ _
Dimensions:
Inches (mm)
+
_
To Next Device or
End-Of Line-Resistor
+
Horn
Signal
Circuit
24V
294
275
294
275
294
275
294
275
FI
Strobe
F.A.C.P.
Strobe
Signal
Circuit
419
402
419
402
419
402
419
402
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
To Next Device or
End-Of LineResistor
In-Rush
15 cd.
30 cd.
60 cd.
95 cd.
20X 20
30X 30
40X 40
50X 50
60X 60
70X 70
80X 80
90X 90
100X 100
110X 110
120X 120
130X 130
H+H
OUT
+ _
177cd.
177cd.
110cd.
IN
+ _
50 X 50
30
20
10
SMD10-3A
F.A.C.P.
Signal
Circuit
To Next Device
or End-Of LineResistor
FI
FI
FI
1
0
1
0
1
0
1
0
3-3/8 (85.7)
Ordering Information:
Maximum
Ceiling
Height (ft.)
F.A.C.P.
Signal
Circuit
FI
ST
A
C
FI
FI
LL
A
90
SMS1-3A
ELECTRO
MECHANICAL
Sync Module
I
F RE
Red
White
3000 Hz
Horn
only
I
F RE
60
60
PC1
Volume
NON-TEMP.
Compound
I
F RE
Selectable
Selectable
90
1
1
0
0
1
1
0
0
Sound Output
( dBA@DC)
FWR
FI R E
90
I
F RE
Compound
Model
Number
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
PC2
Tone
ELECTRO
MECHANICAL
Ceiling/Wall
Ceiling/Wall
Housing
Color
RBX-1
SMD10-3A
SMD10-3A
Flash
Rate
(Times/min.)
FI
177
177
Horn
Sound
Output
PC3
Pattern
90
24
24
Mounting
Type
ELECTRO
MECHANICAL
TEMPORAL
3000 Hz
1
1
1
1
0
0
0
0
=1
45
SH24C-177R
SH24C-177W
Sync
Module
RBX-1
ELECTRO
MECHANICAL
NON-TEMP.
3000 Hz
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
DC
Model
Number
Strobe
Output
(Candela)
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Input
Voltage
(VDC)
RBX-1
Ordering Information:
RBX-1
Wiring Terminals:
45
P P P
PC1
C C C
Volume 3 2 1 16V
PC2
Tone
( mA )
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
FI
SPC-1
I
F RE
Features:
SPC-1
90
SPC-1
FI
MEA
FI
SH
Horn
&
Strobe
@
177cd.
Average Current
E MAR
RV I C
PC3
Pattern
=0
FIR
=1
Compound
90
Compound
Octagon
back box
4 square
back box
STI N
A
OF C L IFOR
TE
WA
LL
LI
UL
C
ST
UL
Double gang
back box
Single gang
back box
Horn/Strobe 177cd.
A
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate
NI
Application:
+
_
WARNING:
* The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
1-13/32 (35)
6-7/8 (174)
2-25/32 (70)
3-3/8 (85.7)
SH24C-3075110
Application:
UL
UL
C
Features:
MEA
Wiring Terminals:
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Ordering Information:
Model
Number
SH24C-3075110R
SH24C-3075110W
Input
Voltage
(VDC)
Strobe
Candela
(Selectable)
Sync
Module
Mounting
Type
Horn
Sound
Output
Flash
Rate
(Times/min.)
Housing
Color
24
24
SMD10-3A
SMD10-3A
Ceiling/Wall
Ceiling/Wall
Selectable
Selectable
60
60
Red
White
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C
06/2003
Double gang
back box
Single gang
back box
Octagon
back box
4 square
back box
SPC-1
SPC-1
SPC-1
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate
Double gang
back box
Single gang
back box
Octagon
back box
4 square
back box
SPC-1
RBX-1
SPC-1
SPC-1
RBX-1
RBX-1
RBX-1
Room Spacing for Wall-Mounted Visible Appliances Minimum Light Output by room Size (Non-Sleeping)
Maximum One Strobe Two Strobes
Room
per Room
per Room
Size
15 cd.
20X 20
NA
30X 30
15 cd.
30 cd.
30 cd.
60 cd.
40X 40
60 cd.
95 cd.
50X 50
95 cd.
135 cd.
60X 60
70X 70
95 cd.
185 cd.
Four Strobes
per Room
NA
NA
15 cd.
30 cd.
30 cd.
60 cd.
40 X 40
50 X 50
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
177cd.
177cd.
110cd.
inches (mm)
3-3/8 (85.7)
Dimensions:
20 X 20
75cd.
30cd.
30cd.
30
20
10
60 cd.
95 cd.
95 cd.
135 cd.
135 cd.
185 cd.
Maximum
Ceiling
Height (ft.)
Four Strobes
per Room
1-13/32 (35)
6-7/8 (174)
2-25/32 (70)
3-3/8 (85.7)
Engineering Specifications:
The audible and visual alarm indicating appliance shall be AMSECO model SH24C-3075110 or equivalent device. The Strobe shall be
listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having three (3) settings 30cd, 75cd and 110cd output. All settings shall be UL1971 listed for both
ceiling and wall mount applications. The Horn shall provide two different field selectable tones, and a High and Low field selectable sound
output setting. The signaling Horn/Strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered
supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with continuously applied minimum
voltage. When strobe synchronization is required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy
chain) or other source of AMSECO sync protocol. The Horn/Strobe shall be capable of CEILING and WALL mount to a variety of back
boxes using the AMSECO SPC-1 retrofit back plate.
Signaling devices shall be installed in all non-sleeping areas as per plans and specifications.
90
90
90
C
E
IL
IN
G
90
Compound
I
F RE
FI
FI
FI
45
45
90
FI
Compound
FI
I
F RE
90
90
FI R E
FI
45
45
90
Compound
45
45
90
90
Compound
Sync Module
SMD10-3A
_
H+H
IN
OUT
FI
FI
FI
To Next Device or
End-Of LineResistor
F.A.C.P.
Signal
Circuit
To Next Device
or End-Of LineResistor
+ _
FI R E
FI
F.A.C.P.
Signal
Circuit
I
F RE
+ _
Sync Module
I
F RE
F.A.C.P.
Strobe
Signal
Circuit
Horn
_
H+H
FI
FI
INPUT OUTPUT
_
_
To Next Device
or End-Of LineResistor
+ _
+
_
To Next Device or
End-Of Line-Resistor
+
Horn
Signal
Circuit
SMD10-3A
To Next Device or
End-Of Line-Resistor
Strobe
F.A.C.P.
Horn Signal
Circuit
Strobe Signal
Circuit
I
F RE
FI
FI
+
_
WARNING:
* The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
Horn
&
Strobe
@
30cd
PC1
Volume
PC2
Tone
NON-TEMP
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
Electro
Mechanical
3000 Hz
TEMPORAL
Electro
Mechanical
3000 Hz
Electro
Mechanical
Horn
3000 Hz
&
Strobe
Electro
@
Mechanical
75cd TEMPORAL
NON-TEMP
3000 Hz
High
Low
High
Low
High
Low
High
Low
Electro
Mechanical
Horn
3000 Hz
&
Strobe
Electro
@
Mechanical
110cd TEMPORAL
NON-TEMP
3000 Hz
=0
P P
C C
3 2
P
C
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
0
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
Sound Output
( dBA @ DC )
FWR
DC
16V
24V
33V
16V
24V
33V
16V
24V
160
138
129
110
129
110
129
110
129
110
170
151
170
151
170
151
170
151
207
188
207
188
207
188
207
188
116
101
116
101
116
101
116
101
148
133
148
133
148
133
148
133
173
158
173
158
173
158
173
158
203
189
203
189
203
189
203
189
276
262
276
262
276
262
276
262
348
334
348
334
348
334
348
334
171
158
171
158
171
158
171
158
221
208
221
208
221
208
221
208
270
257
270
257
270
257
270
257
153
142
153
142
153
142
153
142
195
184
195
184
195
184
195
184
232
221
232
221
232
221
232
221
86
76
87
77
80
73
82
74
86
76
87
77
80
73
82
74
86
76
87
77
80
73
82
74
88
80
88
81
84
76
84
77
88
80
88
81
84
76
84
77
88
80
88
81
84
76
84
77
160
138
0
1
0
1
0
1
0
1
160
138
160
138
218
201
218
201
0
1
0
1
0
1
0
1
218
201
218
201
273
256
273
256
273
256
273
256
0
1
0
1
0
*1
*2
*1
*2
*1
*2
33V
88
83
88
83
84
79
84
79
88
83
88
83
84
79
84
79
88
83
88
83
84
79
84
79
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
PC1
Volume
PC2
Tone
Electro
Mechanical
NON-TEMP
3000 Hz
Horn
Only
Electro
Mechanical
TEMPORAL
3000 Hz
High
Low
High
Low
High
Low
High
Low
=0
P P
C C
3 2
1 1
1 1
1 0
1 0
0 1
0 1
0 0
0 0
P
C
1
1
0
1
0
1
0
1
0
Sound Output
( dBA @ DC )
FWR
DC
16V
24V
33V
16V
24V
33V
16V
24V
33V
34
17
34
17
34
17
34
17
44
25
44
25
44
25
44
25
49
34
49
34
49
34
49
34
33
19
33
19
33
19
33
19
40
27
40
27
40
27
40
27
45
34
45
34
45
34
45
34
86
76
87
77
80
88
80
88
81
84
76
84
77
88
83
88
83
84
79
84
79
*1
*2
73
82
74
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
DC
Current (mA)
16V
@ 30cd
Strobe
Only
@ 75cd
@ 110cd
Average
Peak
In-Rush
Average
Peak
In-Rush
Average
Peak
In-Rush
24V
33V
16V
24V
33V
126
225
90
218
298
131
222
342
168
288
398
72
175
167
338
104
212
374
129
208
430
421
402
248
562
540
320
680
644
136
355
418
186
464
478
235
572
580
113
341
458
155
454
498
192
532
548
254
189
304
306
244
418
386
SH24W-153075
Patented
F
I
R
E
TI
IS N
L
ST
A
O F C A L I FO
R
LL
TE
FIR
E MA R
SH
TE
APPROVED
RVI C
MEA
Features:
* Designed to meet or exceed NFPA/ANSI Standards and ADA
Accessibility Guidelines.
* UL listed for wall mounting.
* Screw terminal capacity up to 12 AWG.
* Universal mounting plate included with each unit.
* 24V DC strobe with two field selectable settings 15cd or 30cd.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Horn field selectable tones:
3000 Hz interrupted or Electro-mechanical
Temporal or Non-temporal
High or Low dBA output
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4 square, single gang, double gang, or
octagonal back box.
* 24 volt strobe models 15 or 30 candela intensity.
* Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMD10-3A Sync Module.
* Available in red or white housing.
15
cd
FM
UL
C
ST
UL
A
NI
Application:
30
cd
15
30
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Tamper Proof
Ordering Information:
Mounting
Type
Horn
Sound
Output
Wiring
Type
Housing
Color
SH24W-153075R
Input
Voltage
(VDC)
24
Selectable
Strobe Output
(Candela)
15 or 30
SMD10-3A
Wall Only
Selectable
Terminals
Red
SH24W-153075W
24
15 or 30
SMD10-3A
Wall Only
Selectable
Terminals
White
Model
Number
Sync
Module
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
Specifications subject to change without notice.
06/2003
Mounting Options:
Strobe with Universal mounting
plate and single gang box.
F
I
R
E
Horn/Strobe
F
I
R
E
Horn/Strobe
4 x 4 x 1-1/2
back box
4 x 4 x 1-1/2
back box
2 back box
F
I
R
E
F
I
R
E
Horn/Strobe
4SP-M
Mounting
Plate
4BX-1
Surface Mount
back box
Horn/Strobe
Inches (mm)
Dimensions:
3 3/8(85.7)
2 1/4(56.9)
5 (127)
3 9/32(83.5)
3 9/32(83.5)
5 (127)
3 3/8(85.7)
1 13/16(46)
Inch (mm)
4.33 (110)
0.2 (5)
3.374 (85.7)
3.374 (85.7)
4.33 (110)
Ordering Information:
Model
Number
SMD10-3A
Mounting
Back Box
Color
4"x4"x1-1/2"
Red
The total current draw from all devices connected to the SMD10-3A should not exceed 3.0A.
The SMD10-3A should only be connected to circuits that provide continuously applied voltage.
Average
DC
FWR
Mounting:
Peak
In-Rush
DC
FWR
DC
FWR
16V
7mA
7mA
30mA
55mA
40mA
57mA
24V
9mA
9mA
32mA
62mA
52mA
75mA
33V
11mA
11mA
34mA
68mA
74mA
99mA
The SMD10-3A module is listed for indoor use with a temperature operating
range of 32 F ~ 120 F ( 0 C ~ 49 C ).
SMD10-3A
Engineering Specifications:
The audible and visual alarm indicating appliance shall be AMSECO model SH24W-153075 or equivalent device. The Strobe shall be
listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having a dual setting of 15cd or 30cd output. The Horn shall provide two different field
selectable tones and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall operate on 24VDC from a
non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal
flash of one flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of WALL mounting to a
universal backbox. Visual signaling devices shall be mounted 80 above the highest floor point or 6 below ceiling; (whichever is lowest)
and are to be installed as per plans and specifications.
45
WALL
90
90
90
45
90
Compound 45
Degrees
+90
+60
+30
0
-30
-60
-90
WALL
90
SMD10-3A
H+ H
IN
To Next Device or
End-Of Line-Resistor
F
I
R
E
OUT
_
+ _
To Next Device or
End-Of Line-Resistor
F
I
R
E
+ _
*The Sync module is rated for 3.0 amperes at 24 VDC.
F.A.C.P.
Strobe Signal
Circuit
F.A.C.P.
Strobe Signal
Circuit
F
I
R
E
To Next Device or
End-Of Line-Resistor
Strobe
Horn
F.A.C.P.
Horn Signal
Circuit
F.A.C.P.
Horn Signal
Circuit
SMD10-3A
_
H+H
IN
_
F
I
R
E
OUT
_
To Next Device or
End-Of Line-Resistor
To Next Device or
End-Of Line-Resistor
WARNING:
* Strobes must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted
Circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
Horn
&
Strobe
@
15cd
PC1
Volume
PC2
Tone
NON-TEMP
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
Electro
Mechanical
3000 Hz
TEMPORAL
=1
Electro
Mechanical
3000 Hz
Electro
Mechanical
Horn NON-TEMP
3000 Hz
&
Strobe
Electro
@
Mechanical
30cd TEMPORAL
3000 Hz
=0
P P
C C
3 2
P
C
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
0
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
24V
112
109
98
91
111
85
98
91
111
85
130
123
143
117
130
123
143
117
118
106
0
1
0
1
0
1
0
1
112
109
118
106
158
155
164
152
0
1
0
1
0
158
155
164
152
Sound Output
( dBA @ DC )
FWR
DC
33V
96
83
108
83
96
83
108
83
133
108
146
108
133
108
146
108
16V
24V
33V
145
142
153
139
145
142
153
139
207
204
215
201
207
204
215
201
115
110
128
105
115
110
128
105
157
152
170
147
157
152
170
147
142
95
119
89
142
95
119
89
168
121
145
115
168
121
145
115
16V
*1
*2
*1
*2
24V
85
75
85
75
81
71
80
71
85
75
85
75
81
71
80
71
87
78
88
78
83
75
83
75
87
78
88
78
83
75
83
75
33V
88
81
88
81
84
77
84
77
88
81
88
81
84
77
84
77
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
PC1
Volume
PC2
Tone
Electro
Mechanical
NON-TEMP
3000 Hz
Horn
Only
Electro
Mechanical
TEMPORAL
3000 Hz
High
Low
High
Low
High
Low
High
Low
=0
P P
C C
3 2
1 1
1 1
1 0
1 0
0 1
0 1
0 0
0 0
P
C
1
24V
33V
28
25
34
22
28
25
34
22
41
34
54
28
41
34
54
28
57
42
70
36
57
42
70
36
1
0
1
0
1
0
1
0
Sound Output
( dBA @ DC )
FWR
DC
16V
24V
33V
30
27
38
24
30
27
38
24
41
36
54
31
41
36
54
31
91
44
68
38
91
44
68
38
16V
*2
33V
85
75
85
75
81
*1
24V
87
78
88
78
83
75
83
75
88
81
88
81
84
77
84
77
71
80
71
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).
DC
Current (mA)
16V
Strobe
Only
@ 30cd
@ 75cd
Average
Peak
In-Rush
Average
Peak
In-Rush
24V
33V
16V
24V
33V
89
127
64
103
103
96
134
135
50
125
87
119
75
119
223
269
269
187
377
377
94
229
229
136
306
306
81
210
210
107
269
269
127
135
170
170
Room Spacing for Wall-Mounted Visible Appliances Minimum Light Output by room Size (Non-Sleeping)
15 cd.
30 cd.
60 cd.
95 cd.
NA
15 cd.
30 cd.
60 cd.
135 cd.
185 cd.
95 cd.
95 cd.
Four Strobes
per Room
NA
NA
15 cd.
30 cd.
30 cd.
60 cd.
Maximum
Room
Size
80X 80
90X 90
100X 100
110X 110
120X 120
130X 130
135 cd.
185 cd.
240 cd.
240 cd.
305 cd.
375 cd.
Four Strobes
per Room
60 cd.
95 cd.
95 cd.
135 cd.
135 cd.
185 cd.
SH24W-75110
Select -A- Horn /Strobe
TM
Patented
Combination
Description:
FO
LL
F IR
E MAR
SH
ST
A
O
TE
F
I
R
E
APPROVED
RV I C
MEA
A DA
Features:
* Designed to meet or exceed NFPA/ANSI Standards and ADA
Accessibility Guidelines.
* UL listed for wall mounting.
* Screw terminal capacity up to 12 AWG.
* Universal mounting plate included with each unit.
* 24V DC strobe with field selectable settings 75cd or 110cd.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Horn field selectable tones:
3000 Hz interrupted or Electro-mechanical
Temporal or Non-temporal
High or Low dBA output
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4 square, single gang, double gang, or.
octagonal back box.
* 24 volt strobe models 75 or 110 candela intensity.
* Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMS1-3A Sync Module.
* Available in red or white housing.
75
cd
FM
ST
STI N
LI F CA LI
UL
C
UL
NI
Application:
11
0cd
75
11
0
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Tamper Proof
Ordering Information:
Model
Number
Input
Voltage
(VDC)
Selectable
Strobe Output
(Candela)
Sync
Module
Mounting
Type
Horn
Sound
Output
Wiring
Type
Housing
Color
SH24W-75110R
24
75 or 110
SMS1-3A
Wall Only
Selectable
Terminals
Red
SH24W-75110W
24
75 or 110
SMS1-3A
Wall Only
Selectable
Terminals
White
06/2003
Engineering Specifications:
The audible and visual alarm indicating appliance shall be AMSECO model SH24W-75110 or equivalent device. The Strobe shall
be listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service.
The candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The Horn shall provide two different
field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall operate on
24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to
produce a signal flash of one flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of
WALL mounting to a universal backbox. Visual signaling devices shall be mounted 80 above the highest floor point or 6 below
ceiling; (whichever is lowest) and are to be installed as per plans and specifications.
45
45
Compound 45
90
45
Compound 45
WALL
90
Degrees
+90
+60
+30
0
-30
-60
-90
90
0
90
Wired Without Audible Silence Feature:
F.A.C.P.
Signal
Circuit_
To Next Device or
End-Of Line-Resistor
F
I
R
E
WALL
90
SMS1-3A
_
H+H
IN_
OUT
_
To Next Device or
End-Of Line-Resistor
F
I
R
E
+ _
+ _
F.A.C.P.
Strobe Signal
Circuit
To Next Device or
End-Of Line-Resistor
F.A.C.P.
Horn Signal
Circuit
Strobe
Horn
F
I
R
E
F.A.C.P.
Strobe Signal
Circuit
F.A.C.P.
Horn Signal
Circuit
SMS1-3A
_
H+H
IN
OUT
_
F
I
R
E
To Next Device or
End-Of Line-Resistor
+ _
To Next Device or
End-Of Line-Resistor
WARNING:
* Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted
circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
NON-TEMP
Electro
Mechanical
3000 Hz
@
75cd
TEMPORAL
Electro
Mechanical
3000 Hz
NON-TEMP
Electro
Mechanical
3000 Hz
@
110cd
Electro
Mechanical
TEMPORAL
3000 Hz
Electro
Mechanical
NON-TEMP
Horn
Only
3000 Hz
Electro
Mechanical
TEMPORAL
3000 Hz
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
P P
C C
3 2
P
C
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
PC1
Volume
PC2
Tone
1
0
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Sound Output
( dBA @ DC )
FWR
DC
24V
33V
144
157
144
157
144
157
144
35
22
35
22
35
22
35
22
16V
24V
33V
16V
24V
33V
115
102
115
102
115
102
115
102
141
128
141
128
141
128
141
128
52
39
52
39
52
39
52
39
125
112
125
112
125
112
125
112
157
212
199
212
199
212
199
212
199
277
264
159
144
159
144
159
144
159
144
205
145
120
145
120
145
120
145
120
173
148
173
148
173
148
173
148
64
39
64
39
64
39
64
39
85
75
85
75
81
71
80
71
85
75
87
78
88
78
83
75
83
75
87
78
88
78
83
75
83
75
87
78
88
78
83
75
83
75
88
81
88
81
84
77
84
77
88
81
88
81
84
77
84
77
88
81
88
81
84
77
84
77
190
205
190
205
190
205
190
45
30
45
30
45
30
45
30
277
264
277
264
277
264
36
23
36
23
36
23
36
23
85
75
81
71
80
71
85
75
85
75
81
71
80
71
24V
16V
24V
16V
24V
33V
75
138 186
134
75 111
75
75
110
98 139
110
110
97
The SH24W-75110 series horn/strobe is listed for indoor use with a temperature operating range of 32 F ~ 120 F ( 0 C ~ 49 C ).
Dimensions:
Inches (mm)
3 3/8(85.7)
2 1/4(56.9)
5(127)
3 9/32(83.5)
3 9/32(83.5)
5(127)
3 3/8(85.7)
1 13/16(46)
Mounting Options:
Horn/Strobe with Universal mounting
plate and single gang box.
Horn/Strobe
F
I
R
E
Horn/Strobe
4 x 4 x 1-1/2
backbox
4 x 4 x 1-1/2
backbox
2 backbox
F
I
R
E
F
I
R
E
Horn/Strobe
F
I
R
E
Horn/Strobe
4SP-M
Mounting
Plate
4BX-1
Surface Mount
back box
SMS1-3A
Sync Module
When used with the SH24W Horn/Strobe Series the SMS1-3A
provides synchronized temporal pattern and a synchronized
strobe flash while using a single pair of wires on a single class
"A" circuit.
SMS1-3A Sync Module
Mounting
Back Box
LL
FIR
E MA R
SH
RVI C
MEA
Color
4"x4"x1-1/2"
Average
Current
(mA)
9
FO
R
Maximum
Load
(Amps)
3
TE
ST
SMS1-3A
Input
Voltage
(VDC)
24
IA
APPROVED
Model Number
TE
FM
ST
A
I STI N
L F CALI
UL
C
UL
Red
* The total current draw from all devices connected to the SMS1-3A should not exceed 3.0A.
**The SMS1-3A should only be connected to circuits that provide continuously applied voltage.
Average
Peak
In-Rush
DC
FWR
DC
FWR
DC
FWR
20V
8mA
8mA
31mA
57mA
44mA
62mA
24V
9mA
9mA
32mA
62mA
52mA
75mA
30V
10mA
10mA
33mA
66mA
70mA
94mA
Mounting:
Dimensions:
Inch (mm)
4.33
(110)
0.2
(5)
3.374
(85.7)
4.33
(110)
3.374
(85.7)
4x4X1-1/2
SMS1-3A
SL24C-177
Ceiling and Wall Mount Strobe
Description:
FI
To Next Device
or End-Of LineResistor
LL
ST
A
STI N
OF CA L IFOR
TE
FI R
E MAR
SH
FI
Control
Panel
LI
Strobe Wiring:
UL
C
ST
UL
A
NI
Application:
Strobe 177cd.
G
RV I C
MEA
Features:
* ADA/NFPA/ANSI Compliant.
* UL listed for Ceiling and Wall mounting under UL1971.
* Screw terminal capacity up to 12 AWG.
* 24V DC strobe with 177cd output.
* Polarized strobes with wide listed voltage ranges using
Filtered DC or unfiltered FWR input voltage.
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* Munts to 4 square, back box.
* 24 volt strobe models.
* Designed for sleeping and non/sleeping areas.
* Synchronization requires an AMSECO SMS1-3A or
SMD10-3A (daisy chain) Sync Module.
* RBX-1 back box skirt for surface mount (optional)
* The SPC-1 retrofit plate allows mounting to a variety of back
boxes (optional).
* Available in red or white housing.
Wiring Terminals:
FI R E
+ _
Current (mA)
Average
@ 177cd
Peak
In-Rush
16V
378
584
460
24V
245
428
476
FWR
33V
185
380
508
16V 24V
468 332
844 804
788 828
33V
264
700
716
Ordering Information:
Model
Number
Input
Voltage
(VDC)
Strobe
Output
(Candela)
Sync
Module
Mounting
Type
Flash
Rate
(Times/min.)
Operating
Voltage Range
(VDC)
Housing
Color
SL24C-177R
SL24C-177W
24
24
177
177
SMD10-3A
SMD10-3A
Ceiling / Wall
Ceiling / Wall
60
60
16 ~ 33
16 ~ 33
Red
White
The strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
Specifications subject to change without notice.
06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24C-177 or equivalent device. The Strobe shall be listed under UL 1971 Standard for
signaling devices for the hearing impaired and shall be approved for fire protective service. The candela output shall be 177cd. The strobe shall be
UL1971 listed for both ceiling and wall mount applications. The signaling Strobe shall operate on 24VDC from a non-coded regulated DC supply or fullwave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with continuously applied
minimum voltage. When strobe synchronization is required, the strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A or other source of
AMSECO sync protocol. The Strobe shall be capable of CEILING and WALL mount ing to a 4 x 4 x 1-1/2 back box. Signaling devices shall be installed
in all sleeping and non/sleeping areas as per plans and specifications.
Compound
90
I
F RE
FI
90
90
I
F RE
FI R E
45
FI
45
FI
FI
45
45
FI
FI
Compound
R
90
90
WA
LL
90
IL
IN
G
90
90
45
Compound
90
Sync Module
H+H
IN
OUT
FI
FI
90
Compound
SMD10-3A
F.A.C.P.
Signal
Circuit
45
To Next Device or
End-Of LineResistor
+ _
Maximum
Ceiling
Height (ft.)
30 X 30
40 X 40
50 X 50
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
177cd.
177cd.
110cd.
I
F RE
30
20
10
Mounting:
*The SPC-1 Universal Retrofit Plate is designed for mounting to a variety of back boxes.
*Surface mount installations, use the RBX-1 Back Box Skirt.
Single gang
back box
Double gang
back box
Octagon
back box
4 square
back box
SPC-1
4 square
back box
SPC-1
SPC-1
RBX-1
RBX-1
RBX-1
Inches (mm)
3-3/8 (85.7)
Dimensions:
RBX-1
6-7/8 (174)
1-13/32 (35)
2-25/32 (70)
3-3/8 (85.7)
SL24C-3075110
Ceiling and Wall Mount
Select -A- Strobe
Description:
AMSECOs Ceiling and Wall mount Select-A-Strobe is designed
to comply with the Americans with Disability Act (ADA) and meet
UL Standard 1971 requirements for emergency signaling
devices for the hearing impaired. The SL24C-3075110 SelectA-Strobe features a unique candela intensity field selector
switch for alternating the candela 30cd, 75cd or 110cd intensity
output. The round housing design offers a low profile
appearance and is clearly labeled with FIRE lettering to be
view from all angles. These appliances are polarized for
connecting to supervised fire alarm circuits. The strobe is
designed with a xenon flashtube and provides a candela
intensity field selector switch for maximum performance. The
Ceiling/Wall mount Select-A-Strobe series is available in red
and white housing 24V DC models. The SL24C-3075110 can be
synchronized by using the SMD10-3A (daisy chain) Sync
Module to comply with NFPA recommendations concerning
photosensitive epilepsy when installing 2 or more visual
appliances within the field of view. The strobe signals are
designed for non-sleeping areas and are listed for indoor use,
ceiling and wall mount, under UL 1971 Standard.
LL
ST
FI R
E MAR
SH
ST
A
STI N
OF CA L IFOR
TE
A
NI
RV I C
MEA
Features:
* Selectable Candela 30cd, 75cd or 110 candela output.
* ADA/NFPA/ANSI compliant.
* UL listed for Ceiling and Wall mounting under UL1971.
* Designed for use in non-sleeping areas.
* Screw terminal capacity up to 12 AWG.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4 x 4 x 1-1/2 back box.
* Synchronization requires an AMSECO SMD10-3A
(daisy chain) Sync Module.
* RBX-1 back box skirt for surface mount (optional)
* The SPC-1 retrofit plate allows mounting to a variety of back
boxes (optional).
* Available in red or white housing.
Application:
The SL24C-3075110 Ceiling Strobe Series is recommended for
use in areas such as: warehouses, meeting rooms, schools,
corridors, apartments, office buildings, restaurants, hotels, and
any other application where effective visual warning is required
by Federal, State, or local authority having jurisdiction.
LI
UL
C
UL
Strobe Wiring:
FI
FI
To Next Device
or End-Of LineResistor
Control
Panel
_
I
F RE
IT
+ _
d
0c
11
75
30
cd
30
Maximum
Ceiling
Height (ft.)
cd
75
Tamper
proof cap
30 X 30
40 X 40
50 X 50
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
177cd.
177cd.
110cd.
30
20
10
Ordering Information:
Model
Number
Input
Voltage
(VDC)
Strobe
Selectable
(Candela)
Sync
Module
Mounting
Type
SL24C-3075110R
SL24C-3075110W
24
24
SMD10-3A
SMD10-3A
Flash
Operating
Rate
Voltage Range
(Times/min.)
(VDC)
Ceiling / Wall
Ceiling / Wall
60
60
16 ~ 33
16 ~ 33
Housing
Color
Red
White
The strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C ~ 49C )
Specifications subject to change without notice.
06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24C-3075110 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
output shall be field selectable, having three (3) settings 30cd, 75cd and 110cd output. All settings shall be UL1971 listed for both
ceiling and wall mount applications. The signaling Strobe shall operate on 24VDC from a non-coded regulated DC supply or fullwave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with
continuously applied minimum voltage. When strobe synchronization is required, the strobe shall be compatible with the AMSECO
SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync protocol. The Strobe shall be capable of CEILING and WALL
mount to a variety of back boxes using the AMSECO SPC-1 retrofit back plate.
Signaling devices shall be installed in all non-sleeping areas as per plans and specifications.
WA
LL
90
90
45
45
90
I
F RE
FI
FI
E
FI
90
FI
FI
Compound
Compound
I
F RE
I
F RE
90
90
45
FI
45
C
E
IL
IN
G
90
90
@ 75cd
@ 110cd
FWR
16V
121
24V
87
33V
70
16V
168
24V
131
33V
110
221
254
183
298
306
236
410
386
Average
Peak
In-Rush
Average
Peak
In-Rush
Average
Peak
In-Rush
Strobe
90
Compound
DC
Current (mA)
@ 30cd
45
Compound
45
90
215
298
127
218
342
162
282
398
165
338
101
209
374
125
204
430
414
402
240
554
540
310
670
644
350
418
180
458
478
227
564
580
338
458
151
450
498
186
526
548
Mounting:
*The SPC-1 Universal Retrofit Plate is designed for mounting to a variety of back boxes.
*Surface mount installations, use the RBX-1 Back Box Skirt.
Single gang
back box
Double gang
back box
Octagon
back box
4 square
back box
SPC-1
4 square
back box
SPC-1
SPC-1
RBX-1
RBX-1
RBX-1
Dimensions:
RBX-1
Inches (mm)
Sync Module
FI
To Next Device or
End-Of LineResistor
3-3/8 (85.7)
OUT
FI
IN
SMD10-3A
_
H+H
F.A.C.P.
Signal
Circuit
+ _
I
F RE
6-7/8 (174)
1-13/32 (35)
2-25/32 (70)
3-3/8 (85.7)
SL24W-153075
Patented
F CA L IFO
LL
ST
A
APPROVED
I STI N
O
TE
F IR
E MAR
SH
FM
ST
UL
C
UL
NI
Application:
ER
VI C
MEA
A DA
Features:
* Designed to meet or exceed NFPA/ANSI Standards and ADA
Accessibility Guidelines.
* UL listed for wall mounting.
* Screw terminal capacity up to 12 AWG.
* Universal mounting plate included with each unit.
* 24V DC strobe with two field selectable settings 15cd or 30cd.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4 square, single gang, double gang,
or octagonal back box.
* 24 volt strobe models 15 or 30 candela Intensity.
* Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMS1-3A Sync Module.
* Available in red or white housing.
Strobe Wiring:
15
cd
F
I
R
E
Control
Panel
30
cd
To Next Device or
End-Of Line-Resistor
F
I
R
E
+ _
15
30
Conductor size (AWG), length and capacity should be taken into
consideration prior to design and installation.
Tamper Proof
Ordering Information:
Model
Number
Input
Voltage
(VDC)
Selectable
Output
(Candela)
Sync
Module
Compatible
Mounting
Type
Universal
Mounting
Plate
Flash
Per/Min.
Housing
Color
SL24W-153075R
24
15 or 30
SMS1-3A
Wall
Included
60
Red
SL24W-153075W
24
15 or 30
SMS1-3A
Wall
Included
60
White
06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24W-153075 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having a dual setting of 15cd or 30cd output. The signaling Strobe shall operate on 24V
DC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to
produce one signal flash per second with continuously applied minimum voltage. The strobe shall be capable of WALL mounting
to a universal backbox. Visual signaling devices shall be mounted 80 above the highest floor point or 6 below ceiling; whichever
is lowest and are to be installed as per plans and specifications.
45
WALL
WALL
90
90
45
Compound 45
90
90
45
90
Compound 45
@
@
30cd
Dimensions:
16V
Average
Peak
In-Rush
15cd
24V
60
99
100
91
129
135
84
122
122
129
164
164
Average
Peak
In-Rush
inches (mm)
33V
16V
24V
118
264
264
178
368
368
47
84
119
71
115
223
33V
89
224
224
128
298
298
76
205
205
102
264
264
2-1/4 (56.9)
5 (127)
FWR
DC
Current (mA)
3-3/8 (85.7)
3-9/32 (83.5)
3-9/32 (83.5)
5 (127)
3-3/8 (85.7)
1-13/16 (46)
F.A.C.P.
Signal
Circuit_
SMS1-3A
_
H+H
IN_
To Next Device or
End-Of Line-Resistor
F
I
R
E
OUT
_
+ _
*The Sync module is rated for 3.0 amperes at 24 VDC.
Mounting Options:
Strobe with Universal mounting
plate and single gang box.
2 backbox
F
I
R
E
F
I
R
E
Strobe
Strobe
4 x 4 x 1-1/2
backbox
4 x 4 x 1-1/2
backbox
F
I
R
E
F
I
R
E
4BX-1
Surface Mount
back box
4SP-M
Mounting Plate
SL24W-75110
Patented
APPROVED
F CA L IFO
LL
ST
A
I STI N
O
TE
F IR
E MAR
SH
FM
ST
UL
C
UL
NI
Application:
R V IC
MEA
A DA
Features:
* Designed to meet or exceed NFPA/ANSI Standards and ADA
Accessibility Guidelines.
* UL listed for wall mounting.
* Screw terminal capacity up to 12 AWG.
* Universal mounting plate included with each unit.
* 24V DC strobe with field selectable settings 75cd or 110cd.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4 square, single gang, double gang, or
octagonal back box.
* 24 volt strobe models 75 or 110 candela Intensity.
* Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMS1-3A Sync Module.
* Available in red or white housing.
Strobe Wiring:
75
cd
F
I
R
E
Control
Panel
11
0cd
To Next Device or
End-Of Line-Resistor
F
I
R
E
+ _
75
11
0
Conductor size (AWG), length and capacity should be taken into consideration
prior to design and installation.
Tamper Proof
Ordering Information:
Model
Number
Input
Voltage
(VDC)
Selectable
Output
(Candela)
Sync
Module
Compatible
Mounting
Type
Universal
Mounting
Plate
Flash
Per/Min.
Housing
Color
SL24W-75110R
24
75 or 110
SMS1-3A
Wall
Included
60
Red
SL24W-75110W
24
75 or 110
SMS1-3A
Wall
Included
60
White
06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24W-75110 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The signaling Strobe shall operate on
24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to
produce a one signal flash per second with continuously applied minimum voltage. The Strobe shall be capable of WALL mounting
to a universal backbox. Visual signaling devices shall be mounted 80 above the highest floor point or 6 below ceiling; whichever
is lowest and are to be installed as per plans and specifications.
45
WALL
WALL
90
90
45
Compound 45
90
90
45
90
Compound 45
16V
75cd
Average
Peak
In-Rush
110cd
Average
Peak
In-Rush
24V
132
157
157
181
194
194
Dimensions:
92
132
132
122
156
156
inches (mm)
33V
16V
24V
33V
71
108
121
94
127
178
354
354
241
432
432
128
280
280
170
356
356
105
242
242
134
302
302
127
2-1/4 (56.9)
5 (127)
FWR
DC
Current (mA)
3-3/8 (85.7)
3-9/32 (83.5)
3-9/32 (83.5)
5 (127)
3-3/8 (85.7)
1-13/16 (46)
F.A.C.P.
Signal
Circuit_
SMS1-3A
_
H+H
IN_
To Next Device or
End-Of Line-Resistor
F
I
R
E
OUT
_
+ _
*The Sync module is rated for 3.0 amperes at 24 VDC.
Mounting Options:
Strobe with Universal mounting
plate and single gang box.
2 back box
F
I
R
E
F
I
R
E
Strobe
Strobe
4 x 4 x 1-1/2
back box
4 x 4 x 1-1/2
back box
F
I
R
E
F
I
R
E
4BX-1
Surface Mount
back box
4SP-M
Mounting Plate
SSC25-177
SSC70-177
Ceiling and Wall Mount
Speaker/Strobe Combination
Description:
LL
FI R
E MAR
SH
ST
A
RV I C
MEA
Features:
* ADA / NFPA / ANSI Compliant
* UL Listed for Ceiling and Wall mounting under UL 1971
* 177 candela output
* Speaker field selectable taps 1/4w, 1/2w, 1w, 2 watts
* Available 25Vrms and 70.7Vrms models
* Screw terminals capacity up to 12 AWG.
* Frequency range 400 Hz ~ 4,000 Hz.
* Integral blocking capacitor for line supervision
* Polarized strobes with wide listed voltage ranges
using filtered DC or unfiltered FWR input voltage
* Meets ADA guidelines for minimum one flash per/sec (1Hz)
* Strobe is polarized and rated at 24VDC
* Synchronization requires an AMSECO SMD10-3A (daisyChain) Sync Module
* RBX-1back box skirt for surface mount (Optional)
* Available in red or white housing
FI
I
F RE
F.A.C.P &
VOICE / EVAC
Speaker
S+ S _
Application:
Strobe
L+ L _
TO NEXT DEVICE
or END-OF-LINE
-RESISITOR
Sync Module
SMD10-3A
_
H+ H
IN
_
OUT
_
TO NEXT DEVICE
or END-OF-LINE
-RESISITOR
Ordering Information:
SSC25-177R
SSC25-177W
SSC70-177R
SSC70-177W
STI N
OF CA L IFOR
TE
Pending
Strobe Speaker
_ S
_
+
+S
Model
Number
25 = 25Vrms
70 = 70.7Vrms
177 = 177cd
R = Red
W = White
LI
UL
C
ST
SSC25-177R
UL
A
NI
How to Order:
Speaker
Voltage
(Vrms)
Strobe
Output
(Candela)
Sync
Module
Speaker
Selectable Taps
(Watts)
Strobe
Flash Rate
(times/min)
Mounting
Type
Housing
Color
25
25
70.7
70.7
177
177
177
177
SMD10-3A
SMD10-3A
SMD10-3A
SMD10-3A
, , 1, 2
, , 1, 2
, , 1, 2
, , 1, 2
60
60
60
60
Red
White
Red
White
The speaker/strobe is listed for indoor use with a temperature operating range of 32 F ~ 120F (0C ~ 49C )
Specifications subject to change without notice.
06/2003
Engineering Specifications:
The Fire alarm speaker shall be capable of reproducing alarm tones or voice commands on 25Vrms or 70.7Vrms. Speakers shall
provide incremental tap settings of , , 1, and 2 watts and shall be selected by means of a jumper wire. The speaker shall have a
frequency range of 400 to 4,000 Hz. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be
approved for fire alarm signaling use. The Strobe shall be listed under UL 1971 Standard for signaling devices for the hearing impaired
and shall be approved for fire protective service. The candela output shall be 177. The signaling strobe shall operate on 24VDC from a
non-coded regulated DC supply or full-wave rectified, unfiltered supply. The strobe shall be designed to produce one signal flash per
second with continuously applied minimum voltage. When strobe synchronization is required, the strobe shall be compatible with the
AMSECO SMS1-3A, SMD10-3A or other source of AMSECO sync protocol. The Speaker/Strobe shall be capable of WALL or CEILING
mounting. The Visual signaling devices are to be installed in all sleeping and non-sleeping areas as per plans and specifications.
IL
IN
G
90
90
FI
I
F RE
FI
45
45
90
FI
FI
90
FI
Compound
Compound
I
F RE
I
F RE
90
90
45
FI
45
C
E
90
90
45
Compound
Speaker specifications:
45
90
25V
2.5
75
Impedance (k ohms)
Sound Pressure Level (dB/10ft)
Frequency Response (Hz)
1.25
78
70.7V
1
0.62
81
0.31
20
10
84
75
78
400 ~ 4,000
200
32F ~ 120F ( 0C ~ 49C )
@177cd
Average
Peak
In-Rush
16V
378
584
460
DC
24V
245
428
476
1
5
81
2
2.5
84
90
Compound
33V 16V
185 468
380 844
508 788
FWR
24V
332
804
828
33V
264
700
716
Maximum
Ceiling
Height (ft.)
30 X 30
40 X 40
50 X 50
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
177cd.
177cd.
110cd.
30
20
10
Surface Mount
Mounting:
4 square
x 2-1/8 deep
back box.
Dimensions:
Inches (mm)
1 (25.5)
3-3/8 (85.7)
I
F RE
1-49/64 (45)
2-25/32 (70)
FI
6-7/8 (174)
FI
3-3/8 (85.7)
RBX-1
back box
skirt
(Optional)
SSC25-3075110
SSC70-3075110
Ceiling and Wall Mount
Select -A- Speaker/Strobe Combination
Description:
FIR
MEA
ST
A
STI N
OF C A L IFOR
LL
TE
E MA R
SH
25 = 25Vrms
70 = 70.7Vrms
3075110 = 30cd, 75cd or 110cd
R = Red
W = White
ST
SSC25-3075110R
LI
UL ULC
A
NI
How to Order:
AMSECOs ceiling and wall mount fire alarm Select-ASpeaker/Strobe are designed to generate attention grabbing
tones and voice commands for emergency signaling evacuation
applications. These highly efficient low profile speakers are
available with field selectable taps , , 1, 2 watts. The low profile
speakers are available in two input voltage models 25 and 70.7
Vrms and can be installed on a standard 4 square back box. The
series is designed with the exclusive Select-A-Strobe. The strobe
features a unique candela intensity field selector switch for
alternating the candela output 30cd, 75cd and 110cd. The strobe
housing is clearly labeled with FIRE lettering and is polarized for
connecting to supervised fire alarm circuits. The strobe is
designed with a xenon flash tube and provides a candela intensity
field selector switch for maximum performance.
The Select-A-Speaker/Strobe Series is available in red or white
housing models. The Strobe can be synchronized by using the
SMD10-3A sync module to comply with NFPA recommendations
concerning photosensitive epilepsy when installing 2 or more
visual appliances within the field of view. The strobe signals are
listed for indoor use, ceiling and wall mount, under UL 1971
Standard.
RV I C
Features:
* ADA / NFPA / ANSI Compliant
* UL Listed for Ceiling and Wall mounting under UL 1971
* Three field selectable settings 30cd, 75cd and 110cd
* Speaker field selectable taps 1/4w, 1/2w, 1w and 2 watts
* Available 25Vrms and 70.7Vrms models
* Screw terminals capacity up to 12 AWG
* Frequency range 400 Hz ~ 4,000 Hz
* Integral blocking capacitor for line supervision
* Polarized strobes with wide listed voltage ranges
using filtered DC or unfiltered FWR input voltage
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4 square back box
* Strobes are polarized and rated at 24VDC.
* Synchronization requires an AMSECO SMD10-3A (daisy
chain) Sync Module
* RBX-1 back box skirt for surface mount (optional)
* Available in red or white housing
S
W
IT
C
H
Application:
The SSC-3075110 Series is recommended for use in areas such
as: warehouses, meeting rooms, schools, corridors,
apartments, office buildings, restaurants, hotels, and any other
application where effective visual warning is required by
Federal, State, or local authority having jurisdiction.
0
11
d
0c
11
75
30
d
0c
cd
75
Tamper
proof cap
Ordering Information:
Model
Number
Speaker
Voltage
(Vrms)
Strobe
Selectable
(Candela)
Sync
Module
Speaker
Selectable Taps
(Watts)
Strobe
Flash Rate
(times/min)
Mounting
Type
Housing
Color
SSC25-3075110R
SSC25-3075110W
SSC70-3075110R
SSC70-3075110W
25
25
70.7
70.7
SMD10-3A
SMD10-3A
SMD10-3A
SMD10-3A
, , 1, 2
, , 1, 2
, , 1, 2
, , 1, 2
60
60
60
60
Red
White
Red
White
The speaker/strobe is listed for indoor use with a temperature operating range of 32 F ~ 120F (0C ~ 49C )
Specifications subject to change without notice.
06/2003
Engineering Specifications:
The Fire alarm speaker shall be capable of reproducing alarm tones or voice commands on 25Vrms or 70.7Vrms. Speakers shall
provide incremental tap settings of , , 1, and 2 watts and shall be selected by means of a jumper wire. The speaker shall have a
frequency range of 400 to 4,000 Hz. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be
approved for fire alarm signaling use. The Strobe shall be listed under UL 1971 Standard for signaling devices for the hearing impaired
and shall be approved for fire protective service. The candela output shall be field selectable, having three setting 30cd, 75cd and 110cd
output. The signaling strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The
strobe shall be designed to produce one signal flash per second with continuously applied minimum voltage. When strobe
synchronization is required, the strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A or other source of AMSECO sync
protocol. The Speaker/Strobe shall be capable of WALL or CEILING mounting. The Visual signaling devices are to be installed in all
non-sleeping areas as per plans and specifications.
90
45
45
Speaker
Strobe
S+ S _
FI
FI
Strobe Speaker
_ S
_
+
+S
FI
90
FI
FI
FI
F.A.C.P &
VOICE / EVAC
Compound
Compound
I
F RE
IL
IN
G
90
L+ L _
TO NEXT DEVICE
or END-OF-LINE
-RESISITOR
FI R E
I
F RE
45
Sync Module
90
90
45
Compound
Speaker specifications:
Rated Input Voltage
( V r.m.s./ 1kHz )
45
45
90
_
H+ H
0
2.5
75
Impedance (k ohms)
Sound Pressure Level (dB/10ft)
Frequency Response (Hz)
1.25
78
@30cd
@75cd
@110cd
Average
Peak
In-Rush
Average
Peak
In-Rush
Average
Peak
In-Rush
16V
121
221
254
183
298
306
236
410
386
DC
24V
87
215
298
127
218
342
162
282
398
33V 16V
70
168
165 414
338 402
101 240
209 554
374 540
125 310
204 670
430 644
FWR
24V
131
350
418
180
458
478
227
564
580
OUT
_
70.7V
1
0.62
81
0.31
20
10
84
75
78
400 ~ 4,000
200
32F ~ 120F ( 0C ~ 49 C )
Compound
IN
_
25V
TO NEXT DEVICE
or END-OF-LINE
-RESISITOR
SMD10-3A
33V
110
338
458
151
450
498
186
526
548
1
5
81
2
2.5
84
75cd.
30cd.
30cd.
75cd.
75cd.
30cd.
177cd.
110cd.
75cd.
177cd.
177cd.
110cd.
Surface Mount
Mounting:
4 square
x 2-1/8 deep
back box.
Wall or Ceiling Mount
Dimensions:
Inches (mm)
4 square
x 2-1/8 deep
back box.
FI
FI
3-3/8 (85.7)
RBX-1
back box
skirt
(Optional)
I
F RE
6-7/8 (174)
1-49/64 (45)
2-25/32 (70)
1 (25.5)
3-3/8 (85.7)
PRODUCT LISTINGS
California
State Fire
Marshal
3022852
MEA
S8680
NYC Department
of Building
168-92-E Vol. 12
7315-0410:167
7315-0410:168
FN-1024-ULX:
24VDC or 12VDC rated @ 10 amps max
Input 115VAC / 60Hz, 4.4 amps
24VDC output
Maximum charge current 3.6 amps
Enclosure size of 15.5"H x 12"W x 4.5"D
STANDARD FEATURES
Input fuse rated @ 3.5 amps/250V
Filtered and electronically regulated output
Short circuit and thermal overload protection
AC fail supervision (form "C" contacts)
Low battery supervision (form "C" contacts)
Battery presence supervision (form "C" contacts)
Built-in charger for sealed lead acid or gel type
batteries
Automatic switch over to stand-by battery when AC
fails
Zero voltage drop when switched over to battery
backup
AC input and DC output LED indicators
Accommodates up to two (2) 12VDC/7AH batteries
Power supply, enclosure, cam lock and battery leads
F00109
06/2010
DESCRIPTION
The FN-642-ULADA, FN-842-ULADA, and FN-1042ULADA are extremely cost effective voltage regulated
remote NAC Power Entenders. They may be connected to any 12 or 24VDC Fire Alarm Control Panel
(FACP). Primary applications include Notification
Appliance Circuit (NAC) expansion (supports ADA
requirements) and will provide auxiliary power to
support system accessories.
PRODUCT LISTINGS
California
State Fire
Marshal
3022852
MEA
S5694
NYC Department
of Building
220-95-E Vol. 18
7315-0410:171
circuits
Two (2) Class B outputs may be paralleled for
more power on an indicating circuit.
One (1) Aux. Power Output @ 1 amp supply
current (with or without battery back up).
Signal Circuit Trouble Memory - Facilitates quickly
locating intermittent system trouble and eliminates
costly and unneccessary service calls. LED's
indicate a prior fault (short, open, ground) has
occured on one or more signaling circuit outputs.
2 wire Horn/Strobe Sync mode allows audible
notification appliances (Horns) to besilenced while
visual notification appliances (Strobes) continue to
operate,
Horn/Strobe sync protocols include: Gentex,
System Sensor, Faraday, Wheelock and Amseco.
Temporal Code 3 Mode.
Steady Mode.
Input to Output Follower Mode (maintainas
synchronization of notification appliance circuits).
March Time.
Compatible with 24VDC or 12VDC fire panles.
Input 115VAC.
AC fail, battery presence & low battery monitoring.
Accommodates up to two (2) 12VDC/12AH batteries.
Power supply, logic board, re enclosure, cam lock,
transformer & battery leads
Find latest revision at www.hochiki.com
F00105
03/2010
Introduction
Analog Sensors
ALG-EA/-V
ALG-EA/-V Specifications
AIE-EA
AIE-EA Specifications
Americium 241 (0.98 Ci)
24.0 ~ 40.7 VDC
41.0 VDC MAXIMUM
350 A Typical
460 A Maximum
Low Power Mode (S-SC)
140 A @ 0.75s
100 A @ 1.50s
2mA (momentary)
When Called (S-SC)
8mA
Alarm mode (S-SC)
Remote LED (during alarm) 8mA
Device Type Code
A8 Hex
Operating Temperature
-10~ 50C
-20~ 60C
Storage Temperature
S-SC Protocol
Half duplex, asynchronous communication
Speed: 1200 bps
1 stop bit, 1 parity bit
Error check: Check-sum, even parity check
TX protocol control: polling, selecting, interrupt
TX code: 8 bit binary data
S-SC line resistance
50 Ohm MAX. (14~18 AWG. wiring)
Dimensions
3-15/16"D X 1-1/2"H
Weight
4.2 oz. (with YBN-NSA-4 base 5.9 oz.)
Test Feature
See control panel operating manual
Environment
Indoor Use Only
Address setting method
EEPROM (refer to control panel
(1 - 127 addresses)
operating manual for address
setting procedure or utilize
Hochiki TCH-B100 - See Page 9)
Base Requirement
HSB-NSA-6 or YBN-NSA-4
Radioactive Source
Voltage Operating Range
Average Current Consumption
Normal Mode (S-SC)
Heat Sensor
Features
ATG-EA
ATG-EA Specifications
Heat Sensing Element
Voltage Operating Range
Average Current Consumption
Normal Mode (S-SC)
Thermistor
24.0 ~ 40.7 VDC
41.0 VDC MAXIMUM
350 A Typical
500 A Maximum
Low Power Mode (S-SC)
110 A @ 0.75s
100 A @ 1.50s
When Called (S-SC)
2mA (momentary)
Alarm mode (S-SC)
8mA
Remote LED (during alarm) 8mA
Device Type Code
98 Hex
Operating Temperature
-10~ 50C
Storage Temperature
-20~ 60C
S-SC Protocol
Half duplex, asynchronous communication
Speed: 1200 bps
1 stop bit, 1 parity bit
Error check: Check-sum, even parity check
TX protocol control: polling, selecting, interrupt
TX code: 8 bit binary data
50 Ohm MAX. (14~18 AWG. wiring)
S-SC line resistance
Dimensions
3-15/16"D X 1-9/16"H
Weight
3.2 oz. (with YBN-NSA-4 base 4.9 oz.)
See control panel operating manual
Test Feature
Environment
Indoor Use Only
Address setting method
EEPROM (refer to control panel
operating manual for address
(1 - 127 addresses)
setting procedure or utilize
Hochiki TCH-B100 - See Page 9)
Base Requirement
HSB-NSA-6 or YBN-NSA-4
Factors to consider
Contents to be protected.
Type of construction and use of structure.
Human occupancy.
Burning characteristics of contents
Space involved.
Height of ceilings.
Surface condition of ceilings.
Total area.
Air movement--stratification.
Vent locations--velocities and dilution.
Deflections and obstructions.
Location Sensors
One smoke sensor covers 450 to 900 square feet.
One heat sensor covers up to 2500 square feet.
Consider local conditions and codes along with engineering evaluations
to determine the proper spacing and specifications.
Warning: HEAT SENSORS ARE NOT LIFE SAFETY DEVICES. WHERE LIFE
SAFETY IS A FACTOR SMOKE SENSORS ARE RECOMMENDED.
Examples
You may use 30-foot spacing on smooth ceilings for smoke sensors.
You may use 50-foot spacing on smooth ceilings for heat sensors.
Beams other obstructions extending more that 18" below the ceiling
reduce the effective range of the sensors. Such obstructions should
designate a new separation point, and be considered a border for a new
section.
Beams or other obstructions extending more that 8" but less than 18"
require reduced spacing at the perpendicular of the obstructions.
NOTE: FOR INFORMATION ON DIFFERING STYLES OF CONSTRUCTION
CONSULT THE NFPA HANDBOOK, SECTION 72.
Warning: DO NOT INSTALL HOCHIKI SMOKE SENSORS IN THE
FOLLOWING AREAS:
Testing
Smoke Sensors
Remember, for a smoke sensor to operate efficiently, combustion
products must enter the outer chamber. Air flow, stratification, velocity,
stagnation, and migration all affect the efficiency and accuracy of the
sensor.
You may use an air flow meter to determine the movement of air within
a structure.
Field testing equipment is available from Hochiki for testing the function
of the sensors. See the Hochiki Tester section in this bulletin and the
control panel operation manual for more information.
Maintenance
Consult local codes and ordinances.
Hochiki recommends biannual confirmation of functional operation and
external appearance.
You can obtain field testing equipment from Hochiki. See the Hochiki
Tester section in this bulletin for more information.
Heat Sensors
There are two basic test methods that can be used to determine proper
operation of the ATG-EA.
1. Testing can be accomplished by use of the built in test feature.
For proper operation refer to the control panel operation manual.
2. Functional testing can be accomplished by using the TTA-1H
heat sensor tester. See testers section.
TECHNICAL BULLETIN HA-96
DECEMBER 2003
OUTER COVER
RECESS AND KEY
OUTER COVER
Tools
Follow the steps in this section to prepare the sensor for cleaning:
1. Remove the sensor from its base.
2. Disassemble sensor by following the NSRT-A100 instructions found
on page 5 of this document.
OUTER COVER
RECESS AND KEY
OUTER COVER
ALIGNMENT
ARROW 1
CHAMBER
COVER
COVER
TABS
(3 total
1 hidden)
SENSING
CHAMBER
OPE
N
SE
CLO
TAB
CATCH
(3 TOTAL
1 hidden)
PHOTODIODE
OUTER
COVER
KEY
OUTER
COVER
KEY
IR LED
ALIGNMENT
ARROW 2
OPTICAL UNIT
(BLACK AREA)
EXPLODED VIEW OF ALG-EA
Tool
You will need:
Hochiki America's NSRT-A100 Cover Removal Tool
Soap solution (1 teaspoon of Lemon Joy to 1 gallon clean water)
Soap bristled brush
Clean dry compressed air
Distilled water
Vacuum
OUTER COVER
RECESS AND KEY
OUTER COVER
STATUS LEDS
OUTER CHAMBER
INSECT SCREEN
LOCATOR
This section explains how to remove the outer cover from the
AIE-EA or the ALG-EA/ ALG-V by using the NSRT-A100.
Tool
You will need:
Hochiki America's NSRT-A100 tool
ALIGN
LOCATOR
HERE
MOUNTING
EARS
ROTATE
TO
REMOVE
COVER
ALIGN
LOCATOR
HERE
NSRT-A100
Testers
The TSE-A100 smoke detector tester
The Hochiki TSE-A100 is one of the most advanced units of its kind and
is the result of extensive research and development aimed at making the
job of testing sensors a simple and efficient operation.
The TSE-A100 can be used to test all types of smoke sensors by
applying smoke from an internal smoke source.
Telescopic Pole
Features
The TSE-A100 employs telescoping construction for easy adjustment
to ceiling height.
Simple operating controls are located on the base of the unit.
The TSE-A100 houses its own source of smoke (punk sticks) within a
special chamber that isolates the combustion material from the
outside. This unique design enables the tester safely to generate a
stable volume of smoke.
The unit comes with a shoulder-sling carrying case for easy
portability from one site to another.
The TSE-A100 extends from 5.25 feet to 14.1 feet.
Instruction Label
Testing a detector
TSE-A100 specifications
Rated Voltage
Battery
Combustion material
Weight
Maximum length
3 VDC
D size (2)
Punk stick (7mm diameter, 150mm long)
5 pounds
14.1 feet
Once you have prepared the TSE-A100, follow the steps in this section
to test smoke detectors.
NOTE: Allow 30 to 60 seconds after igniting punk stick for sufficient
smoke generation. For proper airflow, observe battery polarity.
1. Rotate the combustion chamber so the #2 arrow lines up with the
power indicator screw. The fan powers on and a steady flow of smoke
is released from the tip of the TSE-A100.
2. Raise the extended tip of the TSE-A100 to within 6-8" of the sensor.
The sensor should alarm.
Features
ATG-EA
View of TTA-1H
in relationship
to sensor
Lightweight Head
with built in
circulation fan
Adjustable
aluminum pole
Rubber Bumbers
and Pad
Battery Pack
Battery type
Life
Number of sensors tested
per charge
Weight
Dimensions
Charger
TECHNICAL BULLETIN HA-96
DECEMBER 2003
12 VDC
4 amps
14 amps (2sec. typical)
380F (maximum)
3 sections 3.6ft.(min.) 8.8ft.(max.)
Head 15.87oz.
Pole 2.15 lbs.
Head 4.33in.D X 6.10in.H
Pole 1.38in.D
100
Rain
10
Fine Rain
1
Mist
0.1
0.01
0.001
Wood Smoke
Cigarette Smoke
Pine Resin Smoke
Carbon Powder
Pigments
Ammonia Vapor
Smoke of Zinc Oxide
Gas Molecules
Flare Smoke (magnesium-oxide)
Chimney Smoke
Factory Dust
Dust in Clean Air
Pollen
Yellow Ochre
Bacteria
To naked eye
Viruses
Particles Visible
Through microscope Through high power microscope
Hochiki Sensors
Photoelectric Smoke Sensors
Ionization Smoke Sensors
Features
The TCH-B100-NS is a compact unit and easy to use.
The TCH-B100-NS provides address setting and reading.
Has the diagnostic ability to display the analog value.
Use 9V battery
Automatically increments the address ready to set the address of
the next sensor.
Automatically switches the power off after use
Programming Buttons
Left Gray Button:
Programming
Buttons
Display
Remote
Programming Jack
Red Button:
Address Setting
1. Install sensor onto programmer, ensuring that sensor protrusion
aligns with programmer grooves.
2. Press the left gray button to switch programmed on. A battery
check message will appear followed by the devices address
( un-programmed sensors will read address 127).
3. Set the required address by incrementing the left and right gray
buttons (the display will show three red flashing dots if the address
being programmed is different from the device's current address).
4. When the desired address is present press the red button to store
that address. The three red dots on the display will no longer be
present.
Remote
Programming Cable
(DCP-FRCME-S)
Display Message:
bAt - On upon power up ( battery check). Also on when battery is
low. Low battery good for up to 3,000 address setting
operation.
E0 - Attempting to set an address beyond 127.
E1 - Attempting to program an address with no device connected.
E2 - Can not find device after power up.
E3 - Invalid sensor response
E4 - Can not find the device program.
E5 - Device read error.
E6 - Fail during Analog value reading.
TECHNICAL BULLETIN HA-96
DECEMBER 2003
Introduction
NS Detectors
Our new conventional NS detectors are dramatically small in size like their
predecessor the original low profile conventional smoke detectors. Yet
they maintain the dependability Hochiki customers have come to rely on.
This bulletin documents all the NS Conventional Smoke Detectors
(SLR-24/-24V/-24VN/-24H, SLR-835/-835H/-835HW*/-835B-2/
-835B-2W*/-835BH-2/-835BH-2W*/-835B-4/-835B-4W*/
-835BH-4/-835BH-4W*/, SIJ-24 and DCD-135/190).
* W= Indicates white
The SLR series photoelectric smoke detector has a computerdesigned smoke chamber that can detect smoldering or
fast-flaming fires.
The SLR series has a wider range than other photoelectric
detectors. It's coverage extends into the range of the Ionization
detector. This makes the SLR series a uniquely versatile smoke
detector.
The combination of a high signal-to noise ratio and sensitivity
stability make this sensor effective in a wide range of
environmental conditions.
Two indicator LEDS set at 180 degrees from each other offer
360 degree viewing of detector status.
Automatic built-in test feature. Indicates when chamber is dirty
or if sensitivity has shifted outside its intended range. It will
automatically indicate its status with no testing.
A hidden self locking feature (requires activation).
Inter-changeability with SLK series and SIH series detectors.
SLR-24H
SLR-24/ -24V
SLR-24/-24V/-24VN/-24H Specifications
Light Source
Voltage Operating Range
Nominal Rated Voltage
Working Voltage
Maximum Allowable Voltage
Allowable Wave Form
Average Current Consumption
Supervisory Current
Surge Current
Maximum Allowable Current
Minimum, Alarm Trip Current
Operating Temperature
Storage Temperature
Heat Element Rating
( SLR-24H only)
Dimensions
Weight
Test Feature
Environment
Base Requirement
TECHNICAL BULLETIN HA-97
OCTOBER 2002
SLR-835/-835H/-835B-2/835BH-2/-835B-4/-835BH-4
Front View Of All Versions
SLR-835 Specifications
Light Source
Voltage Operating Range
Nominal Rated Voltage
Working Voltage
Maximum Allowable Voltage
Maximum Ripple
Average Current Consumption
Supervisory Current
38 A (at 12VDC)
55 A (at 24VDC)
70 A (at 35VDC)
200 A (at 24VDC)
Surge Current
150mA Maximum
Maximum Allowable Current
Minimum, Alarm Trip Current 6mA
Alarm Current For SLR-835B-4 48mA (at 12VDC, 25C)
34mA (at 24VDC, 25C)
52mA (at 35VDC, 25C)
Heat Element Rating
135F
( SLR-835H only)
-10 ~ +50C
Operating Temperature
Storage Temperature
-20 ~ +60C
Dimensions of the SLR-835
3-15/16"D X 2.0"H W/TRIM RING
and SLR-835H
Dimensions of the
3-15/16"D X 2.4"H
SLR-835B-2, and -4
SLR-835BH-2, and 835BH-4
3-15/16"D X 2.4"H
Weight of the SLR-835
3.1 oz. (with NS4-100 base 4.6 oz.)
and SLR-835H
Weight of the
3.96 oz. (with Trim Ring 5.76 oz.)
SLR-835B-2, and -4
3.96 oz. (with Trim Ring 5.76 oz.)
SLR-835BH-2, and 835BH-4
Test Feature
Automatic built-in test feature
(see HA-06-074 page 4)
Indoor Use Only
Environment
NS6 Series, NS4 Series, and HSC
Base Requirement
Relay Series
For SLR-835 Only
Mounting Requirement For
SLR-835B-2,/-835BH-2/835B-4/-835BH-4
Trim Ring SLR-835 Baseless
Baseless Detector
SIJ-24
Page 1 of 7
SIJ-24 Specifications
Radioactive Source
Voltage Operating Range
Nominal Rated Voltage
Working Voltage
Maximum Allowable Voltage
Allowable Wave Form
Average Current Consumption
Supervisory Current
Surge Current
Maximum Allowable Current
Minimum, Alarm Trip Current
Operating Temperature
Storage Temperature
Dimensions
Weight
Test Feature
Environment
Base Requirement
Heat Detectors
Factors to consider
Contents to be protected
Type of construction and use of structure
Human occupancy
Burning characteristics of contents
Space involved
Height of ceilings
Surface condition of ceilings
Total area
Air movement--stratification
Vent locations--velocities and dilution
Deflections and obstructions
Locating Detectors
Features
Examples
You may use 30-foot spacing on smooth ceilings for smoke detectors.
You may use 50-foot spacing on smooth ceilings for heat detectors.
Beams or other obstructions extending more than 18" below the ceiling
reduce the effective range of the sensors. Such obstructions should
designate a new separation point, and be considered a border for a new
section.
Beams or other obstructions extending more than 8" but less than 18"
require reduced spacing at the perpendicular of the obstructions.
NOTE: FOR INFORMATION ON DIFFERING STYLES OF
CONSTRUCTION CONSULT THE NFPA HAND BOOK, SECTION 72
WARNING: DO NOT INSTALL HOCHIKI SMOKE DETECTORS IN THE
FOLLOWING AREAS:
DCD-135/ 190
DCD-135/190 Specifications
Heat Sensing Element
Voltage Operating Range
Nominal Rated Voltage
Working Voltage
Maximum Allowable Voltage
Allowable Wave Form
Average Current Consumption
Supervisory Current
Surge Current
Maximum Allowable Current
Minimum, Alarm Trip Current
Operating Temperature
Storage Temperature
Dimensions
Weight
Test Feature
Fixed Temperature Rating
Model DCD-135
Model DCD-190
Rate of Rise Rating (Both)
Environment
Base Requirement
TECHNICAL BULLETIN HA-97
OCTOBER 2002
Thermistor
24.0 VDC
15.0 ~ 33.0 VDC
42.0 VDC MAXIMUM
Filtered DC, 5V Ripple Max.
35 A (at 24VDC)
160 A (at 24VDC)
150mA Maximum
6mA
-10 ~ +50C
-20 ~ +60C
3-15/16"D X 1-1/2"H
3.1 oz. (with NS4-100 base 4.6 oz.)
See page 7 of this bulletin
135F
190F
15F/min.
Indoor Use Only
NS6 Series, NS4 Series, and HSC
Relay Series
Testing
Smoke Detectors
Maintenance
Heat Detectors
There is one basic test method that can be used to determine proper
operation of the DCD-135/190
1 Functional testing can be accomplished by using the TTA-1H
heat detector/sensor tester. See testers section.
Page 2 of 7
Tools
ENCLOSURE
OUTER COVER
Follow the steps in this section to prepare the detector for cleaning:
1. Remove the detector from its base.
2. Disassmble detector by following the NSRT-A100 instructions found
on page 5 of this document.
ALIGNMENT
ARROW 1
CHAMBER
COVER
SENSING
CHAMBER
COVER
TABS
(3 total
1 hidden)
OPE
N
SE
CLO
TAB
CATCH
(3 total
1 hidden)
PHOTODIODE
IR LED
ALIGNMENT
ARROW 2
NOTE:
1. ON SLR-24H, SLR-835BH AND SLR-835H TAKE CARE NOT
TO DISTURB OR DAMAGE THE THERMISTOR HEAT
ELEMENT DURING THE CLEANING PROCEDURE
2. If after testing, the detector is not working within the Prescribed
range then return it to the manufacturer for servicing.
Page 3 of 7
TAB
DIRECTION TO
MOVE TAB
DIAGRAM 1
TAB LOCATIONS
Cleaning Procedure
1. The cleaning instructions are the same as for the SLR-24
Series Detectors (refer to page 3).
Testing Procedure
DIAGRAM 2
Page 3A of 7
CONTACT BLADES
Tools
Follow the steps in this section to prepare the detector for cleaning:
1. Remove the detector from its base, and place it with the bottom up.
2. Take the small screw driver and gently pry each of the Outer Cover OUTER COVER
Clips outward from the center of the detector, and at the same time
CLIP - LARGE
lifting the enclosure upward by the Contact Blades. This will free
the Outer Chamber/ Enclosure form the Outer Cover
CAUTION: Only the Outer Cover may be cleaned with a soap solution.
Never attempt to clean any other part of the detector with
a soap solution. This may render the detector inoperable.
DO NOT ATTEMPT TO REMOVE THE INSECT SCREEN.
OUTER COVER
CLIPS (3 SMALL)
OUTER COVER
STATUS LEDS
OUTER CHAMBER
(ONE HIDDEN)
NOTE: If, after testing, the detector is not working within the prescribed
range, then return it to the manufacturer for servicing.
ENCLOSURE KEYS
(4 TOTAL TWO ARE HIDDEN)
CONTACT BLADE
This section explains how to remove the outer cover from the
SLR-24/-24V/-24VN/-835 by using the NSRT-A100.
Tools
LOCATOR
ALIGN
LOCATOR
HERE
MOUNTING
EARS
ROTATE
TO
REMOVE
COVER
ALIGN
LOCATOR
HERE
NSRT-A100
Testers
The TSE-A100 smoke detector tester
The Hochiki TSE-A100 is one of the most advanced units of its kind and
is the result of extensive research and development aimed at making the
job of testing detectors a simple and efficient operation.
The TSE-A100 can be used to test all types of smoke detectors by
applying smoke from an internal smoke source.
Telescopic Pole
Features
The TSE-A100 employs telescoping construction for easy adjustment
to ceiling height.
Simple operating controls are located on the base of the unit.
The TSE-A100 houses its own source of smoke (punk sticks) within a
special chamber that isolates the combustion material from the
outside. This unique design enables the tester safely to generate a
stable volume of smoke.
The unit comes with a shoulder-sling carrying case for easy
portability from one site to another.
The TSE-A100 extends from 5.25 feet to 14.1 feet.
Instruction Label
TSE-A100 specifications
Rated Voltage
Battery
Combustion material
Weight
Maximum length
3 VDC
D size (2)
Punk stick (7mm diameter, 150mm long)
5 pounds
14.1 feet
Testing a detector
Once you have prepared the TSE-A100, follow the steps in this section
to test smoke detectors.
NOTE: Allow 30 to 60 seconds after igniting punk stick for sufficient
smoke generation. For proper airflow, observe battery polarity.
1. Rotate the combustion chamber so the #2 arrow lines up with the
power indicator screw. The fan powers on and a steady flow of smoke
is released from the tip of the TSE-A100.
2. Raise the extended tip of the TSE-A100 to within 6-8" of the detector.
The detector should alarm.
Features
DCD-135/190
View of TTA-1H
in relationship
to detector
Lightweight Head
with built in
circulation fan
Adjustable
aluminum pole
Rubber Bumpers
and Pad
Battery Pack
Battery type
Life
Number of detectors tested
per charge
Weight
Dimensions
Charger
12 VDC
4 amps
14 amps (2sec. typical)
380F (maximum)
3 sections 3.6ft.(min.) 8.8ft.(max.)
Head 15.87oz.
Pole 2.15 lbs.
Head 4.33in.D X 6.10in.H
Pole 1.38in.D
Fine Rain
Mist
Wood Smoke
Cigarette Smoke
Pine Resin Smoke
Carbon Powder
Pigments
Ammonia Vapor
Smoke of Zinc Oxide
Gas Molecules
Flare Smoke (magnesium-oxide)
Chimney Smoke
Factory Dust
Dust in Clean Air
Pollen
Yellow Ochre
Bacteria
To naked eye
Viruses
Particles Visible
Through microscope Through high power microscope
Hochiki Detectors
Photoelectric Smoke Detectors
Ionization Smoke Detectors
22-Oct-2002
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
MAX
DET
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
EOL
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
2K OHMS
DETECTOR
MODEL
SLR-835B-2
SLR-835B-2W
SLR-835BH-2
SLR-835BH-2W
SLR-835B-2
SLR-835B-2W
SLR-835BH-2
SLR-835BH-2W
SLR-835B-2
SLR-835B-2W
SLR-835BH-2
SLR-835BH-2W
SLR-835B-2
SLR-835B-2W
SLR-835BH-2
SLR-835BH-2W
SLR-835B-2
SLR-835B-2W
SLR-835BH-2
SLR-835BH-2W
SLR-835B-2
SLR-835B-2W
SLR-835BH-2
SLR-835BH-2W
DETECTOR
ID
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
BASE MODEL
BASE ID
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
22-Oct-2002
ADT
ZONE MODEL
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
ADT-XP
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
UNIMODE 4-16
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
XPM-8
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;8W/WO IZE-A
IZ4;9W/WO IZE-A
ZONE
ID
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
B;D
MAX
DET
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
EOL
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
2.2K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
DETECTOR
MODEL
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24F
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-2-RB
HS-22D
HSB-220
HSB-224
YBA-M22
HS-2-RB
HS-22D
HSB-220
HSB-224
YBA-M22
HS-2-RB
HS-22D
HSB-220
HSB-224
YBA-M22
HS-2-RB
HS-22D
HSB-220
HSB-224
YBA-M22
HS-2-RB
HS-22D
HSB-220
HSB-224
YBA-M22
HS-2-RB
HS-22D
HSB-220
HSB-224
YBA-M22
YBA-M22
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
HB--3
22-Oct-2002
ADVANTOR
ZONE MODEL
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
ULF 3000-24
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ZONE
ID
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
ULF1
LOOP
STYLE
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
MAX
DET
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
EOL
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
6.8K
DETECTOR
MODEL
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HB-20
HB-3
HB-4
HB-5
HB-55
HB-56
HB-54
HB-53
HB-20
HB-3
HB-4
HB-5
HB-55
HB-56
HB-54
HB-53
HB-20
HB-3
HB-4
HB-5
HB-55
HB-56
HB-54
HB-53
22-Oct-2002
ANSUL
ZONE MODEL
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE FOUR
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
AUTOPULSE IQ301
415413
415413
415413
415413
415413
415413
415413
415413
415413
415413
415413
415413
415413
415413
415413
416610
416610
416610
416610
416610
416610
416610
416610
416610
416610
416610
416610
416610
416610
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
ZONE
ID
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV.4
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
REV. 1
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
D
D
D
D
D
D
D
D
D
D
D
D
D
D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
MAX
DET
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
24
20
20
1
20
20
20
1
1
20
20
20
20
20
20
1
20
1
25
25
1
25
1
25
EOL
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
417213
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
DETECTOR
MODEL
DCA-135
DCA-190
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
DCA-135
DCA-190
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
1400
1451
1451
1451
1451DH
1851DH
2400
2400AIT
2400AT
2400TH
2451
2451
2451
2451TH
2451TH
2451TH
2851DH
SIH-24F
SIH-24F
SIH-24F
SLD-24F
SLK-24F
SLK-24FH
SLK-24FH
DETECTOR
ID
N/A
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HB-60
HB-60
HB-2
HB-51
HB-73
HB-2
HB-2
HB-51
HB-51
HB-73
HB-2
HB-2
HB-51
HB-73
HB-2
HB-60
HB-60
HB-2
HB-51
HB-73
HB-2
HB-2
HB-51
HB-73
HB-2
HB-2
HB-51
HB-73
HB-2
N/A
A
A
A
A
A
N/A
N/A
N/A
N/A
A
A
A
A
A
A
A
HB-10
HB-3
HB-3
HB-10
HB-3
HB-10
HB-3
22-Oct-2002
C & K SYSTEMS
LOOP
STYLE
A
MAX
DET
10
EOL
2.2K
DETECTOR
MODEL
SLK-12
DETECTOR
ID
HD-4
HB-80
5-Mar-2003
CADDX
LOOP
STYLE
A
A
A
A
MAX
DET
20
20
20
20
EOL
680 OHMS
680 OHMS
680 OHMS
680 OHMS
DETECTOR
MODEL
SLR-835,-835W
SLR-835B-2
SLR-835,-835W
SLR-835B-2
DETECTOR
ID
HD-3
HD-6
HD-3
HD-6
BASE MODEL
BASE ID
NS4-220,NS6-220
N/A
NS4-220,NS6-220
N/A
HB-3
N/A
HB-3
N/A
22-Oct-2002
CHEMETRON
ZONE MODELZONE
ID
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
4
N/A
1
N/A
1
N/A
1
N/A
1
LOOP
STYLE
D
D
D
D
D
D
D
D
D
D
D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B
B
B
B
MAX
DET
60
60
60
50
50
50
50
50
50
50
50
14
14
14
14
14
14
14
14
14
14
14
14
14
10
10
10
10
10
10
10
10
33
33
33
33
EOL
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
2.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
DETECTOR
MODEL
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
DCD-135, DCD-190
DCD-135, DCD-190
DFE-190
DFE-190
SIJ-24
SIJ-24
SLR-24
SLR-24,-24H
SLR-24,-24H
SLR-24, SLR-24H
SLR-24, SLR-24H
SLR-24H
SLR-835B-2
DCD-135
DCD-135
DCD-190
DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SIF-24F
SIH-24F
SLK-24F
SLK-24FH
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-220D
HS-224D
HS-224RB
HS-220D
HS-220RB
HS-224D
HS-224RB
HS-220D
HS-220RB
HS-224D
HS-224RB
HSC-224L
HSC-224L
HSC-220L
HSC-220L
NS4-224,NS6-224
NS4-224,NS6-224
NS4-224,NS6-224
HSC-220R
NS4-220,NS6-220
HSC-224R
HSC-224R
NS4-224,NS6-224
N/A
HSC-220R
NS4-220,NS6-220
HSC-220R
NS4-220,NS6-220
HSC-220R
NS4-220,NS6-220
HSC-220R
NS4-220,NS6-220
HS-220D
HS-220D
HS-220D
HS-220D
HB-3
HB-5
HB-12
HB-3
HB-12
HB-5
HB-14
HB-3
HB-12
HB-5
HB-14
HB-62
HB-62
HB-64
HB-64
HB-5
HB-5
HB-5
HB-72
HB-3
HB-73
HB-73
HB-5
N/A
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-3
HB-3
HB-3
HB-3
22-Oct-2002
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
MAX
DET
20
20
20
20
20
20
20
20
20
20
20
20
20
20
1
1
1
1
EOL
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
DETECTOR
MODEL
DCD-135,-190
DCD-135,-190
DCD-135,-190
DCD-135,-190
SIJ-24
SIJ-24
SLR-24H,-24V
SLR-24H,-24V
SLR-24H,-24V
SLR-835
SLR-835
SLR-835B-2
SLR-835H
SLR-835H
SLR-835,-835W
SIJ-24
SLR-24V
SLR-24V
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HSC-220L
HSC-220R
NS4-220,NS6-220
HSC-220L
HSC-220R
NS4-220,NS6-220
HSC-220R
NS4-100,NS6-100
NS4-220,NS6-220
NS4-100,NS6-100
NS4-220,NS6-220
N/A
HSC-220R
NS4-220,NS6-220
SBC-2R,SBC-2RW
SBC-2
SBC-2
SBC-2R
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-55
HB-3
HB-55
HB-3
N/A
HB-72
HB-3
HB-85
HB-85
HB-85
HB-86
22-Oct-2002
DIGITAL MONITOR
LOOP
STYLE
A
A
A
A
MAX
DET
22
7
22
7
EOL
3.3k
3.3k
3.3k
3.3k
DETECTOR
MODEL
SLK12
SLK-835,-835H
SLK-12
SLK-835,-835H
DETECTOR
ID
HD-4
HD-5
HD-4
HD-5
BASE MODEL
BASE ID
HSB-12-1,-12-1N
HSB-200,-200N
HSB-12-1,-12-1N
HSB-200,-200N
HB-80
HB-55
HB-80
HB-55
22-Oct-2002
DMP
ZONE MODEL
ZONE
ID
10 ON XR10
A
10 ON XR10
A
10 ON XR10
A
10 ON XR20
A
10 ON XR20
A
10 ON XR20
A
10 ON XR20
A
715
A
715,-16
A
715,-16,-8
A
715,-16-,-8
A
715-16
A
715-8
A
715-8
A
10 ON XR200
A
715
A
715
A
715 OR Z 9 &10
A
715, 715-16
A
715,-16
A
715,-16
A
715,-16,-8
A
715-8
A
715-8
A
9 & 10 ON XR200 A
9 ON XR200
A
9,10 ON XR200
A
9,10 ON XR200
A
XR200
A
XR200
A
2-5 ON XR5FC
A
2-5 ON XR5FC
A
2-5 ON XR5FC
A
2-5 ON XR5FC
A
2-5 ON XR5SL
A
2-5 ON XR5SL
A
2-5 ON XR5SL
A
2-5 ON XR5SL
A
6 ON XR6
A
6 ON XR6
A
715
A
715 ON XR6
A
LOOP
STYLE
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
MAX
DET
22
7
7
22
7
7
7
7
7
7
22
7
7
7
7
22
7
22
7
7
7
22
7
7
22
7
7
7
22
7
22
7
7
7
22
7
7
7
7
7
7
7
EOL
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
DETECTOR
MODEL
SLK-12
SLK-835,-835H
SLR-835
SLK-12
SLK-835,-835H
SLR-835
SLR-835B
SLR-835
SLR-835B
SLK-835,-835H
SLK-12
SLR-835
SLR-835
SLR-835B
SLK-835,-835H
SLK-12
SLK-835,-835H
SLK-12
SLK-835,-835H
SLR-835
SLR-835B
SLK-12
SLK-835,-835H
SLR-835
SLK-12
SLK-835,-835H
SLR-835
SLR-835B
SLK-12
SLK-835,-835H
SLK-12
SLK-835,-835H
SLR-835
SLR-835
SLK-12
SLK-835,-835H
SLR-835
SLR-835B
SLR-835
SLR-835B
SLR-835B
SLR-835
DETECTOR
ID
HD-4
HD-5
HD-3
HD-4
HD-5
HD-3
HD-6
HD-3
HD-6
HD-5
HD-4
HD-3
HD-3
HD-6
HD-5
HD-4
HD-5
HD-4
HD-5
HD-3
HD-6
HD-4
HD-5
HD-3
HD-4
HD-5
HD-3
HD-6
HD-4
HD-5
HD-4
HD-5
HD-6
HD-3
HD-4
HD-5
HD-3
HD-6
HD-3
HD-6
HD-6
HD-3
BASE MODEL
BASE ID
HSB-12-1,-12-1N
HSB-200,-200N
NS6-100
HSB-12-1,-12-1N
HSB-200,-200N
NS6-100
NA
NS6-100
NA
HSB-200,-200N
HSB-12-1,-12-1N
NS6-100
NS6-100
NA
HSB-200,-200N
HSB-12-1,-12-1N
HSB-200,-200N
HSB-12-1,-12-1N
HSB-200,-200N
NS6-100
NA
HSB-12-1,-12-1N
HSB-200,-200N
NS6-100
HSB-12-1,-12-1N
HSB-200,-200N
NS6-100
NA
HSB-12-1,-12-1N
HSB-200,-200N
HSB-12-1,-12-1N
HSB-200,-200N
NA
NS6-100
HSB-12-1,-12-1N
HSB-200,-200N
NS6-100
NA
NS6-100
NA
NA
NS6-100
HB-80
HB-55
HB-55
HB-80
HB-55
HB-55
NA
HB-55
NA
HB-55
HB-80
HB-55
HB-55
NA
HB-55
HB-80
HB-55
HB-80
HB-55
HB-55
NA
HD-4
HB-55
HB-55
HB-80
HB-55
HB-55
NA
HB-80
HB-55
HB-80
HB-55
NA
HB-55
HB-80
HB-55
HB-55
NA
HB-55
NA
NA
HB-55
22-Oct-2002
DSC
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
B
B
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
EOL
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
DETECTOR
MODEL
SLR-835, 835W
SLR-835B-2
SLR-835BH-2
SLR-835, 835W
SLR-835B-2
SLR-835BH-2
SLR-835, 835W
SLR-835B-2
SLR-835BH-2
SLR-835, 835W
SLR-835B-2
SLR-835BH-2
DETECTOR
ID
HD-3
HD-6
HD-6
HD-3
HD-6
HD-6
HD-3
HD-6
HD-6
HD-3
HD-6
HD-6
BASE MODEL
BASE ID
NS4-220,NS6-220
N/A
N/A
NS4-220,NS6-220
N/A
N/A
NS4-220,NS6-220
N/A
N/A
NS4-220,NS6-220
N/A
N/A
HB-3
N/A
N/A
HB-3
N/A
N/A
HB-3
N/A
N/A
HB-3
N/A
N/A
22-Oct-2002
EDWARDS
ZONE MODEL
5783B
5783B
5783B
5783B
N/A
N/A
N/A
N/A
ZONE
ID
001
001
001
001
LOOP
STYLE
B
B
B
B
MAX
DET
33
33
33
33
EOL
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
DETECTOR
MODEL
SIF-24F
SIH-24F
SLK-24F
SLK-24FH
DETECTOR
ID
HD-2
HD-3
HD-3
HD-3
HB-3
HB-3
HB-3
HB-3
22-Oct-2002
F.A.S.T. INC.
240204
240204
240204
240204
240204
240204
ZONE
ID
5389
5389
5389
5389
5389
5389
LOOP
STYLE
B
B
B
B
B
B
MAX
DET
15
15
15
15
15
15
EOL
PN260001
PN260001
PN260001
PN260001
PN260001
PN260001
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
22-Oct-2002
FARADAY
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ZONE
ID
FOS1
FOS1
FOS1
FOS1
FOS1
FOS1
FOS1
FOS1
FOS1
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
FOS2
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
D
B
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
5.6K OHM
N/A
5.6K OHM
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
BASE MODEL
BASE ID
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
Page 1 of 2
22-Oct-2002
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
401310, 311, 312
401310, 311, 312
401310, 311, 312
401310, 311, 312
401310, 311, 312
401310, 311, 312
401310, 311, 312
401310, 311, 312
401310
401310
401310
401310
401310
401310
401310
401310
401311
401311
401311
401311
401311
401311
401311
401311
ZONE
ID
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
D
D
D
D
D
C
C
C
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
LOOP
STYLE
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
D
D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
D
D
B
D
B
D
B
D
B
B
D
B
D
B
D
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
5.6K OHM
5.6K OHM
N/A
N/A
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
10808
N/A
N/A
10808
N/A
10808
N/A
10808
N/A
10808
10808
N/A
10808
N/A
10808
N/A
BASE MODEL
BASE ID
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
HS-224L
AL-HS-224D
AL-HS-224D
AL-HS-224D
AL-HS-224D
HS-224L
HS-224L
HS-224L
HS-224L
AL-HS-224D
AL-HS-224D
AL-HS-224D
AL-HS-224D
HS-224L
HS-224L
HS-224L
HS-224L
AL-HS-224D
AL-HS-224D
AL-HS-224D
AL-HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HS-224D
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-18
HB-5
HB-5
HB-5
HB-5
HB-18
HB-18
HB-18
HB-18
HB-5
HB-5
HB-5
HB-5
HB-18
HB-18
HB-18
HB-18
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
HB-5
Page 2 of 2
22-Oct-2002
FIKE
ZONE MODEL
RHINO
RHINO
RHINO
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
10-038
10-038
10-038
10-038
10-038
10-038
10-038
10-038
10-038
10-038
10-039
10-039
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, -2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2141, 10-2144
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ZONE
ID
DET220
DET220
DET220
DET220
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
DET470
102171
102171
102171
102171
102171
102171
MDL. NO
102171
102171
102171
102171
102171
102171
102171
102171
102171
102171
MDL. NO
102171
102171
102171
102171
102171
102171
102171
MDL NO
102171
MDL. NO
038000
038000
038000
038000
038000
038000
038000
038000
038000
038000
038000
038000
LOOP
STYLE
B, D
B, D
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B, D
B
B
B
B
B
B
B
B
B
B
B, D
B
B
B
B
B
B
B
B, D
B
B, D
B
D
B
D
B
D
D
B
B
D
D
B
MAX
DET
50
50
50
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
87
87
87
87
87
87
87
87
87
87
87
87
EOL
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
3.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
4.3K OHM
1.5K OHM
N/A
1.5K OHM
N/A
1.5K OHM
N/A
N/A
1.5K OHM
1.5K OHM
N/A
N/A
1.5K OHM
BASE MODEL
BASE ID
HSC-220L
HSC-220R
NS4-220, NS6-220
N/A
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
NS4-221, NS6-221
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-221, NS6-221
NS4-224, NS6-224
HSC-220R
HSC-221R
HSC-224R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-221, NS6-221
NS4-224, NS6-224
N/A
HS-220D
HS-220D
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-220RB
HS-220RB
YBA-M220
YBA-M220
HS-220D
HS-220D
HB-64
HB-72
HB-3
N/A
HB-72
HB-71
HB-73
HB-3
HB-4
HB-5
HB-72
HB-71
HB-73
HB-3
HB-4
HB-5
HB-72
HB-71
HB-73
HB-3
HB-4
HB-5
HB-72
HB-71
HB-73
HB-3
HB-4
HB-5
HB-72
HB-71
HB-73
HB-3
HB-4
HB-5
HB-4
HB-72
HB-71
HB-73
HB-3
HB-4
HB-5
HB-72
HB-71
HB-73
HB-3
HB-4
HB-4
HB-5
HB-72
HB-71
HB-73
HB-3
HB-4
HB-4
HB-5
N/A
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-12
HB-12
HB-3
HB-3
HB-3
HB-3
Page 1 of 2
22-Oct-2002
ZONE MODEL
10-039
10-039
10-039
10-039
10-039
10-039
10-039
10-039
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
RHINO 10-050
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
SHP 10-051
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
DCM-10-2141
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
10-2171
ZONE
ID
038000
038000
038000
038000
038000
038000
038000
038000
LOOP
STYLE
B
D
D
B
D
B
D
B
DET220
DET
DET220
DET
DET220
DET
DET220
DET220
DET220
DET
DET220
DET
DET220
DET
DET220
DET
DET
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
87
87
87
87
87
87
87
87
1
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
25
25
25
25
25
25
25
25
25
EOL
1.5K OHM
N/A
N/A
1.5K OHM
N/A
1.5K OHM
N/A
1.5K OHM
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3
3.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
BASE MODEL
BASE ID
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-220RB
HS-220RB
YBA-M220
YBA-M220
HSB-224
HSB-220
HSB-24
YBA-M220
YBA-M224
HSB-220
HSB-224
YBA-M220
HSB-220
HSB-220
HSB-224
YBA-M220
YBA-M224
HSB-220
HSB-224
YBA-M220
YBA-M224
YBA-M224
HS-221D
HSB-220
HSB-224
YBA-M220
YBA-M224
HS-221D
HSB-224
YBA-M220
YBA-M224
HB-3
HB-3
HB-3
HB-3
HB-12
HB-12
HB-3
HB-3
HB-53
HB-56
HB-53
HB-3
HB-5
HB-56
HB-53
HB-3
HB-56
HB-56
HB-53
HB-3
HB-5
HB-56
HB-53
HB-3
HB-5
HB-5
HB-4
HB-56
HB-53
HB-3
HB-5
HB-4
HB-53
HB-3
HB-5
Page 2 of 2
22-Oct-2002
FIRELITE
LOOP
STYLE
B, D
B, D
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B
B
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
11
11
15
15
15
15
15
15
15
15
15
15
15
15
11
11
15
15
15
15
15
15
15
15
15
15
15
15
10
10
15
15
15
15
15
15
15
15
10
15
15
11
11
15
15
15
15
15
15
15
15
15
15
10
10
1
1
1
1
1
1
1
10
10
10
15
15
15
15
15
15
EOL
DETECTOR MODEL
2.2K
2.2K
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K
2.2K
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K
2.2K
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K
2.2K
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
LPSD-12
LPSD-12
SLR-835
SLR-835B-2
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835B-2
LPSD-12
LPSD-12
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
LPSD-12
LPSD-12
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835B-2
SLR-835BH-2
SLR-835H
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-835H
SLR-835
SLR-835B-2
LPSD-12
LPSD-12
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835B-2
SLR-835H
SLR-835H
SLR-835,-835W
SLR-835,-835W
SLR-835H,-835HW
SLR-835H,-835HW
SIJ-24
SLR-24V
SLR-24V
SLR-835BH-2
SLR-835H
SLR-835H
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
SIJ-24
SIJ-24
DETECTOR
ID
HD-4
HD-4
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-4
HD-4
HD-3
HD-3
HD-3
HD-3
HD-4
HD-4
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-6
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-5
HD-3
HD-6
HD-4
HD-4
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-5
HD-5
HD-5
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-6
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
BLP-12-R
BLP-12-RN
NS4-220, NS6-220
N/A
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-220, NS6-220
N/A
BLP-12-R
BLP-12-RN
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
BLP-12-R
BLP-12-RN
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-220, NS6-220
N/A
N/A
NS4-220,NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-220,NS6-220
NS4-220, NS6-220
N/A
BLP-12-R
BLP-12-RN
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-220, NS6-220
N/A
HSC-220R
NS4-220,NS6-220
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
N/A
HSC-220R
NS4-220,NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HB-83
HB-83
HB-3
N/A
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
HB-83
HB-83
HB-64
HB-72
HB-3
HB-64
HB-83
HB-83
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
N/A
HB-3
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-3
HB-3
N/A
HB-83
HB-83
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
HB-72
HB-3
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
N/A
HB-72
HB-3
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
Page 1 of 2
22-Oct-2002
LOOP
STYLE
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B,D
B,D
B,D
B,D
B,D
B,D
B,D
B
B
B
B
B
B
B
B
B
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
15
15
15
15
1
1
1
1
1
1
1
1
1
1
1
1
1
10
10
15
15
15
15
15
15
15
15
15
15
20
20
20
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
EOL
DETECTOR MODEL
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835B-2
SLR-835,-835W
SLR-835H,-835HW
SLR-835H,-835HW
SIJ-24
SLR-24V
SLR-24V
SLR-835,-835W
SLR-835,-835W
SLR-835H,-835HW
SLR-835H,-835HW
SIJ-24
SLR-24V
SLR-24V
SLR-835H
SLR-835H
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835B-2
DFE-135, -190
SLR-24H
SLR-24H
DCD-135, DCD-190
DCD-135, DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
DCD-135, -190
DCD-135, -190
DCD-135, -190
DFE-135, -190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835B-2
DFE-135, -190
SLR-24H
SLR-24H
DCD-135, DCD-190
DCD-135, DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
DETECTOR
ID
HD-3
HD-3
HD-3
HD-6
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-5
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HSC-220R
NS4-220, NS6-220
NS4-220, NS6-220
N/A
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2
SBC-2
SBC-2R
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
HSC-220R
NS4-220,NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-220, NS6-220
N/A
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-220, NS6-220
N/A
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HB-72
HB-3
HB-3
N/A
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-72
HB-3
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
UPDATED 9/11/03
Page 2 of 2
22-Oct-2002
FIRESCAN
LOOP
STYLE
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
B/D
MAX
DET
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
EOL
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
4.3K
BASE MODEL
BASE ID
HS-221D
HSB-220
HSB-224
YBA-220
YBA-M224
HS-221D
HSB-220
HSB-224
YBA-M220
YBA-M224
HS-221D
HSB-220
HSB-224
YBA-M220
YBA-M224
HB-4
HB-56
HB-53
HB-3
HB-5
HB-4
HB-56
HB-53
HB-3
HB-5
HB-4
HB-56
HB-53
HB-3
HB-5
22-Oct-2002
ZONE MODEL
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-1
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
IRC-3
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
130022
130022
130022
130022
130022
130022
130022
130022
130022
130022
130022
130022
130082
130082
130082
130082
130082
130082
130082
130082
130082
130082
130082
130082
130108
130108
130108
130108
130108
130108
130108
240113
240113
240113
240113
240113
240113
240119
240119
240119
240119
240119
240119
240205
240205
240205
240205
240205
240205
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
ZONE
ID
5876
5876
5876
5876
5876
5876
5876
5876
5876
5876
5876
5876
3289A
3289A
3289A
3289A
3289A
3289A
3289A
3289A
3289A
3289A
3289A
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
3289B
5389
5389
5389
5389
5389
5389
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
LOOP
STYLE
B
D
B
D
B
D
B
D
B
D
B
D
B
D
B
D
D
B
D
B
D
B
D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
D
D
D
D
D
D
D
D
D
D
D
D
B
D
B
D
B
D
B
D
D
B
B
D
D
B
D
B
D
B
D
MAX
DET
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
260001
N/A
260001
N/A
260001
N/A
260001
N/A
260001
N/A
260001
N/A
260001
N/A
260001
N/A
N/A
260001
N/A
260001
N/A
260001
N/A
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
260001
PN260001
PN260001
PN260001
PN260001
PN260001
PN260001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
DETECTOR
ID
HD-2
HD-2
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
SLK-24F
SLK-24F
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-22D
HS-22D
YBA-M22
YBA-M22
HS-22D
HS-22D
YBA-M22
YBA-M22
HS-22D
HS-22D
YBA-M22
YBA-M22
HS-22D
HS-22D
YBA-M22
YBA-M22
HS-22D
HS-22D
YBA-M22
YBA-M22
HS-22D
HS-22D
YBA-M22
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-22D
YBA-M22
HS-220D
HS-224D
YBA-M224
YBA-M220
HS-220D
HS-M224
YBA-M224D
YBA-M220
HS-220D
HS-224D
YBA-M224
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-M224
HS-M224
YBA-M224D
YBA-M224D
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-224D
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-3
HB-3
HB-5
HB-5
HB-3
HB-3
HB-5
HB-5
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
Page 1 of 3
22-Oct-2002
ZONE MODEL
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1, LSS4
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4CLA
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
4ZEXP
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
ZONE
ID
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
LOOP
STYLE
B
B
D
D
B
B
D
D
B
D
B
B
D
D
B
B
D
D
B
D
B
D
B
D
B
D
B
D
B
D
D
D
D
D
D
D
D
D
D
D
D
B
D
D
B
D
B
D
B
B
D
D
B
D
B
D
B
D
B
B
D
D
B
B
D
D
B
B
D
D
B
D
B
D
B
D
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-224D
HS-M224
HS-M224
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-M224
HS-M224
YBA-M224D
YBA-M224D
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HS-220D
HS-224D
YBA-M224
YBA-M220
HS-220D
HS-M224
YBA-M224D
YBA-M220
HS-220D
HS-224D
YBA-M224
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-M224
HS-M224
YBA-M224D
YBA-M224D
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-M224
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-5
HB-5
HB-3
HB-3
HB-5
HB-5
HB-3
HB-3
HB-5
HB-5
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
Page 2 of 3
22-Oct-2002
ZONE MODEL
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
LSS1/12,LSS4/12
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
MOTHERBOARD
ZONE
ID
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
LOOP
STYLE
B
B
D
D
B
D
B
D
B
D
B
D
B
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
3.9K OHM
3.9K OHM
N/A
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
N/A
3.9K OHM
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-M224
YBA-M224D
YBA-M224D
YBA-M220
YBA-M220
HS-220D
HS-220D
HS-224D
HS-224D
YBA-M224
YBA-M224
YBA-M220
YBA-M220
HB-5
HB-5
HB-5
HB-3
HB-3
HB-3
HB-3
HB-5
HB-5
HB-5
HB-5
HB-3
HB-3
Page 3 of 3
22-Oct-2002
GRINNELL
ZONE MODEL
C200
C200
NA
NA
ZONE
ID
24F
24F
LOOP
STYLE
B
B
MAX
DET
30
30
EOL
7628
7628
BASE MODEL
BASE ID
HS-224D/HSB-224
HS-224D
HB-5
HB-5
22-Oct-2002
ZONE MODEL
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
AL-1500
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP1000
HCP-1000 SERIES
HCP-1000 SERIES
HCP-1000 SERIES
HCP-1000 SERIES
HCP-1000 SERIES
HCP-1000 SERIES
HCP-1000 SERIES
HCP-1000 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
HCP200 SERIES
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
AL-4ZDM
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
UPDATED 9/11/03
ZONE
ID
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
HP-2A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
3
3
3
3
30
30
1
1
1
1
1
1
1
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
3
3
3
3
30
30
1
1
1
1
1
1
1
EOL
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
BASE MODEL
BASE ID
YBF-RL/4H5US
YBF-RL/4H5US
YBF-RL/4H5US
YBF-RL/4H5US
YBF-RL/4H5US
YBF-RL/4H5US
YBF-RL/4H5US
YBF-RL/4H5US
HS-224RB
HS-224RB
HS-224RB
HS-224RB
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, -220W
NS6-220, -220W
N/A
N/A
N/A
N/A
NS4-220, -220W
NS6-220, -220W
SBC-2,SBC-2W
SBC-2R
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, -220W
NS6-220, -220W
N/A
N/A
N/A
N/A
NS4-220, -220W
NS6-220, -220W
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
HB-21
HB-21
HB-21
HB-21
HB-21
HB-21
HB-21
HB-21
HB-14
HB-14
HB-14
HB-14
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
N/A
N/A
N/A
HB-3
HB-3
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
N/A
N/A
N/A
HB-3
HB-3
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
22-Oct-2002
ISI WIRELESS
ZONE MODEL
FMS 1000
FMS 1000
FMS 1000
FMS 1000
FMS 1000
FMS 1000
FMS 500
FMS 500
FMS 500
FMS 500
FMS 500
FMS 500
FMS 500-96
FMS 500-96
FMS 500-96
FMS 500-96
FMS 500-96
FMS 500-96
4ZID
4ZID
4ZM
4ZM
4ZM
4ZM
4ZID
4ZID
4ZM
4ZM
4ZM
4ZM
4ZID
4ZID
4ZM
4ZM
4ZM
4ZM
ZONE
ID
4ZID
4ZID
4ZMB
4ZMA
4ZMB
4ZMA
4ZID
4ZID
4ZMA
4ZMB
4ZMA
4ZMB
4ZID
4ZID
4ZMA
4ZMB
4ZMA
4ZMB
LOOP
STYLE
D
D
B
B
B
B
D
D
B
B
B
B
D
D
B
B
B
B
MAX
DET
66
66
66
15
66
15
66
66
15
66
15
66
66
66
15
66
15
66
EOL
N/A
N/A
4.7K OHM
22K OHM
4.7K OHM
22K OHM
N/A
N/A
22K OHM
4.7K OHM
22K OHM
4.7K OHM
N/A
N/A
22K OHM
4.7K OHM
22K OHM
4.7K OHM
BASE MODEL
BASE ID
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HS-220
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
22-Oct-2002
MIRCOM
ZONE MODEL
FA-1000
FA-1000
FA-1000
FA-101U
FA-101U
FA-101U
FA-101U
FA-101U
FA-101U
FA-101U
FA-101U
FA-101U, FA-1020U
FA-101U, FA-1020U
FA-101U, FA-1020U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-1025U
FA-102U
FA-102U
FA-102U
FA-102U
FA-102U
FA-102U
FA-102U
FA-102U
FA-102U
FA-104/8U
FA-104/8U
FA-104/8U
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/8U, 8UX
FA-104/BUX
FA-104/BUX
FA-104/BUX
FA-200
FA-200
FA-200
FA-200
FA-200, FA-1000
FA-200, FA-1000
FA-200, FA-1000
FA-200, FA-1000
FA-200, FA-1000
FA-200, FA-1000
FA-200, FA-1000
FA-200, FA-1000
FA-1000
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
SERIES 100
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ZONE
ID
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
B, D
B, D
B, D
B
B
B
B
B
B
B
B
B, D
B, D
B, D
B
B
B
B
B
B
B,D
B
B
B,D
B
B
B
B
B
B
B
B
B
B, D
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B
B
B
B
B, D
B
B
B
B
B, D
B, D
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
3.9K OHM
DEF-135, -190
SLR-24H
SLR-24H
DCD-135
DCD-135
DCD-190
DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
DEF-135, -190
SLR-24H
SLR-24H
DCD-135
DCD-135
DCD-190
DCD-190
DFE-135, -190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24H
SLR-24H
DCD-135
DCD-135
DCD-190
DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
DEF-135, -190
SLR-24H
SLR-24H
SLR-24H
SLR-24H
DCD-135
DCD-135
DCD-190
DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
DEF-135, -190
SLR-24H
SLR-24H
DEF-135, -190
SLR-24H
SLR-24H
SLR-835B-2
DCD-135
DCD-135
DCD-190
DCD-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-835B-2
DCD-135
DCD-135
DCD-190
DCD-190
DEF-135, -190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24H
SLR-24H
DETECTOR
ID
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
N/A
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
N/A
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
N/A
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
N/A
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
N/A
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
22-Oct-2002
MODULAR PROT.
LOOP
STYLE
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
HB-10
HB-3
HB-56
HB-53
HB-3
22-Oct-2002
NAPCO
LOOP
STYLE
B
B
B,D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
MAX
DET
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
EOL
DETECTOR MODEL
2.2K OHM
2.2K
2.2K OHM
2.2K
2.2K
2.2K OHM
3.9K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K
2.2K
2.2K OHM
2.2K OHM
2.2K
2.2K OHM
2.2K
2.2K OHM
SLR-835BH-2
SLR-835B-2
SLR-835BH-2
SLR-835B-2
SLR-835B-2
SLR-835BH-2
SLR-835B-2
SLR-835BH-2
SLR-835BH-2
SLR-835B-2
SLR-835B-2
SLR-835B-2
SLR-835BH-2
SLR-835BH-2
SLR-835B-2
SLR-835BH-2
SLR-835B-2
SLR-835BH-2
DETECTOR
ID
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
HD-6
BASE MODEL
BASE ID
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
22-Oct-2002
NOTIFIER
ZONE MODEL
AFM-200
AFM-200
AFM-200
AFM-200
AFM-200
AFM-200
AFM-200
AFP-1010
AFP-1010
AFP-1010
AFP-1010
AFP-1010
AFP-1010
AFP-1010
AFP-1010
AFP-200
AFP-200
AFP-200
AFP-200
AFP-200
AFP-200
AFP-200
AM 2020
AM 2020
AM 2020
AM 2020
AM 2020
AM 2020
AM 2020
MMX-2
MMX-2
RP-1001
RP-1001
RP-1001
RP-1001
RP-1001
RP-1002
RP-1002
RP-1002
RP-1002
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2
MMX-2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
IZ-4,IZM-8
IZ-4,IZM-8
IZ-4,IZM-8
IZ-4,IZM-8
IZM-8
IZM-8
IZM-8
IZM-8
IZM-8
IZM-8
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
ZONE
ID
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B
D
D
B
D
B
B
D
B
D
B
D
B
D
D
B
B
D
MAX
DET
1
25
25
1
25
1
25
1
1
25
25
1
25
1
25
1
25
25
1
25
1
25
1
25
25
1
25
1
25
25
25
30
30
30
30
30
30
30
30
30
15
15
15
20
10
10
10
10
10
10
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
N/A
N/A
4.7K OHM
N/A
4.7K OHM
4.7K OHM
N/A
4.7K OHM
N/A
4.7K OHM
N/A
4.7K OHM
N/A
N/A
4.7K OHM
4.7K OHM
N/A
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIH-24F
SLK-24F/FH
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
SLK-24F/FH
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
DFE-135,-190
SLR-24H
SLR-24H
SLR-835B-2
DCD-135,-190
DCD-135,-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-2-RB
HS-22D
YBA-M22
HS-2-RB
HS-22D
HS-2-RB
YBA-M22
HS-2-RB
HS-2-RB
HS-22D
YBA-M22
HS-2-RB
HS-22D
HS-2-RB
YBA-M22
HS-2-RB
HS-22D
YBA-M22
HS-2-RB
HS-22D
HS-2-RB
YBA-M22
HS-2-RB
HS-22D
YBA-M22
HS-2-RB
HS-22D
HS-2-RB
YBA-M22
HS-220
HS-220
HS-220
HSB-224
HS-220
HS-220
HSB-224
HS-220
HSB-224
HS-220
HSB-224
HSC-220L
HSC-220R
NS4-220, NS6-220
N/A
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HS-22D
HS-22D
HS-220D
HS-220D
YBA-M22
YBA-M22
YBA-M220
YBA-M220
HS-22D
HS-22D
HS-220D
HS-220D
YBA-M22
YBA-M22
YBA-M220
YBA-M220
HS-22D
HS-22D
HB-10
HB-3
HB-3
HB-10
HB-3
HB-10
HB-3
HB-10
HB-10
HB-3
HB-3
HB-10
HB-3
HB-10
HB-3
HB-10
HB-3
HB-3
HB-10
HB-3
HB-10
HB-3
HB-10
HB-3
HB-3
HB-10
HB-3
HB-10
HB-3
HB-56
HB-56
HB-56
HB-53
HB-56
HB-56
HB-53
HB-56
HB-53
HB-56
HB-53
HB-64
HB-72
HB-3
N/A
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
Page 1 of 3
22-Oct-2002
ZONE MODEL
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
S 5000
SFB-400B
SFB-400B
SFB-400
SFB-400
SFB-400B
SFB-400B
SFB-400B
SFB-400B
SFB-400B
SFB-400B
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000
SLG-2000,XPM-8
SLG-400
SLG-400
SLG-404
SLG-404
SLG-404
SLG-404
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
IZM-8, IZE-A
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
MMX-2, M3-TW
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
IZ-4
IZ-4
IZ-4
IZ-4
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4, IZM-8
IZ-4A
IZ-4A
IZ-4A
IZ-4A
ZONE
ID
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
B
D
D
B
A
B
B
D
D
B
D
B
B
D
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
B
B
BD
BD
B
B
B, D
B, D
BD
BD
B, D
B, D
BD
BD
B, D
B, D
B, D
BD
BD
BD
BD
BD
BD
B
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B
B
B
B
MAX
DET
30
30
30
30
D
30
30
30
30
30
30
30
30
30
1
25
25
1
25
1
25
30
30
30
30
30
30
30
30
30
30
10
10
30
30
10
10
30
30
10
10
20
30
30
30
30
30
30
35
35
35
35
10
10
15
10
10
10
10
15
15
35
35
35
35
EOL
DETECTOR MODEL
4.7K OHM
N/A
N/A
4.7K OHM
30
4.7K OHM
4.7K OHM
N/A
N/A
4.7K OHM
N/A
4.7K OHM
4.7K OHM
N/A
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
3.9K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K OHM
4.7K OHM
4.7K
4.7K
4.7K OHM
4.7K OHM
4.7K
4.7K
4.7K OHM
4.7K OHM
4.7K OHM
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K
4.7K
4.7K
4.7K
SLK-24F
SLK-24F
SLK-24F
SLK-24F
N/A
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24F/FH
SLK-24F/FH
SIH-24F
SLK-24F/FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
DCD-135,-190
DCD-135,-190
SIH-24F
SIH-24F
SIJ-24
SIJ-24
SLK-24F/FH
SLK-24F/FH
SLR-24
SLR-24
SLR-835B-2
SIH-24F
SLK-24F/FH
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
DCD-135,-190
DCD-135,-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24H
SLR-24H
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-220D
HS-220D
YBA-M22
YBA-M22
YBA-M220
YBA-M220
HS-22D
HS-22D
HS-220D
HS-220
YBA-M22
YBA-M22
YBA-M220
YBA-M220
HS-2-RB
HS-22D
YBA-M22
HS-2-RB
HS-22D
HS-2-RB
YBA-M22
HSB-220
HSB-224
HSB-220
HSB-224
HS-2-RB
HS-22D,YBA-M22
HSB-220
HSB-224
HS-2-RB
HS-22D,YBA-M22
HSC-220R
NS4-220, NS6-220
HSB-220
HSB-224
HSC-220R
NS4-220, NS6-220
HSB-220
HSB-224
HSC-220R
NS4-220, NS6-220
N/A
HSB-224
HSB-220
HSB-220
HSB-224
HSB-220
HSB-224
HSB-220
HSB-224
HSB-220
HSB-224
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSB-220
HSB-224
HSB-220
HSB-224
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-56
HB-3
HB-3
HB-3
HB-3
HB-10
HB-3
HB-3
HB-10
HB-3
HB-10
HB-3
HB-56
HB-53
HB-56
HB-53
HB-10
HB-3
HB-56
HB-53
HB-10
HB-3
HB-72
HB-3
HB-56
HB-53
HB-72
HB-3
HB-56
HB-53
HB-72
HB-3
N/A
HB-53
HB-56
HB-56
HB-53
HB-56
HB-53
HB-56
HB-53
HB-56
HB-53
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-56
HB-53
HB-56
HB-53
Page 2 of 3
22-Oct-2002
ZONE MODEL
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 500
SYSTEM 5000
SYSTEM 5000
SYSTEM 5000
SYSTEM 5000
SYSTEM 5000
SYSTEM 5000
SYSTEM 5000
SYSTEM 5000
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
XP TRANSPONDER
IZ-8
IZ-8
IZ-8
IZ-8
IZE-A
IZE-A
IZE-A
IZE-A
IZE-A
IZM-8
IZE-A
IZE-A
IZE-A
IZM-8
IZM-8
IZM-8
N/A
N/A
N/A
N/A
N/A
N/A
XPM-8
XPM-8
XPM-8
XPM-8
ZONE
ID
A
A
A
A
A
A
A
A
IZE-A
IZM-8
IZE-A
IZE-A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
BD
BD
BD
BD
BD
BD
BD
BD
B, D
B
B, D
B, D
B, D
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
20
20
20
20
20
20
60
60
60
60
EOL
DETECTOR MODEL
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
2.2K OHM
4.7K
4.7K
4.7K
4.7K
SIH-24F
SIH-24F
SLK-24/FH
SLK-24F/FH
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
SIH-24F
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
SIH-24F
SLK-24F/FH
SLK-24F/FH
DCD-135,-190
DCD-135,-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SIH-24F
SIH-24F
SLK-24F/FH
SLK-24F/FH
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HSB-220
HSB-224
HSB-224
HSB-220
HSB-220
HSB-224
HSB-220
HSB-224
HSB-220
HSB-224
HSB-224
HSB-220
HSB-224
HSB-220
HSB-220
HSB-224
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSB-220
HSB-224
HSB-220
HSB-224
HB-56
HB-53
HB-53
HB-56
HB-56
HB-53
HB-56
HB-53
HB-56
HB-53
HB-53
HB-56
HB-53
HB-56
HB-56
HB-53
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-56
HB-53
HB-56
HB-53
Page 3 of 3
22-Oct-2002
LOOP
STYLE
B
B
B
B
MAX
DET
1
1
1
1
EOL
N/A
N/A
N/A
N/A
DETECTOR
MODEL
SLR-835BH-2
SLR-835BH-2W
SLR-835BH-2
SLR-835BH-2W
DETECTOR
ID
HD-6
HD-6
HD-6
HD-6
BASE MODEL
BASE ID
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
22-Oct-2002
POTTER ELECTRIC
ZONE MODEL
PFC-100 NRC
PFC 100 RC
PFC 100 RC
PFC 100 RC
PFC 100 RC
PFC 100 RC
PFC 100 RC
PFC 100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-100 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-2000 RC
PFC-4410
PFC-4410
PFC-4410
PFC-4410
PFC-4410
PFC-4410
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ZONE
ID
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
LOOP
STYLE
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
25
1
1
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
EOL
DETECTOR MODEL
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
5.1K
SLK-24FH
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
DETECTOR
ID
HD3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-221D
HS-221D
HS-221D
HS-21D
HS-221 RB
HS-221D
HS-21D
HS-221 RB
HSB-221
HSB-221N
HSB-221R
HSB-221
HSB-221N
HSB-221R
HSB-221
HSB-221N
HSC-221R
HSB-221
HSB-221N
HSC-221R
HSB-221
HSB-221N
HSC-221R
HSB-221
HSB-221N
HSC-221R
HSB-221
HSB-221N
HSB-221
HSB-221N
HSB-221
HSB-221N
HB4
HB-2
HB-4
HB-2
HB-13
HB-4
HB-2
HB-13
HB-54
HB-54
HB-71
HB-54
HB-54
HB-71
HB-54
HB-54
HB-71
HB-54
HB-54
HB-71
HB-54
HB-54
HB-71
HB-54
HB-54
HB-71
HB-54
HB-54
HB-54
HB-54
HB-54
HB-54
22-Oct-2002
PROTECTOWIRE
ZONE MODEL
ACR-1600 SERIES
ACR-1600 SERIES
ACR-1600 SERIES
ACR-1600 SERIES
ACR-1600 SERIES
ACR-1600 SERIES
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000
FS2000 SERIES
FS2000 SERIES
FS2000 SERIES
FS2000 SERIES
ZM-2200
ZM-2200
ZM-2200
ZM-2200
ZM-2200
ZM-2200
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91, ZC-91M
ZC-91
ZC-91
ZC-91
ZC-91M
ZONE
ID
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
ZC-91
ZC-91
ZC-91
ZC-91
LOOP
STYLE
AD
AD
AD
AD
AD
AD
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
BD
BD
BD
BD
MAX
DET
20
20
20
20
20
20
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
ELR-1A
ELR-1A
ELR-1A
ELR-1A
ELR-1A
ELR-1A
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
DCD-135
DCD-135
DCD-190
DCD-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24H
SLR-24H
SLR-24H
SLR-835B-2
SIH-24F
SIH-24F
SLK-24F
SLK-24F
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-S
HD-S
HD-3
HD-3
BASE MODEL
BASE ID
HS-220D
HS-220D
HS-220D
HS-220D
HS-220D
HS-220D
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220
NS4-220, NS6-220
N/A
HS-220D
HS-220D
HS-220D
HS-220D
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-3
N/A
HB-3
HB-3
HB-3
HB-3
22-Oct-2002
RADIONICS
ZONE MODEL
D2012,D2112
D2212
D2212, D2412
D2212B
D2212B
D2212BE
D2412UE
D2812
D2812,D2812U
D4112
D4112
D4112
D6112
D6112
D6112
D7112
D7112
D7212
D7212
D7212
D7212
D7212
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7212,D7412
D7412
D7412
D7412
D7412
D8112
D8112
D8112
D8112,D9112
D9112
D9112
D9112,D9412
D9112,D9412
D9112,D9412
D9112,D9412
D9112B,D9124
D9112B,D9124
D9112B,D9124
D9112B,D9124
D9112B,D9124
D9112B,D9124
D9412
D9412
D9412
D9412
D9412
D9412
D9412
D9412
D9412
D9412
2 WIRE
ZONE 1
2 WIRE
1
ZONE 1
1
1
1
2 WIRE
N/A
N/A
N/A
N/A
N/A
N/A
D125B
D125B
D125B
D125B
OWB/125B 24VDC
OWB/D125B 24VDC
OWB/D125B 24VDC
D125B
D125B
D125B
D125B
D125B
D125B
ZONE 1
ZONE 1
ZONE 1
ZONE 1
ONBOARD W/125B
ONBOARD W/D125B
ONBOARD W/D125B
ONBOARD W/D125B
D8112 W/D125B
D8112 W/D125B
N/A
ZONE NO
D125B
D125B
ZONE 1
ZONE 1
ZONE 1
ZONE 1
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
ONBOARD W/D125B
ONBOARD W/D125B
ONBOARD W/D125B
ONBOARD W/D125B
ZONE
ID
POINT1
221201
POINT1
B
221201
B
B
B
POINT1
B
B
1
B
B
2
A
A
A
A
MDL NO
MDL NO
MDL NO
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
2 TO 8
D125B
A
A
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
D125B
MDL NO
MDL NO
MDL NO
MDL NO
LOOP
STYLE
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
MAX
DET
40
15
40
15
15
15
15
15
40
20
20
20
20
20
20
20
20
20
20
80
80
80
40
40
40
40
40
40
40
40
40
40
80
80
15
80
20
20
20
40
20
20
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
80
15
80
80
EOL
1.8K OHM
2K
1.8K OHM
152K
151515
1.8K OHM
1.8K OHM
1.8K OHM
D104F
1.8K OHM
1.8K OHM
D104F
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K
1.8K
1.8K
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K
1.8K
1.8K
1.8K
1.8K OHM
1.8K OHM
D108
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K OHM
1.8K
1.8K
1.8K
1.8K
BASE MODEL
BASE ID
N/A
D261A
N/A
D261A
D261A
D261A
D261A
D261A
N/A
HSB-12-1
HSB-12-1N
YBC-RL/12
HSB-12-1
HSB-12-1N
YBC-RL/12
HSB-12-1
HSB-12-1N
HSB-12-1
HSB-12-1N
HS224D
HS224D
HS224D
HSC-220L
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-224, NS6-224
N/A
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HS224D
HS224D
YBC-AL/12
HS224D
HSB-12-1
HSB-12-1N
YBC-RL/12
N/A
HSB-12-1
HSB-12-1N
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-224, NS6-224
N/A
HSC-220L
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-224, NS6-224
N/A
HS224D
YBC-AL/12
HS224D
HS224D
N/A
HB-80
N/A
HB-80
HB-80
HB-80
HB-80
HB-80
N/A
HB-80
HB-80
HB-40
HB-80
HB-80
HB-40
HB-80
HB-80
HB-80
HB-80
HB-5
HB-5
HB-5
HB-64
HB-72
HB-55
HB-3
HB-5
N/A
HB-72
HB-3
HB-72
HB-3
HB-5
HB-5
HB-40
HB-5
HB-80
HB-80
HB-40
N/A
HB-80
HB-80
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-55
HB-3
HB-5
N/A
HB-64
HB-72
HB-55
HB-3
HB-5
N/A
HB-5
HB-40
HB-5
HB-5
1 of 1
22-Oct-2002
RAULAND-BORG
ZONE MODEL
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FIRE PLEX
FIRE PLEX
FIRE PLEX
FIRE PLEX
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3002
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FA3125
FA3120,FAP3125
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3130,FAP3135
FA3001
FA3001
FA3130,FAP3135
FA3130,FAP3135
ZONE
ID
LP01
LP02
LP01
LP02
LP01
LP02
LP01
LP02
LP02
LP01
LP02
LP01
LP01
LP02
LP02
LP01
LP02
CZ02
CZ01
CZ02
CZ01
CZ01
CZ01
CZ01
CZ02
CZ01
CZ02
CZ02
CZ01
CZ02
CZ02
CZ02
CZ01
CZ02
CZ01
CZ02
CZ01
CZ01
CZ02
CZ02
CZ02
CZ01
LPO1
LPO1
CZ01
CZ01
LOOP
STYLE
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
2 A
2 A
A
A
MAX
DET
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
1
1
1
1
1
1
1
3
1
1
3
1
3
1
1
1
3
1
1
1
1
3
1
3
1
50
50
1
1
EOL
DETECTOR MODEL
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
30K
20K
30K
20K
20K
20K
20K
30K
20K
30K
30K
20K
30K
30K
30K
20K
30K
20K
30K
20K
20K
30K
30K
30K
20K
1344
1344
1346
1346
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SLK-24FH
SIH-24F
SIH-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SLK-24F
SLK-24F
SIH-24F
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HB-3
HB-3
HB-56
HB-56
HB-72
HB-72
HB-3
HB-3
HB-56
HB-56
HB-72
HB-72
HB-3
HB-3
HB-56
HB-72
HB-72
HB-3
HB-3
HB-3
HB-56
HB-3
HB-3
HB-56
HB-56
HB-3
HB-3
HB-56
HB-56
HB-56
HB-3
HB-3
HB-3
HB-56
HB-56
HB-3
HB-3
HB-56
HB-56
HB-3
HB-56
HB-56
HB-3
HB-3
HB-3
HB-3
22-Oct-2002
SECURTON
ZONE MODEL
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2900
MR-2900
MR-2900
MR-2900
MR-2900
MR-2900
MR-2900
MR-2900
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2600
MR-2928
MR-2928
MR-2928
MR-2928
MR-2928
MR-2928
MR-2928
MR-2928
ZONE
ID
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
A
A
A
A
A
A
A
A
LOOP
STYLE
B
B
B
B
B
B
B
B
B, C
B, C
B, C
B, C
B, C
B, C
B, C
B, C
MAX
DET
29
29
25
25
22
22
22
22
34
34
26
26
24
24
24
24
EOL
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
MRD-2904
BASE MODEL
BASE ID
HS-221D
YBA-M221
HS-221D
YBA-M221
HS-221D
YBA-M221
HS-221D
YBA-M221
HS-221D
YBA-M221
HS-221D
YBA-M221
HS-221D
HS-221D
YBA-M221
YBA-M221
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
HB-4
22-Oct-2002
SILENT KNIGHT
ZONE MODEL
5204
5204
5204
5204 12 VOLT
5204 12 VOLT
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5207
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
5820, 5828XL
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
7181
SD500-SDM
N/A
N/A
N/A
N/A
N/A
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
5210
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NA
ZONE
ID
24C
24C
24C
N/A
N/A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24D
24D
24D
24D
24D
24D
24D
24B
24A
24B
24B
24A
24D
24D
24D
24D
24D
24D
24H
24H
24H
24H
24H
24H
24H
24H
24H
24H
24H
24H
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
24B
241
LOOP
STYLE
B
B
B
A
A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
A
B
A
A
B
B
B
B
B
B
B
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B, D
B/D
MAX
DET
30
30
30
20
20
30
30
30
30
30
30
30
30
30
30
30
30
30
30
10
10
30
30
30
30
30
30
30
40
20
40
40
20
30
30
30
30
25
25
12
12
12
12
12
12
12
12
12
12
12
12
30
30
30
30
30
30
30
18
18
18
18
30
30
30
30
20
25
EOL
DETECTOR MODEL
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628 4.7
7628
7628 4.7
7628 4.7
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
DFE-135,-190
SLR-24H
SLR-24H
SLK-24F
SLK-24FH
DCD-135
DCD-135
DCD-190
DCD-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24H
SLR-24H
SLR-835
SLR-835
SLR-835B-2
SIH-24F
SLK-24F
DCD-135
DCD-135
DCD-190
DCD-190
DFE-135,-190
SIJ-24
SIJ-24
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLR-24
SLR-24
SLR-24H
SLR-24H
SIH-24F
SLK-24F
DCD-135,-190
DCD-135,-190
DCD-135,-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835
SLR-835B-2
DCD-135
DCD-135
DCD-190
DCD-190
DFE-135,-190
SIJ-24
SIJ-24
SLK-12
SLK-12
SLK-12
SLK-12
SLR-24
SLR-24
SLR-24H
SLR-24H
SLR-835B-2
SIH-24F
DETECTOR
ID
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-4
HD-4
HD-4
HD-4
HD-3
HD-3
HD-3
HD-3
HD-6
HD-3
BASE MODEL
BASE ID
HSC-220L
HSC-220R
NS4-220, NS6-220
HS-224D
HS-224D
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
NS4-100, NS6-100
NS4-220, NS6-220
N/A
HS-224D/HSB-224
HS-224D/HSB-224
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HS-224D
HS-224D
HS-224C
HS-224C
HS-224D
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HS-224D/HSB-224
HS-224D/HSB-224
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-100, NS6-100
NS4-220, NS6-220
N/A
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSB-12-1
HSB-12-1
HSB-12-1N
HSB-12-1N
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
N/A
YBA-M224
HB-64
HB-72
HB-3
HB-5
HB-5
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-55
HB-3
N/A
HB-5
HB-5
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-5
HB-5
HB-5
HB-5
HB-5
HB-72
HB-3
HB-72
HB-3
HB-5
HB-5
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-55
HB-3
HB-55
HB-3
N/A
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-80
HB-80
HB-80
HB-80
HB-72
HB-3
HB-72
HB-3
N/A
HB-5
Page 1 of 3
22-Oct-2002
ZONE MODEL
ZONE
ID
SD500-SDM
NA
241
SD500-SDM
NA
241
SD500-SDM
NA
241
SK-5208,FC-5208 SK-5217,FC-5217 24J
SK-5208,FC-5208 SK-5217,FC-5217 24J
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK6324
N/A
24F
SK6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-6324
N/A
24F
SK-2224
NA
24F
SK-2224
NA
24F
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK-2224, SK4224 N/A
24FF
SK2224, SK4224 N/A
24F
SK2224, SK4224 N/A
24F
SK2224, SK4224 N/A
24F
SK2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK-2224, SK4224 N/A
24F
SK4224
N/A
24FF
SK4224
N/A
24FF
SK4224
N/A
24FF
SK4224
N/A
24FF
SK5208
N/A
24J
SK5208
N/A
24J
SK5208
N/A
24J
LOOP
STYLE
B, D
B, D
B/D
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B
B
D
D
B
B
B
B
B
B
B
B
B
D
D
D
D
D
D
D
D
D
D
D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
D
D
D
D
B, D
B, D
B, D
MAX
DET
25
25
25
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
1
1
1
1
1
1
1
30
30
15
15
15
15
15
15
15
15
15
15
15
10
10
10
10
30
30
30
30
30
30
30
30
30
30
30
1
1
1
1
1
1
1
10
10
10
30
15
15
15
EOL
DETECTOR MODEL
7628
7628
7628
7628
7628
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7628
7628
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7628
7628
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7628
7628
7628
7628
7628
7628
7628
7628
N/A
N/A
N/A
7628
7628
N/A
N/A
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
N/A
7628
7628
7628
SLK-24F
SLK-24FH
SLR-835B-2
SLR-835H
SLR-835H
DCD-135,-190
DCD-135,-190
DCD-135,-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835
SLR-835B-2
SLR-835H
SLR-835H
SLR-835,-835W
SLR-835,-835W
SLR-835H,-835HW
SLR-835H,-835HW
SIJ-24
SLR-24V
SLR-24V
SIH-24F
SLK-24F, -24FH
DCD-135,-190
DCD-135,-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835
SLR-835B-2
SLR-835BH-2
SLR-835H
SLR-835H
SLR-835H
DCD-135
DCD-135
DCD-190
DCD-190
DFE-135,-190
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24H
SLR-24H
SLR-835,-835W
SLR-835,-835W
SLR-835H,-835HW
SLR-835H,-835HW
SIJ-24
SLR-24V
SLR-24V
SLR-835H
SLR-835H
SLR-835H
SLR-835B-2
DCD-135,-190
DCD-135,-190
DCD-135,-190
DETECTOR
ID
HD-3
HD-3
HD-6
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-5
HD-5
HD-5
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-6
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
N/A
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-5
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-5
HD-5
HD-5
HD-6
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-224D
HS-224D
N/A
HSC-220R
NS4-220,NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-100, NS6-100
NS4-220, NS6-220
N/A
HSC-220R
NS4-220,NS6-220
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
HS-224D/HSB-224
HS-224D
HSC-220L
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-100, NS6-100
NS4-220, NS6-220
N/A
N/A
HSC-220R
NS4-100,NS6-100
NS4-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-220, NS6-220
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
HSC-220R
NS4-100,NS6-100
NS4-220,NS6-220
N/A
HSC-220L
HSC-220R
NS4-220, NS6-220
HB-5
HB-5
N/A
HB-72
HB-3
HB-64
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-55
HB-3
HB-55
HB-3
N/A
HB-72
HB-3
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-5
HB-5
HB-64
HB-3
HB-64
HB-72
HB-3
HB-72
HB-55
HB-3
HB-55
HB-3
N/A
N/A
HB-72
HB-55
HB-3
HB-72
HB-3
HB-72
HB-3
HB-64
HB-72
HB-3
HB-72
HB-3
HB-72
HB-3
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-72
HB-55
HB-3
N/A
HB-64
HB-72
HB-3
Page 2 of 3
22-Oct-2002
ZONE MODEL
SK5208
SK5208
SK5208
SK5208
SK5208
SK5208
SK5208
SK5208
SK5208
SK5208/FC-5208
SK5208/FC-5208
SK5208/FC-5208
SK5208/FC-5208
SK5208/FC-5208
SK5208/FC-5208
SK5208/FC-5208
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
C6000
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ZONE
ID
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24J
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
24E
LOOP
STYLE
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
MAX
DET
15
15
15
15
15
15
15
15
15
1
1
1
1
1
1
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
EOL
DETECTOR MODEL
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
7628
DFE-135,-190
SIJ-24
SIJ-24
SLR-24H, -24V
SLR-24H, -24V
SLR-24H, -24V
SLR-835
SLR-835
SLR-835B-2
SLR-835,-835W
SLR-835,-835W
SLR-835H,-835HW
SLR-835H,-835HW
SIJ-24
SLR-24V
SLR-24V
DCD-135
DCD-135
DCD-135
DCD-135
DCD-135
DCD-135
DCD-190
DCD-190
DCD-190
DCD-190
DCD-190
DCD-190
SIJ-24
SIJ-24
SIJ-24
SIJ-24
SIJ-24
SIJ-24
SLR-24
SLR-24
SLR-24
SLR-24
SLR-24
SLR-24
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-6
HD-5
HD-5
HD-5
HD-5
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HSC-220L
HSC-220R
NS4-220, NS6-220
HSC-220R
NS4-100, NS6-100
NS4-220, NS6-220
NS4-100, NS6-100
NS4-220, NS6-220
N/A
SBC-2,SBC-2W
SBC-2R,SBC-2RW
SBC-2R,SBC-2RW
SBC-2,SBC-2W
SBC-2
SBC-2
SBC-2R
HSC-220R
HSC-221R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
NS6-11, NS4-100
HSC-220R
HSC-221R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
NS6-11, NS4-100
HSC-220R
HSC-221R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
NS6-11, NS4-100
HSC-220R
HSC-221R
NS4-220, NS6-220
NS4-221, NS6-221
NS4-224, NS6-224
NS6-11, NS4-100
HB-64
HB-72
HB-3
HB-72
HB-55
HB-3
HB-55
HB-3
N/A
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-85
HB-72
HB-71
HB-3
HB-4
HB-5
HB-55
HB-72
HB-71
HB-3
HB-4
HB-5
HB-55
HB-72
HB-71
HB-3
HB-4
HB-5
HB-55
HB-72
HB-71
HB-3
HB-4
HB-5
HB-55
UPDATED 9/11/03
Page 3 of 3
22-Oct-2002
SIMPLEX
ZONE MODEL
SERIES 4010
SERIES 4010
SERIES 4010
SERIES 4010
SERIES 4010
SERIES 4010
SERIES 4010
SERIES 4010
4090-9101&-9106
4090-9101&-9106
4090-9101&-9106
4090-9101&-9106
4090-9101&-9106
4090-9101&-9106
4090-9101&-9106
4090-9101&-9106
ZONE
ID
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
LOOP
STYLE
B, D
B, D
B, D
B, D
B, D
B, D
B, D
B, D
MAX
DET
20
20
20
20
20
20
20
20
EOL
DETECTOR MODEL
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
3.3K
40909101
SIH-24F
SIH-24F
SLK-24FB
SLK-24FH
SLK-24FH
SLK-24KB
SLK-24KB
SLK-24FB
DETECTOR
ID
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HB-4
HB-54
HB-4
HB-4
HB-54
HB-4
HB-54
HB-54
SPECTRONICS
PANEL MODEL ZONE MODEL
324
324
324
324
624/641
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
624/MX
640
640
640
640
640
640
640
640
640
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
640/641
641
641
320/LC/OS-24
320/LC/OS-24
320/LC/OS-24
320/LC/OS-24
MX8/WIB
ADS
ADS
ADS
ADS
ADS-H
ADS-H
ADS-H
MX/OSH
MX/OSH
MX/OSH
MX/OSH
MX/OSH
MX/OSH
MX/OSH
MX/OSH
MX/I0-1O
MX/I01O-H
MX/I01O
MX/I01O
MX/I01O
MX/I01O
MX/I01O-H
MX/I01O-H
MX/I0-1O-H
MX/I0-1O-H
MX/I0-1O-H
MX/OSRP
MX/OSRP
MX/OSRP
MX/OSRP
MX8/WIBH
MX8/WIBH
MX8/WIBH
S2W
S2W
S2W
S2WA
S2WA
S2WA
MX8/WIB
MX8/WIB
MX8/WIB
MX8/WIB
MX8/WIB
MX8/WIB
MX8/WIB
S2/OSS
S2/OSS
S2/OSS
S21/OSS
S2A
S2A
S2A
S2A
S2W
S2W
S2W
S2WA
S2WA
S2WA
S2WA
MX8/WIBH
MX8/WIBH
22-Oct-2002
ZONE
ID
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
LOOP
STYLE
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B, D
B
B
B
B, D
B, D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
D
D
D
B
B
B
B
B
B
B
B
B
B
B
D
D
D
D
B
B
B
D
D
D
D
B
B
MAX
DET
15
11
13
13
13
15
11
13
13
50
39
44
50
40
39
44
40
44
39
40
22
39
39
50
19
22
44
44
50
40
40
15
11
13
13
50
40
40
50
40
40
50
40
40
15
50
11
39
44
44
13
15
11
13
13
15
11
13
13
50
44
44
50
39
44
44
50
40
EOL
DETECTOR MODEL
15 K
15 K
15 K
15 K
15K
15 K
15 K
15 K
15 K
4.7K
4.7K
4.7K
4.7K
4.7K OHM
4.7K
4.7K
4.7K OHM
4.7K
4.7K
4.7K OHM
15 k
4.7K
4.7K
4.7K
15 K
15 K
4.7K
4.7K
4.7K OHM
4.7K OHM
4.7K OHM
15 K
15 K
15 K
15 K
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
N/A
N/A
N/A
15 K
4.7K
15 K
4.7K
4.7K
4.7K
15 K
15 K
15 K
15 K
15 K
15 K
15 K
15 K
15 K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K
4.7K OHM
4.7K OHM
SIH-24F
SIH-24F
SLK-24F
SLK-24FG
SLK-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24FH
SIH-24F
SIH-24F
SLK-24F
SIF-24F
SIF-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
SLK-24FH
SIH-24F
SIF-24F
SIF-24F
SIH-24F
SLK-24F
SLK-24F
SLK-24FH
SIH-24F
SLK-24F
SLK-24FH
SIF-24F
SIH-24F
SLK-24F
SLK-24FH
SIF-24F
SLK-24F
SLK-24FH
SIF-24F
SLK-24F
SLK-24FH
SIF-24F
SLK-24F
SLK-24FH
SIF-24F
SIF-24F
SIH-24F
SIH-24F
SLK-24F
SLK-24FH
SLK-24FH
SIF-24F
SIH-24F
SLK-24F
SLK-24FH
SIF-24F
SIH-24F
SLK-24F
SLK-24FH
SIF-24F
SLK-24F
SLK-24FH
SIF-24F
SIH-24F
SLK-24F
SLK-24FH
SIF-24F
SLK-24F
DETECTOR
ID
HD-2
HD-3
HD-3
HD-3
HD-3
HD-2
HD-3
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-3
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-3
HD-3
HD-3
HD-2
HD-3
BASE MODEL
BASE ID
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-22D
HS-200 D
HS-200 D
HS-22D
HS-200 D
HS-200 D
HS-22D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-22D
HS-22D
HS-22D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-200 D
HS-22D
HS-22D
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HB-3
HD-20
HD-20
HB-3
HD-20
HD-20
HB-3
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HB-3
HB-3
HB-3
HD-20
HD-20
HD-20
HD-20
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HD-20
HB-3
HB-3
Page 1 of 2
22-Oct-2002
MX8/WIBH
S2W
S2W
S2W
S2WA
S2WA
S2WA
FASA
FASA
FASA
FASA
FASA
FASA
FASA
FASA
FASA
FASA
ZONE
ID
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
MDL NO
FASA
FASA
MDL NO
MDL NO
FASA
FASA
MDL NO
FASA
FASA
MDL NO
LOOP
STYLE
B
B
B
B
D
D
D
B
D
BD
BD
D
B
B
B
D
BD
MAX
DET
40
50
40
40
50
40
40
50
50
50
39
40
40
44
40
40
44
EOL
DETECTOR MODEL
4.7K OHM
4.7K OHM
4.7K OHM
4.7K OHM
N/A
N/A
N/A
4.7K OHM
N/A
4.7K
4.7K
N/A
4.7K OHM
4.7K
4.7K OHM
N/A
4.7K
SLK-24FH
SIF-24F
SLK-24F
SLK-24FH
SIF-24F
SLK-24F
SLK-24FH
SIF-24F
SIF-24F
SIF-24F
SIF-24F
SLK-24F
SLK-24F
SLK-24F
SLK-24FH
SLK-24FH
SLK-24FH
DETECTOR
ID
HD-3
HD-2
HD-3
HD-3
HD-2
HD-3
HD-3
HD-2
HD-2
HD-2
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
HD-3
BASE MODEL
BASE ID
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HS-22D
HB-22D
HB-22D
HS-200 D
HS-200 D
HB-22D
HB-22D
HS-200 D
HB-22D
HB-22D
HS-200 D
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HB-3
HD-20
HD-20
HB-3
HB-3
HD-20
HB-3
HB-3
HD-20
Page 2 of 2
22-Oct-2002
UPTIME
LOOP
STYLE
B
B
B
MAX
DET
30
24
24
EOL
HB-2
HB-2
HB-2
22-Oct-2002
VIKING
LOOP
STYLE
BD
BD
BD
BD
BD
BD
MAX
DET
30
30
30
30
30
30
EOL
71252
71252
71252
71252
71252
71252
BASE MODEL
BASE ID
HSB-220
HSB-224
HSB-220
HSB-224
HSB-220
HSB-224
HB-56
HB-54
HB-56
HB-54
HB-56
HB-54
22-Oct-2002
WORMALD
LOOP
STYLE
B
B
D
B
B
D
B
B
D
B
B
D
B
B
B
D
B
D
B
B
MAX
DET
75
75
45
75
75
45
75
75
40
75
75
40
75
75
75
40
75
45
75
75
EOL
68710
68710
N/A
70061
70061
N/A
70061
70061
N/A
70061
70061
N/A
70061
70061
70061
N/A
70061
N/A
70061
70061
HB-2
HB-7
HB-2
HB-2
HB-7
HB-2
HB-7
HD-2
HB-2
HB-7
HB-2
HB-2
HB-7
HB-2
HB-2
HB-2
HB-7
HB-2
HB-7
HB-2
LISTING SERVICE
LISTING No.
3240-0410:0155
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Bob Misiuk (714) 670-3248 Fax (714) 522-2268
Email: bmisiuk@hochiki.com
DESIGN:
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as duct smoke detector units for use with separately listed compatible fire alarm
control units to detect an abnormal amount of smoke density in the return air ducts of air
conditioning and ventilating system. The air velocity in the duct shall be between 300-4000
fpm.
NOTE:
For duct application only. Not suitable for open area protection.
*Rev 3-24-2009 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
3242-0410:0179
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model ALK-D duct smoke detector, analog, addressable photoelectric type sensor. Refer to
listee's data sheet for additional detailed product description and operational
considerations.
INSTALLATION:
The unit is intended to be installed to and mounted in air ducts with airflows up to 4000
ft/min. In accordance with listee's printed installation instructions and applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as photoelectric type, duct smoke detectors for use with separately listed compatible
fire alarm control unit, Hochiki Model FireNet 4127 (CSFM Listing No. 7165-0410:159). The
unit is for use with listed compatible bases, Hochiki Model YBN-NSA-4 or HSB-NSA-6
(CSFM Listing No. 7300-0410:132). Suitable for use in ducts with airflows up to 4000
ft/min. Refer to listees Installation Instruction Manual for details.
12-16-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
6911-0410:0175
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models FNV-MP and FNV-DP audio adjunct/voice evacuation systems. The FNV-MP is the
master panel in the system while the FNV-DP is the distributed panel. Each system is
modular in construction. Refer to listee's data sheet for additional detailed product
description and operational considerations. System components:
FNV-PWR2A
FNV-MFP
FNV-DCC
FNV-ASC
FNV-SSC
FNV-MMC
FNV-IOI
FNV-SLC
FNV-MFH
FNV-MBR
FNV-AMI
FNV-FPI
Page 1 of 1
Power Supply
Master Fire Phone Card
Data Communication Control Card
Audio System Control Card
Switch Scan Card
Microphone Master Control Card
Input/Output Card
Switch and LED Card
Master Fire Phone Handset Card
Motherboard Card
Audio Module Interface Card
Motherboard/Relay Card
RATING:
120 VAC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
XLF:
6911-1446:0103
8-28-2008 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
6911-0410:0176
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models EVAX 25, -25E, -50, -50E, -100, -100E, -150, -150E, -200, -200E audio adjunct
system. These units are intended to be used in conjunction with a listed electrically
compatible fire alarm control unit to provide voice communication, paging, evacuation tone
signals, and voice alarm signals with voice override. Refer to listee's data sheet for detailed
product description and operational considerations.
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, wiring diagram, applicable codes
and ordinances and in a manner which is acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
XLF:
6911-1446:0100
8-28-2008 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
6912-0410:0177
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model EVX-4Z and EVX-2ZA zone splitters. The unit is intended to be used in conjunction
with a listee's separtely listed Model EVAX-25 audio adjunct system (CSFM Listing No.
6911-0410:176). Refer to listee's data sheet for detailed product description and
operational considerations.
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, wiring diagram, applicable codes
and ordinances and in a manner which is acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
XLF:
6912-1446:0101
8-28-2008 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7120-0410:0153
Page 1 of 1
CATEGORY:
7120 -- ANNUNCIATORS
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model HRAM-208 remote multiplex annunciator and HRTI-1 Remote trouble Indicator.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
20-19 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. For indoor use only.
MARKING:
APPROVAL:
Listed as annunciator panel for use with listee's separately listed compatible Model
HCP-200 Series fire alarm control unit (CSFM Listing No. 7165-0410:152).
XLF:
7120-1477:0108
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7120-0410:0157
Page 1 of 1
CATEGORY:
7120 -- ANNUNCIATORS
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model HRA-1000 remote multiplex annunciator panel. The main annunciator module
provides indication for 32 zones. Each adder annunciator module provides indication for 48
additional zones. Unit includes main annunciator chassis HRAM-1032 and adder
annunciator chassis HRAX-1048. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
20-29 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. For indoor use only.
MARKING:
APPROVAL:
Listed as annunciator panel for use with listee's separately listed compatible Model
HPC-1000 fire alarm control unit (CSFM Listing No. 7165-0410:154).
XLF:
7120-1477:0107
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7120-0410:0165
Page 1 of 1
CATEGORY:
7120 -- ANNUNCIATORS
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model *FN-LCD-N Network LCD Annunciator and **Model FN-LCD-S Serial LCD
Annunciator. Connects to the control panel via the RS-485 network interface. Employs four
Form C relays that are unsupervised. **Up to 16 FN-LCD-S Serial LCD Annunciators can
be connected to one control panel. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING:
24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as annunciator panel for use with listee's separately listed compatible Model FireNet
4127 fire alarm control unit (CSFM Listing No. 7165-0410:159). Refer to listees Installation
Instruction Manual for details.
NOTE:
*Recert 4-12-2007 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7120-0410:0181
Page 1 of 1
CATEGORY:
7120 -- ANNUNCIATORS
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model FNP-LED Graphix LED eMatrix Mimic Display, where X can be the number 1 or 2
denotes color of the enclosure, and -YYY denotes the number of LED extension boards
which could be 1, 3 or 5 boards.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as annunciators for use with listees separately listed compatible fire alarm control
units. Refer to manufacturers Installation Manual for details.
03-01-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7150-0410:0162
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
INSTALLATION:
In accordance with listee's printed installation instructions and applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm manual pull stations for use with separately listed compatible fire alarm
control units. Model HPS-SAH-WP is suitable for outdoor use. Refer to listees Installation
Instruction Manual for details.
* These manual pull boxes do not meet the requirements of UL Standard 38, 1999 Edition
and California amendments.
7150-1039:0101
XLF:
*Updated 6-22-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7150-0410:0164
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models HPS-CP and HPS/CP/S non-coded boxes. Refer to listee's data sheet for detailed
product description and operational considerations.
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control
units. Refer to listees Installation Instruction Manual for details.
* These manual pull boxes do not meet the requirements of UL Standard 38, 1999 Edition
and California amendments.
7150-0512:0006
XLF:
*Updated 6-22-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7150-0410:0169
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
RATING:
33 Vdc
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm manual pull boxes for use with separately listed electrically and
functionally compatible fire alarm control units.
* These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and
California amendments except models with "LP" suffixes.
*Updated 07-07-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7151-0410:0163
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model HPS-SA-EX/WP with or without the suffix DA-C non-coded, explosion proof,
weather proof manual pull stations. These devices consist of a switch and terminal block
mounted within an explosion proof enclosure. Refer to listee's data sheet for additional
detailed product description and operational considerations.
RATING:
INSTALLATION:
MARKING:
APPROVAL:
Listed as fire alarm manual pull stations for use with separately listed compatible fire alarm
control units. Suitable for use outdoor and in Class I, Group B, C and D; Class II, Group E,
F and G hazardous locations. Refer to listees Installation Instruction Manual for details.
*These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with
California amendments except for models with suffixes -DAH.
7151-1039:0104
XLF:
*Updated 08-27-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7165-0410:0152
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model HCP-201, HCP-202, HCP-204 and HCP-204E fire alarm control units. Non-coded;
automatic, manual, local, remote station, central station, waterflow and sprinkler
supervisory service. System components:
HCP-201,-202,-204,-204E
HDM-204
HRM-204, HRM-208
HPR-100
HDACT-100
BB-815, BB-816
Page 1 of 1
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm control units for use with separately listed electrically and functionally
compatible initiating and indicating devices.
This control unit does not generate a temporal pattern signal. If the distinctive three-pulse
Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with
NFPA 72, 1999 Edition is required, the control unit must be used with appliances that can
generate the temporal pattern signal. Refer to listee's Installation instructions Manual for
details.
NOTE:
For Fire Alarm Verification Feature, the maximum Retard/Reset/Restart period shall not
exceed 30.0 seconds.
XLF:
7165-1477:0109
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7165-0410:0154
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
HCP-1000 fire alarm control unit. Non-coded, automatic, manual, local, auxiliary, remote
station, waterflow and sprinkler supervisory service. System components:
HCP-1000
HBB-1024, HBB-1072
HMCC-1024-6, -12
HMCC-1024-6S, -12S
HECH-1048
HDM-1008
HSGM-1004
HRM-1008
HPR-100
HFA-1024TR
Page 1 of 1
Control Unit
Backbox
24-Zone Chassis
24-Zone Chassis
Expander Chassis
8-Zone Detection Module
4-Zone NAC Module
Relay Adder Module
Polarity Reversal and City Tie
Flush Trim Ring
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm control units for use with separately listed electrically and functionally
compatible initiating and indicating devices.
This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. Refer
to listee's Installation Manual for details.
This control unit meets the requirement of UL-864, 8th Edition Standard.
NOTE:
For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
XLF:
7165-1477:0106
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7165-0410:0159
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model FireNet 4127 Analog Addressable fire alarm control unit. Automatic, manual,
waterflow and sprinkler supervisory service. Refer to the listee's data sheet for detailed
product description and operational considerations. System components:
MODULE
FN-4127-BO
FN-4127-IO
FN-4127-CPA-BO
FN-4127-SLC
FN-4127-NIC
FN-PS402
FN-DAC
FN-ENC
FN-ACC
FN-CTM
D9068
Page 1 of 2
PART NO.
(K6002)
(K6006)
(K6001)
(K6004)
(K6005)
(S402)
(FN-DAC)
(FN-ENC)
(FN-ACC)
(7000-00780)
(D9068)
HMX-DP
HMX-MP
EVX-100
EVX-RM
DESCRIPTION
Control Board
16 Channel Input/Output Board
Front LCD Indicator Panel
Loop 3, 4 Board
Network Card
Power Supply
Digital Alarm Communicator
Enclosures
Battery/Accessory Enclosure
City Tie Module
Bosch Digital Alarm Communication
Transmitter
Voice Evacuation System Distribution Panel
Voice Evacuation System Master Panel
Audio Adjunct Module
Remote Microphone
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm control unit for use with separately listed compatible initiating and
indicating devices. *Also suitable for high-rise applications.
These control units can generate the distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal as required per NFPA 72, 2002 Edition.
This control unit meets the requirements of UL-864, *9th Edition Standard
1. For Fire Alarm Verification Feature (Delay of fire alarm), the maximum
Retard/Reset/Restart period must be adjusted to 30 seconds or less.
NOTE:
*Rev 6-24-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7165-0410:0180
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models FIRENET PLUS 1127 Series. Analog Addressable Fire Alarm System. May be
followed by suffixes -R or -C which represents the color of the panel enclosure, -R for red,
-C for charcoal. Local, manual and automatic, sprinkler supervisory and waterflow
services. Refer to listee's data sheet for additional detailed product description and
operational considerations. System components:
FNP-1127-R; Loop Not Expandable, Red
FNP-1127-C; Loop Not Expandable, Charcoal
FNP-1127D-R; Loop W/Integrated Dialer, Not Expandable, Red
FNP-1127D-C; Loop W/Integrated Dialer, Not Expandable, Charcoal
FNP-1127E-R; Loop Expandable, Red
FNP-1127E-C; Loop Expandable, Charcoal
FNP-1127DE-R; Loop W/Integrated Dialer, Expandable, Red
FNP-1127DE-C; Loop W/Integrated Dialer, Expandable, Charcoal
FNP-1127-SLC; Loop Expansion Module*
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fire alarm control units for use with listed compatible indicating and initiating devices.
Also suitable for high rise applications.
These control units generate a distinctive temporal pattern (Temporal Pattern Fire Alarm
Evacuation) for total evacuation in accordance with NFPA 72, 2002 Edition. This control
unit meets the requirements of UL Standard 864, 9th Edition.
NOTE:
1. For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
XLF:
7165-1714:0115
*Rev. 04-26-10 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7260-0410:0158
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model SRA-24 projected beam smoke detector. Unit consists of a transmitter/receiver unit
and a reflector unit. This device is intended for ceiling installation only between 25 to 100 ft
apart. Refer to the listee's data sheet for detailed product description and operational
considerations.
RATING:
24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction
MARKING:
APPROVAL:
Listed as beam smoke detector for use with separately listed compatible fire alarm control
units. Refer to listees Installation Instructions Manual for details.
4-14-03 KK
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7260-0410:0172
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model SPC-24 Projected Beam, Smoke-Automatic Fire Detector. Unit consists of one
emitter unit and one receiver unit. Refer to listee's printed data sheet for additional product
description and operational consideration.
RATING:
24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as beam smoke detectors for use with separately listed compatible fire alarm control
units.
NOTE:
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7270-0410:0119
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models AL-DFE-135 and AL-DFE-190. Refer to listee's data sheet for detailed product
description and operational considerations.
INSTALLATION:
In accordance with the listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, temperature & electrical ratings and UL label.
APPROVAL:
Listed as system heat detectors when used in conjunction with listed compatible bases
(CSFM Listing No. 7300-0410:132) and separately listed compatible control units.
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7270-0410:0147
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model ATG-EA electronic fixed temperature heat detector (analog) with Models
YBN-NSA-4 and HSB-NSA-6 bases. Unit consists of resistors, capacitors, diodes,
transistors, LED, thermistors, mounted on a printed wiring board inside an enclosure. Refer
to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
Electrical:
39.5 VDC
Temperature Range:
134 F - 149 F
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as heat detector for use with separately listed compatible fire alarm control units.
*Corrected 11-6-2001
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7270-0410:0151
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models DCD-135 and DCD-190, fixed temperature and rate of rise heat detectors. Refer to
listee's data sheet for additional detailed product description and operational
considerations.
RATING:
Temperature:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as fixed temperature and rate of rise heat detector for use listed bases (CSFM
Listing No. 7300-0410:132) and separately listed fire alarm control units.
DCD-135: 135 F
DCD-190: 190 F
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7270-0410:0178
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models DSC-EA Rate-of-rise heat detector. Refer to listee's data sheet for detailed product
description and operational considerations.
RATING:
24 VDC
INSTALLATION:
MARKING:
APPROVAL:
Listed as heat detector when used in conjunction with listed compatible HSB-100 base
(CSFM Listing No. 7300-0410:132) and separately listed compatible control units.
codes
and
12-15-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7271-0410:0135
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models SIH-24F and *SIJ-24 ionization type smoke detector. Refer to listee's data sheet for
detailed product description and operational considerations.
RATING:
24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as ionization smoke detectors when used in conjunction with listed bases (CSFM
Listing No. 7300-0410:132) and separately listed compatible fire alarm control units.
NOTE:
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7271-0410:0148
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model AIE-EA analog addressable ionization type smoke detector with Models YBN-NSA-4
and HSB-NSA-6 bases. Unit consists of resistors, capacitors, diodes, transistors, LED,
diodes and ionization chamber, mounted on a printed wiring board inside an enclosure.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
39.5 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as ionization type smoke detector for use with separately listed compatible fire alarm
control units.
NOTE:
*Rev 11-16-2000
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7272-0410:0107
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm
control units when used in conjunction with listee's listed bases (CSFM Listing No.
7300-0410:132). Models with supplemental heat sensor are not approved for use in lieu of
required heat detectors.
NOTE:
Formerly 7257-0410:107
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7272-0410:0149
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models ALG-EA and ALG-V analog addressable photoelectric type smoke detector with
Models YBN-NSA-4 and HSB-NSA-6 bases. Unit consists of resistors, capacitors, diodes,
transistors, LED, photo diode, mounted on a printed wiring board inside an enclosure.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
39.5 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as photoelectric smoke detector for use with separately listed compatible fire alarm
control units. *Model ALG-V is suitable for in duct use in air velocities up to 4000 ft/min.
NOTE:
*Rev 1-31-2008 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7272-0410:0173
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models ALK-V and ALK-V2* analog addressable photoelectric type smoke detector with
listed compatible bases, Hochiki Model YBN-NSA-4 or HSB-NSA-6 (CSFM Listing No.
7300-0410:132). Unit consists of resistors, capacitors, diodes, transistors, LED, photo
diode, mounted on a printed wiring board inside an enclosure. Refer to listees data sheet
for additional detailed product description and operational considerations.
RATING:
39.5 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as photoelectric smoke detector for use with separately listed compatible fire alarm
control units. Also suitable for in-duct use in air velocities up to 4000 ft/min.
*Rev. 12-17-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7272-0410:0174
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
RATING:
24 Vdc
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as photoelectric smoke detectors for use with listed bases as shown in DESIGN
and compatible listed fire alarm control units.
3-19-2008
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7300-0410:0132
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Bob Misiuk (714) 670-3248 Fax (714) 522-2268
Email: bmisiuk@hochiki.com
DESIGN:
Detector bases (2 and 4-wire). Unit is intended for use with a separately listed compatible
detector head. Refer to listee's data sheet for detailed product description and operational
considerations. Models listed below.
HA-4W
HA-SL
HA-NRA2
HA-L2
HA-L22A
HA-LA2
HA-LNRA2
Page 1 of 2
HA-4W1
HA-SR
HA-L12R
HA-L2A
HA-L22F
HA-LRA
HA-4WX
HA-SLR
HA-2R
HA-L2R
HA-L22R
HA-LRA2
HS-2D
HS-22
HS-200D
HS-221
HS-221XL
HS-224D
HS-2RB
HS-224RB
HA-2
HA-RA2
HA-22R
HA-L22
HA-L22S
HA-LNA2
HS-2
HS-21L
HS-22D
HS-220L
HS-221D
HS-224
HS-225L
HS-220RB
HS-2L
HS-21D
HS-100
HS-220D
HS-221X
HS-224L
HS-225D
HS-221RB
HS-21
HS-22L
HS-220
HS-221L
HS-221XD
HS-225
HS-21RB
HS-2RB4
HSB-2
HSB-12-4
HSB-100
HSB-220N
HSB-224
HSC-4R
HSC-221L
HSC-224R
HSB-2N
HSB-12-1
HSB-12-1N
HSB-12-4N HSB-21
HSB-21N
HSB-200
HSB-200N
HSB-220
HSB-221
HSB-221N
HSB-221S
HSB-224N
HSB-225
HSB-225N
HSC-21L
HSC-220L
HSC-220R
HSC-221R
HSC-224RA
HSC-224L
HSC-225L
HSB-DCP-6
HSB-NSA-6
YBA-M2
YBA-M21
YBA-M22
YBA-M220
YBA-M221 YBA-M224 YBA-M225 YBA-M100
YBA-MAP
YBA-R3
YBA-RL/4
YBA-RL/4-1
YBA-RL/4-2
YBA-RL/4-RA
YBC-RL/12 YBC-RL/12-1
YBC-RL/12-2
YBC-RL/12-4
YBC-RL/4-RA
YBC-RL/2NC
YBC-RL/2NBE YBJ-RL/2ND
YBN-R/2NA
YBN-NSA-4
*Corrected 11-6-2001
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as bases for use with listees separately listed compatible smoke and heat detectors.
Refer to heat or smoke detector listings for compatibility. Models HA-2R, HA-SLR, HA-LRA2
and HSC Series w/ suffix R are also suitable for releasing device service. Model YBA-R3 is
intended for use with thermostat detector only.
NOTE:
Formerly 7300-0410:100, 106, 115, 124, 125, 126, 130, 131 & 133
*Corrected 11-06-2001
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listees data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
LISTING SERVICE
Page 1 of 1
LISTING No.
7300-0410:0150
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as control unit accessories for use with separately listed compatible fire alarm
control units. Refer to listees Installation Instruction Manual for details.
*Rev. 08-23-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire
test results and/or other data but does not make an independent verification of
endorsement or recommendation of the item listed. This listing should not be
requirements or installation criteria.
Refer to listees data sheet, installation
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7300-0410:0160
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models SBC-2, -2R, -4/12, -4/24 detector sounder base. The use of suffix W indicates the
color white. Unit SBC-2R employs a relay. SBC-4 models employ extra output leads for
connection to a control panel intitiating loop. Refer to listee's data sheet for additional
detailed product description and operational considerations.
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as detector base for use with separately listed functionally and electrically
compatible fire alarm control units. Designed specifically for use with listees Models SIJ-24
(CSFM Listing No. 7271-0410:135) Ionization Smoke Detector or Models SLR-24V,
SLR-835 (CSFM Listing No. 7272-0410:107) Photoelectric Smoke Detector. Refer to
listees Installation Instruction Manual for details.
NOTE:
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
10-27-2003
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7300-0410:0161
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Model ASB detector sounder base. Unit has an intregral audible signal for use with
spot-type detector units. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as a detector base for use with separately listed functionally and electrically
compatible fire alarm control units. Designed specifically for use with listees Model ALG-V
(CSFM Listing No. 7272-0410:149) Photoelectric Smoke Detector; Model AIE-EA (CSFM
Listing No. 7271-0410:148) Ionization Smoke Detector; or Model ATG-EA (CSFM Listing
No. 7270-0410:147) Heat Detector. Refer to listees Installation Instruction Manual for
details.
NOTE:
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
8-24-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7315-0410:0166
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction
MARKING:
APPROVAL:
Listed as power supply units for use with separately listed compatible fire alarm control
units. Refer to listees Installation Instruction Manual for details.
NOTE:
The system must have the secondary power supply capable of operating the system for at
least 24 hours battery standby) in the normal condition and followed by not less than 5
minutes of alarm as required by code. The battery circuit must be fully supervised.
XLF:
7315-1335:0109
5-3-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7315-0410:0167
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models FN-1024ULX, FN-300ULX and FN-400ULX power supply units may be followed by
-G, -R, -C, or -B. Models FN-300ULX series are designed to charge sealed lead acid type
rechargeable batteries. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. For fire alarm use, the
standby batteries must provide 24 hours standby power during power loss.
MARKING:
APPROVAL:
Listed as power supply units for use with separately listed compatible fire alarm control
units to provide power for door holders, door strikes or similar devices. Refer to listees
Installation Instruction Manual for details.
NOTE:
XLF:
7315-1335:0100
5-3-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7315-0410:0168
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
Models FN-600ULX-G, -R, -C, -B Power Supply Units. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING:
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction
MARKING:
APPROVAL:
Listed as power supply units for use with separately listed compatible fire alarm control
units. Also suitable for use with access control systems. Authority having jurisdiction should
be consulted prior to installation.
NOTE:
For fire alarm use, the standby batteries must provide at least 24 hours standby power
during power loss. The battery circuit must be fully supervised.
XLF:
7315-1335:0104
5-3-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires
LISTING SERVICE
LISTING No.
7315-0410:0171
Page 1 of 1
CATEGORY:
LISTEE:
Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Michael Um (714) 670-3246 Fax (714) 522-2268
Email: mum@hochiki.com
DESIGN:
RATING:
FN-642-UL2ADA-R and -C, FN-842-UL2ADA-R and -C: 120 VAC input, 12/24 VDC output,
2A (on each indicating circuit)
FN-1042-UL2ADA-R and -C:115 VAC input, 24 VDC output, 2.5A (on each indicating
circuit)
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
APPROVAL:
Listed as a power-limited indicating circuit power supply for use with separately listed
compatible fire alarm control units and indicating devices. Authority having jurisdiction
should be consulted prior to installation.
XLF:
7315-1335:0112
8-27-2007 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria.
Refer to listees data sheet, installation instructions and/or other suitable
information sources.
Date Issued:
Authorized By:
Listing Expires