DYNAMIC RESPONSE OF SEISMO-

RESISTANT BUILDING FRAMES


Najma Nainan
S4 M tech - Civil
MACE, Kothamangalam
najma.nainan@yahoo.co.in

Prof: Alice T V
Associate Professor,
Department of civil engineering
MACE , Kothamangalam
ABSTRACT
Structures on the earth are generally subjected to two types of load: static and dynamic. Static loads are constant
with time while dynamic loads are time- varying. In general, the majority of civil engineering structures are
designed with the assumption that all applied loads are static. The effect of dynamic load is not considered
because the structure is rarely subjected to dynamic loads; more so, its consideration in analysis makes the
solution more complicated and time consuming. This feature of neglecting the dynamic forces may sometimes
become the cause of disaster, particularly, in case of earthquake. Reinforced concrete (RC) shear walls are used
in buildings to resist lateral forces due to wind and earthquakes. They are usually provided between column
lines, in stair wells, lift wells, and in shafts that house other utilities. Shear walls provide lateral load resistance
by transferring the wind or earthquake loads to the foundation. Besides, they impart lateral stiffness to the
system and also carry gravity loads. A well-designed system of shear walls in a building frame improves its
seismic performance significantly. Safety and minimum damage level of a structure could be the prime
requirement of tall buildings. To meet these requirements, the structure should have adequate lateral strength,
lateral stiffness, and sufficient ductility. Among the various structural systems, shear wall-concrete frame could
be a point of choice for the designer. Hence, the present study include: the effect of height of shear wall in the
dynamic response of building frame.
KEY WORDS: Effect of height of shear wall, Dynamic response of building frame, Time history analysis,
Height of shear wall, Dynamic response.
Introduction
The primary objective of earthquake resistant design is to prevent building collapse during earthquakes thus
minimizing the risk of death or injury to people in or around those buildings. Earthquake forces are generated by
the dynamic response of the building to earthquake induced ground motion. This makes earthquake actions
fundamentally different from any other imposed loads. Thus the earthquake forces imposed are directly
influenced by the dynamic inelastic characteristics of the structure itself. The importance of dynamic effects in
structural response depends on the rate of change of external forces and the dynamic properties of structures.
Dynamic responses are stresses, strains, displacement, acceleration etc. The design of buildings for seismic
loads is special, when compares to the design for gravity loads (dead loads and live loads). Gravity loads are
relatively constant, in terms of their magnitude and are treated as static loads. In contrast, seismic loads are
predominantly horizontal (lateral), reversible (the forces are back-and-forth), dynamic (the forces rapidly vary
with time) and of very short duration. The seismic loads are more uncertain than the conventional gravity loads
in terms of magnitude, variation with time and instance of occurrence. The variations of the forces with time
affect the resistance of the building. The maximum magnitudes of the internal forces and their locations in the
structural embers are different from those due to gravity loads. In order to make a building seismo-resistant, it
should have, good building configuration, lateral strength, lateral stiffness, ductility, stability and integrity.


Najma Nainan et al. / International Journal of Engineering Science and Technology (IJEST)
ISSN : 0975-5462 Vol. 4 No.05 May 2012 1865
Objective of study
Reinforced concrete (RC) shear walls are used in buildings to resist lateral forces due to earthquakes. They are
usually provided between column lines, in stair wells, lift wells, and in shafts that house other utilities. Shear
walls provide lateral load resistance by transferring the wind or earthquake loads to the foundation. Besides,
they impart lateral stiffness to the system and also carry gravity loads. A well-designed system of shear walls in
a building frame improves its seismic performance significantly. Safety and minimum damage level of a
structure could be the prime requirement of tall buildings. To meet these requirements, the structure should have
adequate lateral strength, lateral stiffness, and sufficient ductility. Among the various structural systems, shear
wall-concrete frame could be a point of choice for the designer. Hence, the main objective of present study is
the effect of height of shear wall in the dynamic response of building frame.
STRUCTURAL MODELING AND ANALYSIS
SAP 2000 is used to compute the response of thirty (G+29), twenty (G+19) and sixteen storey (G+15) building
for non linear (time history) Dynamic analysis. Results from time history analysis observed for the
displacements to determine the seismic behavior. In the study of effect of height of shear wall, a comparison of
displacements of each storey of different model building for the different height of shear wall was carried out by
time history analysis and studied the effect of height of shear wall in building. Shear wall is modeled using the
4-noded surface elements. The shear walls have been provided with a thickness of 230 mm up to different storey
heights. Related factors taken are seismic Zone factor 0.16, Response reduction factor 3, Importance factor 1,
Damping 0.05, and Foundation Soil type medium. The live load as 3 kN/m
2
for floors.

The storey displacements for various storey levels of 30 storey building are plotted in Fig.1. For various storey
displacements, we can see that the without shear wall is having the maximum storey displacement of
258.629mm and the shear wall upto 30 stories is having the maximum storey displacement of 168.855mm. The
maximum storey displacements for various storey levels of 30 storey building are plotted in Fig.2.
0
5
10
15
20
25
30
35
0 50 100 150 200 250 300
S
T
O
R
E
Y
DISPLACEMENT (MM)
Fig no: 1 - 30 storey building
Without shear wall
Shear wall upto 5 stories
Shear wall upto 10 stories
Shear wall upto 15 stories
Shear wall upto 20 stories
Shear wall upto 25 stories
Shear wall upto 30 stories
Najma Nainan et al. / International Journal of Engineering Science and Technology (IJEST)
ISSN : 0975-5462 Vol. 4 No.05 May 2012 1866


The storey displacements for various storey levels of 20 storey building are plotted in Fig.3. For various storey
displacements, we can see that the without shear wall is having the maximum storey displacement of
160.348mm, and shear wall up to 20 stories is having the maximum storey displacement of 98.171mm. The
maximum storey displacements for various storey levels of 20 storey building are plotted in Fig.4.
0
50
100
150
200
250
300
without
shear
wall
shear
wall upto
5 stories
shear
wall upto
10 stories
shear
wall upto
15 stories
shear
wall upto
20 stories
shear
wall upto
25 stories
shear
wall upto
30 stories
Fig no: 2 - 30 storey building
DISPLACEMENT (MM)
0
5
10
15
20
25
0 50 100 150 200
S
T
O
R
E
Y
DISPLACEMENT (MM)
Fig no: 3 - 20 storey building
Without shear wall
Shear wall upto 5 stories
Shear wall upto 10 stories
Shear wall upto 15 stories
Shear wall upto 20 stories
Najma Nainan et al. / International Journal of Engineering Science and Technology (IJEST)
ISSN : 0975-5462 Vol. 4 No.05 May 2012 1867


The storey displacements for various storey levels of 20 storey building are plotted in Fig.5. For various storey
displacements, we can see that the without shear wall is having the maximum storey displacement of
107.517mm and shear wall up to 16 stories is having the maximum storey displacement of 62.181mm. The
maximum storey displacements for various storey levels of 20 storey building are plotted in Fig.6.

0
20
40
60
80
100
120
140
160
180
without shear
wall
shear wall
upto 5 stories
shear wall
upto 10 stories
shear wall
upto 15 stories
shear wall
upto 20 stories
Fig no: 4 - 20 storey building
DISPLACEMENT (MM)
0
2
4
6
8
10
12
14
16
18
0 20 40 60 80 100 120
S
T
O
R
E
Y
DISPLACEMENT (MM)
Fig no:5 - 16 storey building
Without shear wall
Shear wall upto 4 stories
Shear wall upto 8 stories
Shear wall upto 12 stories
Shear wall upto 16 stories
Najma Nainan et al. / International Journal of Engineering Science and Technology (IJEST)
ISSN : 0975-5462 Vol. 4 No.05 May 2012 1868


The comparison of maximum storey displacements for various storey levels of 30, 20 and 16 storey buildings
(SW 100 models) are plotted in Fig.7 For various storey displacements, we can see that the 30 storey building
is having the maximum storey displacement of 168.855mm, 20 storey building is having the maximum storey
displacement of 98.171mm, 16 storey building is having the maximum storey displacement of 62.181mm.

0
20
40
60
80
100
120
without shear
wall
shear wall upto
4 stories
shear wall upto
8 stories
shear wall upto
12 stories
shear wall upto
16 stories
Fig no: 6 - 16 storey building
DISPLACEMENT (MM)
0
5
10
15
20
25
30
35
0 50 100 150 200
S
T
O
R
E
Y
DISPLACEMENT (MM)
Fig no: 7 - comparison of 30, 20 and 16 storey buildings ( SW - 100)
30 STOREY BUILDING
20 STOREY BUILDING
16 STOREY BUILDING
Najma Nainan et al. / International Journal of Engineering Science and Technology (IJEST)
ISSN : 0975-5462 Vol. 4 No.05 May 2012 1869

The comparison of maximum storey displacements for various storey levels of 30, 20 and 16 storey buildings
(SW 50 models) are plotted in Fig.8. For various storey displacements, we can see that the 30 storey building
is having the maximum storey displacement of 179.066mm, 20 storey building is having the maximum storey
displacement of 104.792mm, 16 storey building is having the maximum storey displacement of 67.86mm.
CONCLUSION
The analytical study on the dynamic response of seismo-resistant building frames was done. The storey
displacements for various heights of shear wall in the dynamic response of building frames are obtained. From
the study, the following conclusion can be drawn out. If the height of shear wall extended up to mid height of
building frames, the displacement goes on decrease. But if the shear wall extended to full length of building
there will not much reduction in the displacement. Hence, there is no need for providing shear wall throughout
the height of high rise buildings. That is the response of shear wall beyond mid height of the building against
lateral forces is least.
REFERENCES
[1] Pankaj Agarwal & Manish Shrikhande Earthquake Resistant Design of Structures. Prentice Hall of India Private Limited, New
Delhi, 2007.
[2] Bharat Bhushan Prasad Fundamentals of Soil dynamics and Earthquake Engineering. PHI Learning Private Limited, New Delhi,
2009.
[3] Anil K. Chopra Dynamics of structures Theory and Applications to Earthquake engineering. Prentice Hall of India Private Limited,
New Delhi, 2008.
[4] IS 1893 (part1): 2002, Indian Standard Criteria for earthquake resistant design of structures, Bureau of Indian standards, New Delhi.
[5] IS: 875 (Part 1) 1987, Code of Practice for Design Loads (Other Than Earthquake) for Buildings and Structures Dead Loads,
Bureau of Indian Standards, New Delhi.
[6] IS: 875 (Part 2) 1987, Code of Practice for Design Loads (Other Than Earthquake) for Buildings and Structures Imposed Loads,
Bureau of Indian Standards, New Delhi.
[7] K. Yoshimura, and M. Inoue, "Dynamic Analysis of Reinforced Concrete Frames with Shear walls", 7
th
World Conference
Proceedings Earthquake Engineering. SymposiumLondon, vol. 2, pp. 1178-1184, 1977.
[8] M. Ishac, and A. Heidebrecht, "Dynamic Response of Asymmetric Shear wall Frame Building Structure," 7
th
World Conference
Proceedings Earthquake Engg. SymposiumLondon, vol. 2, pp. 1363-1368, 1977.
0
5
10
15
20
25
30
35
0 50 100 150 200
S
T
O
R
E
Y
DISPLACEMENT (MM)
Fig no: 8 - comparison of 30, 20 and 16 storey buildings ( SW - 50)
30 STOREY BUILDING
20 STOREY BUILDING
16 STOREY BUILDING
Najma Nainan et al. / International Journal of Engineering Science and Technology (IJEST)
ISSN : 0975-5462 Vol. 4 No.05 May 2012 1870