TECHNIQUES FOR DETECTION AND LOCATION OF PARTIAL DISCHARGES IN POWER
TRANSFORMERS
S. M. Markalous* and A. Wilson**
*LDIC GmbH, Germany, **Doble PowerTest, UK
SUMMARY
On site partial discharge (PD) measurements using UHF and acoustic emission probes are now viable. They can be used for the measurement of PD levels, long term monitoring with remote access through substation communications or the web, and for location of the discharging source. This approach is important for the lifetime management of ageing transformers. For this situation the key tasks are to identify the onset of PD and monitor the levels for any sudden and worsening change that would require an urgent replacement outage. The techniques are described, together with case studies of their application in the field.
INTRODUCTION
At the previous INSUCON conference the failure experience of UK transformers was described [1]. Lightly loaded well designed transformers in a transmission system with N-1 security may well be capable of lifetimes approaching 100 years. But a significant proportion of the power transformer base in the developed world has reached the stage where weaker designs and those with onerous operating conditions are now showing the onset of unreliability and shortened lifetimes. The concern for the network or power station owner is to have reliable estimates of the risk of failure of any of their transformer fleet, and this is more complicated than if a simple age or time at elevated temperatures criterion applied. Managing that risk is the key task for those responsible for the assets. The first step in the decision process will be a condition based assessment. Further steps will include evaluating the consequences of an in-service failure and managing a now identified higher risk on a specific unit. It may be some time - months or years until either the planning cycle for the unit, or circuit containing the unit, allows an opportunity for replacement with minimal business interruption. Within this period critical worsening may occur and the risk of ongoing operation becomes unacceptably high. Therein lies the key tasks- - how to identify a unit with a higher likelihood of failure - how to monitor condition with an increased precision to identify a worsening trend requiring a more immediate outage for replacement.
MANAGING THE RISK OF FAILURE IN AGED TRANSFORMERS
The approach adopted in UK by Doble PowerTest relies heavily upon the evidence gained during the 100-150 tear downs undertaken over the last 10 years [2], [3]. Most of these units have failed beyond economical repair. Investigation is intended not only to identify the root cause, but also to research all key design areas for ageing or damage that is higher than normal for age. In this way a detailed understanding of design groups from the various manufacturers has been built up. This allows the first step in a failure mode and criticality approach to identify the most appropriate diagnostics for a particular design group. As with many items of power equipment, the critical modes fall into the initiation categories of thermal, electrical, ambient and mechanical stress. Consequently, these stresses indicate the type of diagnostics most appropriate. In this paper the focus is upon electrical stress and the production of partial discharges (PD). But these do not only occur within the context of dielectric damage from electric stresses. PD can also occur within the final stages of failure from both overheating involving insulated conductor, and after mechanical deformation. PD techniques for detection and location are important diagnostics, therefore, not only to identify the onset of damage caused by electric stress, but also to monitor a changed and worsening condition initiated by the broader range of stress factors.
PARTIAL DISCHARGE TECHNIQUES
There are four main PD techniques that are available. 1. Oil sampling to detect dissolved gases. 2. Surveys using UHF interference detection 3. Electrical measurement of individual discharges using sensors on the bushing tap, neutral or inserted into the tank. 4. The use of probes to locate the PD site
Oil sampling to detect dissolved gases
Of these the first two in the above list have the longest history. Engineers in the 1920s were testing Buchholz gases for flammability. But it has been the availability of gas chromatography over the last 50-60 years that
2 has advanced the application. Routine analysis of dissolved gases in the oil has now become the diagnostic of choice throughout the world. Oil samples have been taken once or twice a year from the main tank and tap changer selectors for off-site laboratory analysis. More recently cost effective on-line detectors have become available and this is likely to lead to changes in the technology. From such analyses it is possible to detect damage caused by both overheating and PD. Gas from PD source can be separated from thermally driven processes using the key gas method in C57-104, 1991.
However, a rapidly increasing rate of PD will be better indicated from a direct measurement of PD rather than from the integrating process of evolution of gas. Over- reliance upon analysis methods to examine gases from already faulted transformers and gas levels incorporated in CIGRE and IEEE advice documents (such as CIGRE J WG 15/12 01-11 and C57-104) has masked the early detection of developing faults [4]. For that reason the Doble UK group, DPT, rely upon an algorithm developed some 5 years ago. It is based upon the IEEE key gas method of C57- 104 and trained on UK faults [5]. An elevated result from this is the trigger for further investigation, including interrogating the oil test data file for trends in particular gases, or transient excursions. This may then lead to condition assessment using off- line electrical testing.
Surveys using UHF interference detection
Another traditional technique is one based on measuring the interference levels caused by PD. Originally this was intended to verify freedom from PD sources that would interfere with analogue radio reception. Sensors such as rod aerials or high frequency split core current transformers were used, either placed near to the equipment or fitted around earth or bonding leads. Following two catastrophic transformer failures twenty five years ago, both initiated by PD within bushings, research in CEGB led to what is now a routine survey patrol of substations but now using UHF interference scanning [6]. Corona from fittings and discharge along the polluted insulator surfaces will emit electromagnetic radiation only up to 250 MHz. However, PD from defects will extend to much higher frequencies, and in some cases up to 1 GHz. Defects detected include- Loose frame clamps core bolts and internal connections such as- stress shields, and rocket assembles Selector problems Broken barrier board for LTC connections Winding discharges External floating components- even nameplates Faulty (gap type) surge arresters Faulty bushing taps The important advantage of this method is that it can be included in the routine patrols and will survey all substation equipment. It will indicate bushing problems and this is one area where dissolved gas analysis is limited by the difficulties in extracting a gas sample. An example is shown in Figure 1.
Figure 1 UHF scanning during a routine patrol.
Partial discharge detection
The method used for PD testing in factory acceptance testing is described in IEC 60076-3, which is based on the generic standard for PD testing, IEC 60270. This describes the means to measure apparent discharge magnitude. This approach was developed in the 1950s as an aid to materials research and was soon adopted for testing the dielectric integrity in most items of power equipment. However, even with the most simple of dielectric systems, the measurement only reflects the magnitude of the charge relating to the voltage drop and current flow within the sample consequent to a discharge. Whilst this is related to events within the defect and the real amount of charge flowing in the discharge, the relationship between these and the apparent magnitude remains hidden as long as the relative proportions of void and series dielectric remain hidden. The real discharge magnitude is always the larger and a source of error even at the simplest of systems.
For a power transformer the measurement is made using the bushing tap as a capacitance divider, and measuring PD transients travelling to that point using a detector in the 50-400 kHz range. But IEC 60270 also identifies another problem- within windings a single PD event will propagate in a variety of modes, each with their own propagation speed, attenuation factors and frequency content. Winding geometry produces a range of resonances for any electromagnetic signal and it was the recognition of the influence on propagation on measurement errors led to the demise of fixed frequency narrow band detectors in international
3 standards. Thus whilst factory acceptance testing continues to apply IEC 60270 approaches to measure apparent charge, the reality is that this method contains inherent flaws and more useful information may be gained from alternative methods.
Alternative methods also become more relevant when attempting to measure PD transients in the presence of high levels of interference. These may come from communications and broadcast transmissions, corona and surface discharge elsewhere on site. Solutions lie in detection considerably in excess of those used in factory testing and IEC 60076-3.
It is possible to detect propagated signals from the bushing taps, but this is controlled by the levels of attenuation in the winding, resonances in the winding and is affected by external corona and discharge sites. For example the authors have used this approach but found sensitivity of detection has increased from 100 pC to 1000 pC with rain present. Clearly this is not acceptable for an alarm based surveillance diagnostic wanting to achieve sensitivity.
An alternative is to use a UHF probe inserted in an oil valve or access port allowing the transformer tank to screen interference. This will detect the electromagnetic radiation from the PD and not be affected by winding resonances- and so achieving a more uniform performance over a population of transformers having a wide range of designs. The use of UHF probes to detect PD in GIS is well established: it has been used in GIS in the UK since 1985. The basic research underlying the UK installations was undertaken at Strathclyde University. It has been shown that frequency content extends to 1 GHz [7]. Their continuing research and that at Stuttgart University [8] has also shown a variety of typical PD sources involving oil and paper in an oil tank have significant components up to 1 GHz.
Figure 2 Oil valve sensors for power transformers/ reactors for usage on DN 50 / DN 80 gate valve
The UHF method offers a technique that can be used on site, installed even when the transformer remains energized, and can derive results in a high interference environment. Figure 2 shows a typical probe inserted through an oil valve. It is the intention that orders for future transformers should include provision for a number of appropriate valves for sensors see CIGRE A2-27 reports. Signal levels can be monitored and processed using modern signal processing techniques, enhancing signal to noise and providing phase resolved patterns. The latter should provide an effective means of identifying the type of problem causing discharge. Bubbles, floating metal, and voids each have their own characteristic.
The topic of calibration is relevant to this application. Within IEC 60270 and also used in factory testing measurements are made at bushing taps and calibrated against a known charge input across the winding. The UHF method cannot be calibrated in this way. CIGRE contributions [9] and the draft standard IEC 62478 refer to steps such as a sensitivity and/or performance check.
Figure 3 Performance check of UHF probe with an UHF injector
As shown in Figure 3, here the purpose is to confirm the detection sensitivity of the probe itself to a UHF pulse. It is a functional check of the whole measuring path including sensors and partial discharge (PD) acquisition system (Note: this is also of interest for finding optimum frequency bands for the location). Detector devices can be connected to an onsite server, and from there to an external control using LAN/ WAN or internet. It is usual to have trained the software to recognise normal levels and set an alarm level based on pulse magnitudes and repetition rates.
Partial discharge location
If an active PD source is identified- from PD monitoring or from oil testing the next step is to attempt to locate the site. This should allow assessment of the severity or consequence of the discharging. In some cases it may indicate the opportunity for a simple repair. One involves the use of an array of acoustic emission (AE) probes to localise the site. It is based on arrival times of surface waves generated in the tank walls. One method used in UK is to use an array and move the locations to minimise the arrival times. An alternative is to place an array at a fixed position and calculate the location from arrival times and the
4 velocity of the longitudinal waves in the tank walls. Later case studies show results from both types of technique. The future is, however, to use an array of UHF probes to calculate the site. AE probes work well when the site is external to the winding and core, but not so for sites is internal to these areas. Attenuation and reflection will limit success. The UHF probes will not have this limitation.
EXPERIENCE WITH UHF PROBES AND ACOUSTIC LOCATION
Over recent years UHF probes have been used to measure PD in transformers in various networks. Case studies show how this has allowed an instantaneous indication of PD activity, allowing relationships with operating conditions to be identified more readily than with integrated methods such as gas analyses.
Case Study 1- Interference issues Figure 4 shows broad-band frequency views of amplified on-site UHF-noise. At this site a communications tower was very close to the 110 kV transformer. The narrow-band UHF spectrum all are modulated carriers are visible despite the screening to the UHF sensor by the transformer tank. Measuring below 1 GHz and signal processing it is necessary to eliminate these signals. Since these signals are not affected by winding resonances it is possible to select narrow band detection to eliminate this type of interference. Figure 4 amplified UHF noise on UHF probe in a 110 kV transformer
Case Study 2- Comparative measurements Four 3-phase 110/225kV transformers with similiar design and operating use but in different locations were evaluated for PD. Two units had two drain valves accessible and this allowed an extra comparison, the effect of valve location. Figure 5 and 6 show the results. In this study three transformers found with minor PD activity, one transformer with clear and significant PD, Figure 5, and in Figure 6 the effect of probe location.
a) b)
Figure 5 UHF phase-resolved PD pattern from Right drain valves a) One unit with significant PD b) One example from 3 other units
Figure 6 Corresponding UHF pattern from left valves
Case Study 3- Mobile AE sensors to locate PD sites One approach to location is to use an array of AE sensors and determine the arrival times. Three sensors are then re-located to nearer the one with the earliest arrival. This is repeated until a cluster is reached. Figure 7 shows an end result of such a scan with the cluster corresponding to the position of the top of the winding. The history of this 30 year old 275/33 kV 100 MVA transformer was that a close up lightning
5 strike had destroyed a transformer. When the equipment at the remote end of this 6 km line was examined it was found that Buchholz gases existed in one transformer. Power actor measurements confirmed damage but to a different phase to the one receiving the strike. PD location confirmed that it was a second phase that was damaged. The oil was dropped and damage was on one the top of one phase at an inter- connector between two parts of a split HV winding- as Figure 8.
Figure 7 Location using 4 AE probes.
Figure 8 Damage to interconnector
Case study 4 -PD location using fixed AE probes Over a period of several months on- and off-line all- acoustic PD measurements were performed on-site on a 200 MVA single-phase transformer where gas-in-oil diagnosis indicated PD. During an off-line applied voltage test an electrical PD measurement revealed PD with apparent charges up to 600 pC. With an acoustic PD measurement (referred to as 'measurement 1') acoustic pulses were recorded on four sensors and the time of arrival determined. Location was computed from the results at each sensor and based on time of arrival at each sensor, and the transit velocity for AE waves in the tank material. Fig. 9 pictures the top view of the housing of the transformer with the sensor positions and the calculated PD location.
Figure 9 Determining the location of PD source
In Table 1 the location results are summarized. Through the fact that in 'measurement 2' and 'measurement 3' the estimated PD site of independent measurements remained almost the same (spatial deviation of 5.4 cm) a certain reliability of the results was achieved. As well the spatial deviation between the results of the off-line 'measurement 1' and the on- line 'measurements 2/3' using different sensor positions, different number of sensors and also different average sound velocities (based on the different oil temperatures) is in a rather reasonable range. The spatial deviation between 'measurement 1' and 'measurement 2' is 17.0 cm, while it is 18.2 cm between 'measurement 1' and 'measurement 3'.
TABLE 1. Location from AE PD measurements over several months and changes in sensor position- ag in Figure 9
CONCLUSIONS
In recent years a significant progress in so-called non- conventional PD measuring techniques has been made (e.g. standard IEC 62478 in draft stage will apply for UHF and acoustic PD measurements). This was motivated clearly by the need for innovative applications on-site and on-line applications in both measurement and monitoring of different types of high voltage devices.
Compared to the apparent charge method for measurement one great advantage of using the UHF frequency range for the measuring PD signals is the consequential increased immunity against external electromagnetic disturbances.
The combination of appropriate and adapted sensors and modern instruments with innovative signal processing features results into an overall technology which is suitable to measure and asses the condition
Calculated PD-origin x [m] y [m] z [m] measurement 1 (off-line a, b, c, d) 1.40 3.12 2.27 measurement 2 (on-line c, d, e, f, g) 1.25 3.19 2.23 measurement 3 (on-line a, c, d, e, f, g) 1.27 3.22 2.19
6 changes of insulation systems even under the noisiest field-conditions.
Acknowledgements For the fruitful cooperation in the UHF testing applied on transformers the authors are grateful to Prof. Dr.- Ing. S. Tenbohlen, Dipl.-Ing. S. Coenen, University of Stuttgart, Germany, Institute of Power Transmission and High Voltage Technology (IEH).
References [1] A. Wilson, R. J . Heywood and Z. Richardson, The lifetime of power transformers Insucon Conf, Birmingham, UK, 2006. [2] R.J . Heywood, Forensic investigations during tear-downs. Proc. 2007 International Conf. of Doble Clients, Boston, USA. [3] J .A. Lapworth and A.Wilson, The Asset Health Review for Managing Reliability Risks Associated with Ongoing Use of Ageing System Power Transformers. Proc. CMD conference, Beijing 2008. [4] J.A. Lapworth, R.J. Heywood and P.N. Jarman Difficult transformer problems solved by effective testing. Proc. 2008 International Conf. of Doble Clients, Boston, USA. [5] J .A Lapworth, A scoring system for integrating dissolved gas analysis results into a life management process for power transformers Proc. 2002 International Conf. of Doble Clients, Boston, USA. [6] A Wilson and L. D Hall, Partial discharge methods for site testing HV equipment, Proc. 1996 International Conf. of Doble Clients, Boston, USA. [7] M.D. J udd, O. Farrish and B.F. Hampton. Broadband couplers for UHF detection of PD in gas insulated substations. IEE Proc. Sci Meas. Technology, 142, (3), May 1995 pp 237-243. [8] S.M. Markalous, Detection and Location of Partial Discharges in Power Transformers using acoustic and electromagnetic signal, PHD Thesis, University of Stuttgart, 2006 [9] CIGRE TF 15/33.03.05, PD Detection System for GIS: Sensitivity Verification for the UHF Method and the Acoustic Method, Electra No.183, April 1999.