You are on page 1of 2

2V 400Ah(10hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is
absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special one-way valves allow the gases to escape
thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is,
therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid
General Features
Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.
Dimensions and Weight
Length(mm / inch) 211 / 8.31
Width(mm / inch) 176 / 6.93
Height(mm / inch) 329 / 12.95
Total Height(mm / inch) 367 / 14.5
Approx. Weight(Kg / lbs) 26.6/ 58.67
Performance Characteristics
Nominal Voltage 2V
Number of cell 1
Design Life 20 years
Nominal Capacity 77
o
F(25
o
C)
10 hour rate (40A, 1.8V) 400Ah
5 hour rate (68.4A, 1.75V) 342Ah
1 hour rate (235A, 1.6V) 235Ah
Internal Resistance
Fully Charged battery 77
o
F(25
o
C) 0.47mOhms
Self-Discharge
3% of capacity declined per month at 20
o
C(average)
Operating Temperature Range
Discharge -20~60
o
C
Charge -10~60
o
C
Storage -20~60
o
C
Max. Discharge Current 77
o
F(25
o
C) 2000A(5s)
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
Cycle use
Maximum charging current 80A
Temperature compensation -5.0mV/
o
C
Standby use
Temperature compensation -3.3mV/
o
C
Discharge Constant Current (Amperes at 77
o
F25
o
C)
Discharge Constant Power (Watts at 77
o
F25
o
C)
page1 of 2
www.vision-batt.com
+
-
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
End Voltage
Volts/cell
10min 15min 30min 45min 60min 3h 5h 10h
1.60 695 558 406 309 235 108 73.8 43.0
1.65 659 531 388 296 226 105 72.1 42.4
1.70 621 504 369 283 218 101 70.3 41.7
1.75 583 475 350 270 208 96.9 68.4 40.9
1.80 544 447 330 256 198 93.1 65.9 40
End Voltage
Volts/cell
10min 15min 30min 45min 60min 2h 3h 5h
1.60 1217 864 703 609 468 295 203 133
1.65 1146 817 668 580 447 272 199 131
1.70 1074 770 632 547 427 257 193 128
1.75 1004 722 595 516 404 247 187 125
1.80 934 675 558 484 381 234 176 119
CL400E-V
367
2.30-2.35VPC
2.23-2.27VPC
2V400Ah
Charge characteristic curve
Charging time (hours)
C
h
a
r
g
e
d
V
o
l
u
m
e
(%)
C
u
r
r
e
n
t
(xCA)
V
o
l
t
a
g
e
(V)
2.50
2.25
2.00
1.75
0.25
0.20
0.15
0.10
0.05
0
0 2 4 6 8 10 12 14 16 18 20
Constant voltage charge characteristic
o
(0.2CA,25 C)
CHARGED VOLUME
140
120
100
80
60
40
20
0
CHARGE VOLTAGE
CHARGING CURRENT
Self-discharge characteristic
110
100
90
80
70
60
50
40
0 2 4 6 8 10 12 14 16 18 20
Storage time: months
C
a
p
a
c
i
t
y
(
%
)
o
40 C
o
30 C
o
20 C
Life characteristics of standby use
C
a
p
a
c
i
t
y
(
%
)
120
100
80
60
40
20
0
0 5 10 15
Life(year)
Testing conditions: floating voltage: 2.25 to 2.30V/Cell
o o
ambient temperature: 25 C(77 F)
Cycle service life in relation to
depth of discharge
Number of cycles(cycles)
C
a
p
a
c
i
t
y
(
%
)
120
100
80
60
40
20
0
400 800 1200 1600 2000 2400
100% D.O.D. 50% D.O.D. 30% Depth of discharge
Temperature effects on float life
25
20
10
5
0
L
i
f
e
(
y
e
a
r
s
)
o
Temperature( C)
10 20 30 40 50
2.30V/Cell
Relationship between
charging voltage and temperature
-10 0 10 20 30 40 50
o
Ambient temperature( C)
2.6
2.5
2.4
2.3
2.2
ST
ND
Y
SE
A
B
U
C
L
E

E
C
Y
U
S
V
o
l
t
a
g
e

(
V
)
Temperature effects on capacity
120
100
80
60
40
20
0
-20 -10 0 10 20 30 40 50
C
a
p
a
c
i
t
y

(
%
)
o
Temperature( C)
2
0.
C
0.3C
1.0C
0
1C
.
2.0C
O
Discharge characteristic (25 C)
min h
Discharge time
V
o
l
t
a
g
e
(
V
)
2.0
1.6
0
1 2 3 5 10 20 30 60 2 3 5 10 20
760A 380A
40A
101A 68.4A
235A
MH25860
G4M19906-9202-E-16
THEINTERNATIONALCERTIFICATIONNETWORK
ISO9001:2000
THEINTERNATIONALCERTIFICATIONNETWORK
www.vision-batt.com Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail: sales@vision-batt.com
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2011-8)
Page 2 of 2
CL400E-V