You are on page 1of 3

P

Sl.
No.

Flow

Flow

Line Description
(Nm3/hr) (Nm3/min)

Pressure Pressure
Kg/cm2
(g)

Kg/cm2
(a)

INSTRUMENT AIR PIPE SIZING ( Refer to Equipment Selection Calculation)


1
2
3
4
1

IA line from Air Drier to IA Receiver


IA line to Thermax Package (Thermax Data)
IA line to Siemens Package
IA to Others
IA line from Both Unit #1 & #2

120
35
30
5
240

2.00
0.58
0.50
0.08
4.00

8.0
8.0
8.0
8.0
8.0

9.03
9.03
9.03
9.03
9.03

300

5.00

8.0

9.03

1.30

8.0

9.03

3 SA Line to Air Drier

120

2.00

8.0

9.03

4 SA Line CW Pump House

100

1.67

8.0

9.03

5 SA Line to Turbine Building

100

1.67

8.0

9.03

PLANT AIR PIPE SIZING


1 Compressor Outlet Line
2 SA Line to Thermax Boiler Area

IA to Boiler By Thermax

scfm
20

Sm3/hr
Nm3/hr
33.98022 31.1311

PIPE SIZING CALCULATION


Calculated Selected
Pipe OD Thickness Standard
Pipe Size Pipe NB

Velocity Velocity

Temp.

Flow

Pipe ID

(m/sec)

(m/min)

deg. C

(m3/min)

mm

mm

mm

mm

mm

15
15
15
15
15

900
900
900
900
900

50.0
50.0
50.0
50.0
50.0

0.271
0.079
0.068
0.011
0.541

19.57
10.57
9.78
3.99
27.67

25
25
25
25
40

33.4
33.4
33.4
33.4
48.26

4.55
4.55
4.55
4.55
5.08

24.3
24.3
24.3
24.3
38.1

15

900

50.0

0.677

30.94

40

48.26

5.08

38.1

15

900

50.0

0.176

15.78

25

33.4

4.55

24.3

15

900

50.0

0.271

19.57

25

33.4

4.55

24.3

15

900

50.0

0.226

17.86

25

33.4

4.55

24.3

15

900

50.0

0.226

17.86

25

33.4

4.55

24.3

35

(say)

Actual
Velocity
(m/sec)

9.73
2.84
2.43
0.41
7.91

9.89
6.32
9.73
8.10
8.10