COOLING TOWER PERFORMANCE TEST (ID CT)

Manual Input Sheet STATION: UNIT: REPORT DATE: TEST DATE:

TEST DATA
Average Hot Water Temperature Average Cold Water Temperature Average Inlet Air WBT Average Wind Velocity Actual KW of Fans during Test (Average) T HOT WATER T COLD
WATER

TEST VALUE 42.00 32.00 25.00 3.00 65.00 10 29790 33100 36410 32.00 9.00 5.00 9
P Des

UNITS
C C C Meter / sec kW

T WBT V WIND P Act

No. of Cells in Service during Test DESIGN DATA


Design CT Flow (90 %) Design CT Flow (100 %) Design CT Flow (110 %) Design Cold Water Temperature (C) Design Range of Cooling Tower (C) Design Approach of Cooling Tower (C)

No.
T/Hr T/Hr T/Hr C C C

No. of Cells Design


Design KW of Fans CW Duct Inner Dia (ID)

No.
kW meter

59.00 2.60 1.03

PITOT CONSTANT DATA


Pitot Constant DATA DERIVED FROM MANUFACTURERS CURVE Expected Cold Water Temperature : 90% Flow T COLD Expected Cold Water Temperature : 100% Flow Expected Cold Water Temperature : 110% Flow T COLD T COLD

WATER - 90%

29.00 30.00 31.00

From CT [90%] Characteristic curve From CT [100%] Characteristic curve From CT [110%] Characteristic curve

WATER - 100%

WATER - 110%

Important Notes: 1 2 3

For Flow calculation, manometer values to be entered in Xmin and Ymax in cm of water colu To find out the predicted CT flow proceed as follows:

For cells "U 14" & "W 14" the formula to be modified as per the formula in the curve "Variatio

Select cell "W 14", go to tools menu and and select the Goal seek option. In the goal seek menu in the second row put the actual test cold water temperature value In the third row of the goal seek menu select cell "V 14" and click OK

3 PORT HYDRAULIC PITOT TRAVERSE

CW Duct CT # - Vertical Test Port Xmin Ymax DP cm of cm of cm of Velocity wcl wcl m/sec S.No wcl 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 75.00 73.00 72.80 73.50 73.50 74.00 73.00 72.00 73.00 72.30 72.00 72.80 72.00 72.20 71.00 71.00 81.50 83.50 84.00 82.50 82.50 81.50 83.00 84.50 83.00 83.50 84.20 83.80 84.50 84.50 85.50 85.00 6.50 10.50 11.20 9.00 9.00 7.50 10.00 12.50 10.00 11.20 12.20 11.00 12.50 12.30 14.50 14.00 1.51 = 1.54

CW Duct CT # - Horizonta Xmin Ymax DP cm of cm of cm of wcl wcl wcl 82.20 82.10 81.00 81.60 81.80 82.00 82.00 82.20 81.80 82.50 82.00 81.00 81.20 81.00 81.00 81.00 93.00 92.80 93.80 94.00 94.00 93.00 93.20 92.80 93.50 92.50 92.50 94.50 94.50 94.50 95.00 95.00 10.80 10.70 12.80 12.40 12.20 11.00 11.20 10.60 11.70 10.00 10.50 13.50 13.30 13.50 14.00 14.00

10.87 Avg CW Velocity [m/s]

12.01 Total CW Flow [Tons/Hr] =

Ymax in cm of water column (In columns "I", "J", "N" & "O")

ula in the curve "Variation between CW flow vs Expected Cold Water Temperature"

er temperature value

9.81 2 19.62 0.442945 0.9418 0.417165

0.4568 1.03128

VERSE

Duct CT # - Horizontal Test Port Velocity m/sec CW Flow T/Hr


29790 33100 36410 29,534 29.00 30.00 31.00 28.86 40000 32.00

1.58 Flow [Tons/Hr] = 29,534.48

Variation Between CW Flow Vs Expected Cold Water Temperature


31.50

xpected Cold Water Temperature [C]

31.00

y = 0.0003x + 20

30.50

30.00

29.50

Expected Cold Water Temperature [

29.50

29.00

28.50 0 10000 20000 30000 CW Flow Rate [Tons/Hr]

d Cold Water Temperature

y = 0.0003x + 20

40000

COOLING TOWER PERFORMANCE TEST (ID CT) - REPORT


STATION: UNIT: REPORT DATE: TEST DATE:

FIELD TEST PARAMETERS Average Hot Water Temperature Average Cold Water Temperature Average Inlet Air WBT Average Wind Velocity COMPUTATION OF EXPECTED COLD WATER TEMPERATURE Average Inlet Air WBT Average CW Cooling Range Expected Cold Water Temperature : 90% Flow Expected Cold Water Temperature : 100% Flow Expected Cold Water Temperature : 110% Flow

UNITS C C C m/sec C C C C C

TEST VALUE 42.00 32.00 25.00 3.00 25.00 10.00 29.00 30.00 31.00

Expected Cold Water Temp: Actual Flow C CORRECTION IN EXPECTED COLD WATER TEMPERATURE DUE TO WIND Correction factor due to Wind Velovity C Expected Cold Water Temp C RESULTS DESIGN EXPECTED Cold Water Temperature (C) 32.00 29.18 Cooling Range of Cooling Tower (C) 9.00 12.82 Approach of Cooling Tower (C) 5.00 4.18 Cooling Tower Effectiveness (%) No. of Cells Design No. of Cells in Service during Test TOWER CAPABILITY Measured CW Flow (T/Hr) Predicted CW Flow corres.to Test Cold Water Temp. Design KW of Fans Actual KW of Fans during Test (Average) Adjusted CW Flow (T/Hr) Tower Capability 64.29 9 75.43

28.86 0.32 29.18 ACTUAL 32.00 10.00 7.00 58.82

10 Q Meas Q Pred. P Des P Act Q Adj % 29534.48 40000.00 59.00 65.00 25737.44 64.34

Average Wind Velocity (m/sec) Increase in Cold Water Temp

3.00 0.3

CW Temp rise (C)

Wind Increase in Velocity CW Temp m/sec Deg C 0.833 0 1 0 2 0.12 3 0.38 4 0.5 5 0.57

Wind Velocity Correction Factor 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 -0.1 0

y = 0.15x - 0.1342

Wind Velocity (m/sec)

rection Factor

0.1342

ocity (m/sec)