Considered Aera
Procurement Office
Reception Lounge
Waiting Lounge
CSR Office
CSR Office
Xerox Room
Paper Storage
First Aid Room
Documentation Library
Reading Room
IT/UPS Room
Telephone Exchange
Corridor
Lobby
Entry Foyer

Area

% Area

CFM Cap

153.2509 17.54627

18

2123.10

39.0399 4.469825

540.85

38.1568 4.368715

528.61

70.4859 8.070195

976.49

40.85362 4.677484

565.98

23.07129 2.641519

319.62

20.0974 2.301027

278.42

22.52534 2.579011

312.06

78.6549 9.005495

10

1089.66

36.8919 4.223892

511.09

36.8919 4.223892

511.09

76.29635 8.735455

1056.99

119.88 13.72551

14

1660.79

41.0139 4.695835

568.20

76.3 8.735873
873.4101
100

9
100

From AC calculation Total Dehumidified air quantity


20436
340.61 m3/min
12028 CFM
Say
12100 CFM
.
Designig Duct by Equal Friction Method

Total Air
Initial Velocity

12100 CFM
7 m/s

(Considered)

1378 fpm
0.15 in. wg.
1.25

Operating pressure (Considered)


Radius elbow
(Considered)R/D

Initial

Duct Area
From table 6 selected duct size

0.004

8.780842 Sq ft
38 in
x
36 in

Circular equivalent dia


From chart 7 Friction loss
Duct Areas calculated using table 13 and duct sizes table 6.

40.4 in
0.035 in WG per 100 ft of equivalent length

1057.04
12100.00

Duct Section

SUPPLY
Duct
Actual
Size
Area
in
Sq ft

Air Quantity CFM


Duct Area
Capacity Area
CFM
%
%
Sq ft

Main Duct
To Procurement area
To Procurement area
After Procurement area
Main duct to reception
Duct to reception & waiting lodge
TO waiting lodge
Main Duct Library
To library
To entry Foyer
Main duct to lobby
To Lobby and Fyoyer
To UPS Reading Room
To Reading Room
Main duct to CSR Office
To CSR Office
To Tel Exchange
Main Duct to Xerox Room
To First aid room
To xerox room

12100
2123.10
1061.55
275.15936
9700.1034
1069.4633
540.84879
8353.8423
1089.6649
528.52034
6458.8593
1096.7164
1022.1819
511.09
4063.1632
1542.4692
1056.9901
1186.9061
312.0603
598.04799

Add equivalent length calculation

100 100 8.780842 36x38


18 25 2.19521 22x16
9 15 1.273222 14x14
2 3.5 0.307329 6x10
80 85 7.419811 36x32
9 15 1.273222 14x14
4
7 0.614659 10x10
69 76 6.629536 32x32
9 15 1.273222 14x14
4
7 0.614659 10x10
53 61 5.356313 24x36
9 15 1.273222 14x14
8 13 1.141509 12x16
4
7 0.614659 10x10
34 42 3.687954 24x24
13 20 1.712264 14x20
9 15 1.273222 14x14
10 17 1.448839 14x16
3 5.5 0.482946 6x12
5
9 0.790276 8x16

8.89
2.27
1.28
0.39
7.46
1.28
0.65
6.68
1.28
0.65
5.58
1.28
1.24
0.65
3.74
1.81
1.28
1.45
0.45
0.81

Area
Sq ft
11571
2123

12.29 46x40
3.07 18x26

11.9
3.01

275.2
9172
1069
540.8
7825
1090

0.43
10.39
1.78
0.86
9.28
1.78

6x12
46x34
20x14
12x10
44x32
28x10

0.45
10.1
1.81
0.77
9.07
1.71

6459
1097
1022
511.1
4063
1542
1057
1187
312.1
598

7.50
1.78
1.60
0.86
5.16
2.40
1.78
2.03
0.68
1.11

36x32
20x14
20x12

7.46
1.81
1.54

22x36
20x18
28x10
14x22
10x10
10x16

5.07
2.34
1.71
1.99
0.65
1.02

From table 20

Length
m

ft

Elbow

Contraction

Main Duct
16x16
Main duct to reception

6000

19685

7258

23812

Main Duct Library

7184

23570

Main duct to lobby

7300

23950

Main duct to CSR Office

7143

23435

To CSR Office

10000

32808

3
Total
Loss

Velocity in Last section

V2

900.84 ftm
4.5762 m/sec

75% Regain considered

Regain

Total static pressure at fan discharge

RETURN
Duct
Actual
Size
Area
in
Sq ft

0.051 in Wg
51.654 in Wg

5.6134 m Wg

0.561

0.0254 m Wg

25.4

Return

Duct Section

Air Quantity CFM


Duct Area
Capacity Area
CFM
%
%
Sq ft

Area
Sq ft

Duct
Size
in

Actual
Area
Sq ft

Xerox Room
First Aid Room
Telephone exchange
UPS
Reading Room
After Reading Room
After Library

873.21
1185.27
2242.26
786.25
1297.34
3539.60
4629.26

19 26
26 44
49 57
17 24
29 37
77 82
100 100

0.873446
1.478139
1.914862
0.806258
1.226184
2.754714
3.359408

1.222824
2.069395
2.680807
1.128761
1.716657
3.8566
4.703171

10x18
14x22
18x22
12x14
16x16
22x26
24x30

1.15
1.99
2.57
1.09
1.67
3.71
4.68

CSR Office
Lobby
Reception
Waitng Lodge
Procurement Office
After Procurement Office

1817.63
2660.98
3476.99
4005.61
6128.71
6403.86

29 37
42 59
55 63
63 70
96 97
100 100

1.696234
2.741858
2.927747
3.253052
4.484564
4.647217

2.374728
3.838601
4.098845
4.554272
6.27839
6.506104

14x26
18x32
22x28
22x30
32x30
36x28

2.31
3.68
4
4.27
6.22
6.52

11033.13

13000
7
1378 3.359408
1378 4.647217

CFM Cap for each room ( Tentatively considered as per area)

a.
b.
c.
d.
e.
f.
g.
h.
i.

Considered Aera
HR Office
Lobby
MIS Office
MIS Office
C & M.D.'s Room
P.A. to M.D.
Waiting Lounge
Xerox Room
Corridor
Entry Foyer
Total

Area

% Area

CFM

217.6179 29.53323

30

39.4338 5.351615

695.71

70.5 9.567652

10

1243.79

40.98405 5.562002

723.06

5.92353

770.06

26.6889 3.621987

470.86

12

1492.66

43.648
84.606

11.482

7.1126 0.965261

129.4766 17.57145

18

76.79 10.42128
736.8579

Admin Building Conf room


Admin building training room

3839.32

100

125.48
2284.29 571.0722

11

1354.77

100

13000.00

1800
1700

From AC calculation Total Dehumidified air quantity


22050 m3/hr
367.5 m3/min
12978.14 CFM
Say
13000 CFM

Designig Duct by Equal Friction Method

Total Air
Initial Velocity

Operating pressure
Radius elbow

Initial

13000 CFM
7 m/s

(Considered)

1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
From table 6 selected duct size
x
Circular equivalent dia
From chart 7 Friction loss

0.00381

mwg

0.000381 Kg/cm2g

9.433962 Sq ft
34 in
42 in
41.3 in
0.028 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
HR Office
HR Office
After HR Office
Main Duct to Waiting Lodge
Waiting Lounge
To entry Foyer
Main duct to lobby
To Lobby and Fyoyer
Main duct to MIS Office
MIS Office
Main Duct upto MD Room
PA & MD Room
C & M.D.'s Room

Air Quantity CFM


Capacity
CFM
%
13000
3839.32
1919.66
696.56
8464.12
1492.66
677.38299
5723.01
1373.093
4349.92
1966.86
1811.99
1240.92
770.06

Add equivalent length calculation

Duct
Area
%

100
30
15
6
66
12.00
6
45
11
34
16
14
10
6

From table 20

100
37.5
21.5
10.5
72.5
18.5
10.5
53
17.5
42
23
20.5
16.5
10.5

SUPPLY
Area
Duct
Size
Sq ft
in
9.433962
3.537736
2.028302
0.990566
6.839623
1.745283
0.990566
5
1.650943
3.962264
2.169811
1.933962
1.556604
0.990566

42x34
28x20
16x20
8x20
36x30
14x20
8x20
36x22
16x16
28x22
16x22
14x22
14x18
10x16

RETURN
Actual
Area

9.8
3.6
2.07
0.99
6.99
1.81
0.99
5.07
1.67
4
2.27
1.99
1.63
1.02

12322.62
3839.319

13.21 46x44
4.95 28x28

13.1
5.1

696.5561
7786.74
1492.66

1.39 22x10
9.58 38x38
2.44 20x18

1.38
9.43
2.34

5723.01
1373.093
4349.917
1966.855
1811.99
1240.917
770.0589

7.00
2.31
5.55
3.04
2.71
2.18

6.99
2.27
5.44
3.01
2.78
2.12

30x36
16X22
28X30
18X26
24X18
18x18

3029 50.48333
2875 47.91667

1783
1692

1800
1700

Conference Room
Total Air
Initial Velocity
(Considered)

1800
7

CFM
m/s

Operating pressure
Radius elbow

1378
0.15
1.25

fpm
in. wg.

R/D

Duct Area
From table 6 selected duct size
x
Circular equivalent dia
From chart 7 Friction loss

1.306
12
18

900

0.00381

Sq ft
in
in

16.0
0.11

50
58

0.7576197
8
16

SUPPLY
Actual
Area
1.4
0.81

in
in WG per 100 ft of equivalent length
RETURN
1.9593614 20x16

2.07

Training Room
Total Air
Initial Velocity
(Considered)

1700
7

CFM
m/s

Operating pressure
Radius elbow

1378
0.15
1.25

fpm
in. wg.

1.234
14
14

Sq ft
in
in

R/D

Duct Area
From table 6 selected duct size
x
Circular equivalent dia
From chart 7 Friction loss

15.3
0.12

0.00381
SUPPLY
Actual
Area
1.28

in
in WG per 100 ft of equivalent length
RETURN
1.850508 14x20
RETURN

Duct Section

Air Quantity CFM


Capacity
CFM
%

Duct
Area
%

Area

Duct
Size
in

Sq ft

Actual
Area

PA & MD Room
C & M.D.'s Room
Waiting Lodge
After Waiting Lodge

1041.93
1811.99
2063.73
3875.72

10
16
18
34

16.5
23
25
42

1.379
1.923
2.09
3.511

1.931105
2.691843
2.925916
4.915539

18x16
26x16
22x20
26x28

1.87
2.66
2.86
4.74

MIS Office
Lobby
HR Office
HR Office

2537.93
3233.64
7072.96
7644.03

23
29
62
67

30.5
36.5
69
73.5

2.55
3.051
5.768
6.144

3.569618
4.271838
8.075529
8.602194

18x30
22x30
34x36
44x30

3.46
4.27
7.95
8.51

11519.75

13000
7
1378

8.359761

1.81

DUCT SIZING FOR FIRE STATION


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.
b.
c.
d.
e

Area

Primary Health Centre


Radio Station
Control Room
Incharge Control Room
Electrical Room
Total

CFM

56.547 61.58087

62

8.892 9.683247

10

232.40

8.892 9.683247

10

232.40

11.396 12.40994

13

297.84

6.100 6.642701
91.826

From AC calculation Total Dehumidified air quantity


3916 m3/hr
65.26667 m3/min
2304.871 CFM
Say
2400 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

% Area

100

R/D

159.42

100

2400.00

800

2400 CFM
6.5 m/s
1280 fpm
0.15 in. wg.
1.25

Duct Area
From table 6 selected duct size

1477.94 738.9704

0.0038 mwg

0.000381 Kg/cm2g

1.875 Sq ft
26 in
12 in

Circular equivalent dia


From chart 7 Friction loss

19.0 in
0.1 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Electrical Room
Main Duct after Elect Room
Radio Station
Main Duct
Control Room
Main Duct to Incharge Control Room
To Incharge Control

Air Quantity CFM


Capacity
CFM
%
2400
159.42
2240.58
232.40
2008.18
232.40
1097.84
297.84

100
7
94
10
84
10.00
46.00
13.00

Duct
Area
%
100
11.5
95
16.5
87.5
16.5
54
19.5

SUPPLY
Duct
Size
Sq ft
in
Area

1.875
0.215625
1.78125
0.309375
1.640625
0.309375
1.0125
0.365625

26x12
10x6
24x12
10X6
22X12
10X6
10x16
10x6

Actual
Area

RETURN
Duct
Actual
Size
Area
in

Area
Sq ft

1.97
0.39
1.83
0.39
1.69
0.39
1.02
0.39

2.63 16x26

2.66

2.49
1.38
2.30
0.95
1.42
0.51

2.47
1.38
2.47
0.91
2.47
0.52

16x24
10x22
16x24
10x14
16x24
8x10

Add equivalent length calculation

Main Duct
16x16
Main duct to reception

From table 20
Length
m
ft
6000 19685.04

Elbow

Contraction
9

19694.04

7258 23812.34

23820.34

Main Duct Library

7184 23569.55

23576.55

Main duct to lobby

7300 23950.13

23956.13

Main duct to CSR Office

7143 23435.04

23441.04

32811.4

To CSR Office

Velocity in Last section

10000

V2

32808.4

Total

147299.5 ft

Loss

147.2995 in Wg

1084.28 ftm
5.508168 m/sec

75% Regain considered


Total static pressure at fan discharge

Regain

0.02169 in Wg
147.4278 in Wg
1

5.6134 m Wg

0.5613

0.0254 m Wg

25.4

DUCT SIZING CANTEEN BUILDING GROUND FLOOR


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.
b.
c.

Area

Officer's & Staff Dining


Handwash for staff
Sitting Lounge
Total

12.6684 5.066651

268.53

33.2906 13.31438

14

705.66

100

5300.00

250.035

Operating pressure
Radius elbow

100

4325.81 1441.935

5300 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

CFM
82

From AC calculation Total Dehumidified air quantity


8933 m3/hr
148.8833 m3/min
5257.766 CFM
Say
5300 CFM
Total Air
Initial Velocity
(Considered)

Initial

% Area

204.076 81.61897

0.00381 mwg

0.000381 Kg/cm2g

3.846154 Sq ft
20 in
x
30 in

Circular equivalent dia


From chart 7 Friction loss

26.6 in
0.063 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct after 1st reduction
Main Duct after 2nd reduction
Hand wash & Sitting Lodge
To hand wash area
To Sitting Lodge

Air Quantity CFM


Capacity
CFM
%
5300.00
5300.00
3858.06
2416.13
974.19
268.53
705.66

100
100
73
46
19.00
6.00
14.00

Duct
Area
%

Area
Sq ft

SUPPLY
Duct
Size
in

100 3.846154 22X30


79
54
26
10.5
20.5

3.038462
2.076923
1
0.403846
0.788462

22x22
18x18
12x14
10x6
8x16

Actual
Area

Area
Sq ft

3.89
3.89
3.17
2.12
1.09
0.39
0.81

RETURN
Duct
Actual
Size
Area
in

5.384615 32x26
4.253846 20X32
2.907692 20X22

5.37
4.12
2.86

1.4
1.103846 12X14

1.09

Add equivalent length calculation

From table 20
Length
m

Main Duct
16x16
Main duct to reception

ft
6000 19685.04

Elbow

Contraction
9

19694.04

7258 23812.34

23820.34

Main Duct Library

7184 23569.55

23576.55

Main duct to lobby

7300 23950.13

23956.13

Main duct to CSR Office

7143 23435.04

23441.04

32811.4

To CSR Office

Velocity in Last section

10000

V2

32808.4

Total

147299.5 ft

Loss

92.79869 in Wg

664.94 ftm
3.377883 m/sec

75% Regain considered

Regain

Total static pressure at fan discharge

0.068285 in Wg
92.8804 in Wg

5.6134 m Wg

0.56134

0.0254 m Wg

25.4

DUCT SIZING CANTEEN BUILDING 1ST FLOOR SEMINAR HALL


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.

Area

Canteen Building Seminar Hall

From AC calculation Total Dehumidified air quantity


9853 m3/hr
164.2167 m3/min
5799.257 CFM
Say
5900 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

% Area

CFM

259.15

5900 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

0.00

0.00381 mwg

0.000381 Kg/cm2g

4.281567 Sq ft
26 in
x
26 in

Circular equivalent dia


From chart 7 Friction loss

28.4 in
0.065 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct after 1st reduction

Air Quantity CFM


Capacity
CFM
%
5900.00
2950.00

100
50

Duct
Area
%

Area
Sq ft

SUPPLY
Duct
Actual
Size
Area
in

100 4.281567 26x26


58 2.483309 22x18

4.4
2.57

Area
Sq ft

RETURN
Duct
Actual
Size
Area
in
5.99 30x30
3.48 22X24

5.86
3.43

DUCT SIZING CANTEEN BUILDING 1ST FLOOR RECREATION HALL


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.

Area

Canteen Building Seminar Hall

From AC calculation Total Dehumidified air quantity


5639 m3/hr
93.98333 m3/min
3318.99 CFM
Say
3400 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

% Area

CFM

152.6118

3400.00 1133.333

3400 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

0.00381 mwg

0.000381 Kg/cm2g

2.467344 Sq ft
24 in
x
18 in

Circular equivalent dia


From chart 7 Friction loss

22.7 in
0.075 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct after 1st reduction

Air Quantity CFM


Capacity
CFM
%
3400.00
1700.00

100
50

Duct
Area
%

Area
Sq ft

SUPPLY
Duct
Area
Size
Actual
in
Sq ft

100 2.467344 24x18


58 1.43106 14x16

2.57
1.45

Area
Sq ft

RETURN
Duct
Area
Size
Actual
in
Sq ft
3.45 26x20
2.00 26X12

3.35
1.97

DUCT SIZING SERVICE BUILDING GROUND FLOOR


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.
b.
c.
d.
e
f.
g
h

Area

Reception Lounge
Entry Foyer
Electrical Office
IT/Server Room
First Aid Room
Electrical Laboratory
Electrical Laboratory
Corridor
Lobby 1

51.24325

14.5789

15
11

837.93

45.83785 13.04105

14

1017.20

45.83785 13.04105

14

1017.20

20.97125 5.966402

465.38

43.4983 12.37544

13

965.28

245.32

63.78 18.14566

19

1415.36

31.506 8.963579

699.16

100

7800.00

From AC calculation Total Dehumidified air quantity


13129 m3/hr
218.8167 m3/min
7727.438 CFM
Say
7800 CFM
Total Air
Initial Velocity
(Considered)

Initial

100

7800 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

1137.15

3.14519

351.4891

Operating pressure
Radius elbow

CFM

37.75955 10.74274

11.055

Total

% Area

0.00381 mwg

0.000381 Kg/cm2g

5.660377 Sq ft
26 in
x
36 in

Circular equivalent dia


From chart 7 Friction loss

33.3 in
0.055 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
To entry Foyer
Main Duct after entry Foyer
To Reception Lodge
To IT Server Room
Main Duct after reception
Electrical Office
Main Duct after Electrical Office
To electrical laboratory
Main Duct after Electrical lab
To firstaid room
Main Duct upto Lobby
To Lobby

Air Quantity CFM


Capacity
CFM
%
7800.00
837.93
6962.07
1137.15
1017.20
4807.71
1017.20
3790.51
1675.99
2579.90
465.38
2114.52
699.16

100
11
90
15
14
62
14
49
22
38
6.00
28.00
9.00

Duct
Area
%
100
17.5
92
21.5
20.5
69
20.5
57
29.5
46
10.5
35.5
14.5

Area
Sq ft
5.660377
0.990566
5.207547
1.216981
1.160377
3.90566
1.160377
3.226415
1.669811
2.603774
0.59434
2.009434
0.820755

SUPPLY
Duct
Area
Size
Actual
in
Sq ft
26x36
8x20
28x30
14x14
12x16
32x20
12x16
22x24
12x22
18x24
8x10
18x18
6x24

5.44
0.99
5.44
1.28
1.24
4.12
1.24
3.43
1.69
2.78
0.62
2.12
0.84

RETURN
Duct
Area
Size
Actual
in
Sq ft

Area
Sq ft

7.92 34x32
7.29
1.70
1.62
5.47
1.62
4.52
2.34
3.65
0.83
2.81
1.15

34x32
16x16
14x18
32x26
16x16
32x22
26x14
28x20
16x8
24x18
16x8

7.06
1.4
7.06
1.67
1.63
5.37
1.67
4.55
2.31
3.6
0.81
2.78
0.81

DUCT SIZING SERVICE BUILDING FIRST FLOOR


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.
b.
c.
d.
e
f
g

Chemical Office
Ash Handling Office
Corridore
Boiler Office
Store Room
Fuel Office
Entry Foyer
Total

Area
% Area
43.4983 17.25062
45.83785 18.17844

18
19

CFM
1207.54
1272.49

61.6375 24.44429

25

1711.10

43.4983 17.25062

18

1207.54

10.1304 4.017528

281.23

31.0207 12.30223

13

861.16

16.532 6.556284

458.94

252.1551 58.01466

59

6541.06

From AC calculation Total Dehumidified air quantity


11749 m3/hr
195.8167 m3/min
6915.201 CFM
Say
7000 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

7000 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

0.00381 mwg

0.000381 Kg/cm2g

5.079826 Sq ft
28 in
x
28 in

Circular equivalent dia


From chart 7 Friction loss

30.6 in
0.06 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
To entry Foyer
Main Duct upto Chemical Office
To chemical Office
To Ash handling office
Main Duct upto boiler office
To boiler office
Main duct upto store room
To Store Room
Main Duct upto fuel office
To fuel office

Air Quantity CFM


Capacity
CFM
%
7000.00
458.94
6541.06
1207.54
1272.49
4061.03
1207.54
1997.93
281.23
1716.71
861.16

100
7
94
18
19
59
18
29
5.00
25.00
13.00

Duct
Area
%
100
11.5
95
25
26
66.5
25
36.5
9
32.5
19.5

Area
Sq ft
5.079826
0.58418
4.825835
1.269956
1.320755
3.378084
1.269956
1.854136
0.457184
1.650943
0.990566

SUPPLY
Duct
Actual
Size
Area
in
28x28
14x6
30x26
12x18
12x18
22x26
12x18
20x16
12x6
20x14
12x14

5.1
0.52
5.07
1.4
1.4
3.71
1.4
2.07
0.45
1.81
1.09

RETURN
Duct
Actual
Size
Area
in

Area
Sq ft

6.6
6.76
1.78
1.85
4.73
1.78
2.60
0.64
2.31
1.39

34x30
20x14
20x14
28x24
22x12
22x18
10x10
20x18
10x20

6.6
1.81
1.81
4.74
1.69
2.57
0.65
2.34
1.26

DUCT SIZING SERVICE BUILDING FIRST FLOOR MEETING ROOM


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.

Area
88.98955

Meeting Room
Total

CFM
1700.00
1700.00

47.7 m3/min
1684.51 CFM
1700 CFM
1700 CFM
7 m/s

(Considered)

Operating pressure
Radius elbow

Initial

100

88.98955

From AC calculation Total Dehumidified air quantity


2862 m3/hr
Say
Total Air
Initial Velocity

% Area
100

1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

0.00381 mwg

0.000381 Kg/cm2g

1.233672 Sq ft
16 in
x
12 in

Circular equivalent dia


From chart 7 Friction loss

15.1 in
0.12 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct after 1st stage

Air Quantity CFM


Capacity
CFM
%
1700.00
850.00

100
50

Duct
Area
%

Area
Sq ft

SUPPLY
Duct
Actual
Size
Area
in

100 1.233672 12x16


58 0.71553 8x14

1.24
0.72

Area
Sq ft

RETURN
Duct
Actual
Size
Area
in
1.73 16x16

1.67

DUCT SIZING SERVICE BUILDING FIRST FLOOR


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.
b
c
d.

Office Room
Office Room
Turbine Office
Corridore
Boiler Office
Boiler Office
Total

Area
% Area
46.4444 15.42702
13.869 4.606742

16
5

CFM
925.62
276.40

119.3171 39.63248

40

2377.95

66.875 22.21327

23

1332.80

43.4983 14.44844

15

866.91

11.055 3.672041

220.32

301.0588 79.96624

80

6000.00

From AC calculation Total Dehumidified air quantity


9924 m3/hr
165.4 m3/min
5841.046 CFM
Say
6000 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

6000 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

0.00381 mwg

0.000381 Kg/cm2g

4.354136 Sq ft
32 in
x
22 in

Circular equivalent dia


From chart 7 Friction loss

28.9 in
0.06 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct upto office
To Office
Main duct upto Turbine office
To boiler office
To turbine Office
To turbine Office
Main Duct To corridoor

Air Quantity CFM


Capacity
CFM
%
6000.00
6000.00
1202.03
4797.97
1087.23
2377.95
1188.97
666.40

100
100
21
80
19.00
40.00
20.00
12

Duct
Area
%

Area
Sq ft

SUPPLY
Duct
Actual
Size
Area
in

RETURN
Duct
Actual
Size
Area
in

Area
Sq ft

100 4.354136 32x22

4.55

6.10 34x28

6.15

28
84.5
26
48
27
18.5

1.24
3.68
1.15
2.12
1.24
0.81

1.71
5.15
1.58
2.93

16x16
28x28
20x12
22x20

1.67
5.1
1.54
2.86

1.13 10x18

1.15

1.219158
3.679245
1.132075
2.089985
1.175617
0.805515

12x16
32x18
10x18
18x18
12x16
8x16

DUCT SIZING SERVICE BUILDING SECOND FLOOR MEETING ROOM


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.

Area
88.98955

Meeting Room
Total

100

88.98955

From AC calculation Total Dehumidified air quantity


2186 m3/hr
36.43333 m3/min
1286.631 CFM
Say
1300 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

% Area
100

1300.00

1300 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

CFM
1300.00

0.00381 mwg

0.943396 Sq ft
8 in
x
20 in

Circular equivalent dia


From chart 7 Friction loss

13.5 in
0.12 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct after 1st stage

Air Quantity CFM


Capacity
CFM
%
1300.00
650.00

100
50

Duct
Area
%

Area
Sq ft

SUPPLY
Duct
Actual
Size
Area
in

100 0.943396 20x8


58
0.54717 12x8

0.99
0.62

Area
Sq ft

RETURN
Duct
Actual
Size
Area
in
1.32 20x10

1.26

DUCT SIZING SERVICE BUILDING FIRST FLOOR


CFM Cap for each room ( Tentatively considered as per area)

Considered Aera
a.
b.
c.
d
e.

f.
g

Office Room 01
Office Room 02
I & C Office
Office Room 03
Computer Equipment Room
Instrument & Inpection Room
Instrument & Inpection Room
ConnectingCorridor
Corridor
Store

Area
% Area
45.83785 11.13171
43.4983 10.56355

12
11

CFM
901.67
855.65

43.4983 10.56355

11

855.65

43.4983 10.56355

11

855.65

73.8258 17.92858

18

1452.21

45.83785 11.13171

12

901.67

14.1504 3.436421

278.35

23.72 5.760397

466.59

67.78 16.46036

17

1333.29

10.1304 2.460165

411.7772

From AC calculation Total Dehumidified air quantity


13636 m3/hr
227.2667 m3/min
8025.847 CFM
Say
8100 CFM
Total Air
Initial Velocity
(Considered)

Operating pressure
Radius elbow

Initial

8100 CFM
7 m/s
1378 fpm
0.15 in. wg.
1.25

R/D

Duct Area
Required
From table 6 selected duct size

199.27
8100.00

0.00381 mwg

5.878084 Sq ft
28 in
x
34 in

Circular equivalent dia


From chart 7 Friction loss

33.7 in
0.06 in WG per 100 ft of equivalent length

Duct Areas calculated using table 13 and duct sizes table 6.


Duct Section

Main Duct
Main Duct upto Office 1
To Instrument Inspection Room
To Office 1
Main Duct upto office 2
To Office 2
Main Duct upto I & C office
To Office 03
TO I & C Office
Main duct upto Comp Eq Room
To Store Room
To Computer equipment room
To Connecting Corridoor
Main Duct to corridor

Air Quantity CFM


Capacity
CFM
%
8100.00
8077.84
1180.02
855.65
6042.17
901.67
5140.50
855.65
855.65
2984.78
199.27
1452.21
466.59
444.43

100
100
15
11
75
12
64
11
11
37
3.00
18.00
6.00
6.00

Duct
Area
%
100
100
21.5
17.5
80.5
18.5
71
17.5
17.5
44
5.5
25
10.5
10.5

Area
Sq ft
5.878084
5.878084
1.263788
1.028665
4.731858
1.087446
4.17344
1.028665
1.028665
2.586357
0.323295
1.469521
0.617199
0.617199

Duct
Size
in
34x28
34x28
14x14
10x16
34x22
10x18
30x22
10x16
10x16
26x16
10x6
24x10
8x12
8x12

Actual
Area

Area

Duct
Size
in

Sq ft
6.15
6.15
1.28
1.02
4.81
1.15
4.27
1.02
1.02
2.66
0.39
1.5
0.62
0.62

Actual
Area

8.23 38x36

8.89

1.77
1.44
6.62
1.52
5.84
1.44
1.44
3.62
0.45
2.06
0.86
0.86

1.71
1.40
6.60
1.45
5.86
1.40
1.40
3.64
0.45
2.07
0.81
0.81

28x10
12x18
30x34
16x14
30x30
12x18
12x18
30x14
6x12
20x16
16x8
16x8