You are on page 1of 2

CTX-CTL Pressure Transmitter for OEM Applications

OEM applications Excellent price/performance ratio Compact and light-weight CE conformity Output signals: 4...20 mA, 0...10 Vdc, 1...5Vdc, 0.5...4.5 Vdc Automated laser setting Stainless Steel (CTX) or brass (CTL) construction

Series CT transmitters are designed for extremely diverse industrial applications: ventilation, heating, pumps, pressure measurement on water systems (building complexes, etc.), maintaining pressure setpoints on oil compressors, integration in production machinery, agriculture machines, etc. OEM Markets: machine equipments, water treatment, water distribution, energy (diesel engines, cogeneration plants), automatic sequence control, etc.

Specications (20C)
Measurement range Output signal Supply voltage Insulation Load impedance CE Conformity CTX: from -1...1.5 to 0...200 bar, gauge pressure CTL: from -1...1.5 to 0...40 bar, gauge pressure CTX2 - CTL2: 0...10 Vdc CTX3 - CTL3: 4...20 mA CTX4 - CTL4: 1...5 Vdc CTX7 - CTL7: 0.5...4.5 Vdc under 5 Vdc CTX2 - CTL2: 15...30 Vdc CTX3/4 - CTL3/4: 11...30 Vdc CTX7 - CTL7: regulated 5 Vdc power supply Polarity reversion protection > 100 M at 100 Vdc CTX2/4/7 - CTL2/4/7: 5 k CTX3 - CTL3: R (Usupply-11)/0.02 Directive 89/336 CE Pressure Directive 97/23/CE Standard connections CTX Standard connections CTL Protection rating (EN 60529) Typical response time Electrical: DIN 43650 connector, pig tail cable outlet, M12 - 4 contacts plug Pressure: G1/4 EN837, G1/4 DIN 3852-E, G1/2 EN837, 1/4 NPT, 1/2 NPT Electrical: pig tail cable outlet Pressure: G1/4 EN837, 1/4 NPT IP65 3 ms

Vibration resistance (IEC 68-2-6) 1.5 mm (10 - 55 Hz), 20 g (55 Hz - 2 kHz) Shock resistance (IEC 68-2-32) 25 falls from 1 m on concrete ground Weight from 80 g to 150 g depending on versions

Options
Other hydraulic connections (quantity 100 units) Other electrical connections (quantity 100 units) Other units M12 female mobile plug, screw terminal connection (CTX). Code 2260 2 mV/V 30% ouput signal: CTX1/CTL1 versions, please consult us

Global error (linearity, hysteresis and repeatability) with reference to BFSL Typically: 0.4% of F.S. / Max.: 0.5% of F.S. Operating temperature Ambient (Ta) Fluid Storage temperature -25...+85C -25...+100C (Ta 50C) -40...+85C

Compensated temperature range (zero and sensitivity) -10...+55C Zero thermal drift Span thermal drift Wetted parts 0.025% F.S./C max. Typically: 0.01% F.S./C / Max.: 0,015% F.S./C CTX: Ceramic + NBR seal (standard) + 1.4404 (316L) stainless steel CTL: Ceramic + NBR seal (standard) + brass

www.baumerprocess.com Modications reserved

Data sheet A11.01 Page 

Dimensions (mm), connections


DIN 43650 connector
45

Pig tail cable outlet


40

M12 - 4 contacts plug

CTL

50

CTX

48 23 28

CTX

23

3 2 1

CTX3 CTX2 CTX4 CTX7

1 2 3 1 2 3

+ supply - supply ground + supply - sup. / - meas. + measurement ground

23

Red Black Red CTX2/4/7 Black CTL2/4/7 White CTX3 CTL3

+ supply - supply + supply - sup. / - meas. + measurement

4 1

3 2

CTX3 CTX2 CTX4 CTX7

1 2 3 4 1 2 3 4

+ supply - supply ground + supply + measurement - sup. / - meas. ground

Hydraulic connection

15

15

13

23

18

22.7

CTX

23

G 1/4 DIN 3852-E

G 1/4 EN837

G 1/2 EN837

1/4 NPT

1/2 NPT

Measuring Ranges
Pressure in bar
Pressure Max. overpressure Burst pressure specications at 20C 2.5 4 7 4 8 12 6 12 18 10 20 30 16 32 48 25 50 75 40 80 120 60 120 180 100 200 300 160 320 480 200 (1) 360 480

Ordering Details - CTX / CTL


CTxx xx xxxx Model 1...3 digit OEM pressure transmitter, stainless steel construction CTX OEM pressure transmitter, brass construction CTL Output signal 0...10 Vdc 4...20 mA 1...5 Vdc 0.5...4.5 Vdc under 5 Vdc regulated Hydraulic connection G 1/4 G 1/4 DIN 3852-E * G 1/2 * 1/4 NPT 1/2 NPT * Sensor seal NBR (Nitril) standard EPDM FKM (Viton) Pressure range See table Electrical output DIN 43650 connector * Pig tail cable outlet, 1-meter length Pig tail cable outlet, 2-meter length Pig tail cable outlet, 5-meter length M12 - 4 contacts plug * www.baumerprocess.com Modications reserved 4 digit 5 digit 2 B 3 5 6 6 digit 3 5 9 7...9 digit Bxx 10 digit 0 1 2 5 A 2 3 4 7
code B74 B76 B77 B79 B81 B82 B1L B18 B19 B20 B22 B24 B26 B27 B29 B31 B33 B34 Pressure range in bar -1 + 1,5 -1 + 3 -1 + 5 -1 + 9 -1 + 15 -1 + 24 -1 + 39 0 + 2,5 0 + 4 0 + 6 0 + 10 0 + 16 0 + 25 0 0 0 0 0 + 40 + 60 * + 100 * + 160 * + 200 * (1)

* Not available in CTL version


(1) Please consult us for operating specications

Data sheet A11.01 Page 

UK/04-2007 This data sheet may only be reproduced in full.