You are on page 1of 44

CA60Plus

Installation manual
WARNING
This manual contains information on limitations regarding product use and function and information on the
limitations as to liability of the manufacturer. The entire manual should be carefully read.
Contents
PART I. Installation of the CA60Plus alarm control panel............................................................3
1. CA60Plus alarm control panel....................................................................................................4
2. LED60 and LED61 keyboards...................................................................................................5
3. CA60Plus control panel inputs and outputs...............................................................................6
4. Connecting LED60 and LED61 keyboards...............................................................................7
5. Using the PGM1, PGM2 and PGM3 programmable outputs...................................................8
6. Using SIREN programmable output..........................................................................................8
7. Connecting sensors to CA60Plus control panel........................................................................9
8. Connecting the CA60Plus built-in digital communicator..........................................................11
9. Powering the CA60Plus control panel......................................................................................11
10. Installation of the voice dialer - VD60......................................................................................12
11. Proximity cards reader - PR62 - connection....................................................................................13
PART II. Programming the software parameters for CA60Plus alarm control
panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
0. User codes in the CA60Plus control panel..............................................................................15
2. Zone programming...................................................................................................................16
3. Programming the PGM and SIREN programmable outputs...................................................20
4. Time periods............................................................................................................................22
5. Engineer parameters................................................................................................................24
6. Communicator parameters.......................................................................................................26
7. Programming Up/Down Load parameters................................................................................29
8. Programming the voice dialer - VD60..............................................................................31
9. CA60Plus test modes...............................................................................................................32
Supplement A LED61 keyboard for CA60Plus control panel......................................................35
Supplement B Default programming table..................................................................................36
Supplement C Additional information.........................................................................................39
Supplement D General connection scheme.........................................................................................42
Supplement E Example voice messages...................................................................................43
CA60Plus control panel Installation manual 3
PART I. Installation of the CA60Plus alarm control panel
The CA60Plus Alarm control panel was designed and tested in compliance with electromagnetic
compatibility standards.
The following recommendations need to be observed for the proper performance of the alarm station:
1. Ensure the alarm system is properly earthed (grounded)
2. Insulate the high and low voltage cables and use different input openings on the box.
3. Avoid any loops of connecting wires within the very box and in their passage over or under the
printed-circuit boarding.
4. Additional relays must not be placed in the CA60Plus Alarm control panel box as these may
generate electromagnetic interference when switched.
4.1. Use only relays with good insulation between contacts and the winding.
4.2. Relays, connected to outputs with an open commutator, must be designed to accom-
modate a 12 V DC driving voltage and an impedance at the winding greater than
400.
5. The cable connecting the control panel and the keyboard is quadruple. It is strongly recom-
mended not to:
5.1. use this cable to make other connections connect to a telephone line, Flash-lamps
control signals, sirens or relays.
6. Avoid channels or cable forms that contain high voltage cables when placing the connecting
cables. This is very important in cases where such cables are being used to power electric
motors, fluorescent lamps or triple-phase voltage. Where the above is not possible, use only
shielded cables, where the shield is grounded only in the alarm system box.
4 CA60Plus control panel Installation manual
CA60Plus alarm control panel metal box
1. CA60Plus alarm control panel
2
1
1
1
Unscrew (1)
Remove cover (2)
Fig.1a CA60Plus control panel plastic box
1
6
3
5
1
4
Battery
12V / 7 Ah
F - 0,63 A
Transformer
230 Vac 50 / 60 Hz
sec.: 17 V / 24 VA
1
Radio transmitter
2
RESET
F1 BATT
F3 AUX
F2 PGM
PROG
Communicator
LED
2A
1A
1A
1 - Mounting openings
2 - CA60Plus control panel
3 - Mains supply terminal and fuse
holder
4 - Signal cables openings
5 - Mains supply cable hole
6 - Self-security TAMPER button
Fig.1 CA60Plus control panel
EXPAND
CA60Plus control panel Installation manual 5
2. LED60 and LED61 keyboards
Fig.2 CA60Plus LED keyboard
a) Cover
1 2 3
4 5 6
7 8 9
0
ON PROG CLEAR ENTER
A
R
M
M
E
M
CLR ENT 0
1 2 3
4 5 6
7 8 9
P
R
O
G
D
IS
A
R
M
) Bottom
1 1
1
2
1 - Mounting holes
2 - Cables hole
1
1
1
1
1
2
2
CA60Plus alarm control panel plastic box
Fig.1b CA60Plus control panel plastic box
7
8
6
6
6
6
6
6
5
4
3
2
2
2
2
A
c
c
u
m
u
l
a
t
o
r

c
a
b
l
e
1 - Center support
opening (behind PCB)
2 - S
3 - CA 864 control panel
4 - Mains power supply
terminal
5 - Main cable opening
7 -
8 - Tamper button for box
self-protection
upport opening
6 - Add. cable openings
Mains power supply
opening
Mains
transformer
50 / 60 Hz
15-25 V / 50VA
12V / 7 Ah
battery
Room for additional modules
Room for add. Modules
Use to fix
main power supply cable
F - 0,63 A
B
A
T
T
RESET
F1 BATT
F3 AUX
F2 PGM
PROG
Communicator
LED
2A
1A
1A
1
EXPAND
6 CA60Plus control panel Installation manual
3. CA60Plus control panel inputs and outputs
AC - power supply from 17 V/24 V A mains transformer
Earth conductor to EARTH
+AUX and -AUX - 13 V DC power supply to sensors consuming up to 1
+PGM - 13 V DC power supply to additional devices consuming up to 1
PGM1, PGM2 and PGM3 programmable outputs
SIREN siren programmable outputs
Z2, Z3, Z4, Z5 and Z6 zone inputs; ( Z1 zone is at the keyboard)
COM total mass of the zones
and connects the telephone line
1 and 1 connects the telephone device
RED and BLACK keyboard power supply
GREEN and YELLOW interface between the panel and the keyboard
F1 - 2 battery fuse
F2 - 1 fuse for powering sensors, programmable outputs and keyboards
F3 - additional device 1 mains fuse
12 V, 7 Ah battery cables
RESET jumper for hardware RESET and default parameter recovery
Communicator LED LED for status indication of built-in digital communicator
PROG terminal for programming by the manufacturer
EXPAND terminal for expander modules (Voice dialer)
Fig. 3 nputs and outputs CA60Plus control panel i
BATTERY
12 V / 7 Ah
B
A
T
T
B1
A1
B
A
A
C
+
A
U
X
-
A
U
X
+
P
G
M
P
G
M
1
P
G
M
2
P
G
M
3
S
I
R
E
N
Z
2
C
O
M
Z
3
Z
4
C
O
M
Z
5
Z
6
C
O
M
R
E
D
G
R
E
E
N
Y
E
L
L
O
W
B
L
A
C
K
RESET
F1 BATT
F3 AUX
F2 PGM
PROG
Communicator
LED
2A
1A
1A
EXPAND
CA60Plus control panel Installation manual 7
4. Connecting LED60 and LED61 keyboards
The producer has been equipped the LED60 Keyboard with a bundle of wires 20-cm long.
The producer has been equipped the LED61 Keyboard with two wires 10-cm long for zone connec-
tion and terminals for the bus connection. These terminals are marked with the respective colors.
The colors must be observed (see Fig. 4) when connecting the keyboards to the 60Plus Control
Panel.
The LED60 and LED61 Keyboards zone cables are white and black in color. The zone in the key-
boards does not have to be balanced. Where more than one keyboards are connected, the zone in each
one shall be monitored individually. Nevertheless, activating any keyboard zone shall be regard as an
activation of zone 1.
No more than eight keyboards (irrespective of their type) can be connected to one control panel. Each
keyboard must be assigned an individual address, by placing the jumper on the keyboard at its respective
place (see Fig. 5). The individual address ensures TAMPER event identification, whenever the keyswitch
of the respective keyboard is turned on.
LED60 and LED61 Keyboards addresses are assigned with the help of a jumpers. Following the table
(see Fig. 5) the respective address could be programmed. The JT jumper is shortened by default.
The JT jumper must be placed where only one keyboard has been connected. Where more than one
keyboards are connected, the JT jumper should be placed on the most distant one.
The cable connecting the LED60 and the LED61 Keyboards to the CA60Plus Control Panel must
be no longer than 250 m and have a cross-section of no less than 0.25 mm.
Fig. 4 Connecting LED keyboard to CA60Plus control panel
1 2 3
4 5 6
7 8 9
0
ON PROG CLEAR ENTER
YELLOW
WHITE
GREEN
RED
BLACK
BLACK
RED
GREEN
YELLOW
BLACK
CA60Plus control panel
terminals
ZONE 1
DETECTORS WIRES
A
R
M
M
E
M
CLR ENT 0
1 2 3
4 5 6
7 8 9
P
RO
G
D
IS
AR
M
Fig. 5 LED60 and LED61 keyboard jumpers
Addresses *
* The J T jumper must
be set in the most
far unit in the bus.
J0
1
0
0
0
0
1
1
1
J1
0
0
1
1
0
0
1
1
JT*
0
0
0
0
1
0
0
0
J2
0
1
0
1
0
1
0
1
0 = jumper is removed
1 = jumper is set
Rev1.3
JT
J0
J1
J2
T
A
M
P
E
R
CA60Plus
keyboard
Rev. 2.3
GREEN
YELLOW
RED
BLACK
BLACK
WHITE
8 CA60Plus control panel Installation manual
5. Using the PGM1, PGM2 and PGM3 programmable outputs
The 60Plus Alarm Station PGM1, PGM2 and PGM3 outputs have a programmable active level.
This allows them to be used to transmit control signals towards external devices (e.g. a block siren input)
or to directly control low-powered external devices (e.g. relays, LED, etc.). The internal structure of all
PGMs is the same and is shown in Figure 6 a).
Figure 6 b) shows the connection of the relay and a light-emitting diode to the PGM. The active level
of this connection is low.
Fig. 6 b) Controlling light-emitting diode
relay using PGM1 and PGM2 outputs
and
F
2
B
AC
+AUX
-AUX
+PGM
PGM1
PGM2
PGM3
SIREN
Z2
COM
CA60Plus
1k R
E
L
A
Y
L
E
D
Fig. 6 a) Internal structure of programmable
PGMx output
+12 VDC
1 k
PGMx terminal
Permissible current:
- from +12 V - up to 10 mA
- towards GND - up to 100 mA
For SIREN output the
current supplied to GND
is up to 1 A.
6. Using SIREN programmable output
The 60Plus Alarm Station SIREN output is designed to control a siren. The potential of the active
level of the SIREN output is not being controlled. In inactive state the output will have a potential of +12 VDC,
and in active state GND. The internal structure is identical to the one shown in Figure 6 a). It should be
pointed out that the transmitter can pass through to GND electricity of up to 1 A.
Fig. 7 shows how to connect SR110E and SR120 sirens using the SIREN output.
Fig. 7 Controlling sirens using SIREN output
F
2
B
AC
+AUX
-AUX
+PGM
PGM1
PGM2
PGM3
SIREN
Z2
COM
+12 V
-12 V
CA60Plus
SR110E
a) Connecting SR110E using
a double-wire
F
2
B
AC
+AUX
-AUX
+PGM
PGM1
PGM2
PGM3
SIREN
Z2
COM
+12 V
GND
CA60Plus
SR120
BLK
The BLOCK jumper
in
.
SR120 must be
switched on
b) Connecting SR120 using
a double-wire
F
2
B
AC
+AUX
-AUX
+PGM
PGM1
PGM2
PGM3
SIREN
Z2
COM
+12 V
GND
CA60Plus
SR120
BLK
The BLOCK jumper
in
.
SR120 must be
removed
c) Connecting SR120 using a triple-wire
CA60Plus control panel Installation manual 9
7. Connecting sensors to CA60Plus control panel
The security system is mounted with sensors with relay contacts. Fire alarm sensors supplied with
relay outputs can also be used.
Use the supplied 1 k resistors to balance the zones. The balancing resistors are installed on the last
sensor of the chain. The zones, which shall not be used, are terminated by way of the 1 k resistor at the
terminals of the CA60Plus Control Panel, irrespective of the chosen type of zone balancing.
After the initial power up of the station, the zone balance type has to be programmed. By default only
1 balancing resistor is used.
Figure 8 shows the possible options for connecting the sensors and for balancing the zones.
Figure 9 shows the connection between a keyswitch and a fire detector with a relay at the base.
The hardware implementation of zone 4 of the panel permits performance in pulse count mode. This
mode counts short pulses 2 to 4 ms for a period of 20 seconds. The first pulse starts a 20-second
countdown during which pulses are expected to be received. Their number is assigned at Address 28 of
the engineer program. An alarm signal is emitted when this number is reached within the time of 20
seconds. Otherwise the pulse counter will be zeroed after the time of 20 seconds expires.
Activating the pulse count mode will automatically start when a number other than 0 is keyed in at
Address 28 of the engineer program.
b) Connecting Detectors with Two Balancing Resistors
1k
NC
RELAY 1
NC
RELAY 2
NC
RELAY n
NC
TAMPER 1
NC
TAMPER 2
NC
TAMPER n
1k
ZONE x
COM
Fig. 8 Options for connecting detectors to the CA60Plus control panel
) Connecting Detectors with One Balancing Resistor
NC
RELAY 1
NC
RELAY 2
NC
RELAY n
NC
TAMPER 1
NC
TAMPER 2
NC
TAMPER n
1k
1k
ZONE x
TAMPER
ZONE
COM
COM
C) Connecting up to Four Detectors with Two Balancing Resistors
1k
NC
RELAY 1
NC
RELAY 2
NC
RELAY n
NC
TAMPER 1
NC
TAMPER 2
NC
TAMPER n
1k
ZONE x
COM
1k 1k
10 CA60Plus control panel Installation manual
Fig. 9 Connecting a key-switch and a fire detector with relay in the base
to a CA60Plus control panel
Connecting keyswitch with two balancing resistors
1k
NC
NC
1k
ZONE x
COM
Key-switch
Must be normally closed.
Tamper switch of the key-switch.
NC
Key-switch
Must be normally closed.
NC
Tamper switch of the key-switch.
1k
1k
ZONE x
TAMPER
ZONE
COM
COM
Connecting key-switch with one balancing resistor
Connecting a fire detector with a relay in the base
in scheme with two balancing resistors
F
2
B
AC
+AUX
-AUX
+PGM
PGM1
PGM2
PGM3
SIREN
Z2
COM
+12 V
GND
NO
CA60Plus
Fire
detector
base
NC
COM
1k
1k
The programmable output
must be programmed
as Fire Reset and the active
status must be +12 VDC.
Connecting a fire detector with a relay in the base
in scheme with one balancing resistor
F
2
B
AC
+AUX
-AUX
+PGM
PGM1
PGM2
PGM3
SIREN
Z2
COM
+12 V
GND
NO
CA60Plus
Fire
detector
base
NC
COM
1k
The programmable output
must be programmed
as Fire Reset and the active
status must be +12 VDC.
CA60Plus control panel Installation manual 11
9. Powering the CA60Plus control panel
The system should be powered-up only after it is installed and all necessary devices have been con-
nected control panel, keyboard, sensors, etc.
In order to set the station to the producers default parameters place the Reset jumper on the CA60Plus
Control Panel.
Supply 220 V mains power. The keyboard emits a short sound signal and the light-emitting diodes on
the display blink.
Remove the Reset jumper.
Use the red (+) and black (-) cables to connect the battery to the station.
The normal status of the station (all sensors in the security system are inactive and there are no
violated anti-TAMPER chains) is indicated on the keypad by a continuously lit green READY light-
emitting diode. The station has now been programmed the producer default parameters.
All light-emitting diodes will blink and a sound signal will be heard where the keyboard is open or
incorrectly connected.
Where there is an open zone or an open TAMPER for any zone, the light-emitting diode for the
respective zone together with the MEMORY or TAMPER light-emitting diodes on the display will light
up.
NB! An open anti-sabotage chain (TAMPER) in the security system will sound the siren. To
stop the siren key in code 0000. The respective zone light-emitting diode remains perma-
nently lit whereas the TAMPER light-emitting diode will blink. Remove the failure the
TAMPER light-emitting diode remains permanently lit. Key in code 0000 again to clear the
alarm event from the memory.
Any technical trouble in the panel will light up the Trouble indicator. To view these problems introduce
the 0000 manager code and single-press ENTER. The display will indicate a list of current problems. The
indications and their meaning are shown in Figure 11.
Fig. 11 TROUBLE mode indication
LED Technical trouble
1 No 220 V power supply
2 Battery low
3 Fuse burned
4 No telephone line
5 No communication available
6 Active TAMPER within the system
8. Connecting the CA60Plus built-in digital communicator
The telephone line is connected to A and B
terminals on the CA60Plus Control Panel with
no requirements to observe polarity (Fig. 10).
The telephone device is connected to A1 and
B1 terminals on the CA60Plus Control Panel
with no requirements to observe polarity (Fig.
10).
The parameters of the digital communica-
tor are engineer programmed.
It is not necessary to install additional com-
ponents if the built-in communicator is not to be
used.
B1
A1
B
A
}
Telephone line
Telephone device
}
Fig.10 Connecting the CA60Plus
built-in communicator
12 CA60Plus control panel Installation manual
RESET
PROG EXPAND
SP
MIC
REC
MSG
PLAY
M
S
G

VD60
C
A
6
0
P
l
u
s
B
U
S
Y
1
2 2
B1
A1
B
A
10. Installing the VD60 Voice Telephone Dialer into the 60Plus
Fig. 12 Installing the VD60 Voice Telephone Dialer
The VD60 Voice Telephone Dialer module supplements the 60Plus Alarm Control Panel,
which serves to transmit alarm event messages to the user, under the form of eight pre-recorded voice
messages, of up to 5 sec. each. Two message types are supported by zone or by event (see Supple-
ment E Table with Sample Voice Messages).
Turn off the power supply in order to connect the PCB of the voice telephone dialer to the EX-
PAND socket of the CA60Plus Control Panel (1). Fix the PCB onto the pre-mounted plastic spacers
(2). The telephone line should be connected to terminals A and B of the 60Plus Control Panel.
Polarity need not be observed.
The telephone device can be connected to terminals A1 and B1 of the 60Plus Control Panel
with no need of observing polarity.
The voice dialer can simultaneously operate with the built-in digital communicator.
The dialer has one LED status indicator PLAY/RECORD and BUSY, and one single digit LED
display indicating the number of the current message. Use the MSG key to switch-over between
messages. Use the PLAY key to reproduce messages when the REC jumper is turned off, or to
record when it is turned on. A speaker (8-16 ohms) for listening to recorded messages can be con-
nected to the SP socket.
The voice dialer parameters can be engineer programmable.
CA60Plus control panel Installation manual 13
11. PR62 proximity cards reader - PR62 - connection
The PR62 proximity card reader was designed to control security in the systems integrated within the
CA60Plus Control Panel. The excellent card reading distance, the triple color indications, supplemented by
the sound indicator, the integrated output, as well as the fine design, all make the PR62 any attractive supple-
ment to the security system.
The PR62 can be connected to the system bus of the CA60Plus together with the mounted keyboards.
Up to four proximity readers can be included within one security system. Programming the various addresses
onto the readers will provide identification by the TAMPER of each of these. The Table for Address Pro-
gramming is provided in Fig. 13.
The proximity-card enables to arm and disarm the system, as well as to control the electric lock via
integrated output. The internal structure, and the permissible output currents, are provided in Fig. 13.
It is possible that only proximity-card readers be included in a system without having an installed key-
board. In such systems this would hinder current programming of parameters and cards, as well as Log
Review and Technical Trouble indications. Portable LED60, LED61 or LCD62 type keypads can be used to
accomplish such tasks.
Up to 17 cards can be assigned to one security system one card for each of the 16 users and one card
for the main user.
The main system user programmes the performance of the cards. Arming and/or disarming rights must
be assigned for the respective user code.
The user may not be designated a code combination. In such case the only means to control the
security system would be the proximity-card.
. 13 PR62 proximity cards reader connection scheme
Proxi CA62
T
A
M
P
E
R
LED
Y
E
L
L
O
W
B
L
A
C
K
G
R
E
E
N
R
E
D
P
G
M
J1
J2
JT* PR62 addresses*
JT* J1 J2
1 0 0
0 1 0
0 1 0
1 1 0
* The J Tjumper must be set in
the most far unit on the bus.
Internal structure of built-in PGM
+12 VDC
1 k
PGMx terminal
Permissable currents:
- from +12 V - up to 10 mA
- towards GND - up to 100 mA
The output activates for 2
seconds after the recognised
card is drown back.
Two color LED indicator
Signal cables
openings
Mounting openings
Lock
LED indication:
- green - the card is recogni-
sed or required action is done,
- red - the card is not recog-
nised or required action is
rejected,
- yellow (LED blinks) - ready.
14 CA60Plus control panel Installation manual
PART II. Programming the parameters for CA60Plus alarm
control panel
Carefully study this installation manual before programming the alarm station.
The respective parameters can be configured from a keyboard or remote control connected to the
system a personal computer via a telephone using the UDLManager program.
Keyboard programming:
The CA60Plus Alarm System engineer parameters programming mode can be only begin when the
system is in disarmed mode.
Keying in the system engineer code will initiate the CA60Plus Alarm System programming mode for
the engineer parameters. After restoring the default parameters (RESET) the engineer code will remain
7777.
The respective Alarm System parameters can be programmed after a double-digit address is intro-
duced. Use the table with addresses in Supplement A and the detailed instructions about the addresses in
the remaining part of the manual.
The table with addresses provides the system RESET configuration.
A detailed description of the possible parameters, the keypad display indicators and the necessary
programming functions has been provided for each address.
Each address has been provided default configurations after a software or hardware RESET has been
carried out.
The information entered for each address can be confirmed by pressing the ENTER button.
When reviewing the programmed parameters it is recommended to exit any given address by single
pressing the CLEAR button. This function will leave the introduced parameters unchanged.
In case the programmer is disoriented in the engineer menu, it is recommended to exit the menu by
double clicking the CLEAR button and to begin programming the station parameters from the start.
Remote programming using the UDLManager program
To access a UDLManager program system requires a system password and a station program pass-
word. After restoring the default parameters these passwords will be the same and are 1234. In order to
provide access to the system from the central station enter the correct password of the central station at
Address 71.
A 24-hour period automatically begins after default parameters are restored during which the system
is in remote programming standby mode. Following this period, the ring number parameter is zeroed,
whereby the system will be locked for remote programming. This 24-hour period can be canceled by
introducing a telephone number for connecting to the central station at Address 70.
Detailed working instructions for the UDLManager program are provided in the built-in Help files.
The details listed in this manual apply to all parameters for remote system programming.
CA60Plus control panel Installation manual 15
ADDRESSES 02..16 USER CODE 2..16 ATTRIBUTES
The programming is the same as for Address 01.
DEFAULT : codes 02 to 16 have been assigned the attributes Disarm, Full ARM, Stay ARM, Force ARM,
LOG, BYPASS. However, no code combination has been introduced
0. User codes in the CA60Plus control panel
ADDRESS 00 MANAGER ACCESS TO USER CODE ATTRIBUTES
NO Manager access to user code authority is denied.
Light-emitting diodes 1 to 6 do not light up.
YES Manager access to user code authority is granted.
Light-emitting diodes 1 to 6 light up.
DEFAULT : YES
ADDRESS 01 USER CODE 1 ATTRIBUTES
USER CODE 1 attributes are assigned at this address. The user code can have
more than one attribute. Pressing a digital button with the respective number
activates the given attribute. The light-emitting diode with the number of the
pressed digit will light up to indicate the selection. Pressing the same digit again
will inactivate it and the light-emitting diode with the number of the pressed digit
will go out.
Only those light-emitting diodes, which correspond to the assigned attributes, will
remain lit at the end of the procedure. Pressing the ENTER button confirms the pro-
grammed attributes.
1 Disarm Authorizes this user code to Disarm the site.
2 Full ARM Authorizes this user code to Full ARM the site.
3 Stay ARM Authorizes this user code to arm those zones that have not been assigned a
STAY attribute.
4 Force ARM Authorizes this user code to arm with open zones for which a FORCE attribute
has been assigned.
5 Log Authorizes this user code to access log events.
6 Bypass Authorizes this user code to bypass zones in armed site.
DEFAULT : Disarm, Full ARM, Stay ARM, Force ARM, LOG, BYPASS
16 CA60Plus control panel Installation manual
2. Zone programming
ADDRESS 21 ZONE 1 TYPE AND ATTRIBUTES
This address includes two submenus. The zone type is set in the first one and the zone
attributes are set in the second one. Switching over from one submenu to the other is
done with the help of the arrows.
ZONE 1 TYPE SUBMENU
Only one type can be selected for a given zone. Press the digital button, which corre-
sponds to the number of the desired type. The indication is hexadecimal and is shown
in the table.
0 UNUSED The zone is not being used No light-emitting diodes light up
1 Entry/Exit Entry/exit zone Light-emitting diode 6 lights up
2 FOLLOW Follow zone Light-emitting diode 5 lights up
3 INSTANT Instant alarm zone Light-emitting diodes 5 and 6 light up
4 24h Burglar 24-hour instant alarm zone Light-emitting diode 4 light up
5 FIRE 24-hour fire zone Light-emitting diodes 4 and 6 light up
6 PANIC 24-hour panic zone Light-emitting diodes 4 and 5 light up
7 TAMPER 24-hour tamper zone Light-emitting diodes 4, 5 and 6 lights up
8 MEDICAL 24-hour medical zone Light-emitting diode 3 light up
9 SWITCH 24-hour zone switch type Light-emitting diodes 3 and 6 lights up
ZONE 1 ATTRIBUTE SUBMENU
Any one zone can be assigned more than one attribute. Pressing a digital button with
the respective number will activate a given attribute. The light-emitting diode with the
number of the pressed digit will light up to indicate the selection. Pressing the same digit
again will inactivate it and the light-emitting diode with the number of the pressed digit
will go out. At the end of this procedure, the light-emitting diodes, which correspond to
the assigned attributes only, will remain lit.
1 AUTOBYPASS Authorization for automatic Bypassing the zone after reaching the number of
activations per armed mode as set in address 27.
2 BYPASS Authorization to Bypass a zone.
3 STAY The zone is not going to be armed in the STAY mode.
4 FORCE The zone will be bypassed if active when a Force type arm command is set.
5 DOUBLE DOUBLE KNOCK type zone
6 CHIME CHIME mode
DEFAULT : Entry/Exit type with BYPASS and CHIME attributes
Table 1 shows the types of zones and their attributes.
ADDRESS 20 TYPE OF ZONE BALANCING
The type of zone balancing is selected at this address. Every consecutive pressing of a
digital button alternatively changes the type of balancing. Display indications are given
in the table.
ALARM One balancing resistor. Light-emitting diodes 1 to 6 light up.
DUAL Two balancing resistors. Light-emitting diodes 1 to 6 do not light up.
DEFAULT : ALARM
CA60Plus control panel Installation manual 17
ADDRESS 22 ZONE 2 TYPE AND ATTRIBUTES
The programming is the same as for Address 21
DEFAULT : FOLLOW type with BYPASS and STAY attributes
ADDRESS 23 ZONE 3 TYPE AND ATTRIBUTES
The programming is the same as for Address 21
DEFAULT : INSTANT type with BYPASS and STAY attributes
ADDRESS 24 ZONE 4 TYPE AND ATTRIBUTES
The programming is the same as for Address 21
DEFAULT : INSTANT type with BYPASS and STAY attributes
ADDRESS 25 ZONE 5 TYPE AND ATTRIBUTES
The programming is the same as for Address 21
DEFAULT : PANIC type
ADDRESS 26 ZONE 6 TYPE AND ATTRIBUTES
The programming is the same as for Address 21.
DEFAULT : TAMPER type
ADDRESS 29 ENABLING AND DISABLING FOR INSTANT TYPE ZONES
Intrusion in any Instant type zone during exit time is allowed or disallowed at
this address. Enabling this working mode would reduce the probability for a
false alarm signal to be triggered off by mistake on behalf of the user.
INSTANT ENABLE NO Disallows intrusion in INSTANT type zones during exit type.
Light-emitting diodes 1 to 6 do not light up.
YES Allows intrusion in INSTANT type zones during exit type. Light-emitting
diodes 1 to 6 light up.
DEFAULT : NO
ADDRESS 27 NUMBER OF ACTIVATIONS PER ZONE FOR AUTO BYPASS
MODE
The number of activations in one arm mode, which have to be accomplished for
a zone with an assigned AUTO/BPS parameter, are entered at this address.
After reaching the indicated number of activations, the respective zone will be
automatically bypassed.
When disarmed and then again armed the respective zone will remain armed.
DEFAULT : 6
ADDRESS 28 NUMBER OF ACTIVATIONS IN ZONE 4 IN PULSE COUNT
MODE
The number of pulses for zone 4 in Pulse Count mode are entered at this address.
Values of between 0 and 9 pulses can be entered here. The 0 value blocks the
Pulse Count mode and the zone can then function with the regular time for
detecting activation.
The working algorithm for zone 4 in Pulse Count mode has been clarified in
Item 7 on page 8.
DEFAULT : 0
18 CA60Plus control panel Installation manual
INSTANT type An alarm zone which is active only when the site is armed. The zone operates
instantaneously and activates the programmable ALARM type outputs, the
SIREN output and the communicator.
The MEMORY light-emitting diode and the light-emitting diode for the respective
zone will light up when activated in armed mode. After disarming, these light-emitting
diodes will continue to be lit until the user code is entered or until the next arming.
Where the system is unarmed, the activation of the zone is indicated by the
blinking of the respective light-emitting diode for the zone for the time that the
zone remains open.
Violation of INSTANT type zones during Exit Time can be authorized at Address 29.
FIRE type Allows connecting 12 V fire alert sensors to the system. These should avail of
a normally closed relay output in inactive status.
Any activation of the zone will trigger off the SIREN output, the programmable
FIRE type outputs and the station communicator.
Activating this zone will cause the MEMORY light-emitting diode to blink and
the activated zone light-emitting diode to light up continuously, irrespective of
the working mode of the station.
The indication of the memory can be deleted by entering a legal user code,
manager code or during the next arming.
PANIC type Silent Panic only the programmable PANIC type outputs and the station
communicator can be activated. The respective light-emitting diode blinks while
the zone is active. There is no memory indication. After a legal user code is
entered, the MEMORY light-emitting diode and the activated zone light-emitting
diode both light up continuously.
Sound Panic the SIREN output, the programmable PANIC type outputs and
the station communicator are activated. The sirens are instantaneously activated
irrespective of the programmed time delay. Activating the zone will cause the
MEMORY light-emitting diode and the activated zone light-emitting diode to
light up continuously.
The indication of the memory can be deleted by entering a legal user code, a
manager code or during the next arming.
24h Burglar type An alarm zone, which is active, irrespective of the arm mode. The zone operates
instantaneously and activates the programmable ALARM type output, the SIREN
output and the communicator.
The MEMORY light-emitting diode and the light-emitting diode for the respec-
tive zone will light up when activated. After entering a legal code these light-
emitting diodes continue to be lit until the user code is entered a second time or
until the next arming.
Table 1. Types of zones and their attributes
Entry/Exit type Provides time to arm and disarm the site. After arming, the sensor, which was
triggered off in this zone, will not sound an alarm until the programmed EXIT
TIME expires.
No violation of the zone when in armed mode will sound an alarm before the
programmed ENTRY TIME expires.
A sound signal is activated from the keyboard buzzer during entry and exit time.
FOLLOW type An alarm zone which is active only when the site is armed. The zone operates
instantaneously and activates the programmable ALARM type outputs, the
SIREN output and the communicator.
Activating the zone during entry or exit time does not cause an alarm event.
The MEMORY light-emitting diode and the light-emitting diode for the respective
zone will light up when activated in armed mode. After disarming, these light-emitting
diodes will continue to be lit until the user code is entered or until the next arming.
Where the system is unarmed, the activation of the zone is indicated by the
blinking of the respective light-emitting diode for the zone for the time that the
zone remains open.
CA60Plus control panel Installation manual 19
SWITCH type Where this zone type is assigned, the respective panel input is used to transmit
the arming and disarming signal with the help of a keyswitch.
Each pulse at the input changes the system arm mode alternatively.
Arming is only possible in Full Arm mode. Arming will be anticipated only
when the system is ready all zones are inactive.
AUTOBYPASS attribute Assigning this attribute to the respective zone enables automatic bypass in Armed
mode.
The zone will be automatically bypassed following the number of activations
indicated at Address 27 during one single arming.
Any arming will nullify the assigned number of activations of the previous arming.
This attribute is valid for the following zone types: Entry/Exit, Follow,
I nstant, 24h Burglar
BYPASS attribute Assigning this attribute to the respective zone will authorize bypass of the zone
on behalf of the system user or manager.
This attribute is valid for the following zone types: Entry/Exit, Follow,
I nstant, 24h Burglar, Fire, Panic, Tamper, Medical, Keyswitch
STAY attribute Assigning this attribute to the respective zone will authorize the respective Stay
mode zone arming.
This attribute is valid for the following zone types: Entry/Exit, Follow,
I nstant, 24h Burglar
FORCE attribute Assigning this attribute to the respective zone authorizes automatic bypass of
the zone when in Force arm mode.
This attribute is valid for the following zone types: Entry/Exit, Follow,
I nstant, 24h Burglar, Fire, Panic, Tamper, Medical
DOUBLE attribute Assigning this attribute to the respective zone authorizes DoubleKnock mode
performance in the zone.
A 3-min. time interval starts when the sensor in the zone is activated for the first
time in armed mode. An alarm event is registered should a second sensor
activation be recorded within this interval in the same or another zone.
An alarm event will also be registered if no zone is restored within 15 seconds
of the first activation of the zone sensor.
This attribute is valid for the following zone types: Entry/Exit, Follow, I n-
stant, 24h Burglar
CHIME attribute Activating a disarmed zone for which this attribute has been assigned will sound
a specific signal from the keyboards.
This attribute is valid for the following zone types: Entry/Exit, Follow, I n-
stant, 24h Burglar, Fire, Panic, Tamper, Medical, Keyswitch
Table 1. Types of zones and their attributes
MEDICAL type Assigning this zone type will set the programmable MEDICAL type outputs
active and will start the communicator. The activated zone light-emitting diode
will light up irrespective of the system status. The indication of the memory can
be deleted by entering a legal user code, manager code or during the next arming.
TAMPER type Activating this zone type triggers off the SIREN output, the programmable
TAMPER type outputs and the station communicator. Any activation of the
zone would trigger off a sound signal from the keyboard buzzer where the site
has been disarmed and the TAMPER siren output has been programmed as
SILENT.
The TAMPER light-emitting diode and the light-emitting diode for the respec-
tive activated zone will permanently light up continuously when the zone is
activated. The indication of the memory can be deleted by entering a legal
user code or manager code. A continuously open TAMPER is indicated by a
blinking TAMPER light-emitting diode.
20 CA60Plus control panel Installation manual
3. Programming the PGM and SIREN programmable outputs
ADDRESS 31 PGM1 PROGRAMMABLE OUTPUT
The events, which activate the programmable output, are programmed at this
address.
An arbitrary combination of events, which activate the programmable output, is
allowed. The output is activated upon the occurrence of any of the programmed
events and is restored when all programmed events are discarded.
Press a digital button, which corresponds, to a given parameter. The parameter
will have been selected when the light-emitting diode on the display with the
respective number lights up.
To switch from one parameter group over to another use the arrows.
FIRST GROUP PGM1 PARAMETERS
1 ALARM It is activated when Entry\Exit, Follow and Instant type zones are violated while
the system is in armed mode, or when the 24h Burglar type zone, irrespective of
the arm mode, is violated. Output is restored after a legal user code is entered
or following an interval of 1 min.
2 PANIC It is activated when the PANIC type zone is triggered or when PANIC is triggered
from the keyboard. Output is restored after a legal code is entered.
3 TAMPER It is activated when TAMPER is triggered off in any zone, when a TAMPER
type zone is triggered off or when TAMPER is triggered from the keyboard,
irrespective of the arm mode. It is restored after activation is discarded.
4 FIRE It is activated when a FIRE type zone is triggered. It is restored after a legal
code is entered.
5 FIRE RST It is activated for 4 sec. after a legal code is entered.
6 N/OFF It is activated by a command to arm. Output is restored after disarming.
SECOND GROUP PGM1 PARAMETERS
1 MEDICAL It is activated when a MEDICAL type zone is triggered. Output is restored
after all MEDICAL type zones are restored.
2 PS/Bypass It is activated right after a zone has been designated to be bypassed or when the
zone has been assigned a Stay and Instant type arming. Output is restored after
disarming.
3 AC LOSS It is activated when there is a loss of the 220 V mains supply. ! If a delay for
the indication of the mains supply loss has been set (at Address 47), the
output shall be activated 30 minutes after supply loss! Output is restored
after the mains supply is restored.
4 BAT LOW It is activated when the battery voltage falls below 11 V, in case of damage to
the battery (BATT) fuse or if the battery is missing. It is restored after the level
of battery charge reaches a value greater than 12.5 V.
5 FUSE/NO TEL It is activated when a fault occurs in any of the AUX or PGM fuses, and/or
when a fault occurs in telephone line. It passes into inactive state when the fuse
and telephone line is restored.
6 POL +/- This attribute helps select the active level of the output. When - is set (the
light-emitting diode is not lit) the active level is 0 V. At + the active level at the
output is 12 V.
DEFAULT : ON/OFF, POL +
CA60Plus control panel Installation manual 21
ADDRESS 32 PGM2 PROGRAMMABLE OUTPUT
The programming is the same as for Address 31
DEFAULT : ALARM, TAMPER, POL +
ADDRESS 33 PGM3 PROGRAMMABLE OUTPUT
The programming is the same as for Address 31
DEFAULT : AC LOSS, BAT LOW, FUSE/NO TEL, POL +
ADDRESS 34 PROGRAMMABLE SIREN OUTPUT
The SIREN output can be activated by six events. The active level of this
output is low (0 V) and cannot be programmed.
An arbitrary combination of events is allowed to activate this output. It is re-
stored after bell time expires, which can be programmed at Address 42, ex-
pires.
ALARM It is activated when Entry\Exit, Follow and Instant type zones are violated while
the system is in armed mode, or when the 24h Burglar type zone, irrespective of
the arm mode, is violated. The output becomes inactive when a legal user or
manager code is entered or after bell time expires.
TAMPER It is activated when TAMPER is triggered off in any zone or when a TAMPER
type zone is triggered, irrespective of whether the site is armed or not. In case
the event activating the siren output has not been selected, the keyboards shall
emit a sound signal when TAMPER is triggered off. Output becomes inactive
when a legal user or manager code are entered or after the bell time, assigned
at Address 42, expires.
PANIC It is activated when the PANIC type zone is triggered or when PANIC is triggered
from the keyboard. Output becomes inactive when a legal user code is entered
or after the bell time, assigned at Address 42, expires.
FIRE/ALW A sequence of impulses is activated (1 second on, 1 second off) where the
FIRE type zone is triggered. Output becomes inactive when a legal user code is
entered. This event always activates the SIREN output and cannot be
cancelled.
ON SQUAWK It is singly activated for 1 second at the command to arm.
OFF SQUAWK It is activated twice for 1 second in a 1 second interval upon a disarm command.
DEFAULT : ALARM, PANIC, TAMPER, FIRE/ALW
22 CA60Plus control panel Installation manual
ADDRESS 45 SETTING THE DATE
SET DATE The date and month are set (DD.MM). The indication is hexadecimal and the
digits are displayed one by one. To view the date, the digits can be browsed with
the help of the arrows.
DEFAULT : 01.01
ADDRESS 42 PROGRAMMING BELL TIME
BELL TIME Duration is set for the bell time of the sirens. A double-digit figure between 0
and 99 minutes is entered. For a time interval of less than 10 seconds, the first
digit must be 0.
The indication is hexadecimal and the digits are displayed one by one. To view
the introduced data, the digits can be browsed with the help of the arrows.
DEFAULT : 3 minutes
ADDRESS 41 PROGRAMMING ENTRY TIME
ENTRY TIME Entry time is assigned to Entry/Exit type zones. A double-digit figure between 1
and 99 seconds is entered. For a time interval of less than 10 seconds, the first
digit must be 0.
The indication is hexadecimal and the digits are displayed one by one. To view
the introduced data, the digits can be browsed with the help of the arrows.
DEFAULT : 15 seconds
4. Time periods
ADDRESS 40 PROGRAMMING EXIT TIME
EXIT TIME Exit time is assigned to Entry/Exit type zones. A double-digit figure between 1
and 99 seconds is entered. For an interval of time, less than 10 seconds, the first
digit must be 0.
The indication is hexadecimal and the digits are displayed one by one. To view
the introduced data, the digits can be browsed with the help of the arrows.
DEFAULT : 45 seconds
ADDRESS 44 SETTING THE BUILT-IN CLOCK
SET CLOCK The hours and minutes are set (HH:MM). The indication is hexadecimal and
the digits are displayed one by one. To view the clock, the digits can be browsed
with the help of the arrows.
DEFAULT : 00:00 hours
ADDRESS 43 PROGRAMMING BELL DELAY TIME
BELL DELAY Delay is set for initiating the bell time of the sirens. A double-digit figure between
0 and 99 seconds is entered. For a time interval of less than 10 seconds, the first
digit must be 0.
The indication is hexadecimal and the digits are displayed one by one. To view
the introduced data, the digits can be browsed with the help of the arrows.
DEFAULT : 0 seconds
CA60Plus control panel Installation manual 23
ADDRESS 47 220 V AC POWER SUPPLY FAILURE INDICATION DELAY
AC DELAY NO Disables 30 minutes indication delay for 220 V power supply failure in
keyboards and message transmission via digital communicator.
Light-emitting diodes 1 to 6 do not light up.
YES Enables 30 minutes delay indication for 220 V power supply failure in
keyboards and message transmission via digital communicator.
Light-emitting diodes 1 to 6 light up.
DEFAULT : NO
ADDRESS 46 TELEPHONE LINE FAILURE INDICATION DELAY
LF DELAY A delay of 0 to 99 minutes is set prior to indication of a telephone line failure
(). The indication has a hexadecimal expression. Two digits are entered.
When a period is less than 10 minutes the first digit introduced must be
0. If no indication of a dead telephone line is needed, 00 is entered.
DEFAULT : 00 minutes
ADDRESS 48 FIRE SIGNAL DURATION
The duration of the alarm signal for a FIRE event is selected at this address.
Programming this address affects the performance of the programmable SIREN
output.
Every click of a digital button alternatively changes the type of duration of the
sound signal. The display indication is shown in the table.
ENABLED The FIRE signal duration is set at address 42 BELL TIME. The 1 to 6 LEDs
light up.
DISABLED There is a FIRE alarm signal until a valid system user or master user code is
introduced. The 1 to 6 LEDs do not light up.
DEFAULT : DISABLED
ADDRESS 49 TAMPER ALARM SIGNAL
A sound alarm signal is enabled or disabled at this address for a TAMPER
event when the system is not armed. Programming this address will not affect
the TAMPER signal when the system is in armed mode. Programming this
address will affect the performance of the programmable SIREN output.
Every click of a digital button alternatively changes the enabled / disabled
status. The display indication is shown in the table.
ENABLED Enabled sound alarm signal for TAMPER event, when the system is not armed.
The 1 to 6 LEDs light up.
DISABLED Disabled sound alarm signal for TAMPER event, when the system is not armed.
A TAMPER event is indicated by an interrupted sound signal emitted by the
system keyboard. The 1 to 6 LEDs do not light up.
DEFAULT : ENABLED
24 CA60Plus control panel Installation manual
5. Engineer parameters
ADDRESS 53 RESTORING DEFAULT MANAGER CODE (PARTIAL
SOFTWARE RESET)
DEFAULT Restoration of the default manager code. Buttons 1, 2, 3, 4, 5, 6 are pressed in
MANAGER succession and confirmed with the ENTER button.
CODE The station restores the default 0000 manager user code.
ADDRESS 50 ENGINEER CODE CHANGE
ENGINEER CODE A new access code to the alarm station engineer parameters can be assigned at
this address. The light-emitting diodes 3, 4, 5 and 6 on the keypad display light
up. These go out one by one as the new code is entered. The new code has to
be entered a second time.
DEFAULT : 7777
ADDRESS 51 BLOCKING THE HARDWARE RESET
Disables or enables the hardware RESET of the alarm station. Specialized
service is required where the hardware RESET is disabled and the en-
gineer code is obscure.
NO Hardware RESET is disabled.
Light-emitting diodes 1 to 6 do not light up.
YES Hardware RESET is enabled.
Light-emitting diodes 1 to 6 light up.
DEFAULT : YES
ADDRESS 52 RESTORING DEFAULT PARAMETERS (SOFTWARE RESET)
DEFAULT Restoration of default settings of the station. The buttons 1, 2, 3, 4, 5, 6 are
SETTINGS pressed in succession and confirmed with the ENTER button.
ADDRESS 54 AUTHORITY TO ARM USING A ONE PUSH-BUTTON (QUICK
ARM)
QUICK NO Arming disabled without legal user code.
ARM Light-emitting diodes 1 to 6 do not light up.
ENABLE YES Arming enabled without legal user code.
Light-emitting diodes 1 to 6 light up.
DEFAULT : YES
ADDRESS 55 AUTHORITY CODE DURING AMBUSH (AMBUSH CODE)
ENABLE NO Disabled ambush code.
AMBUSH Light-emitting diodes 1 to 6 do not light up.
CODE YES Enabled ambush code. The code is made up by adding 1 to a legal user
code. There is no carrying over for codes ending in the figure 9. For example,
the ambush code for 1234 is 1235, and for 9999 it is 9990.
Light-emitting diodes 1 to 6 light up.
DEFAULT : YES
CA60Plus control panel Installation manual 25
ADDRESS 57 TECHNICAL TROUBLE INDICATION MASK
The mask for sound indication from the keyboard in Technical Trouble mode is
assigned at this address.
The mask for sound indication from the keyboard in Technical Trouble mode is
assigned at this address.
Only those light-emitting diodes whose numbers correspond to technical prob-
lems for which sound indications are available will light up on the display at the
end of the procedure.
1 AC LOST Loss of 220 V mains supply.
2 BATT LOW Drop in battery charge, no battery or burnt out F1 battery fuse.
3 FUSE BLOWN Burnt out PGM fuse.
4 NO TEL LINE Loss of telephone line.
5 COMM ERROR Central station communication failure.
6 TAMPER Activated TAMPER within the system.
DEFAULT : AC LOST, BATT LOW, FUSE BLOWN, NO TEL LINE, COMM ERROR, TAMPER
ADDRESS 56 ENABLED KEYBOARD BLOCKING IN CASE OF ACCESS
CODE ERROR
ENABLE NO Disables keyboard blocking in case of access code mistake.
KBD Light-emitting diodes 1 to 6 do not light up.
BLOCK YES Enables keyboard blocking for 30 sec. following the triple introduction in
sequence of a false code. Light-emitting diodes 1 to 6 light up.
DEFAULT : NO
26 CA60Plus control panel Installation manual
6. Communicator parameters
The parameters of the built-in digital communicator are programmed at this
group of addresses.
Delete the queue of events to be sent to Address 93 by single pressing the 0
button before configuring communicator parameters.
ADDRESS 62 ENTERING PROTOCOL 1 NUMBER FOR THE
COMMUNICATOR
PROTOCOL 1 Enter central station No. 1 protocol number from the attached table. Valid are
the symbols from 0 to 2, where:
[0] User protocol dialer transmits a melody sound signal upon occurrence of
an event listed on the bottom on page 26
[1] ADEMCO CONTACT ID see table with codes in Supplement B
[2] SIA (Level 1) - see table with codes in Supplement B
DEFAULT : 1
ADDRESS 60 ENTERING TELEPHONE NUMBER 1 FOR THE
COMMUNICATOR
Tel No 1 A telephone number is assigned for communicating with central station - No. 1.
The indication is hexadecimal. The telephone number must not exceed 16
characters, including the pulse dialer (ON and 0 buttons), tone dialer (ON
and 1 buttons), pause (ON and 2 buttons), wait DIAL tone (ON and 3
buttons) and delete telephone number (ON and 5 buttons) symbols.
Dialing has been assigned a default tone signal
DEFAULT : there is no number entered
ADDRESS 61 ENTERING PANEL IDENTIFICATION NUMBER 1
PANEL ID 1 Identification number for central station No. 1. Four digits are entered. Valid
are symbols 0 to 9, A to F (SIA) and B to F (ADEMCO)
DEFAULT : 9999
ADDRESS 64 ENTERING PANEL IDENTIFICATION NUMBER 2
PANEL ID 2 Identification number for central station No. 2. Four digits are entered. Valid
are symbols 0 to 9, A to F (SIA) and B to F (ADEMCO)
DEFAULT : 9999
ADDRESS 63 ENTERING TELEPHONE NUMBER 2 FOR THE
COMMUNICATOR
Tel No 2 A telephone number is assigned for communicating with central station No. 2.
The indication is hexadecimal. The telephone number must not exceed 16
characters, including the pulse dialer (ON and 0 buttons), tone dialer (ON
and 1 buttons), pause (ON and 2 buttons), wait DIAL tone (ON and 3
buttons) and delete telephone number (ON and 5 buttons) symbols.
Dialing has been assigned a default tone signal.
DEFAULT : there is no number entered
CA60Plus control panel Installation manual 27
ADDRESS 66 WAIT DIAL TONE
WAIT DIAL TONE NO Disable DIAL signal test.
Light-emitting diodes 1 to 6 do not light up.
YES Enable DIAL signal test
Light-emitting diodes 1 to 6 light up.
DEFAULT : YES
ADDRESS 68 TEST MESSAGE TRANSMITTING PERIOD
TEST PERIOD Duration of transmission of test message in days (DD) is entered. The indication
is hexadecimal. Two digits must be entered. When entering a period
shorter than 10 days the first digit must be 0.
DEFAULT : 01 day
ADDRESS 65 ENTERING PROTOCOL 2 NUMBER FOR THE
COMMUNICATOR
PROTOCOL2 Enter central station No. 2 protocol number from the attached table. Valid are
the symbols from 0 to 2, where:
[0] User protocol dialer transmits a melody sound signal upon occurrence of
an event listed on the bottom on page 2618020xxx
[1] ADEMCO CONTACT ID see table with codes in Supplement B
[2] SIA (Level 1) - see table with codes in Supplement B
DEFAULT : 1
ADDRESS 67 SETTING TEST TIME FOR SENDING MESSAGE
TEST TIME Time of sending test message to central station is entered . Hours and minutes
are entered (HH:MM). The indication is hexadecimal.
DEFAULT : 00:05 hours
ADDRESS 69 TYPES OF MESSAGE TRANSMITTED FROM THE DIGITAL
COMMUNICATOR *
The messages from both telephone numbers to the telephone monitoring central station, as well as the
report algorithm, are programmed at this address. The following report options can be set:
1. Message report from at least one of the two telephone numbers Alternative report.
2. Independent message report to both telephone numbers Split report.
3. Message report from one telephone number, which is also duplicated at the second Both report.
The address consists of two identical submenus, structured as shown below. The first submenu is for
programming the streams of messages to the first telephone number, entered at address 60. The second
submenu is for programming the streams of messages to the second telephone number, entered respectively
at address 63. Switching over between the two submenus can be done with the help of the arrows.
Where message streams are marked only for the first telephone number, the report algorithm to be
used is Alternative report. There should be no marked message streams for the second telephone number.
Where the same message streams for both telephone numbers are marked, the report algorithm to be
used is Both report.
Where different message streams for both telephone numbers are marked, the report algorithm to be
used is Split report.
Both and Split reports can be jointly used.
The digital buttons 1 to 6 are used for programming. Pressing them each time will alternatively
change the status of the respective message type report (LED lights up) or no report (LED does not light
28 CA60Plus control panel Installation manual
* User protocol transmitted messages are ALARM, FIRE, PANIC, TAMPER, MEDICAL and
manually transmitted TEST signal. These messages are not programmable and are transmitted by
one and the same sound signal in the telephone line.
up). At the end of the procedure only those LEDs, which correspond to the designated for report mes-
sages, should remain lit up on the display.
1 ALARM ALARM and TAMPER type messages are transmitted.
2 PANIC PANIC type messages or entered assault code are transmitted.
3 FIRE FIRE and TAMPER type messages are transmitted.
4 ON/OFF+BPS BYPASS, ON/OFF type messages and engineer programming input are
transmitted.
5 MEDICAL MEDICAL type messages are transmitted.
6 TROUBLE TROUBLE and TEST type messages are transmitted.
DEFAULT : 1, 2, 3, 4, 5, 6 for the first telephone number. There are no marked streams for the second telephone
number.
CA60Plus control panel Installation manual 29
ADDRESS 74 NUMBER OF RINGS
NUMBER OF The symbols 0 to 9 are used.
RINGS Up/ down loading is disabled if 0 is entered.
It is recommended this parameter does not exceed the value of 7.
DEFAULT : 7
7. Programming Up/Down Load parameters
ADDRESS 71 PERSONAL COMPUTER IDENTIFICATION NUMBER FOR UP
/ DOWN LOADING
PC ID The PC ID number for up / down loading is configured at this address. Four
digits can be introduced. Valid are symbols 0 to 9.
DEFAULT : 1234
ADDRESS 73 CALL BACK OPTION
This address enables the CALL BACK option function. Every push of the
digital button alternatively changes enabled to disabled status.
The connection fails if an allowed Call Back function is enabled during an incoming
exchange request to up / down load from a PC. The control panel selects the
number specified at Address 70 and an up / down load procedure is initiated.
The display indication on the keypad is described below.
YES The Call Back function is enabled. Light-emitting diodes 1 to 6 are lit.
NO The Call Back function is disabled. Light-emitting diodes 1 to 6 are not lit.
DEFAULT : NO
ADDRESS 72 CONTROL PANEL IDENTIFICATION NUMBER
PANEL ID The control panel up/down loading ID number is entered at this address. Four
digits can be introduced. Valid are symbols 0 to 9.
DEFAULT : 1234
ADDRESS 70 TELEPHONE NUMBER FOR UP / DOWN LOAD
PROGRAMMING
Tel No for An up / down load PC telephone number can be set at this address. The indication
Up / Down Load is hexadecimal. The maximal length must not exceed 16 characters, including
those for the pulse dialer (ON and 0 buttons), tone dialer (ON and 1 buttons),
pause (ON and 2 buttons), wait DIAL tone (ON and 3 buttons) and delete
telephone number (ON and 5 buttons) symbols.
Tone signal dialing was assigned by default.
DEFAULT : No telephone number has been entered
30 CA60Plus control panel Installation manual
ADDRESS 75 ANSWERING MACHINE FUNCTION
This address enables the Answering Machine function for up / down loading.
Every push of the digital button alternatively changes enabled to disabled status.
Priority should be given to any automatic answering devices (like FAX or
telephone answering machines), if such are connected to the telephone line.
The Answering Machine function should be enabled in such cases. During initial
income of a series of calls (rings), the CA60Plus temporizes the maximum
number of calls, set at Address 74. The automatic answering machine must be
adjusted to a fewer number of rings. If within four minutes there is another
series of incoming calls the CA60Plus shall answer the first one.
The display indication is shown in the table.
YES Enabled Answering Machine function. Light-emitting diodes 1 to 6 are lit.
NO Disabled Answering Machine function. Light-emitting diodes 1 to 6 are not lit.
DEFAULT : NO
ADDRESS 76 NUMBER OF COMMUNICATION ATTEMPTS
Assign the number of attempts to connect to the central station for telephone
monitoring and the number of repetitions of voice messages at this address that
the Control Panel will make in case of unsuccessful communication or failure to
acknowledge voice messages. The value assigned at this address is the number
of attempts to be made for each of the telephones configured at addresses 60
and 63 for the digital communicator, and at addresses 81, 82, 83 and 84 for
the voice dialer. (Example: if the assigned value is 4 and two telephone num-
bers, the number of attempts which will be made are 8 4 for each telephone
number). Any messages to the central station will have priority. The attempts to
connect to the central station will be terminated after the assigned number is
reached. Transmission of the occurred events begins via the voice dialer to the
telephones at addresses 81 to 84. The panel waits for 2 sec. after each indi-
vidual message in order to receive a message reception acknowledgement.
This is confirmed when the user presses key 9 on the telephone. The time
needed to transmit one group of voice messages, where no confirmation has
been received, is up to 1 minute. The transmission to the other telephones be-
gins after confirmation has been received from one single telephone. After the
assigned number of voice message transmissions is reached, the attempts to
transmit voice messages will be terminated. The attempts to transmit will be
renewed to the central station first, when the next transmission event occurs.
The values between 0 and 9 are permitted. The desired value is entered by
single-pressing the key of the respective figure. Where the value of 0 is en-
tered, the panel will automatically implicate the value of 4 for the central station
and the value of 2 for the voice dialer.
DEFAULT : 0
CA60Plus control panel Installation manual 31
8. VOICE DIALER PROGRAMMING PARAMETERS
ADDRESS 81 ENTERING TELEPHONE NUMBER 1 FOR THE DIALER
Tel No 1 A telephone number is assigned for communicating via voice dialer No. 1. The indication
is hexadecimal. The telephone number must not exceed 16 characters, including the pulse
dialer (ON and 0 buttons), tone dialer (ON and 1 buttons), pause (ON and 2 buttons),
wait DIAL tone (ON and 3 buttons) and delete telephone number (ON and 5 buttons)
symbols.
Dialing has been assigned a default tone signal
DEFAULT : there are no configured numbers
ADDRESS 80 RECORDING AND LISTENING TO VOICE MESSAGES
One can record and listen to messages in the voice dialer at this address. To record a
message place the REC jumper, select the number of the message by pressing the MSG key,
press and hold the PLAY key and dictate the message into the microphone immediately
when the LED lights up. Release the key. Remove the REC jumper when all messages have
been recorded. To listen to the messages connect an 8-16 ohm speaker to the SP socket.
Use the MSG key to select the number of the message, and press the PLAY key to listen the
recording.
DEFAULT : test message 8
ADDRESS 85 GROUPS OF MESSAGES FOR VOICE DIALER
TRANSMISSION
Programme the groups of message to be transmitted by the voice dialer at this
address. The possible options are 0 and 1. 0 transmits alarm messages by zones, and 1
transmits messages by events (see Supplement E).
DEFAULT : 1
ADDRESS 82 ENTERING TELEPHONE NUMBER 2 FOR THE DIALER
Tel No 2 A telephone number is assigned for communicating via voice dialer No. 2. The indication
is hexadecimal. The telephone number must not exceed 16 characters, including the pulse
dialer (ON and 0 buttons), tone dialer (ON and 1 buttons), pause (ON and 2 buttons),
wait DIAL tone (ON and 3 buttons) and delete telephone number (ON and 5 buttons)
symbols.
Dialing has been assigned a default tone signal
DEFAULT : there are no configured numbers
ADDRESS 83 ENTERING TELEPHONE NUMBER 3 FOR THE DIALER
Tel No 3 A telephone number is assigned for communicating via voice dialer No. 3. The indication
is hexadecimal. The telephone number must not exceed 16 characters, including the pulse
dialer (ON and 0 buttons), tone dialer (ON and 1 buttons), pause (ON and 2 buttons),
wait DIAL tone (ON and 3 buttons) and delete telephone number (ON and 5 buttons)
symbols.
Dialing has been assigned a default tone signal
DEFAULT : there are no configured numbers
ADDRESS 84 ENTERING TELEPHONE NUMBER 4 FOR THE DIALER
Tel No 4 A telephone number is assigned for communicating via voice dialer No. 4. The indication
is hexadecimal. The telephone number must not exceed 16 characters, including the pulse
dialer (ON and 0 buttons), tone dialer (ON and 1 buttons), pause (ON and 2 buttons),
wait DIAL tone (ON and 3 buttons) and delete telephone number (ON and 5 buttons)
symbols.
Dialing has been assigned a default tone signal
DEFAULT : there are no configured numbers
32 CA60Plus control panel Installation manual
ADDRESS 92 PGM1, PGM2, PGM3 and SIREN PANEL PROGRAMMABLE
OUTPUT TEST
OUTPUT TEST Serviceability tests of programmable outputs is carried out by pressing a numbered
1 PGM1 button which corresponds to the programmable output. The respective light-
2 PGM2 emitting diode lights up permanently and the output passes into a low level- 0 V.
3 PGM3 Pressing the button with the corresponding number a second time renders the
4 SIREN SIREN output into a high level 12 V
ADDRESS 91 KEYBOARD TEST
LED TEST Checks the serviceability of the keypad light-emitting diodes and buzzer.
9. CA60Plus test modes
ADDRESS 94 DISPLAY LOG EVENTS
DISPLAY LOG The events recorded in the power independent memory of the station can be
traced with the help of the arrows. The first event which is visualized is the last
recorded.
ADDRESS 90 WALK TEST
WALK TEST Enables functional test of station zones. The respective light-emitting diode blinks
while the zone is activated in this mode. As long as there is an open tamper zone
its respective light-emitting diode remains permanently lit.
ADDRESS 93 DISPLAY COMMUNICATOR
DISPLAY The performance of the communicator can be directly monitored at this address.
COMMUNICATOR The ON button causes test transmission from the communicator to the central
station and from the voice dialer to assigned telephone numbers. The 0 button
aborts any running communication and deletes the queue of events to be sent.
The CLEAR button exits Address 93. The meaning of the light-emit g diodes is
as follows:
ZONE1: blinks searching for a dial free tin line / free signal
permanently lit a dial signal has been identified
ZONE2: blinks dialing the telephone number
permanently lit telephone number has been dialed
ZONE3: blinks expecting a HAND SHAKE from central station
permanently lit the necessary handshake signal has been identi-
fied
ZONE4: blinks transmitting data to central station
permanently lit current data has been transmitted
ZONE5: blinks expecting confirmation from central station
permanently lit transmitted data has been successfully received
ZONE6: permanently lit communication process has been completed and
all data has been successfully transmitted to the central station
After communication has been successfully completed the keyboard emits a
sound signal.
CA60Plus control panel Installation manual 33
ADDRESS 95 DISPLAY UDL PROCESS
UDL/ The Up / Down Load process can be directly monitored at this address.
Direct UDL A single click on the 0 button aborts current communication.
A single click on the ON button can start manual communication. This will
ignore the counter for incoming calls and will directly proceed on to step 2.
Address 95 is exited with the help of the CLEAR button. The meaning of the
light-emitting diodes is as follows:
ZONE1: blinks each blink indicates one received call
permanently lit the number of designated at Address 74 calls
have been received
ZONE2: blinks - a CALL BACK process
permanently lit CALL BACK completed
ZONE3: blinks process of detecting a carrier
permanently lit established connection to PC
ZONE4: blinks receiving data from central station
permanently lit data pack received
ZONE5: blinks transmitting data to central station
permanently lit data pack transmitted
ZONE6: permanently lit up / down loading completed
ADDRESS 96 DIGITAL COMMUNICATOR HARDWARE TEST
MANUFACTURER A step by step test of the hardware of the digital communicator can be done at
TEST this address. A light-emitting diode on the keypad lights up to visualize every
step. There is no time limitation for the steps.
!During the test the digital communicator is blocked and disabled!
The first step of the digital communicator hardware test automatically begins
after Address 96 is entered. Transition between the various steps can be
accomplished with the respective digital buttons 1 to 5 or with the help of the
arrows. The light-emitting diodes on the keypad indicate the number of the
current step:
ZONE1: The built-in relay is activated at this step. As a result the telephone
line, connected to terminals A and B, is discontinued from terminals
A1 and B1, where the local telephone device or some other
apparatus using the telephone line, should be connected. During
this step the telephone line voltage should be measured at terminals
A and B (to read usually between 40 and 60 V DC) and at terminals
A1 and B1 (to read 0 V DC).
ZONE2: The digital communicator has engaged the telephone line here. The
voltage measured at terminals A and B should read between 7.5 V
DC and 10.5 V DC. At the same time the built-in Dial Tone Detector
is also activated- a detector for the DIAL signal.
ZONE3: The digital communicator attributes low frequency to the telephone
line.
ZONE4: The digital communicator attributes high frequency to the telephone
line.
ZONE5: The digital communicator attributes a DTMF signal.
34 CA60Plus control panel Installation manual
ADDRESS 97 ADJUSTING THE BUILT-IN CLOCK
Any adjustments to the built-in clock can be done at this address. Digits between 00
and 99 are permissible. Where no adjustment is required, the value of 50 must be entered.
A respective value, which is greater than 50, is to be entered where the clock runs slow,
and lesser than 50 where it runs quick.
Each unit of value will adjust the clock by 5 seconds per month as speed or lag. This time
adjustment is evenly allocated within the month.
Recommended methodology for calculating the necessary correction value:
The days necessary for 1 minutes time deflection of the built-in clock is set here. The
correction is calculated by the formula:
360/days,
where days are the days specified above. The whole of the result is taken under
consideration. The figure can be rounded up to the larger digit. The result obtained is
added to the current value at this address in case of a lag of the clock, or is subtracted
from the current value at this address in case the built-in clock runs fast.
Example of calculating the adjustment: Suppose the clock lags by 1 minute per 85
days. The result after applying the quoted formula is 4.2. Where the current value at
this address is 50, the corrective factor of 54 needs to be introduced.
DEFAULT : 50
CA60Plus control panel Installation manual 35
The LED61 Keyboard completely overlaps all technical specifications of the LED60 Keyboard and is com-
patible with all software versions of the CA60Plus Control Panel. Information on connecting and configuring
the LED61 Keyboard is available in the CA60Plus Control Panel installation manual.
The light-emitting diodes are separated in two columns one for performance indication and one for zone
indication. The light-emitting diode indications correspond to those described in the User and Installation
Manuals where:
RDY light-emitting diode corresponds to READY light-emitting diode.
TRBL light-emitting diode corresponds to TROUBLE light-emitting diode.
TAMP light-emitting diode corresponds to TAMPER light-emitting diode.
BPS light-emitting diode corresponds to BYPASS light-emitting diode.
ARM light-emitting diode corresponds to ARMED light-emitting diode.
MEM light-emitting diode corresponds to MEMORY light-emitting diode.
The correspondence between the buttons on the LED60 and the LED Keypads is as follows:
DISARM button is not used. MEM button is not used.
PRG button corresponds to PROG button. CLR button corresponds to CLEAR button.
ENT button corresponds to ENTER button. ARM button corresponds to ON button.
Code arming:
Full arming <legal code> ARM and 0
Stay arming <legal code> ARM and 1
Force arming with active zone bypass <legal code> ARM and 2
Instant arming <legal code> ARM and 3
Arming without code confirmation:
Full arming ARM and 0
Stay arming ARM and 1
Force arming with active zone bypass ARM and 2
Instant arming ARM and 3
User program mode entry:
<legal user code>PROG
Manager program mode entry:
<legal manager code>PROG
Engineer program mode entry:
<legal engineer code>
Transmitting a PANIC signal from the keyboard:
By simultaneously pressing the ARM and ENT buttons
Activating a display with system technical trouble:
<legal code>ENT
Assigning hexadecimal digits for program mode parameters:
The ON button is replaced everywhere by the ARM button
A
R
M
M
E
M
CLR ENT 0
1 2 3
4 5 6
7 8 9
P
R
O
G
D
IS
A
R
M
Supplement A LED61 keyboard for CA60Plus control panel
36 CA60Plus control panel Installation manual
Supplement B Default programming table
PROGRAM MENU ADDRESS LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
MANGER ACCESS 00 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
USER CODE 1 01 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 2 02 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 3 03 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 4 04 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 5 05 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 6 06 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 7 07 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 8 08 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 9 09 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 10 10 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 11 11 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 12 12 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 13 13 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 14 14 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 15 15 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
USER CODE 16 16 DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
LOOP TYPE 20 ALARM - LED1 to LED6 light
ZONE 1 TYPE 21
ATTRIBUTS ZONE 1 AUTOBYPASS BYPASS STAY FORCE DOUBLE CHIME
ZONE 2 TYPE 22
ATTRIBUTS ZONE 2 AUTOBYPASS BYPASS STAY FORCE DOUBLE CHIME
ZONE 3 TYPE 23
ATTRIBUTS ZONE 3 AUTOBYPASS BYPASS STAY FORCE DOUBLE CHIME
ZONE 4 TYPE 24
ATTRIBUTS ZONE 4 AUTOBYPASS BYPASS STAY FORCE DOUBLE CHIME
ZONE 5 TYPE 25
ATTRIBUTS ZONE 5 AUTOBYPASS BYPASS STAY FORCE DOUBLE CHIME
ZONE 6 TYPE 26
ATTRIBUTS ZONE 6 AUTOBYPASS BYPASS STAY FORCE DOUBLE CHIME
AUTOBYPASS COUNT 27
PULSE COUNT 28
ENABLE INSTANT 29 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
PGM 1
31 ALARM PANIC TAMPER FIRE FIRE/RST ON/OFF
MEDICAL PS/bypass AC LOSS BAT LOW FUSE/NO TEL Pol+ / -
PGM 2 32 ALARM PANIC TAMPER FIRE FIRE/RST ON/OFF
MEDICAL PS/bypass AC LOSS BAT LOW FUSE/NO TEL Pol+ / -
PGM 3 33 ALARM PANIC TAMPER FIRE FIRE/RST ON/OFF
MEDICAL PS/bypass AC LOSS BAT LOW FUSE/NO TEL Pol+ / -
SIREN OUTPUT 34 ALARM PANIC TAMPER FIRE/ALW ON SQUAWK OFF SQUAWK
EXIT TIME 40
ENTRY TIME 41
BELL TIME 42
BELL DELAY 43
SET CLOCK 44
SET DATE 45
LF DELAY 46
AC DELAY 30min 47 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
FIRE DURATION 48
Until a valid user code is entered - LED1 to
LED6 do not light
Bell time at address 42 - LED1 ot LED6 light
TAMPER ALARM 49
Audible alarm signel TAMPER disabled in
Disarm mode - LED1 to LED6 do not light
Audible alarm signel TAMPER enabled in
Disarm mode - LED1 to LED6 light
ENGINEER CODE 50 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
RESET ENABLE 51 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
DEFAULT SETTINGS 52
PART. RESET 53
Press the keys f rom 1 to 6 consequently and conf irm by ENTER
Clock setting ( HH:MM). Def ault -> 00:00.
Date setting ( dd:mm). Def ault -> 01.01.
Telephone line f ault indication delay (0-99 MIN). Def ault -> 0.
Press the keys f rom 1 to 6 consequently and conf irm by ENTER
0-99 SEC. Def ault -> 45.
0-99 SEC. Def ault -> 15.
0-99 MIN. Def ault -> 3.
0-99 SECDef ault -> 0.
Number of activations (0 to 9). Def ault -> 0.
DUAL - LED1 to LED6 do not light
UNUSED \ E-E \ FOLOW \ INSTANT \ 24h \ FIRE \ PANIC \ TAMPER \ MEDICAL \ SWITCH
UNUSED \ E-E \ FOLOW \ INSTANT \ 24h \ FIRE \ PANIC \ TAMPER \ MEDICAL \ SWITCH
UNUSED \ E-E \ FOLOW \ INSTANT \ 24h \ FIRE \ PANIC \ TAMPER \ MEDICAL \ SWITCH
UNUSED \ E-E \ FOLOW \ INSTANT \ 24h \ FIRE \ PANIC \ TAMPER \ MEDICAL \ SWITCH
UNUSED \ E-E \ FOLOW \ INSTANT \ 24h \ FIRE \ PANIC \ TAMPER \ MEDICAL \ SWITCH
UNUSED \ E-E \ FOLOW \ INSTANT \ 24h \ FIRE \ PANIC \ TAMPER \ MEDICAL \ SWITCH
Number of activations (0 to 9). Def ault -> 6.
CA60Plus control panel Installation manual 37
Supplement B Default programming table
Default programming
PROGRAM MENU ADDRESS LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
QUICK ARM ENABLE 54 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
ENABLE AMBUSH COD 55
ENABLE KBD BLOCK 56 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
TROUBLE MASK 57 AC LOST BATT LOW FUSE BLOWN NO TEL LINE COMM ERROR TAMPER
TEL No 1 60
PANEL ID 1 61
PROTOCOL 1 62
TEL No 2 63
PANEL ID 2 64
PROTOCOL 2 65
WAIT DIAL TONE 66 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
TEST TIME 67
TEST PERIOD 68
69 ALARM PANIC FIRE ON/OFF+BPS MEDICAL TROUBLE
ALARM PANIC FIRE ON/OFF+BPS MEDICAL TROUBLE
TEL No PC FOR UDL 70
PC ID FOR UDL 71
PANEL ID FOR UDL 72
CALL BACK 73 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
No OF RINGS 74
ANSW. MACHINE 75 NO - LED1 to LED6 do not light YES - LED1 to LED6 light
COMM ATTEMPTS 76
VOICE DIALER PRG 80
VOICE DIALER
TEL No 1
81
VOICE DIALER
TEL No 2
82
VOICE DIALER
TEL No 3
83
VOICE DIALER
TEL No 4
84
VOICE DIALER
EVENTS
85 0 - Allarm or Tamper by zones, ambush code
1 - Allarm, Panic, Tamper, Fire, Medical,
LOST, LOW
WALK TEST 90 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
LED TEST 91
OUTPUTS TEST 92 PGM1 PGM2 PGM3 SIREN
COMMUNIC.DISPLAY 93 Dial Tone Dialing Wait HS Send Data Wait Kof f All Sent
DISPLAY LOG 94
UDL / Direct UDL 95 RING CALL BACK CURRIER RECEIVE TRANSMIT END
MANUFACTURER TEST 96 RELAY DIAL TONE LOW FREQ HIGH FREQ
CLOCK ADJUSTMENT 97
LOG f ile review
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
4 digits. Def ault -> 1234.
4 digits. Def ault -> 1234.
One digit (0 to 9). Def ault -> 7.
Records and Playback voice message into voice dialer
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
DIALER MESSAGES
A number f rom 00 to 99
From 0 to retries. Def ault -> 0, meaning 4 retries.
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
4 digits + A, B, C, D. Def ault -> 9999.
Enter the communication protocol number (0-User dialer; 1-Contact ID; 2-SIA). Def ault -> 1.
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
4 digits + A, B, C, D. Default -> 9999.
Enter the communication protocol number (0-User dialer; 1-Contact ID; 2-SIA). Def ault -> 1.
TEST report time (HH:MM). Def ault -> 00:05.
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
Max phone number length 16 symbols, pulse dialing=ON+0, DTMF dialing=ON+1,
pause=ON+2, Dial tone detect=ON+3, clear number=ON+5. Def ault -> no number.
NO - LED1 to LED6 do not light YES - LED1 to LED6 light
TEST autoreporting (DD). Default -> 1.
38 CA60Plus control panel Installation manual
Supplement B Default programming table
Default programming
User programming table with defaults
USER (X) MENU ADDRESS LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
CHANGE OWN CODE 0 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
BYPASS 1 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
DISPLAY LOG 2
CHIME 3 OFF - LED1 to LED6 do not light ON - LED1 to LED6 light
LOG f ile review
Manager programming table with defaults
MANAGER MENU ADDRESS LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
CHANGE OWN CODE 00 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
RemDisarm RemArm RemCodeAcc RemProg RemLog RemBypass
CHANGE USER 1 01 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 2 02 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 3 03 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 4 04 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 5 05 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 6 06 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 7 07 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 8 08 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 9 09 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 10 10 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 11 11 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 12 12 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 13 13 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 14 14 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 15 15 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
CHANGE USER 16 16 DIGIT 1 DIGIT 2 DIGIT 3 DIGIT 4
DISARM FULL ARM STAY ARM FORCE ARM LOG BYPASS
DISPLAY LOG 20
CHIME 30 OFF - LED1 to LED6 do not light ON - LED1 to LED6 light
BYPASS 40 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SET CLOCK 50
SET DATE 51
USER CARD LEARN 60
USER CARD DELETE 61
COMMUNIC.DISPLAY 93 Dial Tone Dialing Wait HS Send Data Wait Kof f All Sent
CLOCK ADJUSTMENT 97 A number f rom 00 to 99
User number (00 to 16) conf irmed by ENTER
LOG f ile review
Clock setting ( HH:MM)
Date setting ( dd:mm)
User number (00 to 16)
CA60Plus control panel Installation manual 39
Coding recordings in log events
Log events can be viewed at Ad-
dress 94 of the engineer program-
ming.
In order to view a previous event
press the button. In order to
view a next event press the but-
ton. To view additional informa-
tion (xx is the user code or event
zone number) press ENTER. Sin-
gle click the ENTER button to re-
turn to the list of events.
Recorded events can be viewed
with the help of the table, which
shows message coding within the
system and LED keypad indica-
tion. All possible combinations of
keypad light-emitting diodes, the
meaning of each combination and
the decoding of the specifying re-
cording xx for the number of the
user code or zone, are shown for
ease in reading log event record-
ings.
Supplement C Additional information
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Burglary Alarm type event in xx zone
Burglary Alarm type restoring event in xx zone
Fire type alarm event in xx zone
Fire type restoring event in xx zone
Panic type alarm event in xx zone
Panic type restoring event in xx zone
Tamper type alarm event in xx zone
Tamper type restoring event in xx zone
Medical type alarm event in xx zone
Medical type restoring event in xx zone
Burglary Alarm type xx zone bypass
Burglary Alarm type xx zone bypass restoring
Fire type xx zone bypass
Fire type xx zone bypass restoring
Panic type xx zone bypass
Panic type xx zone bypass restoring
Tamper type xx zone bypass
Tamper type xx zone bypass restoring
Medical type xx zone bypass
Medical type xx zone bypass restoring
Disarm by xx user
Remote disarming by xx user
Disarming by key-switch in xx zone
Arming by xx user
Remote arming by xx user
Arming by key-switch in xx zone
Quick arm type arming
Program mode entry
Program mode exit
Introducing ambush code by xx user
Telephone line failure
Recovery of faulty telephone line
Unsuccessful communication
Periodic test message communication
Digital communicator manual test
Fuse blown
Restored fuse
System default RESET
Loss of 220 V AC power supply
Restored 220 V AC power supply
Low battery charge level
Restored battery charge level
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
40 CA60Plus control panel Installation manual
Supplement C Additional information
Table of protocol Contact ID transmitted codes from CA60Plus
Code
100 Medical alarm Medical alarm
110 Fire alarm Fire alarm
120 Panic alarm Panic alarm
121 Duress code Code introduced under duress
130 Burglary alarm Alarm
137 Tamper alarm Tamper alarm
300 System trouble Trouble in the system
301 AC Loss No 220 V power supply
305 System RESET System parameters default reset
311 Battery missing No battery
351 Teleco Fail Telephone line failure
354 Failure to communicate Communication error
401 Open/Close by user Arming/Disarming by user
407 Remote Arm/Disarm Remote Arming/Disarming
408 Quick arm Quick arming (no code)
409 Keyswitch Open/Close Arming/Disarming from key-switch
571 Fire bypass Bypassing a FIRE type zone
572 24 h zone bypass Bypassing a 24 h Burglary type zone
573 Burglary bypass Bypassing an Entry/Exit, Follow or Instant type zone
601 Manual TEST report Manual TEST signal
602 Periodic TEST report Periodic TEST signal
627 Program mode entry Engineer programming mode entry
628 Program mode exit Engineer programming mode exit
Meaning
Default code passwords:
Manager code - 0000
User code 1 - 1111 - all rights
User code 2 - **** - all rights
User code 3 - **** - all rights
User code 4 - **** - all rights
User code 5 - **** - all rights
User code 6 - **** - all rights
User code 7 - **** - all rights
User code 8 - **** - all rights
User code 9 - **** - all rights
User code 10 - **** - all rights
User code 11 - **** - all rights
User code 12 - **** - all rights
User code 13 - **** - all rights
User code 14 - **** - all rights
User code 15 - **** - all rights
User code 16 - **** - all rights
Engineer code - 7777
**** - no code combination
Hexadecimal table
Key: - lights O - not light.
The expression ON and 1 means pressing the ON and 1 buttons in succession.
Value Status LED3..6 Keys
LED 3 LED 4 LED 5 LED 6 Combination
0 0
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
A ON and 0
B ON and 1
C ON and 2
D ON and 3
E ON and 4
F ON and 5
CA60Plus control panel Installation manual 41
Table of protocol SIA Level 1 transmitted codes from CA60Plus
Code
AR AC Restore Restore 220V power supply
AT AC Loss No 220 V power supply
BA Burglary alarm Alarm
BB Burglary bypass Bypassing an Entry/Exit, Follow or Instant type zone
BH Burglary Restore Restore alarm
BU Burglary bypass Restore
Restore after Bypassing an Entry/Exit, Follow or Instant
type zone
CL Quick arm Quick arming (no code)
CL Arming by user Arming by user
CQ Remote arming Remote arming
CS Arming by keyswitch Arming from key-switch
FA Fire alarm Fire alarm
FB Fire bypass Bypassing a FIRE type zone
FH Fire Restore Restore after Fire alarm
FU Fire bypass Restore Restore after bypassing a FIRE type zone
HA Duress code Code introduced under duress
LB Program mode entry Engineer programming mode entry
LX Program mode exit Engineer programming mode exit
MA Medical alarm Medical alarm
MB Medical bypass Bypassing a Medical type zone
MH Medical Restore Restore after Medical alarm
MU Medical bypass Restore Restore after bypassing a Medical type zone
OP Disarm by user Disarming by user
OQ Remote disarm Remote disarming
OS Disarm by keyswitch Disarming from key-switch
PA Panic alarm Panic alarm
PB Panic bypass Bypassing a Panic type zone
PH Panic Restore Restore after Panic alarm
PU Panic bypass Restore Restore after bypassing a Panic type zone
RP Periodic TEST report Periodic TEST signal
RX Manual TEST report Manual TEST signal
TA Tamper alarm Tamper alarm
TB Tamper bypass Bypassing a Tamper type zone
TH Tamper Restore Restore after Tamper alarm
TU Tamper bypass Restore Restore after bypassing a Tamper type zone
YC Failure to communicate Communication error
YK Telephone line Retsore Restored telephone line
YP Fuse blown Blown fuse
YQ Fuse Restore Restored fuse
YR Battery Restore Restored battery
YS Telephone line Fault Telephone line failure
YT Battery missing No battery
YW System RESET System parameters default reset
Meaning
Supplement C Additional information
42 CA60Plus control panel Installation manual
Supplement D General connection scheme
CA 60 Plus
+ PGM
+ AUX
KEYBOARD
A
C
+
A
U
X
+
P
G
M
P
G
M
1
P
G
M
2
P
G
M
3
S
I
R
E
N
Z
2
C
O
M
Z
3
Z
4
Z
5
Z
6
C
O
M
C
O
M
R
E
D
G
R
N
Y
L
W
B
L
C
K
RESET
BATT
2A
1A
1A
DIALER
Keyboard1
Keyboard 2
PR 60
P
o
w
e
r
f
u
l

o
u
t
p
u
t








m
a
x

2

12V
Connecting with
double EOL
resistor
CONNECTING ZONE
INPUTS
N.C.
N.O.
Z COM
1k
Connecting with
single EOL
resistor
1k
T
A
M
P
E
R
Z COM
1k
N.C.
R
e
d
G
r
e
e
n
Y
e
l
l
o
w
B
l
a
c
k

P
G
M

o
u
t
p
u
t
s


m
a
x

1
0
0
m
A
12V
A
B
A1
B1
L
I
N
E
C
O
M
P
o
w
e
r


s
u
p
p
l
y

f
o
r

d
e
t
e
c
t
o
r
s
a
n
d

a
u
x
i
l
l
a
r
y

c
o
m
p
o
n
e
n
t
s
P
o
w
e
r

s
u
p
p
l
y

f
o
r

P
G
M



a
n
d

s
i
r
e
n
220V/0,63A
N
L
Z1
White
Black
Z1
White
Black
PGM
T
E
L
E
P
H
O
N
E
17V
17W - 25W
PROG EXPAND
SP
MIC
REC
MSG
PLAY
M
S
G

VD60
B
U
S
Y
1
2 2
CA60Plus control panel Installation manual 43
Revision history
Revision 4.31
1. Added menu 48 - fire duration.
2. Added menu 49 - enable/disable audible TAMPER.
3. Changed menu 69 - second half - events for transmit by second phone.
4. Added menu 76 - communications attempts.
5. Added menu 93 - communicator test.
6. Added menu 97 - internal clock adjustement.
7. Possibility of FORCE arming for zone type KEYSWITCH.
8. Added sound signal ALLARM to keyboards.
9. Clear LOG files after hardware RESET.
Revision 4.33
1. In menu 61 and 64 - panel ID can be hexadecimal.
Revision 5.0
1. Added possibility to attach voice dialer.
2. Added menu 80 - record and playback of voice messages.
3. Added menu 81, 82, 83, 84 - four phone numbers for voice dialer.
4. Added menu 85 - message type transission for voice dialer.
Message Event Example message
1 Alarm or tamper from Zone1 Alarm from Zone 1 or Alarm in Entrance
zone
2 Alarm or tamper from Zone2 alarm from Zone 2 or Alarm in the corridor
3 Alarm or tamper from Zone3 Alarm from Zone 3 or Alarm in the children
room
4 Alarm or tamper from Zone4 Alarm from Zone 4 or Alarm in the dinning
room
5 Alarm or tamper from Zone5 Alarm from Zone 5 or Alarm in the bedroom
6 Alarm or tamper from Zone
6
Alarm from Zone 6 or Cable interrupting in
the alarm system
7 The control panel turn off
with Ambush code
Duress code have been entered
8 Personal message Message for Mr. John Smith


Message Event Example message
1 Alarm in the system Burglary alarm
2 Panic alarm in the system Panic or Duress code have been entered
3 Tamper alarm in the system Cable interrupting in the alarm system
4 Fire alarm in the system Fire
5 Medical alarm in the system Medical alarm
6 AC loss AC power supply interrupting
7 Battery low Battery too low
8 Common message Message for Mr. John Smith
Supplement E Example vioce message
Table 1: Message by zones (in 85 addres entered 0)
Table 2: Message by events (in 85 addres entered 1)
Guarantee
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any
defective product when it is returned to the factory. All parts replaced and/or repaired shall be
covered for the remainder of the original guarantee, or for ninety (90) days, whichever period is
longer. The original purchaser shall immediately send manufacturer a written notice of the
defective parts or workmanship, which written notice must in all cases be received prior to
expiry of the guarantee.
International Guarantee
Foreign customers shall enjoy the same guarantee rights as those enjoyed by any customer in Bulgaria,
except that manufacturer shall not be liable for any related customs duties, taxes or VAT, which may be
payable.
Guarantee Procedure
This guarantee will be granted when the appliance in question is returned. The manufacturer
shall accept no product whatsoever, of which no prior notice has been received.
Conditions for waiving the guarantee
This guarantee shall apply to defects in products resulting only from improper materials or
workmanship, related to its normal use. It shall not cover:
Damages resulting from transportation and handling;
Damages caused by natural calamities, such as fire, floods, storms, earthquakes or
lightning;
Damages caused by incorrect voltage, accidental breakage or water; beyond the control
of the manufacturer;
Damages caused by unauthorized system incorporation, changes, modifications or
surrounding objects:
Damages caused by peripheral appliances (unless such peripheral appliances have
been supplied by the manufacturer:
Defects caused by inappropriate surrounding of installed products;
Damages caused by failure to use the product for its normal purpose; Damages caused
by improper maintenance;
Damages resulting from any other cause, bad maintenance or product misuse.
In the case of a reasonable number of unsuccessful attempts to repair the product, covered by
this guarantee, the manufacturers liability shall be limited to the replacement of the product as
the sole compensation for breach of the guarantee. Under no circumstances shall the
manufacturer be liable for any special, accidental or consequential damages, on the grounds of
breach of guarantee, breach of agreement, negligence, or any other legal notion.
Waiver
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other
guarantees, explicit or implicit (including any implicit guarantees on behalf of the dealer, or
adaptability to specific purposes), and over any other responsibilities or liabilities on behalf of
the manufacturer. The manufacturer does neither agree, nor empower, any person, acting on
his own behalf, to modify or alter this Guarantee, nor to replace it with another guarantee, or
another liability with regard to this product.
Unwarranted Services
The manufacturer shall repair or replace unwarranted products, which have been returned to its
factory, at its sole discretion under the conditions below. The manufacturer shall accept no
products for which no prior notice has been received.
The products, which the manufacturer deems repairable, will be repaired and returned. The
manufacturer has prepared a price list and those products, which can be repaired, shall be paid
for every repaired appliance.
The closest equivalent product, available at the time, shall replace the products manufacturer
deems unrepairable. The current market price shall be charged for every replaced product.
1
8
0
2
0
3
5
1


R
e
v
.
5
.
0

0
1
/
2
0
0
5

You might also like