INTRODUCTION
Minature Circuit Breakers (MCBs),
with latest technology, offer an
ideal protection to the electrical
distribution system. Whatever
be the application, these MCBs
offer perfect overload and short
circuit protection, in B, C and D
types from 6A to 63A.
SALIENT FEATURES
MCBs having breaking capacity
of 10kA, 2 positions and 20kA, 3
positions.
Current limiting design - low
let-through energy.
Silver graphite contacts for
weld-free operation.
Trip-free mechanism ensures
tripping even if operating knob
is held forcibly in ON position.
Terminals on both sides, with
pressure plates suitable for 25
sq.mm cables.
Shrouded terminal on both sides
make MCBs finger - touch proof.
Neutral advance mechanism, i.e.
neutral contact opens last and
closes before phase contact,
which always ensures zero
potential before phase potential.
Padlocking facility in ON/OFF
position.
TECHNICAL SPECIFICATIONS
10 kA, 2 Position MCBs
Specifications conforming: IEC
898-1995.
No. of poles : 1,2,3 and 4 pole
(SP, SPN, DP, TP, TPN and FP).
Tripping characteristics : B, C
and D.
Current ratings: 6, 10, 16, 20,
25, 32, 40 and 63A. On request,
1A to 5A.
Rated voltage : Upto 415V, AC.
Frequency : 50/60Hz
Fixing : On 35 mm DIN rail.
Breaking capacity : 10 kA.
Mechanical Life : 100,000
operations.
Electrical life : 20,000 operations.
Temperature : -5C to 55C,
Terminals : On both sides, with
pressure plates for 25 sq.mm
cable.
TRIPPING CHARACTERISTICS (IEC 898-1995)
Time/Current Characteristic Curve for B,C, & D Types.
20 kA, 3 Position MCBs
3 positions, ON, TRIP and OFF
for clear status indication.
All other specifications, current
ratings etc. to be same as 10kA, 2
Position MCBs.
TRIPPING CHARACTERISTICS
AND APPLICATIONS
B TYPE
Thermal operations are as per IEC
898-1995. Magnetic operating limit is
3 to 5 times rated current. MCBs with
B characteristics are used primarily
for wiring protection in lighting, socket
outlet and control circuit.
C TYPE
Thermal operations are as per
IEC 898-1995. Magnetic operating
limit is 5 to 10 times rated current.
MCBs with C characteristics are
used for overload and short circuit
protection primarily to protect
equipment with high making
10
4
(Sec)
10
3
10
2
10
1
10
-1
10
-2
10
-3
1 1.52 34 5 10 20 304050
Multiples of rated current
T
r
i
p
p
i
n
g

T
i
m
e
current (e.g. motors and transformers).
D TYPE
Thermal operations are as per
IEC 898-1995. Magnetic operating
limit is 10 to 20 times rated
current. Miniature Circuit Breakers
with D characteristics ensure that
even electrical equipment with
very high making current as
starting of heavy motors,
transformers, capacitor switching,
group of lights etc. do not lead to
undesired early tripping.
10
4
(Sec)
10
3
10
2
10
1
10
-1
10
-2
10
-3
1 1.52 34 5 10 20 304050
Multiples of rated current
T
r
i
p
p
i
n
g

T
i
m
e
D
10
4
(Sec)
10
3
10
2
10
1
10
-1
10
-2
10
-3
1 1.5234 5 10 20 304050
Multiples of rated current
T
r
i
p
p
i
n
g

T
i
m
e
DIMENSIONS (in mm)
Series datar
Miniature Circuit Breakers (MCBs)
ORDERING PROCEDURE
Please specify current rating, kA,
positions, type (B,C or D), poles
and voltage or temperature if other
than standard.
NOTE:
MCBs with current rating of 100
amp and breaking capacity of 20
kA are soon to be introduced.
All dimensions are in mm
TYPE B TYPE C TYPE D
45.00
34.5
37.5
58.0
68.0
5.5
75
1
5
.0
17.5
1 POLE 1 POLE+N
& 2 POLE
35.00 52.50
3 POLE
70.00
3 POLE+N
& 4 POLE
3 Back -- Index Page -- Next
INTRODUCTION
The technology for ELCBs is
imparted by F&G (Germany), leading
manufacturers of ELCBs and further
developed inhouse for 10 kA. Residual
Current Operated Earth Leakage
Circuit Breakers are internationally
accepted means of providing protection
from electric shocks and fires
caused due to earth leakage currents.
FEATURES:
Conforms to IEC 1008.
Truly Current Operated i.e.
operation even at nominal one volt.
Series datar
Current Operated Earth Leakage
Circuit Breakers (ELCBs)
additional features.
1. 2 connection levels, block
rail connection ie. other
than cables - busbar etc
and direct wiring ie. cables,
wires etc.
2. Shrouded terminals with
pressure plate for up to 50
mm cable.
3. Combi slotted head screws.
TECHNICAL SPECIFICATIONS
Product Upto 3kA ELCBs 10kA ELCBs
In (Rated Current) 16A, 25A, 40A, 63A 16A, 25A, 40A, 63A, 80mA, 100mA
In (Sensitivity) 30mA, 100mA, 300mA, 500mA 10mA
**
, 30mA, 100mA, 300mA, 500mA
Un (Rated Voltage) 240V AC, 415 V AC 240 V AC, 415 V AC
No. of Poles 2P (SP+N), 4P (TP+N) 2P (SP+N), 4P (TP+N)
Environment dry dry
Enclosure IP 30 IP 30
Short circuit withstand
16A / 25A : 1500A
capacity
40A : 2000A 10kA
63A : 3000A
Tripping time <30ms <30ms
Terminals For 25mm cable Shrouded with pressure plate, for 50mm cable
Frequency 50 / 60 Hz 50 / 60 Hz
Operational life (Electrical) > 20,000 operations
>20000 operations upto 63A
>10000 operations for 80 & 100A.
Mounting DIN Rail (35 mm) DIN Rail (35 mm)
Fuse Max. 63 A quick break, 50 A delayed break
Number of makes/breaks 2 makes and breaks 1 make and break
* measured 2 In in compliance with CEE 27 and 18.
**
Available on request.
4.3
45
70
75
4
68
66
74
35.5
15.5
0.5 30
DIMENSIONS (in mm) WIRING DIAGRAM
L1 N
L1 N
2 pole
T
L1 L2 L3 N
L1 L2 L3 N
4 pole
IEC 479 EFFECT OF ELECTRIC
CURRENT ON HUMAN BODY
direct contact indirect contact
prickling tetanization respiratory
trouble
ventricular
fibrillation
heart
arrest
Zone 1. Usually no reaction effect.
Zone 2. Usually no pathophysiologi-
cally dangerous effect.
Zone 3. Usually no danger of
fibrillation (more than 50%
probability).
Zone 4. Fibrillation danger (more
than 50% probability).
All dimensions are in mm
Upto 3 kA ELCBs
10 kA ELCBs
ORDERING PROCEDURE : Please specify current rating, kA, sensitivity, voltage, poles and test voltage (Ut).
17.5
3
.
5
35.5 5.5
4
1
.
5
8
3
4
1
.
5
4
9
0

43.5
60.5
71.6
71
52.5
17.5
L1 L3 L5 N
L2
T
L4 L6 N
15.2
4POLE 2POLE
4
5
ON
OFF
6
7
8
3
T
ON
OFF
L2 N
L1 N
35
4
5
6
7
8
3
15.2 3
.
5
30 mA trip
Zone 1
10000
5000
2000
1000
500
200
100
50
20
0.1 0.2 0.5 0.5 1 2 5 10 20 50 100 200 5001000 2000 mA 10000
T (ms)
Zone 2
Zone 3
Zone 4
Repeat accuracy 5%
Neutral Advance Mechanism.
Operation even in case of neutral
failure i.e. it operates even if
leakage occurs when incoming /
outgoing neutral is snapped.
Tripping time within 30m.sec.*
Trip free mechanism - i.e. during
fault, resetting is impossible
and it trips internally, even if
held in ON position forcibly.
Operates on Core Balance
Current Trasformer principle.
Provides optimum protection.
10kA ELCBs have following
4 Back -- Index Page -- Next
provide excellent protection even at
earth resistance of 330 ohms (for
extra safe voltage 10 volts), a device
up to 100 mA sensitivity may be
chosen where earth resistance is not
likely to exceed 30 Ohms. The earth
resistance is of no consequence when
considering protection from direct
contact and as such only 30 mA
sensitivity device should be chosen for
protection against direct contact. The
value of 30 mA* has been arrived at
as the 'no alternative disconnection
current' where an overwhelming
majority of individuals are unable to
disassociate voluntarity from the live
conductor, and instant automatic
interruption of supply is necessary.
FIRES
Protection form fires due to earth
leakage is best obtained by using
ELCB+MCB of 300mA or 500mA
sensitivity. Where downstream
distribution has been done through
30mA/100mA ELCB+MCB, some
degree of time discrimination may
be necessary by selecting the fire
protection devices with a small
deliberate delay (about 250
milliseconds).
MCB (LOAD CURRENT RATING)
The rated load currents of the
ELCB+MCB combination are 6A,
10A, 16A, 20A, 25A, 32A, 40A and
63A. The bimetal trip is so
adjusted that no tripping will occur
upto 1.3 times the rated current.
BREAKING CAPACITY
The combination features a high
breaking capacity of 9 kA at 440 V. This
TRIPPING CHARACTERISTICS (IEC 898-1995)
Series datar
ELCB + MCB Combinations
TYPE B TYPE C
Domestic equipment where
there is proximity to moisture/
conductive liquids e.g. water
heaters, washing machines,
electric irons, pump sets etc.
Construction and outdoor
electrical equipment such as
lifts, hoists, vibrators, polishing
machines etc. as switchning
and isolation device.
Motors and Pumps.
Operation theatres and electrically
operated medical equipment such
as X-ray machines, saws etc.
Neon sign installations.
Low and medium voltage electrical
distribution and equipment.
STANDARDS
ELCB+MCB combination conforms
to international standards like VDE
0664, CEE 27, SS 97, IEC 898 BS
4293: 1983, IEC 1009 etc.
EFFECT OF TEMPERATURE
The calibration of the ELCB device
being in conformity with BS 4293:
1983, the sensitivity of the device
will be between 50% and 100% of
the rated sensitivity.
The sensitivity of the ELCB+MCB
combination will be within permissible
limits when used in the temperature
range of -5to 50Centigrade.
EARTH LEAKAGE
The selection of sensitivity for
protection from electrocution should
be co-ordinated to the type and
quality of system earthing. While the
maximum sensitivity of 30mA will
INTRODUCTION
ELCB+MCB combi nat i on off ers
comprehensive protection against
overcurrent, short circuit, earth
leakage and earth fault. ELCB+MCB
is recommended to be used as
the main incoming circuit breaker
instead of conventional iron clad
main switches. Further, downstream
distribution with this combination will
also replace DP/TPN interruption
and switching devices. The high
breaking capacity of 9kA at 440
V allows safe, fuseless distribution.
Typical short circuit faults in real life
situation do not exceed 3000A for
loads of even 63A.
TECHNOLOGY
Technology for ELCB+MCB
combination is imparted by F & G ,
Germany.
FEATURES
All protections truly current operated
No nuisance tripping
Current limiting design
High breaking capacity
Maintenance-free
Neutral advance mechanism
Operation even in case of
neutral failure i.e. it operates if
leakage occurs even when
incoming neutral is snapped
Time / Current tripping
characteristics of B and C types
are available.
Trips at leakage current of
30mA within 30 ms
APPLICATIONS
The use of ELCB+MCB will ensure
total foolproof and reliable protection
from all hazards of low and medium
voltage electricity. The operation of
the device being independent of
extraneous parameters (like supply
voltage, temperature, humidity etc.)
it provides dependable protection
from all conceivable electrical faults
which may cause electrocution,
fires and result in destruction of
life and property and excessive
metering due to leakage.
It is recommended to use,
ELCB+MCB combination for:
Residential premises as
main incoming protection after
energy meter instead of fuses
and main switch.
10
4
(Sec)
10
3
10
2
10
1
10
-1
10
-2
10
-3
1 1.5 2 3 4 5 10 20 30 40 50
Multiples of rated current
T
r
i
p
p
i
n
g

T
i
m
e
10
4
(Sec)
10
3
10
2
10
1
10
-1
10
-2
10
-3
1 1.5 2 3 4 5 10 20 30 40 50
Multiples of rated current
T
r
i
p
p
i
n
g

T
i
m
e
5 Back -- Index Page -- Next
36.50
49.00
45.00
68.00
37.50
5.50
1
5
.0
63.50
82.50
70.00 105.00
6
9
.
5
0
8
2
.
5
0
of the cases the short circuits being
primarity due to earth faults, the earth
leakage tripping and MCB triping
will tend to overlap in their functions
without any hindrance.
fault energy, but only the small energy
before interruption, thus relieving
the system of high thermal and
magnetic stresses associated with
the clearing of heavy faults. In majority
allows a safe, fuseless distribution
system for loads up to 63A. The
current limiting feature ensure that the
wiring system as such, does not have
to carry the full brunt of prospective
DIMENSIONS (in mm)
TECHNICAL SPECIFICATIONS
ORDERING PROCEDURE
Please specify current rating,
sensitivity, voltage, poles and
temperature, if other than standard.
All dimensions are in mm
SALIENT FEATURES
Silver Cadmium Contacts for
weld free operations.
Terminals on both sides with
pressure plates for 50 sq. mm cable.
Both side terminals are finger-
touch proof.
ON/OFF indication.
35 mm Din Rail Mounting.
Maintenance free.
Compact size.
INTRODUCTION
Isolators are used in the
distribution network as incomer for
switching ON/OFF with suitable
MCBs as outgoing unit.
DIMENSIONS
Similar to Series datar MCBs.
ORDERING PROCEDURE
Please specify current rating,
poles and voltage.
Nomenclature ELCB+MCB
(In) Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, 63A
(In) Rated Sensitivity 30 mA 0.1A 0.3A 0.5A
(Un) Rated Voltage 240V 415 V 240 V 415 V 240 V 415V 240 V 415 V
No. of Poles 2 (SP+N) 4 (TP+N) 2 (SP+N) 4(TP+N) 2(SP+N) 4(TP+N) 2(SP+N) 4(SP+N)
Max. earth 10V 333 100 33 20
resistance 24V 800 240 80 48
Environment dry
Enclosure IP 30
Short circuit breaking
capacity
9kA
Max. Fuse rating 63A quick break, 50A delayed break
Terminals Shrouded, with pressure plate for 25mm
2
cable
Tripping time <30 ms*
Frequency 50/60 Hz
Operational life > 20,000 operations (at full load)
Temperature -5 to 55C
Type B or C
Mounting DIN Rail (35 mm)
* measured at 2 In in compliance with CEE 2718
2 (SP + N) 4 (TP + N)
Series datar
Isolators
TECHNICAL SPECIFICATIONS
Specifications IEC 947 Part III
Poles 1, 2, 3 and 4 poles (SP,DP,TP and FP)
Current Rating 40A, 63A, 100A
Rated Voltage 240V, 415V AC
Frequency 50 / 60Hz
Mounting DIN Rail (35 mm)
Utilisation Category AC 22A
Insulation Level 600V
Short time withstand current
Dynamic - 1.7 kA pk.
Thermal - 1.2 kA rms for 1.0 sec.
S.C. Making Current 1.7 kA pk
Series datar
ELCB + MCB Combinations (Continued)
6 Back -- Index Page -- Next
25, 32, 35 and 40 Amps. On
request : 0.5, 1, 2, 4, 5, 50
and 63Amps.
Rated voltage : 240V,415V AC.
(220 V DC MCBs on request)
Frequency : 50/60 Hz.
Breaking Capacity : 3kA to
10kA (IEC 898-1995). All
ratings are offered with
breaking capacity from 3kA to
10kA as per Customer specific
requirement.
Service life : 100,000 Mechanical
operations.
Service life at rated current :
25,000 operations.
Dimensions : Depth : 68 mm,
Width : 17.5 mm no. of poles.
Cover : 45 mm.
Temperature : -5C t0 55C
ORDERING PROCEDURE
Please specify current rating, type
(B,C or D), poles, breaking capacity
and voltage or temperature if other
than standard.
weld free operations.
Plastic DIN rail clip for reduced
possibilities of phase to earth
short circuit.
Terminals on both sides with
pressure plate, suitable for 25
sq.mm cable.
Padlocking facility in ON/OFF
position.
Snap mounting on 35 mm DIN
Rail.
Flame retardant casing to
withstand the glow wire test at
960C as per IEC 695.
Neutral advance mechanism.
TECHNICAL SPECIFICATION
Confirming to IEC 898 (1995),
VDE 0641, BS 3871.
No. of poles : 1, 2, 3 and 4
poles. (SP, SPN, DP, TP, TPN
and FP)
Tripping characteristies : Type
B, C and D.
Curent ratings : 6, 10, 16, 20,
INTRODUCTION
The MCBs are in Technical
Collaboration with F & G, Germany,
and have wide range applications in
domestic, commercial, agricultural
and industrial electrical installations.
SALIENT FEATURES
Completely finger protected
and shrouded terminals
conforming to IP 30.
High breaking capacity of 10kA
(as per IEC : 898-1995) fault
withstanding capacity without
back-up protection.
Current limiting design for
reduced let through energy and
opening time. Helps in effective
arc quenching.
Trip free mechanism is
independent of the position
of the knob. Even if the operating
knob is held forcibly in ON
position, the trip free mechanism
ensures tripping internally.
Silver graphite contacts for
Series 9000, SAFELINE
Miniature Circuit Breakers (MCBs)
sq.mm cable. All other features
and technical specifications are
same as Series 9000, SAFELINE
MCBs. Please refer the drawings
for dimensions.
These MCBs are also in Technical
Collaboration with F & G,
Germany and similar to Series
9000, except that the terminals are
not shrouded and can take upto 16
All dimensions are in mm
All dimensions are in mm
DIMENSIONS
NOTE:
Please refer to page 1 for details
of type B, C and D tripping
characteristics.
Series 1100, SAFELINE
Miniature Circuit Breakers (MCBs)
45.00
37.5
44.0
60.0
68.0
5.5
75
17.5
1 POLE 1 POLE+N
& 2 POLE
35.00 52.50
3 POLE
70.00
3 POLE+N
& 4 POLE
75
45.00
43.0
60.5
68.0
5.5
75
17.5
1 POLE
7 Back -- Index Page
SALIENT FEATURES
Completely finger protected,
shrouded terminals. Enclosure
conforms to IP 30.
Silver graphite contacts ensure
weld free operation.
Plastic DIN rail clip reducing
the chances of phase to earth
short circuit.
Terminals on both sides are with
pressure plate and suitable for
25 sq.mm cable.
Padlocking facility in ON/OFF
position.
Snap mounting on 35 mm DIN rail.
Flame retardant casing to
withstand the flow wire test at
960C as per IEC 695.
TECHNICAL SPECIFICATION
No. of poles : 1, 2, 3 and 4
poles. (SP, DP, TP, and FP)
Curent ratings : 40 and 63 Amps.
Rated voltage : 240V, 415V AC.
Frequency : 50/60 Hz.
Service life : 100,000 mechanical
operations.
Service life at rated current :
25,000 operations.
Dimensions : Depth : 68 mm,
Width : 17.5 mm no. of poles,
Cover : 45 mm.
Temperature : -5C t0 55C
DIMENSIONS
Similar to Series 9000 SAFELINE
MCBs.
ORDERING PROCEDURE
Please specify current rating, type
(B,C or D), poles and voltage or
temperature if other than standard.
INTRODUCTION
The Isolators are used in the
distribution network as incomer to
the distribution box and can be
switched ON/OFF. SP and DP
isolators are used in single phase
circuits, while TP and FP Isolators
are used in three phase circuits.
The Distribution Boxes (DBs) in
the ranges of Plug & Sockets DB,
SPN DB, SPN Consumer Units or
DBs, TPN DB and Power DB are
offered on request.
In the SPN Consumer Units, DP
Isolators are used as incomers
and SP MCBs are used as
outgoing units.
In the TPN DBs and Power DBs,
the FP Isolators are used as
incomers unit and TP, TPN, SP,
DP MCBs are used as outgoing
units.
Series 9000, SAFELINE
Isolators
CG International
A Division of
Crompton Greaves Limited
Jagruti, Kanjurmarg (East),
Mumbai (Bombay) - 400 042. (INDIA)
Telephones : +91-22-578 2451
Direct : +91-22-577 6524 / 6649
Fax : +91-22-577 4066
E mail : cgi @ cgl.co.in
Home Page : http://www.cgl.co.in/international/
C
G
.
I
D
/
4
8
/
M
C
B
/
3
/
9
9
Product improvement is a continuous process. Hence, data given in this catalogue is subject to change without intimation.

You might also like