01 01 01

B3871 - 26.06.2013 CTAp1 - 30.000mc/h

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:23 1 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703

1800

1600

60

1540

Fresh
30

1540

G4

Z-100

SD
130

Supply
30

80 60

260

60 260

560

600

760

2360

920

60 130

1220 (1)

760 (2) 5320

2360 (3)

980 (4)

Door stop and heat exchanger connection not obligatory!

Service switch Electric Light switch Measuring port General opening Differential pressure Pointer thermometer Contact manometer U-tube manometer T ube manometer

dp Individual section-Weight [kg ] dp 1 437 T hermometer 2 275 Drain tray heater 3 873 Frost protection heating 4 386 T rap Mixing valve Overall accessories5 kg Actuator Break point T otal 1976 kg Fitted components LS70

X1K#IHSE
Project

Z188160VBVA 30000 m/h


O ffer-Position

Q uantity

Service side
Responsible

1 : 40

B3871-30.000mc/h
Plant O rder No. Internal office staff

CTAp1
Customer

LPlus V.54.85/26.06.2013

2000

1880

60
1820

Fresh
30

1820

G4

Z-100

SD

Supply
130

60

60 260

560

600

760

2360

920

60 130

1220 (1)

760 (2) 5320

2360 (3)

980 (4)

Door stop and heat exchanger connection not obligatory!

Service switch Electric Light switch Measuring port General opening Differential pressure Pointer thermometer Contact manometer U-tube manometer T ube manometer

dp Individual section-Weight [kg ] dp 1 437 T hermometer 2 275 Drain tray heater 3 873 Frost protection heating 4 386 T rap Mixing valve Overall accessories5 kg Actuator Break point T otal 1976 kg Fitted components LS70

X1K#IHSE
Project

Z188160VBVA 30000 m/h


O ffer-Position

Q uantity

Top view
Responsible

30

1 : 40

B3871-30.000mc/h
Plant O rder No. Internal office staff

CTAp1
Customer

LPlus V.54.85/26.06.2013

GEA CAIRplus SX 188.160IVBV - 1 Pcs Plant: CTAp1 Customer position: 30.000mc/h function volume flow Velocity Eurovent Application: Installation site: Air direction: Arrangement type: - Casing in standard version - Thickness of casing wall60 mm - Unit casing properties as of EN 1886 (2007)* - Mechanical stability D2* - Casing leakage L1 (Model Box) - Casing leakage L2 (Real unit) - Filter-bypass leakage F9* - Thermal insulation T2* - Thermal bridging factor TB3* Insertion loss as of DIN EN 1886 [Hz] 125 250 500 1000 2000 4000 8000 [dB] 17 21 27 30 31 31 40 * based on model box test Material quality - Inner skin Aluzink sheet steel with anti-fingerprint coating (FeP02G AZ 185) Corrosion protection class III per DIN 55928 Part 8, suitable for outside installation - Outer skin Galvanized sheet steel, polyester coated, colour RAL 9002, grey-white - Interior parts Galvanized sheet steel or equivalent - Frame profiles Aluminium AlMgSi 0.5 001 - 4 set Transport lifting lug, max. 1500 kg (Set 4pcs.)

Supply air 30000 m3/h 2.8 m/s

Standard Inside installation Horizontal Single

002 - 1 set Stainless steel cover for intermediate and dividing joint profiles (automatic design and selection) 003 - 1 set Base frame, galvanized steel - height 80 mm

SUPPLY
004 - 1 Pcs Intake/discharge hood installed on end wall 005 - 1 Pcs Damper across unit cross-section internal installed on end wall Standard, galvanized, working in opposite directions 006 - 1 Pcs Open front wall - across unit cross-section with duct connection frame

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:25 4 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703

007 - 2 Pcs Number of necessary actuator drives, by others - min. torque 15Nm for each drive 010 - 1 Pcs Multifunction - unit for standard built-in parts 011 - 1 Pcs Door stop - galvanized 012 - 1 Pcs Bag filter - unit Filter class: G4 in accordance with EN 779 Filter class Medium synthetic fibre Filter frame galvanized efficiency EM % filter efficiency AM % Built in frame standard brackets Galvanized construction dimensioning Pa 013 - 1 Pcs Door stop - galvanized 014 - 1 Pcs Evaporative humidifier - unit Design: 2-stage Efficiency temperature/rel. humidity temperature/rel. humidity 015 - 1 Pcs 016 - 1 Pcs Icing sensor - installed 017 - 1 Pcs Fan - unit High-performance centrifugal impeller without spiral casing Fan Typ ER10C-8DN.M7.1R-ROD Air volume flow m/h 30000 pressure sum external Pa 150 total Pa 571 actual speed 1/min 751 Efficiency % 74.9 shaft power kW 6.35 sound power - not weighted dB 95 sound power A-weighted dB(A) 91 motor rated power kW 11.00 rated speed 1/min 720 018 - 2 Pcs Measuring nippe (aluminium) 019 - 1 Pcs Rubber compression nipple 020 - 1 Pcs Door stop - galvanized 021 - 1 Pcs Inspection window for door/service panel

G4 0 90.0 115

% C/% C/%

81 36.0/35.0 25.7/82.2

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:25 5 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703

022 - 1 Pcs Sound attenuator unit Section absorption principle splitters press. drop octave band attenuator frequency 63 125 250 500 1000 2000 4000 8000 Hz Hz Hz Hz Hz Hz Hz Hz

Pa

62 insertion loss 4 9 20 21 24 17 14 14 flow sound power 58 54 49 45 42 38 35 32

dB dB dB dB dB dB dB dB

023 - 1 Pcs Open front wall - across unit cross-section with duct connection frame 024 - 1 Pcs Flexible connection installed on end wall Connection profile with 4-hole screw connection as galvanized version manufacturer Length/Width/Height Weight Number Transport sections GEA mm kg 5320/2000/1800 1976 4

01 02

CTAp2 - 10.000mc/h

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:25 6 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703

1480

1280 1220

60

Fresh
80 60 30
260

1220

G4

Z-560

SD
130

Supply
30

60 260

480

440

760

1240

600

60 130

980 (1)

760 (2) 3640

1240 (3)

660 (4)

Door stop and heat exchanger connection not obligatory!

Service switch Electric Light switch Measuring port General opening Differential pressure Pointer thermometer Contact manometer U-tube manometer T ube manometer

dp Individual section-Weight [kg ] dp 1 201 T hermometer 2 162 Drain tray heater 3 261 Frost protection heating 4 144 T rap Mixing valve Overall accessories5 kg Actuator Break point T otal 774 kg Fitted components LS70

X1K#IHSE
Project

Z096128VBVA 10000 m/h


O ffer-Position

Q uantity

Service side
Responsible

1 : 40

B3871-10.000mc/h
Plant O rder No. Internal office staff

CTAp2
Customer

LPlus V.54.85/26.06.2013

1080

960

60 900

Fresh
30 60

900

G4

Z-560

SD
130

Supply
30

60 260

480

440

760

1240

600

60 130

980 (1)

760 (2) 3640

1240 (3)

660 (4)

Door stop and heat exchanger connection not obligatory!

Service switch Electric Light switch Measuring port General opening Differential pressure Pointer thermometer Contact manometer U-tube manometer T ube manometer

dp Individual section-Weight [kg ] dp 1 201 T hermometer 2 162 Drain tray heater 3 261 Frost protection heating 4 144 T rap Mixing valve Overall accessories5 kg Actuator Break point T otal 774 kg Fitted components LS70

X1K#IHSE
Project

Z096128VBVA 10000 m/h


O ffer-Position

Q uantity

Top view
Responsible

1 : 40

B3871-10.000mc/h
Plant O rder No. Internal office staff

CTAp2
Customer

LPlus V.54.85/26.06.2013

GEA CAIRplus SX 096.128IVBV - 1 Pcs Plant: CTAp2 Customer position: 10.000mc/h function volume flow Velocity Eurovent Application: Installation site: Air direction: Arrangement type: - Casing in standard version - Thickness of casing wall60 mm - Unit casing properties as of EN 1886 (2007)* - Mechanical stability D2* - Casing leakage L1 (Model Box) - Casing leakage L2 (Real unit) - Filter-bypass leakage F9* - Thermal insulation T2* - Thermal bridging factor TB3* Insertion loss as of DIN EN 1886 [Hz] 125 250 500 1000 2000 4000 8000 [dB] 17 21 27 30 31 31 40 * based on model box test Material quality - Inner skin Aluzink sheet steel with anti-fingerprint coating (FeP02G AZ 185) Corrosion protection class III per DIN 55928 Part 8, suitable for outside installation - Outer skin Galvanized sheet steel, polyester coated, colour RAL 9002, grey-white - Interior parts Galvanized sheet steel or equivalent - Frame profiles Aluminium AlMgSi 0.5 001 - 4 set Transport lifting lug, max. 1500 kg (Set 4pcs.)

Supply air 10000 m3/h 2.3 m/s

Standard Inside installation Horizontal Single

002 - 1 set Stainless steel cover for intermediate and dividing joint profiles (automatic design and selection) 003 - 1 set Base frame, galvanized - height 80mm

SUPPLY
004 - 1 Pcs Intake/discharge hood installed on end wall 005 - 1 Pcs Damper across unit cross-section internal installed on end wall Standard, galvanized, working in opposite directions 006 - 1 Pcs Open front wall - across unit cross-section with duct connection frame

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:29 9 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703

007 - 1 Pcs Number of necessary actuator drives, by others - min. torque 15Nm for each drive 010 - 1 Pcs Multifunction - unit for standard built-in parts 011 - 1 Pcs Door stop - galvanized 012 - 1 Pcs Bag filter - unit Filter class: G4 in accordance with EN 779 Filter class Medium synthetic fibre Filter frame galvanized efficiency EM % filter efficiency AM % Built in frame standard brackets Galvanized construction dimensioning Pa 013 - 1 Pcs Evaporative humidifier - unit Design: 2-stage Efficiency temperature/rel. humidity temperature/rel. humidity 014 - 1 Pcs 015 - 1 Pcs Icing sensor - installed 016 - 1 Pcs Fan - unit High-performance centrifugal impeller without spiral casing Fan Typ ER56C-4DN.E7.1R-ROD Air volume flow m/h 10000 pressure sum external Pa 150 total Pa 500 actual speed 1/min 1356 Efficiency % 76.1 shaft power kW 1.83 sound power - not weighted dB 91 sound power A-weighted dB(A) 87 motor efficiency class IE2 rated power kW 2.20 rated speed 1/min 1430 017 - 2 Pcs Measuring nippe (aluminium) 018 - 1 Pcs Rubber compression nipple 019 - 1 Pcs Door stop - galvanized 020 - 1 Pcs Inspection window for door/service panel 021 - 1 Pcs Sound attenuator unit Section absorption principle

G4 0 90.0 112

% C/% C/%

82 36.0/35.0 25.6/83.1

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:29 10 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703

splitters press. drop octave band attenuator frequency 63 125 250 500 1000 2000 4000 8000 Hz Hz Hz Hz Hz Hz Hz Hz

Pa

38 insertion loss 2 6 14 15 17 13 11 12 flow sound power 48 43 39 35 32 28 25 22

dB dB dB dB dB dB dB dB

022 - 1 Pcs Open front wall - across unit cross-section with duct connection frame 023 - 1 Pcs Flexible connection installed on end wall Connection profile with 4-hole screw connection as galvanized version manufacturer Length/Width/Height Weight Number Transport sections GEA mm kg 3640/1080/1480 774 4

GEA Klimatechnik SRL


/ B3871 LPlus 5.48.5.1/100 // B3871.LP4 / / 26.06.201315:16:29 11 Bd Mihai Viteazul 30B RO-300222 Timsoara Romania Tel/Fax .(+40) 256 203044 / (+40) 356 423703