Instruction Manual

Specification for steam turbine control fluid

1. 2.

Type Fire-resistant-oil (Phosphate esters) Quality The quality of the new control fluid (fire-resistant-oil) must conform to the following criteria Item Kinematic viscosity Pour point Density Water content Total acid number Flash point Ignition point Air release property (50 C) (15 C) (40 C) (20 C) Specification for new fluid 3844 115210 18 cst (mm/s) cst (mm/s) C :

Testing method Standard No. JIS K2283 ASTM D445 ASTM D97 JIS K2249 ASTM D941 / D1298 / D1481 JIS K2275 ASTM D95 / D1744 JIS K2501 ASTM D974 ASTM D92 ASTM E659 DIN 51381 ASTM D3427 ASTM D892 JIS B9930 ISO 4406 DIN 51592 DIN 51373 *1

1.121.25 g/cm 0.1 0.1 235 550 5 100 450 wgt. % mg KOH/g C C min. cm sec.

Foaming characteristics (25 C) Foam stability (25 C) Contamination level (by the particle count method) Content of solid particles Oxidation stability Hydrolysis stability Chlorine content Burning behavior Electrical resistivity

within code 17/14 or SAE grade 3 0.05 2.0 2.0 50 5


8

wgt. % mg KOH/g mg KOH/g mg/kg sec.

0.5 10 m

Note : No additives for improving the viscosity index can be contained. The brands of steam turbine control fluid in Lubricant list in O&M manual are only permitted to use for the control fluid system of this turbine.

Fuji Electric Co., Ltd.

INV-ST3388-025a-E

13

3.

Method of pouring new fluid into the tank New fluid should be filtered by a filter of contaminant removal rating less than 1m (absolute), when poured into the tank. Higher grade cleanness will be recommended if available

INV-ST3388-025a-E

23

4.

Criteria for steam turbine control fluid and periodical testing instruction Testing interval *2 Item Specification for new fluid Control criterion for operation Test procedures For 1st year after commissioning After filled with new fluid and every month After filled with new fluid and every 4 months After filled with new fluid and every month After filled with new fluid and every month At periodical inspection After 1 year from commissioning After filled with new fluid and every 2 months Reason and description

Kinematic viscosity

3844 cst @ 40 C 1.121.25 g/cm max. @ 15 C 0.1 wt% max.

New fluid value within 10% @ 40 C 1.121.25 g/cm @ 15 C / 4 C 0.15 wt% max. *3
*3 *4

JIS-K2283 ASTM-D445 JIS-K2249 ASTM-D941/ D1298/ D1481 JIS-K2275 ASTM-D95/D1744 JIS-K2501 ASTM-D974

Before startup

* Viscosity range allowed for equipment is rather large. But judge how hydraulic fluid is deteriorated according to manufacturer's recommendation to the same level of new fluid value within 10% as other plants.

Density

Before startup

After filled with new * Intend for detecting deterioration or mixing with foreign fluid and every 4 months materials. * Minimize to avoid servo valve corrosion and quickened After filled with new deterioration of hydraulic fluid. fluid and every 2 months After filled with new fluid and every 2 months * Minimize to avoid servo valve corrosion and hydraulic fluid deterioration. *4 Set the normal target to 0.1 mg KOH/g max. and control it never to override 0.3 mg KOH/g with sufficient margin.

Water content

Before startup

Total acid number Contamination level (particles/100 m) D : Particle size 5D 10 m 10D 25 m 25D 50 m 50D 100 m 100 mD / Fibrous / Non fibrous

0.1 mg KOH/g max.

0.3 mg KOH/g max. Within SAE grade 3 or 5 *5 (* TARGET LEVEL) ( 9,700 ) ( 2,680 ) ( 380 ) ( 90 ) ( 32 ) ( 27 ) ( 5)

Before startup

Within SAE grade 3 24,000 5,360 780 110 11

JIS B9930 Microscopic Process, Automatic Particle Counting Method

After filled with new fluid and every month

Before startup

* TARGET shall be SAE grade 2 for normal control which has sufficient margin and the same as for similar plants where high pressure control fluid is used. After filled with new fluid and every 2 months *5 In the worst condition within SAE grade 3 for servo valve inlet ultra-precision filter or downstream and within SAE grade 5 for others.

*6

Chlorine content

50 mg/kg max.

(50 mg/kg max.) *6

Oxyhydrogen flame combustion-potential titration method JIS C2321 (old edition) JIS-K2580 Molybdenum blue method DIN 51381 ASTM D3427

After filled with new fluid and every 4 months After filled with new fluid and every month After filled with new fluid and every 4 months When found abnormal When found abnormal

Before startup

After filled with new fluid and every 4 months

Control the operation in terms of inorganic chlorine. No limit value is specified for the equipments. However, in conformity with the fluid manufacturer's recommendation, set the level to 50 mg/kg max. the same as other plants and observe the trend.

Inorganic chlorine

* (ASTM No. 1.5 max.) 5 min. max. @ 50C

1.0 ppm max. * (ASTM No. 1.5 max.) Watch the trend (for reference) 7 min. max. @ 50C

Before startup

* Minimize to avoid servo valve corrosion and hydraulic fluid After filled with new deterioration. fluid and every 2 months After filled with new fluid and every 4 months When found abnormal When found abnormal * No requirement is specified by the equipments. However, in conformity with the fluid manufacturer's recommendation, select the same level as other plants and observe how the fluid tends to deteriorate. * Minimize to avoid servo valve corrosion and hydraulic fluid deterioration. * In order to maintain stable operation of pumps and control equipments.

Color

Before startup

Phosphoric acid Air release property

Note

*1 *2 *3

: The oxidation stability test need not be always conducted at the time of delivery. It might be replaced by the sample test. : If an abnormal condition is found, then the test interval shall be shortened. : If total acid number exceeds 0.1 mg KOH/g or water content exceeds 0.1 wt% for continuous two test periods, the exchanging interval for earth filter is shortened from every 5 months to every 2 months. If total acid number exceeds 0.2 mg KOH/g, change the earth filter media to alumina filter media [from HILSORB (manufacturer : HILCO) to SELEXSORB (ditto)].

INV-ST3388-025a-E