- Abstract -

General informations:
Shall be provided the following electrical equipment:
- Electrical installations for lighting and inside plugs
- Switchboards
- Wiring of internal strength and protection against electric shock
- Electrical general supply connection, generator
- Electrical installations and lightning protection

This project represent a theoretical foundation to construct an electrical installations for an
office building with 2S + P + 5 levels with the height of 3 m for basement and the height of 3,15m
for ground and first floor.
Voltage of the lens is 3x400/230 V at a frequency of 50Hz. Power supply to the building
electrical system is made in electric transformer station.The electricity tariff is uniform so, for this
builiding, will be a general one column.
The General electric panel of light and power is supply from transformer wich is loacated at
100 m from the outer wall of the building through a CYABY cable 3 x 150 + 70 and from
conductors PVC insulation and protection posed to the earth. The secondary switchboards light and
power supplying is made by simple radial columns.
The electric transformer supplies the switchboard station general light and power (TGLF)
and general safety switchboard (TGS) installed in a room with general electric panel destination
from the basement of number two.
The building is equipped with a pump group, consisting of two pumps, one active and one
backup, with installed capacity of 3 kW, in case of fire, located in pumps room.
The pumps are part of critical receivers building and this are supply from a separate control
box, named switchboard for fire pumps, powered in two ways: one way is from the transformer and
the second way is represented by the supply of safety panel powered by a generator with automatic
25 kVA starting power, located on the terrace.
Switch on the power of intervention based on source is done automatically by AAR systems
(source inverter). From the safety panel also supplies exhaust lighting, lighting for marking hydrants
fitted with fluorescent lighting power and W 1x8 hour autonomy, switchboard for pumps wastewater
(TPU) with installed capacity of 3 kW and extractor nuisance property located on the terrace with
installed power of 5 kW.
Computation of the lighting system was made using Dialux program, which has the principle
of the calculation method of use factor.

Criteria used to form electrical circuits and light plugs are:
- Maximum power circuit of light is about 1200 W and the number of lighting fixtures on the circuit
does not exceed 10-12.
- The length of the light circuit to be less than or equal to 50 m.
-Outlets not installed on the outer walls or in bathrooms.
- A power plugs circuit is 2000W and the number of outlets does not exceed 10 to 12 places setting
on the circuit.
- Depending on the situation, can be used simple or double switches
Location lighting on plans situation was made uniform or uneven (asymmetric), depending
on each situation. Uneven settlement, is to give such a luminaire or more lamps, depending on the
room or destination. Another location is uneven lighting near the wall of the vitreous.
Drawing light and outlet circuits on the ground floor and first floor was made of wire buried
in tube type located FY protection type IPY links doses can be done in simple and centralized, the
distance from the luminaire dose is less than or equal to 9 m, and the route dose luminaire should not
have more than 3 elbows.
Interior lighting control is done locally by switches or switches mounted flush to hp = 1.5 m.
Drawing light circuits in the basement was done in FY conductor type, apparently mounted in
a protective tube type IPY, links can be done in single doses, using switches, double sealed and
mounted plugs apparently.
Power plant is the engine located in the boiler, central air handling, pumps room, motors for
elevators, exhaust extractor, the defrost switchboard and the ramp and wastewater switchboard.
For protection against atmospheric tension provided with an installation of lightning striking
device type (PDA) Prevectron 2 - connected to the earth socket joint 1ohm Rt.